surge protection made simpleâ„¢ for coaxial data cables

2
Product obsoleted on July 6, 2018. No recommended replacements. Technical Data 2159 Effective December 2016 Supersedes January 2013 In-line BNC connector data signal surge protective device for coaxial cable systems Catalog number: BSPD5BNCSI Description: The Bussmann™ series BSPD5BNCSI two-stage in-line surge arrester is for protecting coaxial cable- connected systems (such as video and camera systems) from potential damage. The BSPD5BNCSI shielded surge arrester is plugged into coaxial terminal equipment or connections. Common applications include protecting outdoor video surveillance systems or video control centers. The cable shield is indirectly grounded via a gas discharge tube to avoid being influenced by leakage pickups. The arrester input is used as a socket and the protected output as a plug. Agency information UL ® 497B Listed RoHS complaint Features Plug-in surge protective device for easy retrofitting Directly plugs into terminal equipment with BNC coaxial connections Integrated indirect shield grounding avoids leakage pickups Dimensions — mm 74.00 300.00 APPROX 24.00

Upload: others

Post on 11-Feb-2022

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Surge Protection Made Simpleâ„¢ for Coaxial Data Cables

Produc

t obs

oleted

on Ju

ly 6,

2018

. No r

ecom

mende

d rep

lacem

ents.

Technical Data 2159Effective December 2016Supersedes January 2013

In-line BNC connector data signal surge protective device for coaxial cable systems

Catalog number:• BSPD5BNCSI

Description:

The Bussmann™ series BSPD5BNCSI two-stage in-line surge arrester is for protecting coaxial cable-connected systems (such as video and camera systems) from potential damage.

The BSPD5BNCSI shielded surge arrester is plugged into coaxial terminal equipment or connections.

Common applications include protecting outdoor video surveillance systems or video control centers.

The cable shield is indirectly grounded via a gas discharge tube to avoid being influenced by leakage pickups. The arrester input is used as a socket and the protected output as a plug.

Agency information

• UL® 497B Listed• RoHS complaint

Features• Plug-in surge protective device for easy

retrofitting• Directly plugs into terminal equipment with

BNC coaxial connections• Integrated indirect shield grounding avoids

leakage pickups

Dimensions — mm

74.00

300.00 APPROX

24.00

Page 2: Surge Protection Made Simpleâ„¢ for Coaxial Data Cables

Produc

t obs

oleted

on Ju

ly 6,

2018

. No r

ecom

mende

d rep

lacem

ents.

Eaton.com/bussmannseries

In-line BNC connector data signal surge protective device for coaxial cable systems

Technical Data Effective December 2016

Follow us on social media to get the latest product and support information.

The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.

Eaton and Bussmann are valuable trademarks of Eaton in the U.S. and other countries. You are not permitted to use the Eaton trademarks without prior written consent of Eaton.

UL is a registered trademark of the Underwriters Laboratories, Inc.

Eaton1000 Eaton BoulevardCleveland, OH 44122Eaton.com

Bussmann Division114 Old State RoadEllisville, MO 63021United StatesEaton.com/bussmannseries

© 2016 EatonAll Rights ReservedPrinted in USAPublication No. 2159 — BU-SB13142December 2016

Gas discharge tube

Bi-polar suppressor diode

Capacitor

Decoupling resistor

Circuit diagramCatalog numbers and specifications

Catalog number BSPD5BNCSINominal voltage (UN) 5 VMax. continuous operating DC voltage (UC) 8 VC2 Nominal discharge current (8/20 µs) per line (In)

2.5 kA

C2 Nominal discharge current (8/20 µs) shield-PG (In)

10 kA

Voltage protection level line-shield for In C2 (Up)

≤25 V

Voltage protection level line-shield at 1 kV/µs C3 (Up)

≤15 V

Voltage protection level shield-PG at 1 kV/µs C3 (Up)

≤600 V

Insertion loss at 265 MHz ≤3 dBReturn loss at 40 MHz ≥20 dBImpedance (Z) 75 ΩSeries impedance per line 10 ΩCapacitance line-shield (C) ≤50 pFOperating temperature range -40°C to +80°CConnection (input / output) BNC Socket (female) /

BNC Plug (male)Grounding Via outgoing earth

conductor 18 AWG (0.75 mm2)

Shield grounding Indirectly via an integrated spark gap element

Test standards IEC 61643-21 / EN 61643-21

Agency information UL 497BWarranty 5 Years*

* See Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/Surge.

In-line BNC SPD Applications

Catalog number BSPD5BNCSIBus systems and measuring, and control technologyControl Net XMelsec Net 2 XData networksArcnet XVideo systems

Video (coax) X