substation portable pq loggers - tmi instruments · 2014. 7. 3. · substation portable pq loggers...

4
Substation portable PQ loggers bravo spi 3/4 voltage inputs, up to 32 current inputs | Compact IP 65 enclosure with rubber protection | Class S according to IEC 61000-4-30, Ed2 | Power quality analysis according to EN 50160 | Power supply external or from measuring circuit | Built-in Li battery as backup for power interruptions | Internal memory 512 MB | USB com interface, WiFi; GPRS, HSDPA+GPS (options) | Direct installation on LV busbars and feeders Simultaneous measuring on busbar and all feeders Up to 32 current channels with Rogowski coils Measuring of power quality and load profiles Compliance PQ report according to EN 50160 Highlights Key features 1

Upload: others

Post on 30-Mar-2021

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Substation portable PQ loggers - TMI Instruments · 2014. 7. 3. · Substation portable PQ loggers bravo spi 3/4 voltage inputs, up to 32 current inputs | Compact IP 65 enclosure

Substation portable PQ loggers

bravo spi

3/4 voltage inputs, up to 32 current inputs | Compact IP 65 enclosure with rubber protection | Class S according to IEC 61000-4-30, Ed2 | Power quality analysis according to EN 50160 | Power supply external or from measuring circuit | Built-in Li battery as backup for power interruptions | Internal memory 512 MB | USB com interface, WiFi; GPRS, HSDPA+GPS (options) | Direct installation on LV busbars and feeders

Simultaneous measuring on busbar and all feeders

Up to 32 current channels with Rogowski coils

Measuring of power quality and load profiles

Compliance PQ report according to EN 50160

Highlights

Key features

1

Page 2: Substation portable PQ loggers - TMI Instruments · 2014. 7. 3. · Substation portable PQ loggers bravo spi 3/4 voltage inputs, up to 32 current inputs | Compact IP 65 enclosure

BRAVO SERIES SPI are robust portable PQ loggers for substation. It measures all PQ parameters according to the measuring methods from IEC 61000-4-30, Cl. S. Main applications are: to measure voltage compliance at substation busbar, measurement and record of PQ parameters on busbar and load profiles on feeders (up to 32 current channels).

Typical BRAVO SPI configuration with accessories

The purpose of this multifunction instruments is registration off all PQ parameters for each feeder in low voltage facilities. Measuring: frequency, voltage, current, phase angels, unbalance, harmonics, flickers. Calculating: active, reactive, harmonic and apparent power, energy, PF. Record of voltage events like dips, swells and interruptions. Statistic analysis of measured results according to EN 50160.

4 voltage inputs 0-400 VAC

3 to 32 current inputs 0-3000 AAC (CT - dependable) Measuring sensors for current are Rogowski coils up to 3000A Sampling 128 samples/cycle, continuous measuring cycle 200ms Built-in internal UPS battery with autonomy of 10 min Power supply from the measuring circuit, external network or internal UPS The choice of main memory aggregation interval from 200 ms to 2 h The concept of data marking (Flagging) Flicker measurement according to IEC 61000-4-15 Measurement of harmonics and interharmonics up to 50th according to IEC 61000-4-7 Analogue input for Pt100 temperature sensor (option)

512 MB internal memory for all measured parameters Saving the max and min values with timestamp Daily profile for a given date and for a day with a max consumption

Locali Interface USB 2.0 for fast data download, configure and upgrade Wifi wireless interface (option) GPRS wireless interface (option)

Basic features

Measuring characteristics

Data storage

Communication

2

Page 3: Substation portable PQ loggers - TMI Instruments · 2014. 7. 3. · Substation portable PQ loggers bravo spi 3/4 voltage inputs, up to 32 current inputs | Compact IP 65 enclosure

3

ALFASOFT - Software for data collection and analysis | Basic PC software for data collection and analysis is included for free with every instrument. The stored data can be transferred from the instrument using various communication interfaces (USB, Wifi). Software displays various graphs, charts and tables. Each stored data can be processed and visualized in details. Software supports various data export formats including xcl, cvs i pdf. According to user requirements, specific reports can be added for specific applications.

ALFASOFT software package consists of the following modules:

AlfaEval.BASE module for advanced processing of archived data – trend visualization, archives, reports, export AlfaEval.DAQ module for work with instrument: settings, collection of archived

data and export to other formats Alfa Eval.ONLINE module for online communication with meter and read of actual measurement values

AlfaEval.BASE module allows easy and flexible overview of data from multiple instruments: The main archive contains all important values which

are recorded at pre-selected intervals (200 ms – 2 h). M and S profiles of the measurements with a one

minute aggregation of most important values – voltage, current, power, frequency, etc.

PQ Main archive is available only for instruments that supports PQ features. Contains 10-min data and weekly evaluations according to EN50160.

PQ Events contains events in voltage (dips, swells, interruptions) which are stored along with the start time, end time and phase.

Energy Archive contains data of energy consumption in the four quadrants and three tariffs.

Pmax Archive contains max 3-phase power value of the current month.

AlfaEval.DAQ module is used for communication directly with the instrument using a local or remote communication, and provides: Instrument setting and wiring testing Search and download archives captured from the

instrument and store them in the default database or file (binar, CSV, XLS)

Review records of all values, including phase diagrams and waveforms of voltage and current.

Page 4: Substation portable PQ loggers - TMI Instruments · 2014. 7. 3. · Substation portable PQ loggers bravo spi 3/4 voltage inputs, up to 32 current inputs | Compact IP 65 enclosure

4

BRAVO SPI Technical specifications

Measured valuesFrequency

fNOM 50/60 Hz

Range 42.5 ÷ 57.5 Hz/51 ÷ 69 Hz

Accuracy ± 010 mHz

Voltage

Number of channels 4

UNOM (phase/line) 250/300 VAC – 300/520 AAC

Measurement method Continuous (gapless) according IEC 61000-4-30

Measurement range 3 ÷ 400 VAC/5 ÷ 1380 VAC

AccuracyRange 5 ÷ 500 VAC

Complete measuring range± 0.1% of rd. ± 0.02% F.S.± 0.1% of rd. ± 0.06% F.S.

Voltage unbalance

Measurement range 0 ÷ 5%

Accuracy ± 0.15%

THD in voltage

Measurement range 0 – 20%

Accuracy ± 0.3%

Voltage harmonics and interharmonics

Measurement range 10 – 100% from Class 3, IEC 61000-2-4 ed2

Accuracy Double the value of Class II, IEC 61000-4-7 ed2

Flicker

Measurement range 0.4 ÷ 10

Accuracy According toEN 61000-4-15

Current (including Rogowski current sensors)

Instrument type/channelsBRAVO SPI-2 (6/8 sensors)BRAVO SPI-4 (12/16 sensors)BRAVO SPI-8 (24/32 sensors)

2 x 3/4 sensors (2 feeders)4 x 3/4 sensors (4 feeders)8 x 3/4 sensors (8 feeders)

INOM 30 – 3000 AAC

Measurement range 0.5 ÷ 3300 AAC

Accuracy (conductor vertical to sensor, conductor in centre of sensor)

± 0.5% of rd. ± 0.05% F.S.

Current unbalance

Measurement range 0 ÷ 5%

Accuracy ± 0.15%

THD in current

Measurement range 0 – 200%

Accuracy ± 0,3% of rd. ± 0,3% F.S.

Current harmonics and interharmonics

Measurement range 10 – 100% of INOM

AccuracyIh ≤ 10% of INOM

Ih > 10% of INOM

± 0.5% of INOM

± 5% of rd.

Active/reactive power, Power factor

Reference conditionsU & IPF for active powerPF for reactive power

U ≥ 5% F.S. UNOM, I ≥ 5% F.S.PF = 1,00PF = 0,00

Accuracy act./react. power ± 1.0% of rd. ±0.5% F.S.

Accuracy PF ± 0.01

Current probe

Number of current sensors in one probeCSA-Ix000-1MFC1CSA-Ix000-3MFC1CSA-Ix000-4MFC1

134

Operating voltage max. 300 VAC

Overvoltage category/pollution degree, safety

III/2 – according to IEC EN 61010-1, double insulation

Protection IP 40, internal use only

Other specificationsIED 61000-4-30 ed2 class. Class S

Evaluation method PQ Weekly, according to EN 50160 or on request

Voltage inputs:power and impedance

< 0.1 VA (15MΩ)

Current inputs:power and impedance

Not specified

Power supplystandard input

additional LV input (option)

85 ÷ 480 VAC/40 ÷ 70 Hz (8 VA)80 ÷ 680 VDC (8 W)8 ÷ 55 VAC/40 ÷ 70 Hz (8 VA)8 ÷ 75 VDC (8 W)

Overvoltage class/pollution degree300 VAC measuring rangeentire measuring range

III/2 – according to EN 61010-1II/2 – according to EN 61010-1

Working temperature -25 to 60°C

Storage temperature -40 to 85°C

Humidity < 95% – uncondensed

EMC – radiation EN 50081-2, EN 55011, Class AEN 55022, Class A

EMC – immunity EN 61000-4-2 , EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-11

RTC accuracy +/- 2 sec per day

Internal Batteryfor RTC – duration

> 5 years (no power supply)

Local communication interfaces

USB 2.0

Remote communication interfaces

WLAN-IEEE 802.11 b,g

Communication protocol MODBUS, IEC 60870-5-104 (option)

Class of protection IP 40

Dimensions 250x210x70 mm

Weight (without cablesand current probes)

0.8 kg

For more information contact Adabel [email protected] | [email protected] | www.adabel.hr