substation equipments & its functions

21
SUB-STATION EQUIPMENTS & ITS FUNCTIONS Lightening Arrester Lightening arrestors are the instrument that are used in the incoming feeders so that to prevent the high voltage entering the main station. This high voltage is very dangerous to the instruments used in the substation. Even the instruments are very costly, so to prevent any damage lightening arrestors are used. The lightening arrestors do not let the lightening to fall on the station. If some lightening occurs the arrestors pull the lightening and ground it to the earth. In any substation, the main important is of protection which is firstly done by these lightening arrestors. The lightening arrestors are grounded to the earth so that it can pull the lightening to the ground. The lightening arrestor works with an angle of 30° to 45° making a cone. C V T A capacitor voltage transformer (CVT) is a transformer used in power systems to step-down extra high voltage signals and provide low voltage signals either for measurement or to operate a protective relay. In its most

Upload: monzer-abdallah-eisa

Post on 19-Feb-2017

545 views

Category:

Engineering


4 download

TRANSCRIPT

Page 1: Substation equipments & its functions

SUB-STATION EQUIPMENTS & ITS FUNCTIONS

Lightening Arrester

Lightening arrestors are the instrument that are used in the incoming feeders so that

to prevent the high voltage entering the main station. This high voltage is very dangerous

to the instruments used in the substation. Even the instruments are very costly, so to

prevent any damage lightening arrestors are used. The lightening arrestors do not let the

lightening to fall on the station. If some lightening occurs the arrestors pull the lightening

and ground it to the earth. In any substation, the main important is of protection which is

firstly done by these lightening arrestors. The lightening arrestors are grounded to the

earth so that it can pull the lightening to the ground. The lightening arrestor works with an

angle of 30° to 45° making a cone. 

C V T

A capacitor voltage transformer (CVT) is a transformer used in power systems to

step-down extra high voltage signals and provide low voltage signals either for

measurement or to operate a protective relay. In its most basic form the device consists of

three parts: two capacitors across which the voltage signal is split, an inductive element

used to tune the device to the supply frequency and a transformer used to isolate and

further step-down the voltage for the instrumentation or protective relay. The device has at

least four terminals, a high-voltage terminal for connection to the high voltage signal, a

ground terminal and at least one set of secondary terminals for connection to the

instrumentation or protective relay. CVTs are typically single-phase devices used for

measuring voltages in excess of one hundred kilovolts where the use of voltage

transformers would be uneconomical. In practice the first capacitor, C1, is often replaced

by a stack of capacitors connected in series. This results in a large voltage drop across the

Page 2: Substation equipments & its functions

stack of capacitors that replaced the first capacitor and a comparatively small voltage drop

across the second capacitor, C2, and hence the secondary terminals.

Wave Trap

Wave trap is an instrument using for tripping of the wave. The function of this trap

is that it traps the unwanted waves. Its function is of trapping wave. Its shape is like a

drum. It is connected to the main incoming feeder so that it can trap the waves which may

be dangerous to the instruments here in the substation. 

 Instrument Transformer

Instrument transformers are used to step-down the current or voltage to measurable

values. They provide standardized, useable levels of current or voltage in a variety of

power monitoring and measurement applications. Both current and voltage instrument

transformers are designed to have predictable characteristics on overloads. Proper

operation of over-current protection relays requires that current transformers provide a

predictable transformation ratio even during a short circuit.

These are further classified into two types which are discussed below.

a. Current Transformers

b. Potential Transformers

Current Transformer

Current transformers are basically used to take the readings of the currents entering

the substation. This transformer steps down the current from 800 amps to 1 amp. This is

done because we have no instrument for measuring of such a large current. The main use

of this transformer is

a. Distance Protection

b. Backup Protection

c. Measurement

Page 3: Substation equipments & its functions

A current transformer is defined as an instrument transformer in which the

secondary current is substantially proportional to the primary current (under normal

conditions of operation) and differs in phase from it by an angle which is approximately

zero for an appropriate direction of the connections. This highlights the accuracy

requirement of the current transformer but also important is the isolating function, which

means no matter what the system voltage the secondary circuit need to be insulated only

for a low voltage.

The current transformer works on the principle of variable flux. In the ideal current

transformer, secondary current would be exactly equal (when multiplied by the turns ratio)

and opposite to the primary current. But, as in the voltage transformer, some of the

primary current or the primary ampere-turns are utilized for magnetizing the core, thus

leaving less than the actual primary ampere turns to be transformed into the secondary

ampere-turns. This naturally introduces an error in the transformation. The error is

classified into current ratio error and the phase error

 Potential Transformer

There are two potential transformers used in the bus connected both side of the bus.

The potential transformer uses a bus isolator to protect itself. The main use of this

transformer is to measure the voltage through the bus. This is done so as to get the detail

information of the voltage passing through the bus to the instrument. There are two main

parts in it

a. Measurement

b. Protection

The standards define a voltage transformer as one in which the secondary voltage is

substantially proportional to the primary voltage and differs in phase from it by an angle

which is approximately equal to zero for an appropriate direction of the connections. This

Page 4: Substation equipments & its functions

in essence means that the voltage transformer has to be as close as possible to the ideal

transformer.

In an ideal transformer, the secondary voltage vector is exactly opposite and equal

to the primary voltage vector when multiplied by the turn’s ratio.

In a practical transformer, errors are introduced because some current is drawn for

the magnetization of the core and because of drops in the primary and secondary windings

due to leakage reactance and winding resistance. One can thus talk of a voltage error

which is the amount by which the voltage is less than the applied primary voltage and the

phase error which is the phase angle by which the reversed secondary voltage vector is

displaced from the primary voltage vector.

Bus Bar

The bus is a line in which the incoming feeders come into and get into the

instruments for further step up or step down. The first bus is used for putting the incoming

feeders in la single line. There may be double line in the bus so that if any fault occurs in

the one the other can still have the current and the supply will not stop. The two lines in

the bus are separated by a little distance by a conductor having a connector between them.

This is so that one can work at a time and the other works only if the first is having any

fault.

A bus bar in electrical power distribution refers to thick strips of copper or

aluminum that conduct electricity within a switchboard, distribution board, substation, or

other electrical apparatus. The size of the bus bar is important in determining the

maximum amount of current that can be safely carried. Bus bars are typically either flat

strips or hollow tubes as these shapes allow heat to dissipate more efficiently due to their

high surface area to cross sectional area ratio. The skin effect makes 50-60 Hz AC bus

bars more than about 8 mm (1/3 in) thick inefficient, so hollow or flat shapes are prevalent

in higher current applications. A hollow section has higher stiffness than a solid rod of

Page 5: Substation equipments & its functions

equivalent current carrying capacity, which allows a greater span between bus bar

supports in outdoor switchyards. A bus bar may either be supported on insulators or else

insulation may completely surround it. Bus bars are protected from accidental contact

either by a metal enclosure or by elevation out of normal reach.

Neutral bus bars may also be insulated. Earth bus bars are typically bolted directly

onto any metal chassis of their enclosure. Bus bars may be enclosed in a metal housing, in

the form of bus duct or bus way, segregated-phase bus, or isolated-phase bus.

Circuit Breaker

The circuit breakers are used to break the circuit if any fault occurs in any of the

instrument. These circuit breaker breaks for a fault which can damage other instrument in

the station. For any unwanted fault over the station we need to break the line current. This

is only done automatically by the circuit breaker. There are mainly two types of circuit

breakers used for any substations. They are

a. SF6 circuit breakers

b. Spring circuit breakers.

The use of SF6 circuit breaker is mainly in the substations which are having high

input kv input, say above 220kv and more. The gas is put inside the circuit breaker by

force i.e. under high pressure. When if the gas gets decreases there is a motor connected to

the circuit breaker. The motor starts operating if the gas went lower than 20.8 bar. There is

a meter connected to the breaker so that it can be manually seen if the gas goes low. The

circuit breaker uses the SF6 gas to reduce the torque produce in it due to any fault in the

line. The circuit breaker has a direct link with the instruments in the station, when any

fault occur alarm bell rings.

The spring type of circuit breakers is used for small kv stations. The spring here

reduces the torque produced so that the breaker can function again. The spring type is

Page 6: Substation equipments & its functions

used for step down side of 132kv to 33kv also in 33kv to 11kv and so on. They are only

used in low distribution side.

Transformer

There are three transformers in the incoming feeders so that the three lines are step

down at the same time. In case of a 220KV or more KV line station auto transformers are

used. While in case of lower KV line such as less than 132KV line double winding

transformers are used.

The transformer is transported on trailor to substation site and as far as possible

directly unloaded on the plinth. Transformer tanks up to 25 MVA capacity are generally

oil filled, and those of higher capacity are transported with N2 gas filled in them +ve

pressure of N2 is maintained in transformer tank to avoid the ingress of moisture. This

pressure should be maintained during storage, if necessary by filling N2 Bushings -

generally transported in wooden cases in horizontal position and should be stored in that

position. There being more of fragile material, care should be taken while handling them.

Radiators – These should be stored with ends duly blanked with gaskets and end plates to

avoid in gross of moisture, dust, and any foreign materials inside. The care should be

taken to protect the fins of radiators while unloading and storage to avoid further oil

leakages. The radiators should be stored on raised ground keeping the fins intact. 

Oil Piping. The Oil piping should also be blanked at the ends with gasket and blanking

plates to avoid in gross of moisture, dust, and foreign All other accessories like

temperature meters, oil flow indicators, PRVs, buchholz relay; oil surge relays; gasket ‘ O

‘ rings etc. should be properly packed and stored indoor in store shed. Oil is received in

sealed oil barrels. The oil barrels should be stored in horizontal position with the lids on

either side in horizontal position to maintain oil pressure on them from inside and

subsequently avoiding moisture and water ingress into oil. The transformers are received

Page 7: Substation equipments & its functions

on site with loose accessories hence the materials should be checked as per bills of

materials.

Isolator

The use of this isolator is to protect the transformer and the other instrument in the

line. The isolator isolates the extra voltage to the ground and thus any extra voltage cannot

enter the line. Thus an isolator is used after the bus also for protection.

Control and Relay Panel

The control and relay panel is of cubical construction suitable for floor mounting.

All protective, indicating and control elements are mounted on the front panel for ease of

operation and control. The hinged rear door will provide access to all the internal

components to facilitate easy inspection and maintenance. Provision is made for

terminating incoming cables at the bottom of the panels by providing separate line-up

terminal blocks. For cable entry provision is made both from top and bottom. The control

and relay panel accepts CT, PT aux 230 AC and 220V/10V DC connections at respective

designated terminal points. 220V/10V DC supply is used for control supply of all internal

relays and timers and also for energizing closing and tripping coils of the breakers. 230V

AC station auxiliary supply is used for internal illumination lamp of the panel and the

space heater. Protective HRC fuse are provided with in the panel for P.T secondary. Aux

AC and battery supplies. Each Capacitor Bank is controlled by breaker and provided with

a line ammeter with selector switch for 3 phase system & over current relay (2 phases and

1 Earth fault for 3 ph system). Under voltage and over voltage relays. Neutral Current

Unbalance Relays are for both Alarm and Trip facilities breaker control switch with

Page 8: Substation equipments & its functions

local/remote selector switch, master trip relay and trip alarms acknowledge and reset

facilities.

Protective Relaying

Protective relays are used to detect defective lines or apparatus and to initiate the

operation of circuit interrupting devices to isolate the defective equipment. Relays are also

used to detect abnormal or undesirable operating conditions other than those caused by

defective equipment and either operate an alarm or initiate operation of circuit interrupting

devices. Protective relays protect the electrical system by causing the defective apparatus

or lines to be disconnected to minimize damage and maintain service continuity to the rest

of the system. There are different types of relays.

i. Over current relay

ii. Distance relay

iii. Differential relay

iv. Directional over current relay

i. Over Current Relay

The over current relay responds to a magnitude of current above a specified value.

There are four basic types of construction: They are plunger, rotating disc, static, and

microprocessor type. In the plunger type, a plunger is moved by magnetic attraction when

the current exceeds a specified value. In the rotating induction-disc type, which is a motor,

the disc rotates by electromagnetic induction when the current exceeds a specified value.

Static types convert the current to a proportional D.C mill volt signal and apply it to

a level detector with voltage or contact output. Such relays can be designed to have

various current-versus-time operating characteristics. In a special type of rotating

induction-disc relay, called the voltage restrained over current relay. The magnitude of

voltage restrains the operation of the disc until the magnitude of the voltage drops below a

threshold value. Static over current relays are equipped with multiple curve characteristics

Page 9: Substation equipments & its functions

and can duplicate almost any shape of electromechanical relay curve. Microprocessor

relays convert the current to a digital signal. The digital signal can then be compared to

the setting values input into the relay. With the microprocessor relay, various curves or

multiple time-delay settings can be input to set the relay operation. Some relays allow the

user to define the curve with points or calculations to determine the output characteristics.

ii. Distance Relay

The distance relay responds to a combination of both voltage and current. The

voltage restrains operation, and the fault current causes operation that has the overall

effect of measuring impedance. The relay operates instantaneously (within a few cycles)

on a 60-cycle basis for values of impedance below the set value. When time delay is

required, the relays energizes a separate time-delay relay or function with the contacts or

output of this time-delay relay or function performing the desired output functions. The

relay operates on the magnitude of impedance measured by the combination of restraint

voltage and the operating current passing through it according to the settings applied to

the relay. When the impedance is such that the impedance point is within the impedance

characteristic circle, the relay will trip. The relay is inherently directional. The line

impedance typically corresponds to the diameter of the circle with the reach of the relay

being the diameter of the circle.

iii. Differential Relay

The differential relay is a current-operated relay that responds to the difference

between two or more device currents above a set value. The relay works on the basis of

the differential principle that what goes into the device has to come out .If the current does

not add to zero, the error current flows to cause the relay to operate and trip the circuit.

The differential relay is used to provide internal fault protection to equipment such

as transformers, generators, and buses. Relays are designed to permit differences in the

input currents as a result of current transformer mismatch and applications where the input

currents come from different system voltages, such as transformers. A current differential

Page 10: Substation equipments & its functions

relay provides restraint coils on the incoming current circuits. The restraint coils in

combination with the operating coil provide an operation curve, above which the relay

will operate. Differential relays are often used with a lockout relay to trip all power

sources to the device and prevent the device from being automatically or remotely

reenergized. These relays are very sensitive. The operation of the device usually means

major problems with the protected equipment and the likely failure in re-energizing the

equipment.

iv. Directional Over current Relay

A directional over current relay operates only for excessive current flow in a given

direction. Directional over current relays are available in electromechanical, static, and

microprocessor constructions. An electromechanical overcorrect relay is made directional

by adding a directional unit that prevents the over current relay from operating until the

directional unit has operated. The directional unit responds to the product of the

magnitude of current, voltage, and the phase angle between them or to the product of two

currents and the phase angle between them. The value of this product necessary to provide

operation of the directional unit is small, so that it will not limit the sensitivity of the relay

(such as an over current relay that it controls). In most cases, the directional element is

mounted inside the same case as the relay it controls. For example, an over current relay

and a directional element are mounted in the same case, and the combination is called a

directional over current relay. Microprocessor relays often provide a choice as to the

polarizing method that can be used in providing the direction of fault, such as applying

residual current or voltage or negative sequence current or voltage polarizing functions to

the relay.

DC Power Supply

I . DC Battery and Charger

Page 11: Substation equipments & its functions

All but the smallest substations include auxiliary power supplies. AC power is

required for substation building small power, lighting, heating and ventilation, some

communications equipment, switchgear operating mechanisms, anti-condensation heaters

and motors. DC power is used to feed essential services such as circuit breaker trip coils

and associated relays, supervisory control and data acquisition (SCADA) and

communications equipment. This describes how these auxiliary supplies are derived and

explains how to specify such equipment. It has Single 100% battery and 100% charger,

Low capital cost, No standby DC System outage for maintenance. Need to isolate

battery/charger combination from load under boost charge conditions in order to prevent

high boost voltages.

I I . Battery and Charger configurations

Capital cost and reliability objectives must first be considered before defining the

battery and battery charger combination to be used for a specific installation. The

comparison given in Table 5.1 describes the advantages and disadvantages of three such

combinations.

Capital cost and reliability objectives must first be considered before defining the

battery/battery charger combination to be used for a specific installation. The comparison

given describes the advantages and disadvantages of three such combinations

III . 400V DC Battery

Make: Exide                                                               

Capacity: 300 AH at 27°

No. of Cells: 110 No.

Date of installation: 06/2001

Make: Universal,

Sr. No. : BC 1020/82

Date of manufacturing: 4/2000

Page 12: Substation equipments & its functions

Input Rating: Voltage: 415 V + 10 %

Output Rating : Float: 220 V, 10 Amp

  Boost: 180 V, 30Amp          

Functions of Associated System in SubstationFunctions of Associated System in Substation is as shown below in table-4.1

Table-4.1 Functions of Associated System in Substation

Sr

.

System Function

1. Substation Earthing system

- Earth mat

- Earthing spikes

- Earthing risers

To provide an earth mat for connecting neutral points,

equipment body, support structures to earth. For safety of

personnel and for enabling earth fault protection. To

provide the path for discharging the earth currents from

neutrals, faults, Surge Arresters, overheads shielding wires

etc. with safe step-potential and touch potential.

2. Overhead earth wire shielding or

Lightning masts.

To protect the outdoor substation equipment from

lightning strokes.

3. Illumination system (lighting)

- for switchyard

- buildings

- roads etc.

To provide proper illumination to substation yard.

4. Protection system

- protection relay panels

- control cables

- circuit breakers

- CTs, VTs etc.

To provide alarm or automatic tripping of faulty part from

healthy part and also to minimize damage to faulty

equipment and associated system.

5. Control cable For Protective circuits, control circuits, metering circuits,

communication circuits

6. Power cable To provide supply path to various auxiliary equipment and

Page 13: Substation equipments & its functions

machines.

7. PLCC system

power line carrier communication

system

For communication, telemetry, tele-control, power line

carrier protection etc.

8. Telephone, telex, microwave,

OPF

For internal and external communication

9. Auxiliary standby power

system

For supplying starting power, standby power for

auxiliaries.

10

.

Fire Fighting system

- Sensors, detection system

- water spray system

- fire port, panels, alarm

System.

- water tank and spray system

To sense the occurrence of fire by sensors and to initiate

water spray, to disconnect power supply to affected region

to pinpoint location of fire by indication in control room.