SUBSTATION DESIGN CRITERIA DOCUMENT East Point Collector Station Schoharie Co, NY Prepared for NextEra Energy Prepared by TRC 10 Maxwell Drive Clifton Park NY 12065 Project # 327851 June 2019

Upload: others

Post on 12-May-2020

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SUBSTATION DESIGN CRITERIA DOCUMENT€¦ · The load on the insulator (cantilever, tension, compression, torsion) shall not exceed the respective insulator strength published in ANSI

SUBSTATION DESIGN CRITERIA

DOCUMENT

East Point Collector Station

Schoharie Co, NY

Prepared for

NextEra Energy

Prepared by

TRC 10 Maxwell Drive

Clifton Park NY 12065

Project # 327851

June 2019

Page 2: SUBSTATION DESIGN CRITERIA DOCUMENT€¦ · The load on the insulator (cantilever, tension, compression, torsion) shall not exceed the respective insulator strength published in ANSI

NextEra Energy June 2019

East Point Revision 0

Substation Design Criteria

i

REVISION INDEX

Written by: Andrew Dion, PE - TRC Date: April 1, 2019

Revised by: Date:

Reviewed by: D. R. Gilman Date: April 17, 2019

Approved by: Date:

Revision Description Date

0 Issued for Project Record June 20, 2019

Page 3: SUBSTATION DESIGN CRITERIA DOCUMENT€¦ · The load on the insulator (cantilever, tension, compression, torsion) shall not exceed the respective insulator strength published in ANSI

NextEra Energy June 2019

East Point Revision 0

Substation Design Criteria

Page 1 of 8

Design Criteria Document

Substation Systems

Project: East Point Collector Substation

Client: NextEra Energy

Project Location: Schoharie Co, NY

Date: June 2019

Revision: 0

General Description

Summary East Point Collector Substation will be designed and built to collect roughly 50MW of PV solar power

located in upstate New York and transmit to a nearby 69kV interconnection point. The 110’ x 144’

substation yard will consist of two (2) incoming 34.5kV collector line feeders, each with circuit breaker

protection feeding onto the substation bus and through a 69-34.5kV Power Transformer with associated

69kV high voltage circuit breaker, disconnect switches, instrument transformers and revenue metering.

Page 4: SUBSTATION DESIGN CRITERIA DOCUMENT€¦ · The load on the insulator (cantilever, tension, compression, torsion) shall not exceed the respective insulator strength published in ANSI

NextEra Energy June 2019

East Point Revision 0

Substation Design Criteria

Page 2 of 8

Standards and Reference Documents

Applicable federal, state, and local codes and standards shall also be observed. A summary of the

industry codes and standards to be used are as follows:

Industry References ANSI American National Standards Institute

NEMA National Electrical Manufacturers Association

NESC National Electrical Safety Code

NEC National Electrical Code

RUS 1724E-300 U.S. Dept. of Agriculture Design Guide for Rural Substations

AISC American Institute of Steel Construction

ASTM American Society for Testing and Materials

ACI American Concrete Institute

AWS American Welding Society

IEEE Institute of Electrical and Electronics Engineers

CSI Construction Specifications Institute

NFPA National Fire Protection Association

IES Illuminating Engineering Society

ASCE American Society of Civil Engineers

NPCC Northeast Power Coordinating Council

Page 5: SUBSTATION DESIGN CRITERIA DOCUMENT€¦ · The load on the insulator (cantilever, tension, compression, torsion) shall not exceed the respective insulator strength published in ANSI

NextEra Energy June 2019

East Point Revision 0

Substation Design Criteria

Page 3 of 8

Design Criteria & System Parameters

System Parameters – 69kV System

Nominal Voltage 69kV Line to Line

Maximum Design Level Voltage 72kV

Basic Impulse Level 350kV

Design Continuous Amperage 1200 Amps

Fault Current Level (Equipment) 40kAIC (RMS Symmetrical)

Grounding Grounded Wye

Post Project 3 Phase-Fault Current 20kA (3L-Gnd)

3 Phase Fault Current for Bus Design 30kA

Post Project 1 Line to Gnd. Fault Current 17.5kA

L-Gnd. Fault Current for Ground Grid Design 20kA

Min. Withstand Fault Capability:

• Short Time 38kA

• RMS Asymmetrical (Momentary) 61kA

• Peak Asymmetrical 99kA

Post Project Line-Line Fault Current 30kA

System Parameters – 34.5kV System

Nominal Voltage 34.5kV Line to Line

Maximum Design Level Voltage 35kV

Basic Impulse Level 200kV

Design Continuous Amperage 1200 Amps

Fault Current Level (Equipment) 40kAIC (RMS Sym)

Grounding Effectively Grounded

Post Project 3 Phase-Fault Current 20kA (3L-Gnd)

3 Phase Fault Current for Bus Design 25kA

Post Project 1 Line to Gnd. Fault Current 17.5kA

L-Gnd. Fault Current for Ground Grid Design 20kA

Min. Withstand Fault Capability:

• Short Time 38kA

• RMS Asymmetrical (Momentary) 61kA

• Peak Asymmetrical 99kA

Post Project Line-Line Fault Current 30kA

Listed design values to be validated and updated during detail engineering based on System

Impact Study (SIS) and corresponding Aspen fault model for the collector substation.

Page 6: SUBSTATION DESIGN CRITERIA DOCUMENT€¦ · The load on the insulator (cantilever, tension, compression, torsion) shall not exceed the respective insulator strength published in ANSI

NextEra Energy June 2019

East Point Revision 0

Substation Design Criteria

Page 4 of 8

Electrical Clearances

Yard Clearances The substation shall be designed to provide at a minimum, the yard clearances and spacing in Table 1-1.

Equipment spacing shall be in accordance with the applicable codes.

Table 1-1

Yard Minimum Clearances

Nominal Operating

Voltage (Ph-Ph)1,2,

kV Nom

Basic Impulse Level

(BIL)1,2, kV Peak

Minimum Phase-to-

Phase, Metal-to-

Metal, Inches1

Phase-to-Ground,

Metal-to-Metal,1

Inches

69 350 31 25

34.5 200 18 15 1 ANSI C37.32 2 NESC, Section 12

Outdoor Bus Clearances & Spacings

Standard Phase Spacings 69kV 8’ – 0”

34.5kV 3’ – 0”

The substation bus shall be designed to maintain the clearances and spacing in Table 1-2. The values

given below shall be treated as the minimum allowed.

Table 1-2

Minimum Bus Clearances (Outdoor)

Nominal

Operating

Voltage

(Ph-Ph),

kV Nom

Basic

Impulse

Level

(BIL),

kV Peak

Vertical

Clearance

of

Unguarded

Parts,2

Inches

Horizontal

Clearance

of

Unguarded

Parts,2

Inches

Vertical

Break

Disconnecting

Switches, 1

Inches

Side Break

Disconnecting

Switches,1

Inches

All Horn

Gap

Switches

(Vertical

and Side

Break),1

Inches

72.5 350 125 59 60 72 84

34.5 200 114 48 36 48 60 1 ANSI C37.32 2 NESC, Section 12

High & Medium Voltage Bus System & Hardware

Bus Tubular bus fittings shall be 360 degree circumferential swage 2 piece compression type with NEMA

configured equipment terminal pad configurations as manufactured by DMC or approved equal. All

tubular bus spans exceeding 20’ shall include 795KCM AAC dampening cable for Aeolian vibration

control. Bus supports shall be bolted aluminum two piece ring type - capable of either slip of fixed

Page 7: SUBSTATION DESIGN CRITERIA DOCUMENT€¦ · The load on the insulator (cantilever, tension, compression, torsion) shall not exceed the respective insulator strength published in ANSI

NextEra Energy June 2019

East Point Revision 0

Substation Design Criteria

Page 5 of 8

support with anti-chatter springs. The 34.5kV tubular aluminum bus will be 2 or 4 inch I.P.S., and will

transition to 1272KCM or 795KCM AAC to 69kV and 34.5kV yard equipment.

Conductors

69kV conductor leads for the yard equipment will be (1) 1272KCM AAC. Transformer conductor leads

will be (1) 1272KCM AAC.

34.5kV conductor leads for the cable terminators and surge arresters will be (1) 1272KCM AAC.

Transformer conductor leads will be (1) 1272KCM AAC.

Insulators The load on the insulator (cantilever, tension, compression, torsion) shall not exceed the respective

insulator strength published in ANSI C29.9, Tables 1 or 2. All insulators for the rigid bus system and

disconnect switches shall be porcelain station post, standard creep, and shall be ANSI 70 gray in color.

Standard strength, High strength or Extra-high strength insulators will be specified according to project

criteria resulting from three phase symmetrical bus design fault current.

Apparatus Insulators (69kV):

• Nominal Voltage 69kV

• Type Station Post

• BIL 350kV

• Color ANSI-70

• Cantilever Strength 1500/3000 lbs standard/high strength

• NEMA TR No. 216/278

Apparatus Insulators (34.5kV):

• Nominal Voltage 34.5kV

• Type Station Post

• BIL 200kV

• Color ANSI-70

• Cantilever Strength 2000 lbs minimum (standard strength)

• NEMA TR No. TR-210

Page 8: SUBSTATION DESIGN CRITERIA DOCUMENT€¦ · The load on the insulator (cantilever, tension, compression, torsion) shall not exceed the respective insulator strength published in ANSI

NextEra Energy June 2019

East Point Revision 0

Substation Design Criteria

Page 6 of 8

Major Equipment

(1) - 69/34.5/13.8kV Power Transformer • Vendor TBD

• High Voltage 69kV Grounded-Wye

• Low Voltage 34.5kV Grounded-Wye

• Ter. Voltage 13.8kV Delta (Buried)

• MVA 36/48/60

34.5kV Switch • Vendor TBD

• Type Vertical Break

• Voltage 38kV

• BIL 200kV

• Cont. Current 1200A

• kA Mom. 61kA

69kV Operated Line Switch • Vendor TBD

• Type Vertical Break

• Voltage 69kV

• BIL 350kV

• Cont. Current 1200A

• kA Mom. 61kA

• Control Volt. 125VDC

69kV Transformer Switch • Vendor TBD

• Type Center Break

• Voltage 69kV

• BIL 350kV

• Cont. Current 1200A

• kA Mom. 61kA

69kV Ground Switch • Vendor TBD

• Type Vertical Break

• Voltage 69kV

• BIL 350kV

• kA Mom. 61kA

Page 9: SUBSTATION DESIGN CRITERIA DOCUMENT€¦ · The load on the insulator (cantilever, tension, compression, torsion) shall not exceed the respective insulator strength published in ANSI

NextEra Energy June 2019

East Point Revision 0

Substation Design Criteria

Page 7 of 8

AC Station Service

Design Criteria The AC station service system shall be sized to accommodate all new and known future substation AC

power requirements. AC Station service will be established from two independent sources.

The Primary station service will originate from the 34.5kV bus and feed a single phase 25kVA

transformer. A 240/120V grounded-wye, 1 phase, 3 wire secondary will be derived and used as the

Primary station service.

The Alternate station service will originate from a nearby distribution line or emergency generator and

will be selected during the detailed design process.

An automatic transfer switch (ATS) will be installed and fed from the two independent station service

sources.

Substation Lighting

Design Criteria All interior building and exterior yard lighting will be designed per NextEra Energy or applicable

industry standard. Outdoor Yard lighting designed to a 2.4 foot-candle average, and will be building

wall, and pole structure mounted. Light fixture maintenance can be accomplished with equipment / bus

in service by qualified personnel.

Materials • Building Entry Light, Wallpack, 70W, HPS, with Full Visor

o Lithonia TWA-70S

• Floodlight, 250W, HPS

o Lithonia TFLU-250S

Direct Stroke Protection

Design Criteria A three (3) 60ft. lightning mast will be utilized for the direct stroke protection. The analysis of then

lightning protection for the substation yard will employ IEEE-998 “Rolling Sphere method” for the

69kV voltage level and “Fixed Angle method” for the voltages below 69kV.

Grounding

Design Criteria

The fault current that will be used for grounding system design will be based on 20 kA. IEEE-80

Standard current split factor will be used to determine the return ground current.

Page 10: SUBSTATION DESIGN CRITERIA DOCUMENT€¦ · The load on the insulator (cantilever, tension, compression, torsion) shall not exceed the respective insulator strength published in ANSI

NextEra Energy June 2019

East Point Revision 0

Substation Design Criteria

Page 8 of 8

Subgrade Grounding A 4/0 (19 strand) copperweld conductor will be installed 18” below finish yard grade. The 4/0

conductor will be arranged throughout the yard in an overlapping rectangular grid pattern, extending 3

feet beyond the fenceline (including gate swing radius), with 20 foot by 20 foot spacing as determined

by design software. The grid spacing will be closer in the proximity of electrical equipment, and will be

connected at all conductor intersections. Two (2) steel copper clad ground rods ¾” x 10’, with threaded

couplings will be installed as dictated by design software and client standards throughout the yard area

connected to the 4/0 grid, to enhance the grid system’s effectiveness, by penetrating into stable & lower

resistivity unfrozen soil layers. The sub-grade ground grid connectors will be the “Hyground irreversible

compression system” type - as manufactured by Burndy. All group operated airswitch mechanisms will

have personnel protection mats below grade (installed with 4” of crushed stone cover) at each operating

mechanism location. This protection mat will be connected to the operating handle, and to the ground

grid to maximize personnel protection from touch potentials. Connected pigtails (4/0 ) extending from

the subgrade grid to the base of equipment structures, and stands will bond all above grade facilities.

The below grade grounding conductor will loop around yard structures. The substation yard finish grade

will consist of a 4 inch layer of coarse crushed rock (3,000 OHM-meter), which is considered for safe

yard step and touch potentials.

Structure & Equipment Grounding Ground grid pigtails will connect to the base of structure legs using bronze bolted or copper compression

clamps as required at each leg for single and double leg structures, or at diagonally opposite legs for four

leg structures and stands. Bronze mechanical connectors will also support jacketed 4/0 copper

conductor to be run along structures and stands for grounding of equipment casings, surge arresters,

ground switches, and overhead shield wires.

Where aluminum structures are used, bolted connections will be used and connections will be plated to

accept copper conductors. Copper conductors shall be covered in solid dielectric insulation to avoid

dissimilar metal corrosion from the contact of aluminum and copper.

All above grade equipment will be properly bonded to the station ground grid using a continuous

conductor path.

Fence Grounding The substation perimeter fence posts will be bonded using 4/0 copperweld pigtails from the station

ground grid at regular intervals, and where each overhead transmission phase conductor (if applicable)

crosses the fenceline with bolted bronze pipe-type mechanical connectors. Fence corner and gate posts

shall be bonded directly to a ground rod. Gate frames and top rails will be bonded with 1/0 stranded

copper, with the gate frame using a high strand 600V welding cable for maximum flexibility.

Grounding of the chain-link fence, barbs, and bottom tension wire will be completed with a #2 stranded

bare copper conductor and tinned bronze split bolt mechanical connectors.

Page 11: SUBSTATION DESIGN CRITERIA DOCUMENT€¦ · The load on the insulator (cantilever, tension, compression, torsion) shall not exceed the respective insulator strength published in ANSI

34.5KV COLLECTOR LINE 2

(NOTE 2)

34.5KV COLLECTOR LINE 1

(NOTE 2)

0::: z 0::: z 0 oo 0-2 f- ~ w f--

u~ 8 [I] f- Wf-_J - (/) _J (/) _J 0::: >- _J [I] 0 f- (/) 0 ::::J u (/) u (/)

0

A

52-K2

(3) V.T.'S ¢-GND. 175: 1

0::: z oo f--u~ Wf-_J (/) _J [I]

0 ::::J u (/)

z 0 -<) (/) 2 (/) w 2f-(/) (/)

<) z>-<C (/) 0::: f-

()

<)

()

<)

<)

<)

<)

<)

<)

<)

<)

/ ( • ~ ~ .

---

--

• I •

~

V

-

' '

-

1h '

T cc VT

LEGEND OF SYMBOLS:

POWER TRANSFORMER (30)

SURGE ARRESTER

30 GROUND SWITCH

FAULT INT. DEVICE (CKT. BKR.)

30 GROUP OPER. AIRBREAK W/ ARCING HORNS

H.V. TERM. TO SOLID DI-ELECTRIC U.G. CABL::

COUPLING CAPACITOR VOLTAGE TRANSFORMER

REVENUE METERING

.·~ STATION SERVICE TRANSFORMER

FUSED DISCONNECT (HOOKSTICK)

VOLTAGE l / TRANSFORMER '/

(WOUND)

SUBSTATION FENCE - - c~ -

LINE DEMARCATION

DISCONNECT SWITCH, _/_ GROUP OPERERATED

1 2 ------ ---_f 3

I 1200A 1200A 1200A <)

:::r::

(3) 36KV DUTY CYCLE 29KV MCOV

INT. CL.

(/) ::::J rn

3 2 1

T1 1-3¢

34.5-13.8-69KV Y-6-Y

<)

<)

<)

<)

(3) <)

36/48/60MVA T1 H EM @, ~~~a; -,<Ji 52-K1 i < > i 1200A KXXX-1 'Y' A T /, <) i 69kV

- -_L_--'3=---1-+----1-200 ~A------<1200

1-A--1~200-A---+-------tt-( ¢-2-) --------+---3=--(➔ )<---3--------~ ~-----<

12001-A-+-+_-!H-_~~-,_....,. '----,f-) -----=-3- LINE XXX

X1 X2 H1 H2 -- --:::c X3 XO H3 HO :::r::

- __ _t61KA :::r:: __ MOM. -:::r:: :::r::

(3) 36KV DUTY CYCLE 29KV MCOV

INT. CL.

<)T~C REV

A ISSUED FOR REVIEW

(3) 36KV DUTY CYCLE 29KV MCOV

INT. CL.

--

(3) 36KV DUTY CYCLE 29KV MCOV

STA. CL.

(1) 25KVA STA. SERV. 19920-120Y

T2 T1

T3

AC DIST PNL

/240V ATS

--(3) 72KV

DUTY CYCLE 48KV MCOV

STA. CL.

DISTRIBUTION LINE (~1) ))-------t,-.N r--~-- OR

249 Western Avenue

Augusta, ME 04330

DESCRIPTION

EMER. GENERATOR

PROJECT NO: 327851

DATE DES CHK APP

06/20/19 AAD DG AKD

(3) 72KV DUTY CYCLE 48KV MCOV

STA. CL.

MD/TRC DESIGNED

MD/TRC DRAWN

DG/TRC CHECKED

AKD/TRC APPROVED

REVIEW 1

REVIEW2

<)

<)

<)

<)

<)

<)

<)

<)

<)

<)

REFERENCE DRAWINGS: 327851-101 - EAST POINT GENERAL ARRANGEMENT PLAN 327851-102 - EAST POINT ELEVATIONS & SECTIONS A-A, B-B 327851-103 - EAST POINT SECTIONS C-C, D-D 327851-104 - EAST POINT YARD LIGHTING PLAN 327851-105 - EAST POINT FENCE & GROUNDING PLAN 327851-106 - EAST POINT FENCE & GROUNDING DETAILS 327851-107 - EAST POINT CONTROL HOUSE ELECTRICAL LAYOUT PLAN

NOTES:

1. THIS DESIGN ASSUMES EACH WIND-TURBINE GENERATOR STEP-UP OPERATES WYE-WYE WITH FOUR WIRE COLLECTOR LINES TO COLLECTOR SUBSTATION FOR A SOLIDLY GROUNDED FACILITY AT 34.5KV. NO GROUND BANK IS SHOWN UNDER THIS ASSUMPTION.

2. VOLTAGE WILL BE REGULATED AT EACH COLLECTOR LINE BY FEEDER NETWORK INVERTERS.

PRELIMINARY EAST POINT

34.5KV/69KV COLLECTOR SUBSTATION

POWER ONE-LINE DIAGRAM

SCHOHARIE COUNTY NEW YORK

06/20119 DATE

NONE SCALE

<)T~C 327851-100

REV.

A

Page 12: SUBSTATION DESIGN CRITERIA DOCUMENT€¦ · The load on the insulator (cantilever, tension, compression, torsion) shall not exceed the respective insulator strength published in ANSI

z:

ADJUST DIRECTION OF NORTH ARROW

AS NEEDED

51'-0"

"' C D "' 0 0 - -~ ~r 7~ -

i """ """

~ J I . I

[U~. ,..----, F F F 2'-10"

-

9 -"" -N

wb a:- [I] z _, cc ::J ... -0 .- [l] 06 ()._ w _, cc ~ ... ~ -0 ~- - [l]

0 _, ... ~ ~TI -

EX EX EX [U1 1

' ;;;=9 a:-w 00

cc_ [I] z

~~w.===:======>\llJ~[ ]!!\\J>7·· r====c: •~---c"~---,----~Jt SUBSTATION [[ _]

~· "' ' 1-;

' - ,.,, ::J ' - ' -

.cl ' ' ~ [l] u w ~ ~. a:-oo cc_ u _,

[l] - 00

- - -- - -- -1---t-----i~+-!!~ff'l~~==:==: :3_~:Bt IIIUG'

BASELINE ~*:::::;==,½Ajlij; ~i~; ~==;:=~-}:,;;,..,,1ilr AL w 2'-10"

f] , ,-, ' '"'' L

(=:

- =

-~ s s s~

327851-102 iLJ'-- :__ r ~

Fl II J7 • 1=:i

© . ~LIGHTNING

MAST

.

144'--0"

I

I I [I]

~ ' ,I(!

i I

4~*~~~ . . ~ ~Ll~ s

\ ... ". 1·"."J ' _;/F =\i :, [l] ~~ -

·~ ij w

I

I

--~,,.~-J..,~,- r -~;...~,-J~'P ,o

[l] s I

I

, CABLE RISER & SUPPT. STR.

COLLECTOR BUS STR.'S

BUS SUPPORT

l TRANSFORMER C SWITCH STAND _ CKT. BUS - SUPP.

-

-

~0'-0"

CONTROL HOUSE 14' X 28'

14•.o·

i

12'-0"

I I

I

zl ow -z f-_ <C _J >-w g:i I :{2 ::::, rn (f)

& LIGHTNING MAST BKR.

16'-0" 13•.o· 6'-0"

PLAN VIEW

REFERENCES

-~

,. ·/

-

-= =

INSTR. TFMR.

= =

= =

I. /. h-t: ;,-]I,

"' •,

~LIGHTNING MAST

ccvr/SA & LIGHTNING MAST

10'-0"

i' T~C ~1 REV

A ISSUED FOR REVIEW

SWITCH STAND

l

~ 00

~ 00

- -

20'-0"

B N 0

7~ "'

[I] --:-~~

F

I.,., [l]

l "F

~~::~ QJ F

BUS C SUPP.

5'-0" l

~ 23'--0" A / e·-o·

249 Western Avenue

Augusta, ME 04330

DESCRIPTION

TO 69KV -------SWITCHYARD

_jA 327851-102

PROJECT NO: 327851

DATE DES CHK

06/20/19 MD DG

SUBSTATION BASELINE

APP

AKD

NOTES: 1. BUS SUPPORTS PROVIDED AND INSTALLED AS SHOWN FOR

THE FOLLOWING 1YPES: F-FIXED BUS SUPPORT S-SLIP BUS SUPPORT EX-EXPANSION BUS SUPPORT

2. CLEARANCES FOR ALL BUS & CONDUCTOR TO BE PER VALUES PUBLISHED IN ANSI C37.32 TABLE 5:

69KV-PHASE TO PHASE 7'-0" (CENTERLINE-CENTERLINE) -PHASE TO GROUND 2'-1" (METAL TO METAL)

34.5KV-PHASE TO PHASE 3'-0" (CENTERLINE-CENTERLINE) -PHASE TO GROUND 1 '-3" (METAL TO METAL)

3. WIRE CONDUCTOR MINIMUM BEND RADIUS TO BE INSTALLED NO LESS THAN:

1272KCM-20 INCHES 336KCM-10 INCHES 4/0 COPPER-8 INCHES 2/0 COPPER-6 INCHES 1/0 /W.C-5.5 INCHES #2 COPPER-4 INCHES

REFERENCE DRAWINGS: 327851-100 - EAST POINT POWER ONE LINE DIAGRAM 327851-102 - EAST POINT ELEVATIONS & SECTIONS A-A, B-B 327851-103 - EAST POINT SECTIONS C-C, D-D 327851-104 - EAST POINT YARD LIGHTING PLAN 327851-105 - EAST POINT FENCE & GROUNDING PLAN 327851-106 - EAST POINT FENCE & GROUNDING DETAILS 327851-107 - EAST POINT CONTROL HOUSE ELECTRICAL LAYOUT PLAN

I I 0 5 10 15 20 30

SCALE (FEET) ½" = 1'-0"

PRELIMINARY MDITRC EAST POINT DESIGNED

MDITRC 34.5KV/69KV COLLECTOR SUBSTATION DRAWN

DGITRC GENERAL ARRANGEMENT PLAN

CHECKED 1 TRANSFORMER DESIGN AKDITRC APPROVED

SCHOHARIE COUNTY NEW YORK

06/20/19 ¢)T~C REV.

REVIEW 1 DATE 327851-101 A 1/8"=1'-0"

REVIEW2 SCALE

Page 13: SUBSTATION DESIGN CRITERIA DOCUMENT€¦ · The load on the insulator (cantilever, tension, compression, torsion) shall not exceed the respective insulator strength published in ANSI

8'-0" CHAIN LINK FENCE (TYP.)

/

,, i'•t:,, "

42'-0~

5' 0 w

I

I

!}] YARD LIGHT , f_J!OUNTING

' 5' 0 M

'

I

LIGHTNING MAST

28'-G•

110'-0"

34.5KV UNDERGROUND

COLLECTOR LINES

25'-0"

15'-0"

8'-0"

SECTION B-B

CABLE RISER & SUPPT. STR.

10'-0"

8'-0"

--BUS SUPPORT

/3" SPS ALUM TUBE

COLLECTOR BUS STR.'S

14'-0"

[j]

,_

,-

I ~

If_ BUS SUPPORT

12'-0"

YARD LIGHT ';\\ MOUNTING ~1

REFERENCES

2-1272KCM MC

· I

~~1. 11, \~Jzu YARD LIGHT "1 f, MOUNTING

I I

1272KCM MC

Pc 1 r~ t;Jt - . '

II [

,,

TRANSFORMER If_ SWITCH STAND I

CKT. BKR.

,I

5' 0 w

~ LIGHTNING MAST

6'-0"

& LIGHTNING MAST

16'-0" 13'-0"

144'-0"

ELEVATION A-A

/

8'-0" CHAIN LINK FENCE (TYP.)

<)T~C 249 Western Avenue

Augusta, ME 04330

~------" 3" SPS \ /3 ½" SPS r-ALUM TUBE ALUM TUBE

,--~==,,~=~-?"~/=¥~~~~~-'===~===-~======,,?""'===~TO 69KV SWITCHYARD

,_

/' .. _j_ \\ I

C BUS I INSTR. SUPPORT

13'-0" 6'-0" 6'-0"

FMR.

b _,- c:..

~ ·' w fl

,;:;

CCVT/SA

10'-0"

J_

9

" ,;:;

SWITCH STAND

PROJECT NO: 327851

23'-0"

C BUS SUPPORT

6'-0"

/ •'

8'-0" CHAIN LINK FENCE (TYP.)

MDITRC DESIGNED

MDITRC DRAWN

NOTES: 1. BUS SUPPORTS PROVIDED AND INSTALLED AS SHOWN FOR

THE FOLLOWING TYPES: F-FIXED BUS SUPPORT S-SLIP BUS SUPPORT EX-EXPANSION BUS SUPPORT

2. CLEARANCES FOR ALL BUS & CONDUCTOR TO BE PER VALUES PUBLISHED IN ANSI C37.32 TABLE 5:

69KV-PHASE TO PHASE 7'-0" (CENTERLINE-CENTERLINE) -PHASE TO GROUND 2'-1" (METAL TO METAL)

34.5KV-PHASE TO PHASE 3'-0" (CENTERLINE-CENTERLINE) -PHASE TO GROUND 1 '-3" (METAL TO METAL)

3. WIRE CONDUCTOR MINIMUM BEND RADIUS TO BE INSTALLED NO LESS THAN:

1272KCM-20 INCHES 336KCM-10 INCHES 4/0 COPPER-8 INCHES 2/0 COPPER-6 INCHES 1 /0 AMC-5.5 INCHES #2 COPPER-4 INCHES

REFERENCE DRAWINGS: 327851-100 - EAST POINT POWER ONE LINE DIAGRAM 327851-101 - EAST POINT GENERAL ARRANGEMENT PLAN 327851-103 - EAST POINT SECTIONS C-C, D-D 327851-104 - EAST POINT YARD LIGHTING PLAN 327851-105 - EAST POINT FENCE & GROUNDING PLAN 327851-106 - EAST POINT FENCE & GROUNDING DETAILS 327851-107 - EAST POINT CONTROL HOUSE ELECTRICAL LAYOUT PLAN

I I 0 5 10 15 20

SCALE (FEET) ½" = 1'-0"

PRELIMINARY EAST POINT

34.5KV/69KV COLLECTOR SUBSTATION

ELEVATIONS & SECTIONS A-A, B-B

30

REV DESCRIPTION DATE DES CHK APP DG/TRC CHECKED

A ISSUED FDR REVIEW 06/20/19 MD DG AKD

AKDITRC APPROVED

REVIEW 1

REVIEW2

1 TRANSFORMER DESIGN SCHOHARIE COUNTY

06/20/19 DATE

118"=1'-0" SCALE

<)T~C 327851-102

NEW YORK

REV.

A

Page 14: SUBSTATION DESIGN CRITERIA DOCUMENT€¦ · The load on the insulator (cantilever, tension, compression, torsion) shall not exceed the respective insulator strength published in ANSI

336KCM MC

I --

VT~ NOTE 4

VT J,B.

~ - . n. ~

-

1. (i, 34.5KV

COLUMN

16'-0"

4" SPS ,,r ALUM

/ TUBE

-·.

--

,.

-

.1.

; , \', i / \ \ /,' •\ .. '

COLLECTOR LINE 2 (i, 34.5KV

[l] [1] ,o. .o. ,~""\~ ~,·~~

\ '\ .. \\ // . . /• // ..

l/ ',\ .. ..

•j . . ·.,

COLUMN

SECTION C-C LINE-SIDE

[I] .o. 4" SPS "~'<~

// .. '\

TUBE

-

16'-0"

COLLECTOR LINE

[l] .0------------,..,,.__..,

'i \ \ .

- -- -

1

~ ----+-----L

'•

,.

.1 (i, 34.5KV

COLUMN

336KCM MC

~--- ·1-------->;:1-------------''----.r-"----Q.------'-----~--__;;;;l---.,l

ALUM~ /~/ \s .. '

~ ~---+--- -L

336KC MC

ARRESTER'S,'

. -

I

~

(i, 34.5KV COLUMN

l

1272KCM ;

1272KCM ;

- -MC---

L MC---

L 336KCM

(1YP.) (1YP.) MC

[l] [1] [I] [l] [1] [I]

0 VT NOTE 4

···, R VT J.B.

,,-, .. ,,-, .. ~ ft

~

1.

- -

I

-

16'-0" 16'-0"

COLLECTOR LINE 1 (i, 34.5KV COLLECTOR LINE 2 (i, 34.5KV COLUMN

SECTION D-D BUS-SIDE

REFERENCES

COLUMN

i' T~C 249 Western Avenue

~1 Augusta, ME 04330

REV DESCRIPTION

A ISSUED FOR REVIEW

MDITRC DESIGNED

MDITRC PROJECT NO: 327851 DRAWN

DG/TRC DATE DES CHK APP CHECKED

AKDITRC APPROVED

REVIEW1

06/20/19 MD DG AKD REVIEW2

NOTES: 1. BUS SUPPORTS PROVIDED AND INSTALLED AS SHOWN FOR

THE FOLLOWING 1YPES: F-FIXED BUS SUPPORT S-SLIP BUS SUPPORT EX-EXPANSION BUS SUPPORT

2. CLEARANCES FOR ALL BUS & CONDUCTOR TO BE PER VALUES PUBLISHED IN ANSI C37.32 TABLE 5:

115KV-PHASE TO PHASE 7'-0" (CENTERLINE-CENTERLINE) -PHASE TO GROUND 2'-1" (METAL TO METAL)

34.5KV-PHASE TO PHASE 3' -0" (CENTERLINE-CENTERLINE) -PHASE TO GROUND 1'-3" (METAL TO METAL)

3. WIRE CONDUCTOR MINIMUM BEND RADIUS TO BE INSTALLED NO LESS THAN:

1272KCM-20 INCHES 336KCM-10 INCHES 4/0 COPPER-8 INCHES 2/0 COPPER-6 INCHES 1 /0 AAAC-5.5 INCHES #2 COPPER-4 INCHES

4. BUS TIE VOLTAGE TFMRS. TO BE INSTALLED H1-PHASE HZ-GROUND.

REFERENCE DRAWINGS: 327851-100 - EAST POINT POWER ONE LINE DIAGRAM 327851-101 - EAST POINT GENERAL ARRANGEMENT PLAN 327851-102 - EAST POINT ELEVATIONS & SECTIONS A-A, B-B 327851-104 - EAST POINT YARD LIGHTING PLAN 327851-105 - EAST POINT FENCE & GROUNDING PLAN 327851-106 - EAST POINT FENCE & GROUNDING DETAILS 327851-107 - EAST POINT CONTROL HOUSE ELECTRICAL LAYOUT PLAN

~- I I I I 0 5 10 15 20

SCALE (FEET) ~" = 1'-0"

PRELIMINARY EAST POINT

34.5KV/69KV COLLECTOR SUBSTATION

SECTIONS C-C, D-D

1 TRANSFORMER DESIGN SCHOHARIE COUNTY NEW YORK

06/20/19 ¢)T~C REV.

DATE 327851-103 A 3/16"=1'-0'

SCALE

Page 15: SUBSTATION DESIGN CRITERIA DOCUMENT€¦ · The load on the insulator (cantilever, tension, compression, torsion) shall not exceed the respective insulator strength published in ANSI

z 0 w -z f- -<( _J >-w Cf) Cf)

ADJUST DIRECTION ml<( :::J (I]

OF NORTH ARROW Cf)

AS NEEDED YARD LIGHTING SCHEDULE

I 1.0 1.3 1.8 1 2.9 1 3.3 2.2 ~-2 1 2.3 1 3.4 3.1 2.1 0.8 LIGHT NO. TYPE WATTAGE

MOUNTING ORIENTATION

I ILi CA~cL; HEIGHT /DEGREES) CCT.

YL 1 TFLU 250S 250W 30FT 40 60 ---

YL2 TFLU 250S 250W 30FT 320 60 ---

I I

/s,j ?@\ < •

YL3~ '\,'\._ YL 4 YL3 TFLU 250S 250W 30FT 220 60 ---

YL4 TFLU 250S 250W 30FT 140 60 ---YL5 TFLU 250S 250W 30FT 90 60 ---

I 1.4 1 3.7 1 5.4 1 . .4 6.9 4.7 1 7.0 1 6.2 4.1 2.8 1.0 YL6 TFLU 250S 250W 30FT 0 60 ---

CHL1 TWA 70S 70W 1 OFT --- --- ---

CHL2 TWA 70S 70W 1 OFT --- --- ---I

I I

STATISTICS - OVERALL SITE

+1. +3.9 +5.4 7.8 4.5 3.7 1.3 DESCRIPTION SYMBOL AVERAGE MAXIMUM MINIMUM MAX/MIN AVERAGE/MIN

SITE + 3.4 fc 9.6 fc 0.2 fc 48.0:1 17.0:1

' ====H== '

+3. .1 + 1.6 o· SUBSTATION SUBSTATION --- ---

BASELINE - "-"- ~! BASELINE

piiiJI ¼i~, ~·-. o·

I 5.1 .9 1 6.0 I 270 90'

1 5.6 1 7.0 1 5.0 1 6.8 1 7.3 1 4.7 o·

6.9 8.5 3.9 4.1 7.9 7.5 2.5 180'

8L6 YL2 ~" . .t~f YL 1 YARD LIGHT YARD LIGHT

+1.6 -.<·.~ +6.2 +4, I +4.4 +5.1 +4.1 +4.1 TILT ORIENTATION ANGLE 7.0 3.3 3.5 -3.3~2.4 2.4 @D .

Ii - ~

+3.! LEGEND

+1.1 2.0 5.5 +5.4 3.0 2.6 +2.5 +1.7 1.1 0.8 + 1.0 +1.4 1.4 I

@) "A" LIGHT FIXTURE, LITHONIA CONTOUR TFLU-250S (WOOD POLE MOUNTED)

I

I 1.2 2.6 4.2 1 4.4 1 4.1 2.5 1.6 I 1.2 1 0.9 0.7 0.5 1 0.4 1 0.4 0.4 @) "c" LIGHT FIXTURE, LITHONIA CONTOUR TWA-70S (BUILDING MOUNTED)

I NOTES: I

I 1 . 13.$ 1.7 1.1 1 0.8 1 0.6 0.5 0.4 1 0.3 1 0.3 0.3 1. YARD FLOOD FIXTURES YL-1, YL-2, YL-3, YL-4, YL-5 & YL-6 ARE MOUNTED 30'-0" ABOVE FINISHED GRADE. 2. EXTERIOR CONTROL HOUSE FIXTURES ARE MOUNTED 10'-o" ABOVE FINISHED GRADE.

I 3. INCIDENT LIGHT LEVEL POINTS ARE SPACED AT 10' X 1 O'. 4. THE AVERAGE ILLUMINATION IN THE SUBSTATION YARD IS 3.4 FOOTCANDLES. 5. YARD LIGHTING CONTROL EQUIPMENT IS DEFINED ON DWG. 327851-XX. 6. LIGHTING CALCULATIONS WERE PERFORMED USING VISUAL 2016, VERSION 2.08. 7. OVERALL SITE LAYOUT INCLUDES PROPOSED PERIMETER AND PROPOSED WORK LIGHTING.

+4.0 + 1.9 + 1.~ +0.6 +0.5 +0.3 +0.2 +0.2 8. PERIMETER LIGHTING CONTROL OPTIONS ARE ON/OFF /AUTO.

2.5 4.4 1.0 0.8 0.4 0.3 9. WORK LIGHTING CONTROL OPTIONS ARE ON/OFF.

□v 61w REFERENCE DRAWINGS: -z f-_ <( _J 327851-100 - EAST POINT POWER ONE LINE DIAGRAM >-1w 327851-101 - EAST POINT GENERAL ARRANGEMENT PLAN

~I~ 327851-102 - EAST POINT ELEVATIONS & SECTIONS A-A, B-B :::J (I]

327851-103 - EAST POINT SECTIONS C-C, D-D Cf)

327851-105 - EAST POINT FENCE & GROUNDING PLAN 327851-106 - EAST POINT FENCE & GROUNDING DETAILS 327851-107 - EAST POINT CONTROL HOUSE ELECTRICAL LAYOUT PLAN

PLAN VIEW

~-~ I I

0 5 10 15 20 30

SCALE (FEET) ½" = 1'-0"

PRELIMINARY

.. , T~C MDITRC EAST POINT 249 Western Avenue DESIGNED

~1 Augusta, ME 04330 MDITRC 34.5KV/69KV COLLECTOR SUBSTATION PROJECT NO: 327851 DRAWN

DGITRC YARD LIGHTING PLAN

REFERENCES REV DESCRIPTION DATE DES CHK APP CHECKED 1 TRANSFORMER DESIGN AKDITRC APPROVED

SCHOHARIE COUNTY NEW YORK

06/20/19 ¢)T~C REV.

REVIEW1 DATE 327851-104 A 1/8"=1'-0"

A ISSUED FOR REVIEW 06/20/19 MD DG AKD REVIEW2 SCALE

Page 16: SUBSTATION DESIGN CRITERIA DOCUMENT€¦ · The load on the insulator (cantilever, tension, compression, torsion) shall not exceed the respective insulator strength published in ANSI

ADJUST DIRECTION OF NORTH ARROW

AS NEEDED

SUBSTATION ---------BASELINE

(

~

~

3•-0· 3'-0" 9•-0·

I'\ - -v

H ~

t

t--

V

----

t-, t V

~-I,

20'-0"

- - " '-.,,I

t

I I I I

~ I I

~ I

I I I I I I I I

- -I I I I

l~ I I

~ I

I I I I I I -

~ - I

I ---- - -I L..J

~ I

I I I I

I I I I I I I I I I I I

t - - ◄

I- - -7

I I

I- - - _J

t ◄

t

._...__

CONTROL HOUSE FOUNDATION

• ►,--..._

V J,. " l j '-J

20'-0"

I

I -I I

C

- -

◄ I

'

' /

zl o 1w -z ';;;:I_J f- w (f) (f) ffi<( :::, m Cfll

I

-

t I

I I

I t

I I

I I

I I

I • I

---j-~I

'

I I

t

I

I I

I I

I ' t

I I

I I

I I

I

I I

I I

t

'

zl olw -z f-_ <(_j f-W (f) (f)

~io§

' '-

20'-0" 20'-0"

' ~

\ '/

- - - -

- - -7

) I ,---I I I I· 'I

I I I I I ------- -------I I

- - -7 I I

r1 I I 1- I I I I

'

/_ - ~ - _J ,_ - ,-

I :, -

PLAN VIEW

20'-0" 20'-0" 9'-0" 3•-0· 3'-0"

- - " - - - - ' ' '-.,,I '- / ~

◄~- ~ t ◄

9 "' -

◄ t ◄ ◄

6 _, 0

"'

t - -

~ -;- ~: r6: ~~1 ' - ◄ /'. " I IL __ _J

I I '

~; '- !I

I I I I I L - - _J

~ 'l I I I SUBSTATION ---------- --------- - - - ------I~ I ' - - 7 ~: I I I 11 - - 7 I I

I i' I

I I~ I 5'

_J~ 0

- _J L "'

BASELINE

L - _J '\

- - - t ◄ ◄

6 , -- 7 _, 0

"' I I I I L -- _J

◄ t ◄ ◄ ,--: " '- !I

5' 0

"'

~ -

◄ t ◄ ◄ ~ ~ A J)._

1~ /-1 'i ~ I

" L ~

'-J

YV ' '/

6 _, 0 -

() ' ' '-/

36'-0"

~, T~C 249 Western Avenue

~1 Augusta, ME 04330

PROJECT NO: 327851

REFERENCES REV DESCRIPTION DATE DES CHK

A ISSUED FOR REVIEW 06/20/19 AAD DG

~--~ 0 5

APP

AKD

LEGEND OF SYMBOLS:

SYMBOL DESCRIPTION MATERIAL MARK

--0-- 8' PERIMETER FENCE

GROUND CLAMP, GALV. PIPE TO CABLE (FOR LINE POST)

GROUND CLAMP, GALV. PIPE TO CABLE (FOR GATE POST)

GROUND CLAMP, GALV. PIPE TO CABLE (FOR INTERMEDIATE POST)

SPLIT BOLT CONNECTOR

2/0 COPPER GROUND STRAND SOFT DRAWN

4/0 COPPER GROUND WIRE 19 STRAND SOFT DRAWN

/ 4/0 COPPER WIRE PIGTAIL

GROUND CLAMP, GALV. PIPE TO CABLE

GROUND CLAMP, GALV. PIPE TO CABLE (FOR GATE FRAME)

CONNECTOR, GROUND, #2/0 TO GALV. PIPE

• 4/0 TO 4/0 COPPER WIRE CROSS CONNECTION

... 4/0 TO 4/0 COPPER WIRE TEE CONNECTION

■ 4/0 TO 1/0 COPPER WIRE TEE CONNECTION

BRAID,1%" X 18", TINNED COPPER, FERRULE ENDS,

I I I I I 4' X 6' COPPER WIRE SWITCH MAT

8 GROUND ROD LOCATION

@ FENCE POST

NOTES: 1. PERIMITER GROUND CONDUCTOR TO BE A CONTINUOUS LOOP. 2. THE GROUND GRID SHALL BE 4/0 COPPERWELD AND

BURIED AT A MINIMUM DEPTH OF 2'-0" BELOW GRADE.

GD1

G04

G05

GOB

GD7

G08

G09

G09

G10

G11

G12

G13

G13

G15

G16

G17

G20

TBD

3. TAPS FROM MAIN GRID SHALL BE AT LOCATIONS INDICATED TO GROUND STRUCTURE COLUMNS, EQUIPMENT, ETC.

4. PROVIDE TAPS FOR FENCE GROUND AT EACH GATE POST, CORNER POST AND FOR EVERY THIRD OR FOURTH LINE POST.

5. ALL TAPS SHALL EXTEND AT LIEAST 6'-0" ABOVE FINISHED GRADE (AFG), UNLESS OTHERWISE NOTED.

REFERENCE DRAWINGS: 327851-100 - EAST POINT POWER ONE LINE DIAGRAM 327851-101 - EAST POINT GENERAL ARRANGEMENT PLAN 327851-102 - EAST POINT ELEVATIONS & SECTIONS A-A, B-B 327851-103 - EAST POINT SECTIONS C-C, D-D 327851-104 - EAST POINT YARD LIGHTING PLAN 327851-106 - EAST POINT FENCE & GROUNDING DETAILS 327851-107 - EAST POINT CONTROL HOUSE ELECTRICAL LAYOUT PLAN

10 15 20 30

SCALE (FEET) ½" = 1'-0"

PRELIMINARY MDITRC EAST POINT DESIGNED

MDITRC 34.5KV/69KV COLLECTOR SUBSTATION DRAWN

DG/TRC FENCE & GROUNDING PLAN

CHECKED 1 TRANSFORMER DESIGN AKDITRC SCHOHARIE COUNTY NEW YORK

APPROVED

06/20/19 ¢)T~C REV.

REVIEW 1 DATE 327851-105 A 1/8"=1'-0"

REVIEW2 SCALE

Page 17: SUBSTATION DESIGN CRITERIA DOCUMENT€¦ · The load on the insulator (cantilever, tension, compression, torsion) shall not exceed the respective insulator strength published in ANSI

STATION GROUND GRID

PER GATE QUANTITIES G05 Qty 4 G10 Qty 2 G07 Qty 24 G11 Qty 2 GOB Qty 32' G09 Qty 20'

G12 Qty 2

G13 Qty 2

G16 Qty 4'

STATION GROUND GRID

/ G07 3

I "Y

El

G12

G13

FINISH GRADE

G16

I:

G05

G07 3

/ -

I ,·o I

·~G07

V

• V

G16

V •

GO7 .v.

G11

Gor----,,,.; • \ (rG11 . . ',.

"· I -, ,a

V

/ ·,' V

DETAIL "A" 24'--0" MAIN GATE GROUNDING

' _! __

FINISH GRADE

DETAIL "H" TYPICAL 115KV CCVTIIA

GROUNDING

OPERATOR ·~ GROUND BRAID

' lf

(NEAR-SIDE) --- ...,;-G17

(FAR-SIDE) • • •~5 G09 STATION GROUND GRID

G13 G13

DETAIL "F" TYPICAL GROUND DETAIL

AT WORM GEAR SW. OPER. MECH.

./ G07 3

I G12

, ,,..o"

G07

V

V V

V •

'>"/G01 1/ '-

• V

G01~

G13

G13

GOB

. .

G09

/

V / .

A . .

V ..

-_ FOR J.B. GND. I ----- SEE DETAIL 'I'

THISDWG

G09

TENSION WIRE

STATION

V

• • V

G09 STATION GROUND GRID

PER CORNER POST QUANTITIES G03 Qty 1 G09 Qty W G07 Qty 10 G12 Qty 2 G08 Qty 20' G13 Qty 1

G13

DETAIL "B" CORNER POST GROUNDING

WHEN GND. - 1 ----1 CONTINUES BEYOND J.B. ADD

1

STATION GROUND GRID

II

DETAIL "I"

1½' I i '

;.,

;.,

I

TYPICAL JUNCTION BOX GROUNDING

1¾" w·

I 11 1

1½'

--- - .. - - - - - t - • G13 ~ -ccg--m' ,,,·-rni~-m-=--i:a

GROUND ::~ _/ ~ ". \ '

G09 __,/ ··---~--•~• --~----~'

·---

1¾" ---W'

V's' I

Cf "[ ---- -v -

DETAIL "G" TYPICAL GROUND DETAIL

FOR CONTROL HOUSE GROUND BAR

REFERENCES

I

G01 --..__•,

TENSION------._ WIRE

A

• V

V • V

o, I

V

V /

• V /

G12

GO7

VL--G0B

. .. /

/

G09 STATION GROUND GRID

PER END POST QUANTITIES G04 Qty 1 G09 Qty 10' G07 Qty 6 G12 Qty 1 GOB Qty 8' G13 Qty 1

G13

DETAIL "c" END POST GROUNDING

4/0 CABLE TO 4/0 CABLE

CROSS OR TEE

4/0 CABLE TO ¾" GROUND ROD

f). -._--.~1 •._,,

V

-1 ' '

T~C 249 Western Avenue

Augusta, ME 04330

REV DESCRIPTION

A ISSUED FOR REVIEW

A

> '.

G01

TENSION---,_ ;, WIRE ".

V • ..

V

"' V /

X ·< GOB

✓ \

STATION GROUND GRID

PER INTERMEDIATE POST QUANTITIES G13

.. • V

GOB/

,'.

G09

V • V

V •

V

V

V

A

/ V

V A

G06 Qty 1 G12 Qty 1 G07 Qty 6 G13 Qty 1

G08Qty8' G09Qly 10'

DETAIL "D" INTERMEDIATE POST GROUNDING

GROUND PAD

TERM. 5&6

(2) .500-13UNC HOLES ON 1.75 [44.5] CENTERS 2 PLACES DIAGONALLY

OPPOSITE

TERM. 3&4

,, ;J ,! '1

,1==------'\-----,L---_cCt=J--1 ( l·I I)

(GROUND WIRE AND CONNECTORS

SHOWN ON NEAR-SIDE)

LIFTING LUG (REF) (GROUND WIRE

AND CONNECTORS SHOWN ON FAR-SIDE)

STATION GROUND GRID

BURNDY CAT.#YGL29C29 MARK"G13" CONDUCTOR RANGE:

COND. "A" -#2 SOL-250KCM COND. "B" -#2 STR-250KCM

COMPRESSION TOOLS: Y750/Y35/Y39 HYPRESS Y45 HYPRESS W/ PT6515 ADAPTER Y46 HYPRESS W/ P-UADP ADAPTER

DIE SET CAT.# U997 ONE (1) CRIMP REQUIRED

BURN DY CAT.#YGL34C29 MARK"G14" CONDUCTOR RANGE:

ROD-¾"-¾" CABLE - #2 STR.-250KCM

COMPRESSION TOOLS: Y750/Y45/Y46 HYPRESS

Y750 COND."A" DIE SET CAT.# PU998 Y750 COND."B" DIE SET CAT.# U997 Y45 COND. "A" DIE SET CAT.# S99B OR PU99B Y45 COND. "B" DIE SET CAT.# U997 Y46 COND. "A" DIE SET CAT.# P99B OR PU99B Y46 COND. "B" DIE SET CAT.# U997 ONE (1) CRIMP REQUIRED TWO (2) CRIMP ON GND ROD PRECRIMP GND ROD USE CAT.#U2CABT

FINISH GRADE

DETAIL "J" TYPICAL BREAKER & MECH.

HOUSING GROUNDING

PROJECT NO: 327851

DATE DES CHK APP

06/20/19 MD DG AKD

TERM. 1&2

(2)4" PVC CONDUIT

4/0 CABLE TO 1/0 CENTER WIRE

GROUND MAT

4/0 CABLE TO 1/0 CENTER WIRE

GROUND MAT

TOP RAIL JOINT

G12

DETAIL "E" TOP RAIL JOINT GROUNDING

OPERATOR~ GROUND BRAID

,._,;:y."'?-,Q 0-l"' >"-Dj."'•)'(j~!_,

(NEAR-SIDE) - ' (FAR-SIDE) - STATION GROUND GRID.

DETAIL "K" TYPICAL VEE SWITCH

GROUNDING

REFERENCE DRAWINGS: 327851-100 327851-101 327851-102 327851-103 327851-104 327851-105 327851-107

EAST POINT POWER ONE LINE DIAGRAM EAST POINT GENERAL ARRANGEMENT PLAN EAST POINT ELEVATIONS & SECTIONS A-A, B-B EAST POINT SECTIONS C-C, D-D EAST POINT YARD LIGHTING PLAN EAST POINT FENCE & GROUNDING PLAN EAST POINT CONTROL HOUSE ELECTRICAL LAYOUT PLAN

BURNDY CAT.#YGHC29C29 MARK"G23' CONDUCTOR RANGE:

RUN - #3/0 STR.-250KCM TAP - #3/0 STR-250KCM

COMPRESSION TOOLS: Y750/Y35/Y39 HYPRESS

DIE SET CAT.# U997 ONE (1) CRIMP REQUIRED

BURNDY CAT.#YGHC29C26 MARK"G15" CONDUCTOR RANGE:

RUN - #3/0 STR.-250KCM TAP - #6 SOL.-2/0 STR

COMPRESSION TOOLS: Y750/Y35/Y39 HYPRESS

DIE SET CAT.# U997 ONE (1) CRIMP REQUIRED PRELIMINARY

MDITRC DESIGNED

MDITRC DRAWN

DGITRC CHECKED

AKDITRC APPROVED

REVIEW1

REVIEW2

EAST POINT

34.5KV/69KV COLLECTOR SUBSTATION

FENCE & GROUNDING DETAILS

1 TRANSFORMER DESIGN SCHOHARIE COUNTY

06/20/19 DATE

NONE SCALE

327851-106

NEW YORK

REV.

A

Page 18: SUBSTATION DESIGN CRITERIA DOCUMENT€¦ · The load on the insulator (cantilever, tension, compression, torsion) shall not exceed the respective insulator strength published in ANSI

,xx

rx'x ,,_.

iXX)

N

ADJUST DIRECTION OF NORTH ARROW

AS NEEDED

LEGEND:

l -SINGLE TOGGLE SWITCH

}3 -3 WAY TOGGLE SWITCH

] -HVAC THERMOSTAT

--

/

----+ -WIRING HOME RUN, SINGLE POLE

>-> -WIRING HOME RUN, DOUBLE POLE

~•G -DOUBLE DUPLEX OUTLET, 20A

-

I I

HVAC

l[~lTEtLARM

JYARD LTG. CONTROL

I

--( -

~11 ---", -~

-_L

~

_mrrt~~~ ~

l~t~ER ~

]lltER ~

~

MAIN DISC.

~

~

ATS

~

~

AC PNL.

~

MAIN DC DISC.

DC PNL.

3'-9"

I .. , .. ,-*--"•.,'•I J ,_, r_: (_, ,_: :_, '+-f:l C ~i ':,---S:,1

I

14'-0"

I ~~A(. -7

I

VENT. CONTROL

FILE

~tI~fAJc ANNUNCIATOR

OPTIONAL METERING

-

REJ,~}c6'4fRoL >

/ /

C -

T1 > RELAY /CONTROL /

/

/

/

C.L 3&4 RELAY7CONTROL

4'-1"

I ._,_ •• _,_ .. _*-"· I ., .. _,_· 1 ·'_• ,_ .. , I ,_1 :_, ,_-. :_, r_: U :_·, ,_: '~ ,_. _) '=· ,~, (C,

I I

' __J

EXHAUST FAN

DESK

._,. I ,_, '='

CONTROL ROOM FLOOR PLAN

LIGHTING SCHEDULE:

-

-

-

SYNC PANEL

-

II

t:: X w

I -------~

xx, -

c,1 -FLOURESCENT LIGHT FIXTURE, 2 LAMP 4', 32 WATT, 120V

-OUTDOOR LIGHT FIXTURE, HIGH PRESSURE SODIUM, 70 WATT, 120V

:1(X; -__ -~[ -EMERGENCY BATTERY LIGHT/EXIT SIGN, 120V

f-­x w

LL

I

t I

I

+ I

I

-

-

-n I I

--- -+ --------~~

• • .

I

I_ I I__J

---

- -

• • •

--

I , .. , ,. I '._) ,_: :_·, i:i-B '.:,)

' ~-1- - ---

' I I

I

--

-

'

t '

. - ' - I

- -

I

'. ·r

CONTROL ROOM LIGHTING PLAN

REFERENCES REV

A ISSUED FOR REVIEW

-

-

'

[ L

11J_ r')

>-"++ ~

[~ }--

~

249 Western Avenue

Augusta, ME 04330

DESCRIPTION

' ' I

PROJECT NO: 327851

DATE DES CHK APP

06/20/19 AA□ DG AKO

M0ITRC DESIGNED

MDITRC DRAWN

DG/TRC CHECKED

AKDITRC APPROVED

REVIEW1

REVIEW2

REFERENCE DRAWINGS: 327851-100 - EAST POINT POWER ONE LINE DIAGRAM

327851-101 - EAST POINT GENERAL ARRANGEMENT PLAN 327851-102 - EAST POINT ELEVATIONS & SECTIONS A-A, B-B 327851-103 - EAST POINT SECTIONS C-C, D-D 327851-104 - EAST POINT YARD LIGHTING PLAN 327851-105 - EAST POINT FENCE & GROUNDING PLAN 327851-106 - EAST POINT FENCE & GROUNDING DETAILS

PRELIMINARY

EAST POINT

34.5KV/69KV COLLECTOR SUBSTATION

CONTROL HOUSE ELECTRICAL LAYOUT PLAN

1 TRANSFORMER DESIGN SCHOHARIE COUNTY NEW YORK

06/20/19 DATE

3/8"=1'-0" SCALE

REV.

327851-107 A