    Detailed Performance Summary For EFR-1Project: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM

    PackagedChillerReport:DoNotEdit;

    Unit Information

      Tag Name: EFR-1

      Model Number: 30RB090

      Condenser Type: Air Cooled  Compressor Type: Scroll

      Nameplate Voltage: 208/230-3-60 V-Ph-Hz  Quantity: 2  Manufacturing Source: Charlotte, NC USA  Refrigerant: R410A  Capacity Control Steps: 4  Minimum Capacity: 22.0 %  Shipping Weight: 6590 lb  Operating Weight: 6855 lb  Unit Length: 142 in  Unit Width: 89 in  Unit Height: 90 in  Minimum Outdoor Operating Temp: 32 °F  Chiller Pressure Drop: 11.6 ft wg

     Performance Information

      Cooling Capacity: 90.8 Tons  Total Compressor Power: 80.7 kW  Total Fan Motor Power: 13.8 kW  Pump Power: 8.79 kW  Total Unit Power (without pump): 94.5 kW  Total Unit Power (with pump): 103.3 kW  Efficiency (without pump): 11.52 EER Evaporator Information  Fluid Type: Fresh Water   Fouling Factor: 0.00010 (hr-sqft-F)/BTU  Leaving Temperature: 44.0 °F  Entering Temperature: 54.0 °F  Fluid Flow: 217.1 gpm Condenser Information

      Altitude: 3116 ft  Number of Fans: 6

      Total Condenser Fan Air Flow: 74400 CFM  Entering Air Temperature: 86.0 °F 

    Accessories and Installed Options

      Al Fin/Cu Tube, Pre-Coat  Dual Pump, 15 HP w/ VFD

      Single Point  Coil Trim Panels Electrical Information  Unit Voltage: 208/230-3-60 V-Ph-Hz  Connection Type: Single Point  Minimum Voltage: 187 Volts  Maximum Voltage: 253 Volts

      Electrical Electrical Amps Circuit 1 Circuit 2

    MCA 470.3 ---

    MOCP 500.0 ---

    ICF 925.7 ---

    Rec Fuse Size 500.0 ---

    Packaged Chiller Builder NACO 3.49m Page 1 of 16

  • 8/20/2019 Submittal Chillers

    2/16

    Detailed Performance Summary For EFR-1Project: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM

    Integrated Pump Information  Dynamic Head At Pump: 131.0 ft  Dynamic Head External To Chiller: 119.5 ft

     Packaged Chiller Builder NACO 3.49m Page 2 of 16

  • 8/20/2019 Submittal Chillers

    3/16

    Detailed Performance Summary For EFR-1Project: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM

    Integrated Part Load Value (AHRI)  IPLV: 13.68 EER

    Unit Performance

    Percent of Full Load Capacity, % 100 75 50 25

    Percent of Full Load Power, % 100.0 61.3 35.9 16.4

    Unloading Sequence B B B B

    Cooling Capacity, Tons 86.3 64.7 43.2 21.6

    Total Unit Power, kW 101.1 62.0 36.3 16.5

    Efficiency, EER 10.25 12.54 14.28 15.67Evaporator Data

    Fluid Entering Temperature, °F 54.0 51.5 49.0 46.5

    Fluid Leaving Temperature, °F 44.0 44.0 44.0 44.0

    Fluid Flow Rate, gpm 207.2 207.2 207.2 207.2

    Fouling Factor, (hr-sqft-F)/BTU 0.0001 0.0001 0.0001 0.0001Condenser Data

    Entering Air Temperature, °F 95.0 80.0 65.0 55.0

     

     All performance efficiency data are without pump.Sound power measured in accordance with ANSI/AHRI 370-2001.

    Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Using Vapor Compression Cycle CertificationProgram, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRIDirectory at www.ahridirectory.org.

     Packaged Chiller Builder NACO 3.49m Page 3 of 16

  • 8/20/2019 Submittal Chillers

    4/16

    Detailed Performance Summary For EFR-1Project: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM

    Unit Parameters  Tag Name: EFR-1

      Model Number: 30RB090

      Condenser Type: Air Cooled

      Compressor Type: Scroll

      Chiller Nameplate Voltage: 208/230-3-60 V-Ph-Hz  Quantity: 2

      Manufacturing Source: Charlotte, NC USA

      Refrigerant: R410A

      Shipping Weight: 6590 lb  Operating Weight: 6855 lb  Unit Length: 142 in  Unit Width: 89 in  Unit Height: 90 in

    1 - Chiller Height Above Ground2 - Horizontal Distance From Chiller to Receiver 3 - Receiver Height Above Ground  (See Note 3)

    Accessories and Installed Options  Al Fin/Cu Tube, Pre-Coat  Dual Pump, 15 HP w/ VFD 

    Single Point  Coil Trim Panels 

    Acoustic InformationTable 1. A-Weighted Sound Power Levels (dB re 1 picowatt). See note #1.

    Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall

    100% Load 37 68 80 87 93 97 93 89 80 100

    75% Load 36 72 80 87 93 97 92 89 80 100

    50% Load 37 68 80 87 93 97 92 88 79 100

    25% Load 31 64 75 81 87 90 87 83 72 94

    Table 2. A-Weighted Sound Pressure Levels (dB re 20 micropascals) calculated based upon user defined input fordimensions 1, 2 and 3 as shown in above diagram. See note #2 and #3.

    Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall100% Load 9 40 52 59 65 69 65 61 52 72

    75% Load 8 44 52 59 65 69 64 61 51 72

    50% Load 9 40 52 58 64 69 64 60 51 72

    25% Load 3 36 47 53 58 62 59 54 44 65

    Notes: (1) Measurements performed in accordance with AHRI Standard 370 for air cooled Chillers.(2) Chiller is assumed to be a point source on a reflecting plane.(3) Without user defined input, the default dimensions used to construct Table 2 are as follows:

    1 - Chiller Height Above Ground = 0.0 ft  2 - Horizontal Distance From Chiller to Receiver = 30.0 ft  3 - Receiver Height Above Ground = 3.0 ft

     Packaged Chiller Builder NACO 3.49m Page 4 of 16

  • 8/20/2019 Submittal Chillers

    5/16

    Detailed Performance Summary For EFR-1 OP MCHXProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM

    PackagedChillerReport:DoNotEdit;

    Unit Information

      Tag Name: EFR-1 OP MCHX

      Model Number: 30RB090

      Condenser Type: Air Cooled  Compressor Type: Scroll

      Nameplate Voltage: 208/230-3-60 V-Ph-Hz  Quantity: 2  Manufacturing Source: Charlotte, NC USA  Refrigerant: R410A  Capacity Control Steps: 4  Minimum Capacity: 22.0 %  Shipping Weight: 6107 lb  Operating Weight: 6372 lb  Unit Length: 142 in  Unit Width: 89 in  Unit Height: 90 in  Minimum Outdoor Operating Temp: 32 °F  Chiller Pressure Drop: 11.6 ft wg

     Performance Information

      Cooling Capacity: 91.1 Tons  Total Compressor Power: 80.2 kW  Total Fan Motor Power: 13.8 kW  Pump Power: 8.80 kW  Total Unit Power (without pump): 94.1 kW  Total Unit Power (with pump): 102.9 kW  Efficiency (without pump): 11.61 EER Evaporator Information  Fluid Type: Fresh Water   Fouling Factor: 0.00010 (hr-sqft-F)/BTU  Leaving Temperature: 44.0 °F  Entering Temperature: 54.0 °F  Fluid Flow: 217.8 gpm Condenser Information

      Altitude: 3116 ft  Number of Fans: 6

      Total Condenser Fan Air Flow: 74400 CFM  Entering Air Temperature: 86.0 °F 

    Accessories and Installed Options

      Micro Channel  Dual Pump, 15 HP w/ VFD

      Single Point  Coil Trim Panels Electrical Information  Unit Voltage: 208/230-3-60 V-Ph-Hz  Connection Type: Single Point  Minimum Voltage: 187 Volts  Maximum Voltage: 253 Volts

      Electrical Electrical Amps Circuit 1 Circuit 2

    MCA 470.3 ---

    MOCP 500.0 ---

    ICF 925.7 ---

    Rec Fuse Size 500.0 ---

    Packaged Chiller Builder NACO 3.49m Page 5 of

  • 8/20/2019 Submittal Chillers

    6/16

    Detailed Performance Summary For EFR-1 OP MCHXProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM

    Integrated Pump Information  Dynamic Head At Pump: 131.0 ft  Dynamic Head External To Chiller: 119.3 ft

     Packaged Chiller Builder NACO 3.49m Page 6 of

  • 8/20/2019 Submittal Chillers

    7/16

  • 8/20/2019 Submittal Chillers

    8/16

    Detailed Performance Summary For EFR-1 OP MCHXProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM

    Unit Parameters  Tag Name: EFR-1 OP MCHX

      Model Number: 30RB090

      Condenser Type: Air Cooled

      Compressor Type: Scroll

      Chiller Nameplate Voltage: 208/230-3-60 V-Ph-Hz  Quantity: 2

      Manufacturing Source: Charlotte, NC USA

      Refrigerant: R410A

      Shipping Weight: 6107 lb  Operating Weight: 6372 lb  Unit Length: 142 in  Unit Width: 89 in  Unit Height: 90 in

    1 - Chiller Height Above Ground2 - Horizontal Distance From Chiller to Receiver 3 - Receiver Height Above Ground  (See Note 3)

    Accessories and Installed Options  Micro Channel  Dual Pump, 15 HP w/ VFD 

    Single Point  Coil Trim Panels 

    Acoustic InformationTable 1. A-Weighted Sound Power Levels (dB re 1 picowatt). See note #1.

    Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall

    100% Load 37 68 80 87 93 97 93 89 80 100

    75% Load 36 72 80 87 93 97 92 89 80 100

    50% Load 37 68 80 87 93 97 92 88 79 100

    25% Load 31 64 75 81 87 90 87 83 72 94

    Table 2. A-Weighted Sound Pressure Levels (dB re 20 micropascals) calculated based upon user defined input fordimensions 1, 2 and 3 as shown in above diagram. See note #2 and #3.

    Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall100% Load 9 40 52 59 65 69 65 61 52 72

    75% Load 8 44 52 59 65 69 64 61 51 72

    50% Load 9 40 52 58 64 69 64 60 51 72

    25% Load 3 36 47 53 58 62 59 54 44 65

    Notes: (1) Measurements performed in accordance with AHRI Standard 370 for air cooled Chillers.(2) Chiller is assumed to be a point source on a reflecting plane.(3) Without user defined input, the default dimensions used to construct Table 2 are as follows:

    1 - Chiller Height Above Ground = 0.0 ft  2 - Horizontal Distance From Chiller to Receiver = 30.0 ft  3 - Receiver Height Above Ground = 3.0 ft

     Packaged Chiller Builder NACO 3.49m Page 8 of

  • 8/20/2019 Submittal Chillers

    9/16

    Detailed Performance Summary For EFR-1 OP 30RAPProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM

    PackagedChillerReport:DoNotEdit;

    Unit Information

      Tag Name: EFR-1 OP 30RAP

      Model Number: 30RAP090

      Condenser Type: Air Cooled  Compressor Type: Scroll

      Nameplate Voltage: 208/230-3-60 V-Ph-Hz  Quantity: 1  Manufacturing Source: Charlotte, NC USA  Refrigerant: R410A  Capacity Control Steps: 6  Minimum Capacity: 17.0 %  Shipping Weight: 4663 lb  Operating Weight: 4763 lb  Unit Length: 151 in  Unit Width: 88 in  Unit Height: 78 in  Minimum Outdoor Operating Temp: 32 °F  Chiller Pressure Drop*: 26.5 ft wg

      *Use Chiller Pressure Drop for sizing pumps. This valueincludes losses due to chiller piping, fittings, 40 mesh factorysupplied strainer and BPHX. Performance Information

      Cooling Capacity: 87.8 Tons  Total Compressor Power: 84.2 kW  Total Fan Motor Power: 8.61 kW  Pump Power: 8.71 kW  Total Unit Power (without pump): 92.8 kW  Total Unit Power (with pump): 101.5 kW  Efficiency (without pump): 11.35 EER Evaporator Information  Fluid Type: Fresh Water 

      Fouling Factor: 0.00010 (hr-sqft-F)/BTU  Leaving Temperature: 44.0 °F  Entering Temperature: 54.0 °F  Fluid Flow: 209.9 gpm  Evaporator Pressure Drop*: 12.2 ft wg  *Refer to Chiller Pressure Drop for sizing pumps. Condenser Information

      Altitude: 3116 ft  Number of Fans: 6

      Total Condenser Fan Air Flow: 61500 CFM  Entering Air Temperature: 86.0 °F 

    Accessories and Installed Options

      Al Fin/Cu Tube, Pre-Coat  Value Sound

      Dual Pump, 15 HP w/ VFD  Single Point Electrical Information  Unit Voltage: 208/230-3-60 V-Ph-Hz  Connection Type: Single Point

      Electrical Electrical Amps Circuit 1 Circuit 2

    MCA 425.1 ---

    MOCP 450.0 ---

    ICF 695.3 ---

    Rec Fuse Size 450.0 ---

    Packaged Chiller Builder NACO 3.49m Page 9 of 16

  • 8/20/2019 Submittal Chillers

    10/16

    Detailed Performance Summary For EFR-1 OP 30RAPProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM

    Integrated Pump Information  Dynamic Head At Pump: 132.0 ft  Dynamic Head External To Chiller: 105.6 ft

     Packaged Chiller Builder NACO 3.49m Page 10 of 16

  • 8/20/2019 Submittal Chillers

    11/16

    Detailed Performance Summary For EFR-1 OP 30RAPProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM

    Integrated Part Load Value (AHRI)  IPLV: 15.07 EER

    Unit Performance

    Percent of Full Load Capacity, % 100 75 50 25

    Percent of Full Load Power, % 100.0 54.4 32.8 13.8

    Unloading Sequence A A A A

    Cooling Capacity, Tons 84.0 63.0 42.0 21.0

    Total Unit Power, kW 99.8 54.3 32.8 13.7

    Efficiency, EER 10.09 13.91 15.38 18.34Evaporator Data

    Fluid Entering Temperature, °F 54.0 51.5 49.0 46.5

    Fluid Leaving Temperature, °F 44.0 44.0 44.0 44.0

    Fluid Flow Rate, gpm 201.5 201.5 201.5 201.5

    Fouling Factor, (hr-sqft-F)/BTU 0.0001 0.0001 0.0001 0.0001Condenser Data

    Entering Air Temperature, °F 95.0 80.0 65.0 55.0

    For some 75% operating points, the efficiency may be calculated at a condenser inlet air operating temperature as much as 0.8

    degrees higher.

     

     All performance efficiency data are without pump.Sound power measured in accordance with ANSI/AHRI 370-2001.

    Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Using Vapor Compression Cycle CertificationProgram, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRIDirectory at www.ahridirectory.org.

     Packaged Chiller Builder NACO 3.49m Page 11 of 16

  • 8/20/2019 Submittal Chillers

    12/16

    Detailed Performance Summary For EFR-1 OP 30RAPProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM

    Unit Parameters  Tag Name: EFR-1 OP 30RAP

      Model Number: 30RAP090

      Condenser Type: Air Cooled

      Compressor Type: Scroll

      Chiller Nameplate Voltage: 208/230-3-60 V-Ph-Hz  Quantity: 1

      Manufacturing Source: Charlotte, NC USA

      Refrigerant: R410A

      Shipping Weight: 4663 lb  Operating Weight: 4763 lb  Unit Length: 151 in  Unit Width: 88 in  Unit Height: 78 in

    1 - Chiller Height Above Ground2 - Horizontal Distance From Chiller to Receiver 3 - Receiver Height Above Ground  (See Note 3)

    Accessories and Installed Options  Al Fin/Cu Tube, Pre-Coat  Value Sound  Dual Pump, 15 HP w/ VFD  Single Point 

    Acoustic InformationTable 1. A-Weighted Sound Power Levels (dB re 1 picowatt). See note #1.

    Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall

    100% Load 42 75 82 88 94 95 93 89 84 100

    75% Load 42 75 82 88 94 95 92 89 84 100

    50% Load 41 74 81 88 93 94 91 88 83 99

    25% Load 40 73 80 87 92 93 90 87 82 98

    Table 2. A-Weighted Sound Pressure Levels (dB re 20 micropascals) calculated based upon user defined input for

    dimensions 1, 2 and 3 as shown in above diagram. See note #2 and #3.

    Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall

    100% Load 14 47 54 60 66 67 64 61 56 72

    75% Load 14 47 54 60 66 66 64 61 56 72

    50% Load 13 46 53 59 65 66 63 60 55 71

    25% Load 12 45 52 58 64 65 62 59 54 70

    Notes: (1) Measurements performed in accordance with AHRI Standard 370 for air cooled Chillers.(2) Chiller is assumed to be a point source on a reflecting plane.(3) Without user defined input, the default dimensions used to construct Table 2 are as follows:

    1 - Chiller Height Above Ground = 0.0 ft  2 - Horizontal Distance From Chiller to Receiver = 30.0 ft  3 - Receiver Height Above Ground = 3.0 ft

     Packaged Chiller Builder NACO 3.49m Page 12 of 16

  • 8/20/2019 Submittal Chillers

    13/16

    Detailed Performance Summary For EFR-1 OP 30RAP MCHXProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM

    PackagedChillerReport:DoNotEdit;

    Unit Information

      Tag Name: EFR-1 OP 30RAP MCHX

      Model Number: 30RAP090

      Condenser Type: Air Cooled  Compressor Type: Scroll

      Nameplate Voltage: 208/230-3-60 V-Ph-Hz  Quantity: 1  Manufacturing Source: Charlotte, NC USA  Refrigerant: R410A  Capacity Control Steps: 6  Minimum Capacity: 17.0 %  Shipping Weight: 4310 lb  Operating Weight: 4411 lb  Unit Length: 151 in  Unit Width: 88 in  Unit Height: 78 in  Minimum Outdoor Operating Temp: 32 °F  Chiller Pressure Drop*: 26.6 ft wg

      *Use Chiller Pressure Drop for sizing pumps. This valueincludes losses due to chiller piping, fittings, 40 mesh factorysupplied strainer and BPHX. Performance Information

      Cooling Capacity: 88.1 Tons  Total Compressor Power: 83.7 kW  Total Fan Motor Power: 8.54 kW  Pump Power: 8.72 kW  Total Unit Power (without pump): 92.2 kW  Total Unit Power (with pump): 101.0 kW  Efficiency (without pump): 11.46 EER Evaporator Information  Fluid Type: Fresh Water 

      Fouling Factor: 0.00010 (hr-sqft-F)/BTU  Leaving Temperature: 44.0 °F  Entering Temperature: 54.0 °F  Fluid Flow: 210.6 gpm  Evaporator Pressure Drop*: 12.3 ft wg  *Refer to Chiller Pressure Drop for sizing pumps. Condenser Information

      Altitude: 3116 ft  Number of Fans: 6

      Total Condenser Fan Air Flow: 61500 CFM  Entering Air Temperature: 86.0 °F 

    Accessories and Installed Options

      Micro Channel  Value Sound

      Dual Pump, 15 HP w/ VFD  Single Point Electrical Information  Unit Voltage: 208/230-3-60 V-Ph-Hz  Connection Type: Single Point

      Electrical Electrical Amps Circuit 1 Circuit 2

    MCA 425.1 ---

    MOCP 450.0 ---

    ICF 695.3 ---

    Rec Fuse Size 450.0 ---

    Packaged Chiller Builder NACO 3.49m Page 13 of 16

  • 8/20/2019 Submittal Chillers

    14/16

    Detailed Performance Summary For EFR-1 OP 30RAP MCHXProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM

    Integrated Pump Information  Dynamic Head At Pump: 131.9 ft  Dynamic Head External To Chiller: 105.3 ft

     Packaged Chiller Builder NACO 3.49m Page 14 of 16

  • 8/20/2019 Submittal Chillers

    15/16

    Detailed Performance Summary For EFR-1 OP 30RAP MCHXProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM

    Integrated Part Load Value (AHRI)  IPLV: 15.14 EER

    Unit Performance

    Percent of Full Load Capacity, % 100 75 50 25

    Percent of Full Load Power, % 100.0 54.5 32.9 13.8

    Unloading Sequence A A A A

    Cooling Capacity, Tons 84.2 63.1 42.1 21.0

    Total Unit Power, kW 99.4 54.2 32.7 13.7

    Efficiency, EER 10.17 13.99 15.45 18.40Evaporator Data

    Fluid Entering Temperature, °F 54.0 51.5 49.0 46.5

    Fluid Leaving Temperature, °F 44.0 44.0 44.0 44.0

    Fluid Flow Rate, gpm 202.1 202.1 202.1 202.1

    Fouling Factor, (hr-sqft-F)/BTU 0.0001 0.0001 0.0001 0.0001Condenser Data

    Entering Air Temperature, °F 95.0 80.0 65.0 55.0

    For some 75% operating points, the efficiency may be calculated at a condenser inlet air operating temperature as much as 0.8

    degrees higher.

     

     All performance efficiency data are without pump. An uncoated Novation condenser coil was selected for this product. This is based on an installed location that must be analyzed and

    guidance provided by applications engineering and a non-corrosive localized environment.Sound power measured in accordance with ANSI/AHRI 370-2001.

    Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Using Vapor Compression Cycle CertificationProgram, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRIDirectory at www.ahridirectory.org.

     Packaged Chiller Builder NACO 3.49m Page 15 of 16

  • 8/20/2019 Submittal Chillers

    16/16

    Detailed Performance Summary For EFR-1 OP 30RAP MCHXProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM

    Unit Parameters  Tag Name: EFR-1 OP 30RAP MCHX

      Model Number: 30RAP090

      Condenser Type: Air Cooled

      Compressor Type: Scroll

      Chiller Nameplate Voltage: 208/230-3-60 V-Ph-Hz  Quantity: 1

      Manufacturing Source: Charlotte, NC USA

      Refrigerant: R410A

      Shipping Weight: 4310 lb  Operating Weight: 4411 lb  Unit Length: 151 in  Unit Width: 88 in  Unit Height: 78 in

    1 - Chiller Height Above Ground2 - Horizontal Distance From Chiller to Receiver 3 - Receiver Height Above Ground  (See Note 3)

    Accessories and Installed Options  Micro Channel  Value Sound  Dual Pump, 15 HP w/ VFD  Single Point 

    Acoustic InformationTable 1. A-Weighted Sound Power Levels (dB re 1 picowatt). See note #1.

    Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall

    100% Load 42 75 82 88 94 95 93 89 84 100

    75% Load 42 75 82 88 94 95 92 89 84 100

    50% Load 41 74 81 88 93 94 91 88 83 99

    25% Load 40 73 80 87 92 93 90 87 82 98

    Table 2. A-Weighted Sound Pressure Levels (dB re 20 micropascals) calculated based upon user defined input for

    dimensions 1, 2 and 3 as shown in above diagram. See note #2 and #3.

    Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall

    100% Load 14 47 54 60 66 67 64 61 56 72

    75% Load 14 47 54 60 66 66 64 61 56 72

    50% Load 13 46 53 59 65 66 63 60 55 71

    25% Load 12 45 52 58 64 65 62 59 54 70

    Notes: (1) Measurements performed in accordance with AHRI Standard 370 for air cooled Chillers.(2) Chiller is assumed to be a point source on a reflecting plane.(3) Without user defined input, the default dimensions used to construct Table 2 are as follows:

    1 - Chiller Height Above Ground = 0.0 ft  2 - Horizontal Distance From Chiller to Receiver = 30.0 ft  3 - Receiver Height Above Ground = 3.0 ft

     Packaged Chiller Builder NACO 3.49m Page 16 of 16