This document shall not be used for construction unless signed and sealed for construction. Sheet No. Original Size Title Project Client Designer Drawn Scale Plot Date: Filename: 20 April 2017 - 3:33 PM G:\111\11121669 RP Performing Arts Center HVAC\06-CAD\Sheets\11121669 M-702.dwg Arch E1 Date Plotted By: Erik Omlid Project No. Sheet of Reuse of Documents This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD and shall not be reused in whole or in part for any other project without GHD's written authorization. © 2017 GHD Drafting Check 0 1" Bar is one inch on original size sheet Design Check Issue No. Drawn Approved Date Project Manager PERMIT SUBMITTAL CITY OF ROHNERT PARK PERFORMING ARTS CENTER HVAC 2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 F 1 707 527 8679 W www.ghd.com GHD Inc. M29562 6/30/17 No. Exp. R E G I S T E R E D P R O F E S S I O N A L E N G I N E E R S T A T E O F C A L I F O R N I A T E R R Y W O N G M E C H A N I C A L PLAN CHECK COMMENTS 1 04/21/2017 ENERGY COMPLIANCE M-702 E. OMLID T. WONG B. THOM AS SHOWN

Upload: others

Post on 07-Feb-2022

13 views

Category:

Documents


0 download

TRANSCRIPT

This document shall not be used forconstruction unless signed and sealed forconstruction. Sheet No.

Original Size

Title

Project

ClientDesignerDrawn

Scale

Plot Date: Filename:20 April 2017 - 3:33 PM G:\111\11121669 RP Performing Arts Center HVAC\06-CAD\Sheets\11121669 M-702.dwg

Arch E1

Date

Plotted By: Erik Omlid

Project No.

Sheet of

Reuse of DocumentsThis document and the ideas and designs incorporatedherein, as an instrument of professional service, is theproperty of GHD and shall not be reused in whole or in partfor any other project without GHD's written authorization.© 2017 GHD

DraftingCheck

0 1"

Bar is one inch onoriginal size sheet

DesignCheck

IssueNo. Drawn Approved Date

ProjectManager

PERMIT SUBMITTAL CITY OF ROHNERT PARKPERFORMING ARTS CENTER HVAC

2235 Mercury Way Suite 150Santa Rosa California 95407 USAT 1 707 523 1010 F 1 707 527 8679 W www.ghd.com

GHD Inc.M295626/30/17

No.Exp.

REG I

S TER

ED PRO FE S S I ON A L E NGI NEER

S TA T E O F C A L I F O R N I A

T E R R Y W O N G

M E C H A N I C A L

PLAN CHECK COMMENTS1 04/21/2017

ENERGY COMPLIANCE

M-702

E. OMLID T. WONG

B. THOM

AS SHOWN

This document shall not be used forconstruction unless signed and sealed forconstruction. Sheet No.

Original Size

Title

Project

ClientDesignerDrawn

Scale

Plot Date: Filename:20 April 2017 - 3:33 PM G:\111\11121669 RP Performing Arts Center HVAC\06-CAD\Sheets\11121669 E-001.dwg

Arch E1

Date

Plotted By: Erik Omlid

Project No.

Sheet of

Reuse of DocumentsThis document and the ideas and designs incorporatedherein, as an instrument of professional service, is theproperty of GHD and shall not be reused in whole or in partfor any other project without GHD's written authorization.© 2017 GHD

DraftingCheck

0 1"

Bar is one inch onoriginal size sheet

DesignCheck

IssueNo. Drawn Approved Date

ProjectManager

PERMIT SUBMITTAL CITY OF ROHNERT PARKPERFORMING ARTS CENTER HVAC

2235 Mercury Way Suite 150Santa Rosa California 95407 USAT 1 707 523 1010 F 1 707 527 8679 W www.ghd.com

GHD Inc.E169296/30/17

No.Exp.

REG I

S TER

ED PRO FE S S I ON A L E NGI NEER

S TA T E O F C A L I F O R N I A

E R I C M . P E NN

E L E C T R I C A L

PLAN CHECK COMMENTS1 04/21/2017

ANNOTATION

SWITCHING

LIGHTING

CONDUIT

MAIN SWITCHBOARD

DISTRIBUTION PANEL BOARD

COMBINATION METER/MAIN SERVICE PANEL

BRANCH CIRCUIT PANEL BOARD, SURFACE OR FLUSHMOUNTED

LIGHTING CONTROL PANEL

SIGNAL TERMINAL CABINET OR CONTROL PANELSURFACE OR FLUSH MOUNTED

SIGNAL TERMINAL BACKBOARD

CONCRETE UNDERGROUND HAND HOLE(NUMBER DENOTES CHRISTY SIZE)

TRANSFORMER

EQUIPMENT

GENERAL ELECTRICAL NOTESELECTRICAL SYMBOLS LEGEND

KEYNOTE

DEMOLITION NOTE

RACEWAY, FEEDER OR CIRCUIT DESIGNATION (SEE SCHEDULE)

LIGHTING FIXTURE TYPE DESIGNATION(SEE SCHEDULE)

DETAIL INDICATOR SECTION INDICATOR

MECHANICAL EQUIPMENT DESIGNATION(SEE SCHEDULE)

CCTV CAMERA, CEILING MOUNT

INTERCOM CALL IN SWITCH - MOUNTING HEIGHT: +44" AFF, UON

TELEPHONE OUTLET FOR WALL MOUNTED TELEPHONEMOUNTING HEIGHT: +44" AFF UON

DATA OUTLET - MOUNTING HEIGHT: +18" AFF UON

TELEPHONE/DATA OUTLET, FLUSH TYPE UONMOUNTING HEIGHT: +18" AFF UON

SURFACE RACEWAY WITH POWER AND TELEPHONE/DATARECEPTACLES AS INDICATED

CATV OUTLET - MOUNTING HEIGHT: +96" AFF UON

AUDIO/VIDEO OUTLET - MOUNTING HEIGHT: +18" AFF UON

CLOCK WITH BUZZER - MOUNTING HEIGHT: SEE PLANS

BELL, STANDARD 6" - MOUNTING HEIGHT: SEE PLANS PA SYSTEM

SPEAKER - WALL MOUNTED

PA SYSTEM SPEAKER - CEILING MOUNTED

PA SYSTEM HORN - MOUNTING HEIGHT: SEE PLANS

DUPLEX RECEPTACLE, 15A 125V 2P 3W, GROUNDING TYPE,MOUNTING HEIGHT: +18" AFF UON

DUPLEX RECEPTACLE - SPLIT WIRED, SWITCHED

DUPLEX RECEPTACLE - EMERGENCY POWER

DUPLEX RECEPTACLE - CEILING MOUNTED

FLOOR RECEPTACLE, 15A 125V 2P 3W, GROUNDING TYPE,FLUSH TYPE UON

DOUBLE DUPLEX RECEPTACLE, 15A 125V 2P 3W, GROUNDING TYPE,MOUNTING HEIGHT: +18" AFF UON

SINGLE RECEPTACLE, 20A 125V 2P 3W, GROUNDING TYPE,MOUNTING HEIGHT: +18" AFF UON

SPECIAL PURPOSE RECEPTACLE AS DESIGNATEDSEE 'SPECIAL SYMBOLS' ON EACH SHEET

DUAL SERVICE RECESSED FLOOR BOX WITH DUPLEX AND DATARECEPTACLES

JUNCTION BOX, CODE SIZED UON

FLOOR JUNCTION BOX

DISCONNECT SWITCH - FUSED WHERE APPLICABLE

MOTOR STARTER, COMBINATION WITH DISCONNECT SWITCH

MOTOR STARTER OR CONTROLLER

MOTOR CONNECTION

CEILING EXHAUST FAN

WATER HEATER

POWER POLE: P=POWER, T=TELEPHONE,D=DATA, C=COMBINATION

TEST PORT

GROUND ROD

GUY WIRE AND ANCHOR

THERMOSTAT (SEE MECHANICAL DRAWINGS)COORDINATE MOUNTING HEIGHT

BYPASS TIMER OR TIME SWITCH

PUSHBUTTON

LIGHTING CONTACTOR

CONDUIT INSTALLED ABOVE GRADE

CONDUIT INSTALLED UNDERGROUND OR UNDER SLAB

CONDUIT STUB-OUT WITH CAP

FLEXIBLE CONDUIT WHIP TO LIGHT FIXTURE OR EQUIPMENT

FLUORESCENT FIXTURE, RECESSED

RECESSED DOWN LIGHT FIXTURE

RECESSED DIRECTIONAL FIXTURE (ARROW INDICATES AIMING)

FLUORESCENT FIXTURE, SURFACE MOUNTED

SURFACE, PENDANT OR OTHER FIXTURE

LARGE DIAMETER PENDANT, DEPICTING APPROXIMATE DIAMETER

FLUORESCENT FIXTURE, WALL MOUNTED

WALL-MOUNTED HID, INCANDESCENT, OR COMPACT FLUORESCENTFIXTURE

FLUORESCENT FIXTURE, PENDANT OR CABLE HUNG

LIGHT TRACK AND TRACK-MOUNTED FIXTURES

BATH FAN WITH INTEGRAL LIGHT

EXIT SIGN, SINGLE FACE WITH DIRECTIONAL ARROWS AS INDICATED

EXIT SIGN, DOUBLE FACE WITH DIRECTIONAL ARROWS AS INDICATED

EXIT SIGN, LOW LEVEL

COMBINATION EXIT/EMERGENCY LIGHT FIXTUREMOUNTING HEIGHT: +8'-0" AFF, UON

EMERGENCY FIXTUREMOUNTING HEIGHT: +8'-0" AFF, UON

DENOTES FIXTURE CONNECTED TO EMERGENCY CIRCUIT

ADJUSTABLE SPOT OR FLOOD (ARROW INDICATES AIMING)

OUTDOOR SITE LIGHT, POLE MOUNTED LUMINAIRE ARROWINDICATES AIMING DIRECTION, IF APPLICABLE

BOLLARD OR POST-TOP FIXTURE

LIGHT SWITCH, SPST - MOUNTING HEIGHT: +44" AFF, UON

LIGHT SWITCH, DPST - MOUNTING HEIGHT: +44" AFF, UON

LIGHT SWITCH, 3-WAY - MOUNTING HEIGHT: +44" AFF, UON

LOW VOLTAGE SWITCH, MOMENTARY CONTACT, 3-POS.,CENTER-OFF, MOUNTING HEIGHT: +44" AFF, UON

TIMER SWITCH - MOUNTING HEIGHT: +44" AFF, UON

CIRCUIT AND SWITCH DESIGNATION FOR LIGHTING FIXTURE

CIRCUIT AND RELAY DESIGNATION FOR LIGHTING FIXTURES(SEE CORRESPONDING LIGHTING CONTROL PANEL RELAYSCHEDULE)

DIMMER SWITCH - MOUNTING HEIGHT: +44" AFF, UON

OCCUPANCY SENSOR POWER PACK, 1-CIRCUIT, MOUNTED ABOVECEILING

OCCUPANCY SENSOR POWER PACK, 2-CIRCUITMOUNTED ABOVE CEILING

OCCUPANCY SENSOR, CEILING MOUNTED, LINE VOLTAGE

OCCUPANCY SENSOR, CEILING MOUNTED, LOW VOLTAGE

OCCUPANCY SENSOR, WALL MOUNTED, LINE VOLTAGE, 1-CIRCUITMOUNTING HEIGHT: +44" AFF, UON

OCCUPANCY SENSOR, WALL MOUNTED, LINE VOLTAGE, 2-CIRCUITMOUNTING HEIGHT: +44" AFF, UON

PHOTO CONTROL SWITCH - MOUNT ON BUILDING EXTERIOR

TIME CLOCK FOR LIGHTING CONTROL

COMMUNICATION

POWER

CONDUIT HOME RUN TO DESIGNATED PANEL, TERMINAL, ORCONTROL CABINETEXAMPLES:

NOTE FOR CONDUIT: THE TIC MARKS INDICATE THE QUANTITY OF#12 AWG WIRES OR, IF INDICATED, THE QUANTITY OF OTHER SIZEWIRE OR CABLES.

SEE THE SINGLE LINE DIAGRAM FOR FEEDER SIZES.EXAMPLES: = (3) #12 = (2) #10

= (1) TYPE F1 CABLE. SEE CABLE SCHEDULE.F1

T

OBJECT LINES

NEW OBJECTS(HEAVY CONTINUOUS LINES, UNDERGROUND CONDUITHEAVY DASHED LINES)

EXISTING OBJECTS TO REMAIN. MAY INCLUDE NEW CIRCUITING ETC.(FINE CONTINUOUS LINES, UNDERGROUND CONDUITFINE DASHED LINES)

EXISTING OBJECTS TO BE DEMOLISHED(EXTRA FINE DASHED LINES, SCREENED)

ABBREVIATIONS(D) DEMOLISH(E) EXISTING(F) FUTURE(N) NEW

A AMPERESAC ALTERNATING CURRENTAF AMP FRAMEAFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEAHU AIR HANDLING UNITAIC AMPS INTERRUPTING CAPACITYANN ANNUNCIATORATS AUTOMATIC TRANSFER SWITCHAWG AMERICAN WIRE GAUGE

BAT BATTERYBFG BELOW FINISH GRADE

CATV CABLE TELEVISIONC CONDUITCB CIRCUIT BREAKERCCTV CLOSED CIRCUIT TELEVISIONCO CONDUIT ONLYCPT CONTROL POWER TRANSFORMERCT CURRENT TRANSFORMERCU COPPER

DC DIRECT CURRENT

EF EXHAUST FANEGU ENGINE GENERATOR UNITEM EMERGENCYEMT ELECTRICAL METALLIC TUBINGENT ELECTRICAL NON-METALLIC TUBINGEP EXPLOSION PROOF

FA FIRE ALARMFACP FIRE ALARM CONTROL PANELFC FOOT CANDLEFU FUSE

GND GROUNDGFCI GROUND FAULT CIRCUIT INTERRUPTERGFI GROUND FAULT INTERRUPTERGFR GROUND FAULT RELAY

HID HIGH INTENSITY DISCHARGEHOA "HAND-OFF-AUTO" SWITCHHP HORSEPOWERHPS HIGH PRESSURE SODIUMHVAC HEATING, VENTILATION &

AIR-CONDITIONING

IG ISOLATED GROUND

JB JUNCTION BOX

KAIC KILO-AMPS INTERRUPTING CAPACITYKV KILOVOLTKVA KILOVOLT-AMPKW KILOWATTKWH KILOWATT-HOUR

LPS LOW PRESSURE SODIUMLV LOW VOLTAGE

MCB MAIN CIRCUIT BREAKERMCC MOTOR CONTROL CENTERMCP MOTOR CIRCUIT PROTECTORMFR MANUFACTURERMH METAL HALIDEMLO MAIN LUGS ONLYMV MEDIUM VOLTAGE

NIC NOT IN CONTRACTNL NIGHT LIGHTNTS NOT TO SCALE

OC ON CENTER

PA PUBLIC ADDRESSPT POTENTIAL TRANSFORMERPVC POLYVINYL CHLORIDEPB PULL BOX, ELECTRICAL

RECPT RECEPTACLE, OUTLETRGS RIGID GALVANIZED STEEL (CONDUIT)RVSS REDUCED VOLTAGE SOFT STARTRTU REMOTE TERMINAL UNIT

TV TELEVISION MONITOR (SET)TVSS TRANS. VOLT. SURGE SUPPRESSOR

UF UNDER FLOORUG UNDERGROUNDUON UNLESS OTHERWISE NOTEDUPS UNINTERRUPTIBLE POWER SUPPLY

V VOLTVA VOLT-AMPVFD VARIABLE FREQUENCY DRIVE

WP WEATHERPROOFWPI WEATHERPROOF IN USE

XFMR TRANSFORMER

ELECTRICAL LEGEND, NOTES, AND ABBREVIATIONS

E-001

E. OMLID E. PENN

B. THOM

AS SHOWN

1. UNLESS SPECIFICALLY INDICATED OTHERWISE, ALL EQUIPMENT INDICATED SHALL BECONSIDERED NEW AND PROVIDED BY THE CONTRACTOR COMPLETE, INSTALLED, TESTED AND FUNCTIONING.

2. ALL WORK SHALL CONFORM TO AND BE PERFORMED IN ACCORDANCE WITH CODES,STANDARDS, AND ORDINANCES AS SET FORTH BY THE AUTHORITIES HAVING JURISDICTIONAND THEIR LATEST ADOPTED EDITIONS OF THE FOLLOWING PUBLICATIONS:

(A) NATIONAL ELECTRICAL CODE

(B) NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

(C) AMERICANS WITH DISABILITIES ACT (ADA)

3. THE CONTRACTOR IS RESPONSIBLE TO MAINTAIN ALL EQUIPMENT IN A SAFE AND FUNCTIONALCONDITION. KEEP DEAD FRONT EQUIPMENT IN PLACE WHILE EQUIPMENT IS ENERGIZED.CONDUCT ALL CONSTRUCTION OPERATIONS IN A SAFE MANNER FOR EMPLOYEES AS WELL ASOTHER WORK PERSONS OR ANYONE VISITING THE JOB SITE. PROVIDE BARRIERS, FLAGS,TAPE, ETC. AS REQUIRED TO MAINTAIN SAFETY.

4. INFORMATION SHOWN AS EXISTING CONDITIONS WAS PRIMARILY GAINED FROM "AS BUILT"DRAWINGS AND LIMITED FIELD INVESTIGATION. BEFORE CONSTRUCTION, VISIT SITE TOVERIFY EXISTING CONDITIONS AND MAKE ALLOWANCE FOR VARIATIONS FROM THAT SHOWN.

5. DEMOLITION WORK SHOWN WAS PREPARED FOR THE CONVENIENCE OF THE CONTRACTOR.THE ENGINEER DOES NOT REPRESENT THAT ALL ITEMS WHICH MAY REQUIRE DEMOLITIONHAVE BEEN SHOWN. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO CAREFULLYEXAMINE THE SITE AND THE CONTRACT DOCUMENTS AND TO PERFORM ALL DEMOLITION ANDRECONSTRUCTION WHICH MAY BE REQUIRED FOR THE PROPER EXECUTION AND COMPLETIONOF THE WORK.

6. INTERCEPT, EXTEND, REROUTE, REPULL CONDUCTORS AND OTHERWISE MODIFY EXISTINGCONDUCTORS OF ALL SYSTEMS AS REQUIRED TO MAINTAIN AND/OR ESTABLISH PROPERFUNCTION AND SATISFY DESIGN INTENT. REMOVE ALL ABANDONED CONDUCTORS ANDCONDUIT.

7. PRIOR TO COMMENCING WORK, COORDINATE WITH FWS REPRESENTATIVE. WHEREDISCONNECTING, MODIFYING OR WORKING ON EXISTING EQUIPMENT OR SYSTEMS, PROVIDEA WRITTEN METHOD OF PROCEDURE OUTLINING DATES, TIMES, DURATION AND DESCRIPTIONOF PROPOSED WORK PRIOR TO COMMENCING WORK FOR APPROVAL.

8. DRAWINGS INDICATE THE REQUIRED EQUIPMENT, DEVICES, FIXTURES, ETC. AND THEIRRELATED CIRCUITING REQUIREMENTS. THE CONTRACTOR IS RESPONSIBLE FORCOORDINATION OF THE DEVICE LOCATIONS WITH ALL DISCIPLINES. PRIOR TO COMMENCINGWORK, COORDINATE WITH OTHER TRADES TO PREVENT CONFLICTS.

9. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR SLAB AND BEAM NOTES FORTHE INSTALLATION OF ANCHORS, HANGERS, AND OTHER ELECTRICAL SUPPORTS.

10. ALL EQUIPMENT SHALL BE LISTED AND LABELED PER RECOGNIZED ELECTRICAL TESTINGLABORATORY AND INSTALLED PER THE LISTING REQUIREMENTS AND THE MANUFACTURERSINSTRUCTIONS.

11. ALL EQUIPMENT SHALL BE GROUNDED PER THE REQUIREMENTS OF NEC ARTICLE 250.EQUIPMENT GROUNDING CONDUCTORS SHALL BE INSTALLED IN ALL POWER SYSTEMRACEWAYS.

14. WIRING METHODS FOR THIS PROJECT SHALL BE AS DEFINED IN SPECIFICATION SECTION 26 0519 AND AS REQUIRED BY CODE, LOCAL ELECTRICAL UTILITY PROVIDER AND AUTHORITYHAVING JURISDICTION/

15. PULLROPES: ANY RACEWAY WITHOUT CABLE OR WIRE SHALL BE INSTALLED WITH MINIMUM200 POUND TEST PULL LINE.

16. MAINTAIN AS BUILT CONDITIONS OF THE INSTALLATION DURING CONSTRUCTION AND SUBMITTHE FINAL CONSTRUCTED CONDITIONS TO THE OWNER/ARCHITECT FOR THEIR RECORDS.

UP

AA

BB

CC

7 8 9 106

AC 1-3

AC 2-2

AC 2-3

2

2

2

UP

A

B

C

7 8 9 10

AC 4-1

AC 1-2

This document shall not be used forconstruction unless signed and sealed forconstruction. Sheet No.

Original Size

Title

Project

ClientDesignerDrawn

Scale

Plot Date: Filename:20 April 2017 - 3:33 PM G:\111\11121669 RP Performing Arts Center HVAC\06-CAD\Sheets\11121669 ED101.dwg

Arch E1

Date

Plotted By: Erik Omlid

Project No.

Sheet of

Reuse of DocumentsThis document and the ideas and designs incorporatedherein, as an instrument of professional service, is theproperty of GHD and shall not be reused in whole or in partfor any other project without GHD's written authorization.© 2017 GHD

DraftingCheck

0 1"

Bar is one inch onoriginal size sheet

DesignCheck

IssueNo. Drawn Approved Date

ProjectManager

PERMIT SUBMITTAL CITY OF ROHNERT PARKPERFORMING ARTS CENTER HVAC

2235 Mercury Way Suite 150Santa Rosa California 95407 USAT 1 707 523 1010 F 1 707 527 8679 W www.ghd.com

GHD Inc.E169296/30/17

No.Exp.

REG I

S TER

ED PRO FE S S I ON A L E NGI NEER

S TA T E O F C A L I F O R N I A

E R I C M . P E NN

E L E C T R I C A L

PLAN CHECK COMMENTS1 04/21/2017

1 MEZZININE LEVEL 1SCALE: 1/8" = 1'- 0"

2 MEZZININE LEVEL 2SCALE

0 16'8'4' N

0 16'8'4' N

PANEL MDPA

AC 3-1

AC 2-1

AC 1-1

AC 5-1

2

2

2

2

1

2

2

SHEET GENERAL NOTES

1. EXISTING CONDUIT NOT SHOWN FOR CLARITY.

2. LOCK OUT AND TAG OUT POWER CIRCUITS TO (E) HVAC UNITS PRIOR TO DEMOLITION.

SHEET KEYNOTES

1. EXISTING PANEL MDPA TO REMAIN. REMOVE (E) CIRCUIT BREAKERS AND PROVIDE (N) ASSHOWN ON PANEL SCHEDULE.

2. EXISTING DISCONNECT SWITCH TO REMAIN. PROTECT INCOMING FEEDER FROM PANELMDPA AND RE-USE. REMOVE CONDUIT AND CABLE BETWEEN (E) DISCONNECT AND (E)HVAC EQUIPMENT.

ELECTRICAL DEMOLITION POWER PLANS

ED-101

E. OMLID E. PENN

B. THOM

AS SHOWN

UP

AA

BB

CC

7 8 9 106

AC 1-3

AC 2-2

AC 2-3

2

2

2

AC

2-3

AC1-3

AC2-2

CONTINUED ONLEVEL 2

1LB-33

UP

A

B

C

7 8 9 10

AC 4-1

AC 1-2

AC

1-2

AC

4-1

AC1-1

AC5-1

AC2-1

AC3-1 CONTINUED

ON LEVEL 1

This document shall not be used forconstruction unless signed and sealed forconstruction. Sheet No.

Original Size

Title

Project

ClientDesignerDrawn

Scale

Plot Date: Filename:20 April 2017 - 3:34 PM G:\111\11121669 RP Performing Arts Center HVAC\06-CAD\Sheets\11121669 E-101.dwg

Arch E1

Date

Plotted By: Erik Omlid

Project No.

Sheet of

Reuse of DocumentsThis document and the ideas and designs incorporatedherein, as an instrument of professional service, is theproperty of GHD and shall not be reused in whole or in partfor any other project without GHD's written authorization.© 2017 GHD

DraftingCheck

0 1"

Bar is one inch onoriginal size sheet

DesignCheck

IssueNo. Drawn Approved Date

ProjectManager

PERMIT SUBMITTAL CITY OF ROHNERT PARKPERFORMING ARTS CENTER HVAC

2235 Mercury Way Suite 150Santa Rosa California 95407 USAT 1 707 523 1010 F 1 707 527 8679 W www.ghd.com

GHD Inc.E169296/30/17

No.Exp.

REG I

S TER

ED PRO FE S S I ON A L E NGI NEER

S TA T E O F C A L I F O R N I A

E R I C M . P E NN

E L E C T R I C A L

PLAN CHECK COMMENTS1 04/21/2017

1 MEZZININE LEVEL 1SCALE: 1/8" = 1'- 0"

2 MEZZININE LEVEL 2SCALE

0 16'8'4' N

0 16'8'4' N

PANEL MDPA

AC 3-1

AC 2-1

AC 1-1

AC 5-1

2

2

2

2

1

2

ELECTRICAL POWER PLANS

E-101

E. OMLID E. PENN

B. THOM

AS SHOWN

SHEET GENERAL NOTES

1. EXISTING CONDUIT TO BE RE-USED NOT SHOWN FOR CLARITY.

2. REFER TO MECHANICAL DRAWINGS FOR LOCATIONS OF EACH HVAC UNIT. COORDINATEWITH VENDOR FOR FINAL POINT OF CONNECTION.

SHEET KEYNOTES

1. (E) PANEL MDPA. RE-USE (E) AND PROVIDE (N) CIRCUIT BREAKERS AS SHOWN ON PANELSCHEDULE. PROTECT FEEDER CABLES FOR RE-USE AND RECONNECT TO (N) OR (E)CIRCUIT BREAKERS.

2. PROVIDE (N) CONDUIT AND CABLE BETWEEN (E) DISCONNECT SWITCH AND (N) HVACUNIT. SIZE PER NEC REQUIREMENTS BASED ON SUPPLY IN CIRCUIT BREAKER IN PANELMDPA. RE-USE (E) FEEDER BETWEEN DISCONNECT AND PANEL.

3. EXTEND (E) RECEPTACLE CIRCUIT TO (N) LOCATIONS AS SHOWN. PROVIDE (N) CONDUITAND CABLE, OUTLET BOXES, AND WIRING DEVICES AS INDICATED.

33

3

(E)

3

1

1

1

This document shall not be used forconstruction unless signed and sealed forconstruction. Sheet No.

Original Size

Title

Project

ClientDesignerDrawn

Scale

Plot Date: Filename:20 April 2017 - 3:34 PM G:\111\11121669 RP Performing Arts Center HVAC\06-CAD\Sheets\11121669 E-601.dwg

Arch E1

Date

Plotted By: Erik Omlid

Project No.

Sheet of

Reuse of DocumentsThis document and the ideas and designs incorporatedherein, as an instrument of professional service, is theproperty of GHD and shall not be reused in whole or in partfor any other project without GHD's written authorization.© 2017 GHD

DraftingCheck

0 1"

Bar is one inch onoriginal size sheet

DesignCheck

IssueNo. Drawn Approved Date

ProjectManager

PERMIT SUBMITTAL CITY OF ROHNERT PARKPERFORMING ARTS CENTER HVAC

2235 Mercury Way Suite 150Santa Rosa California 95407 USAT 1 707 523 1010 F 1 707 527 8679 W www.ghd.com

GHD Inc.E169296/30/17

No.Exp.

REG I

S TER

ED PRO FE S S I ON A L E NGI NEER

S TA T E O F C A L I F O R N I A

E R I C M . P E NN

E L E C T R I C A L

PLAN CHECK COMMENTS1 04/21/2017

ELECTRICAL SCHEDULES

E-601

E. OMLID E. PENN

B. THOM

AS SHOWN

PANEL SCHEDULEPANEL NAME: MDPA VOLTAGE: 480/277 NEMA RATING: 1 MOUNTING: SURFACE NOTES:

MAINS RATING: MLO A MCB PHASE: 3 AIC RATING: 10K LOCATION: MECHANICAL ROOM 224BUS RATING: 600 A WIRE: 4 DEMAND FACTOR: STD

CKT NO. USE DESCRIPTION BKRSIZE CKT KVA CKT AMPS WIRE SIZE

WIRELENGTH

(FT)

VOLTAGEDROP % PHASE VOLTAGE

DROP %WIRE

LENGTH(FT)

WIRE SIZE CKT AMPS CKT KVA BKRSIZE DESCRIPTION USE CKT NO.

1 HAC 5-1 15/3

3.13 11.30 12 25 0.18 A 0.19 25 10 20.00 5.5425/3 AC 4-1

H 23 H 3.13 11.30 12 25 0.18 B 0.19 25 10 20.00 5.54 H 45 H 3.13 11.30 12 25 0.18 C 0.19 25 10 20.00 5.54 H 67 H

AC 3-1 30/36.07 21.90 10 25 0.21 A 0.56 75 6 46.00 12.74

60/3 AC 2-3H 8

9 H 6.07 21.90 10 25 0.21 B 0.56 75 6 46.00 12.74 H 1011 H 6.07 21.90 10 25 0.21 C 0.56 75 6 46.00 12.74 H 1213 H

AC 2-2 60/312.74 46.00 6 65 0.49 A 0.29 25 6 46.00 12.74

60/3 AC 2-1H 14

15 H 12.74 46.00 6 65 0.49 B 0.19 25 6 46.00 12.74 H 1617 H 12.74 46.00 6 65 0.49 C 0.19 25 6 46.00 12.74 H 1819 H

AC 1-3 60/312.74 46.00 6 75 0.56 A 0.19 25 6 46.00 12.74

60/3 AC 1-2H 20

21 H 12.74 46.00 6 75 0.56 B 0.19 25 6 46.00 12.74 H 2223 H 12.74 46.00 6 75 0.56 C 0.19 25 6 46.00 12.74 H 2425 H

AC 1-1 60/312.74 46.00 6 215 1.61 A

60/3H 26

27 H 12.74 46.00 6 25 0.19 B H 2829 H 12.74 46.00 6 25 0.19 C H 3031 H

60/3A

60/3H 32

33 H B H 3435 H C H 3637 H

60/3A

60/3H 38

39 H B H 4041 H C H 42

CONNECTED KVA DEMAND KVA DEMAND AMPS USE LEGEND VOLTAGE DROP CALCULATIONPHASE A: 91.2 91.2 329.2 ID LOAD TYPE ASSUMED PF VOLTAGE DROP IS BASED ON THE IEEE RED BOOK AND 2011

NEC CHAPTER 9 TABLE 9 FORMULA:ASSUMPTIONS:

PHASE B: 91.2 91.2 329.2 H HVAC 0.85 POWER FACTOR VARIED BY LOAD TYEPHASE C: 91.2 91.2 329.2 L LIGHTING 0.80 VD = I * ( R * PF + X * SIN(ACOS(PF)) * L CONDUIT TYPE RGS

STD DEMAND LOAD BASED ON 125% OF THE LARGEST MOTOR AND 100% OFTHE REMAINING MOTORS, 125% OF CONTINUOUS LOADS, 100% OFNONCONTINUOUS LOADS, AND 50% OF RECEPTACLE LOADS BEYOND THEFIRST 10KVA

M MOTOR 0.85 WITH AN ADDITIONAL MULTIPLIER OF 2 FOR SINGLE PHASEAND 1.732 FOR 3-PHASE LOADS

WIRE MATERIAL CUR RECEPTACLE 0.80P PANEL 0.85 R AND X VALUES ARE TAKEN FROM 2011 NEC CHAPTER 9

TABLE 9. LENGTH IS IN 1000FT INCREMENTSO OTHER 0.85

PANEL SCHEDULEPANEL NAME: 1LB VOLTAGE: 208/120 NEMA RATING: 1 MOUNTING: RECESSED NOTES: EXISTING PANEL TO REMAIN - NO WORK REQUIRED

MAINS RATING: MLO PHASE: 3 AIC RATING: VERIFY LOCATION: WOMEN'S DRESSING ROOMBUS RATING: 100 A WIRE: 4 DEMAND FACTOR: STD

CKT NO. USE DESCRIPTION BKRSIZE CKT KVA CKT AMPS WIRE SIZE

WIRELENGTH

(FT)

VOLTAGEDROP % PHASE VOLTAGE

DROP %WIRE

LENGTH(FT)

WIRE SIZE CKT AMPS CKT KVA BKRSIZE DESCRIPTION USE CKT NO.

1 SPARE 20/1 A 20/1 SPARE 23 SPARE 20/1 B 6.00 0.72 20/1 WARDROBE 45 SPARE 20/1 C 12.50 1.50 20/1 WASHING MACHINE 67 MECH WELL T.C. AND RECEPT 20/1 0.50 4.17 A 3.00 0.36 20/1 DRESSING ROOM 89 DRESSING ROOM 20/1 0.36 3.00 B 3.00 0.36 20/1 DRESSING ROOM 1011 DRESSING ROOM 20/1 0.36 3.00 C 3.00 0.36 20/1 DRESSING ROOM 1213 DRESSING ROOM 20/1 0.36 3.00 A 3.00 0.36 20/1 DRESSING ROOM 1415 DRESSING ROOM 20/1 0.36 3.00 B 3.00 0.36 20/1 DRESSING ROOM 1617 DRESSING ROOM 20/1 0.36 3.00 C 3.00 0.36 20/1 DRESSING ROOM 1819 DRESSING ROOM 20/1 0.36 3.00 A 3.00 0.36 20/1 DRESSING ROOM 2021 DRESSING ROOM 20/1 0.36 3.00 B 3.00 0.36 20/1 DRESSING ROOM 2223 DRESSING ROOM 20/1 0.36 3.00 C 3.00 0.36 20/1 DRESSING ROOM 2425 DRESSING ROOM 20/1 0.36 3.00 A 3.00 0.36 20/1 DRESSING ROOM 2627 STARS DRESSING 20/1 0.18 1.50 B 15.00 1.80 20/1 VENDING MACHINES 2829 STARS DRESSING 20/1 0.18 1.50 C 15.00 1.80 20/1 VENDING MACHINES 3031 WATER COOLER 20/1 1.80 15.00 A 15.00 1.80 20/1 VENDING MACHINES 3233 WATER HEATER + MAINTENANCE 20/1 0.59 4.92 10 88 0.76 B 15.00 1.80 30/3 DRYER 3435 MECHANICAL 20/1 0.36 3.00 C 15.00 1.80 30/3 3637 EXHAUST FAN 20/1 1.13 9.42 A 15.00 1.80 30/3 3839 SPARE 20/1 B 20/1 SPACE 4041 SPARE 20/1 C 20/1 SPACE 42

CONNECTED KVA DEMAND KVA DEMAND AMPS USE LEGEND VOLTAGE DROP CALCULATIONPHASE A: 9.6 9.6 79.6 ID LOAD TYPE ASSUMED PF VOLTAGE DROP IS BASED ON THE IEEE RED BOOK AND 2011

NEC CHAPTER 9 TABLE 9 FORMULA:ASSUMPTIONS:

PHASE B: 7.3 7.3 60.4 H HVAC 0.85 POWER FACTOR VARIED BY LOAD TYEPHASE C: 7.8 7.8 65.0 L LIGHTING 0.80 VD = I * ( R * PF + X * SIN(ACOS(PF)) * L CONDUIT TYPE RGS

STD DEMAND LOAD BASED ON 125% OF THE LARGEST MOTOR AND 100% OFTHE REMAINING MOTORS, 125% OF CONTINUOUS LOADS, 100% OFNONCONTINUOUS LOADS, AND 50% OF RECEPTACLE LOADS BEYOND THEFIRST 10KVA

M MOTOR 0.85 WITH AN ADDITIONAL MULTIPLIER OF 2 FOR SINGLE PHASEAND 1.732 FOR 3-PHASE LOADS

WIRE MATERIAL CUR RECEPTACLE 0.80P PANEL 0.85 R AND X VALUES ARE TAKEN FROM 2011 NEC CHAPTER 9

TABLE 9. LENGTH IS IN 1000FT INCREMENTSO OTHER 0.85