study committee a3

2
Study Commiee A3 High Voltage Equipment I�� C � L � E� S Conseil Internaonal des Grands Réseaux Électriques hp://www.cigre.org Failure Frequencies for High Voltage Circuit Breakers, Disconnectors, Earthing Switches, Instrument Transformers and Gas Insulated Switchgear CIGRÉ working group A3.06 "Reliability of High Voltage Equipment": M. Runde, C. E. Sölver, A. Carvalho, M. L. Cormenzana, H. Furuta, W. Grieshaber, A. Hyrczak, D. Kopejtkova, J. G. Krone, M. Kudoke, D. Makareinis, J. F. Marns, K. Mestrovic, I. Ohno, J. Östlund, K.-Y. Park, J. Patel, C. Protze, J. Schmid, J. E. Skog, B. Sweeney, F. Waite, B. Bergman, and S. Tsukao. The CIGRÉ reliability survey Equipment covered (U ≥ 60 kV): • Circuit breakers (only single pressure SF 6 ) • Disconnectors and earthing switches • Instrument transformers • GIS; including a “GIS pracce survey” Failure and populaon data collected for the me period 2004 – 2007 Both major and minor failures included 90 ulies from 30 countries parcipated by returning completed Excel-based quesonnaires Six Technical Brochures containing all results under way Failure frequency calculaon Example: Two failures over a four-year period in a populaon of 25 circuit breakers Failure frequency: 2.0 failures / 100 CB-years Surveyed service experience SF 6 circuit breakers: 281 090 CB-years Disconnectors and earthing switches: 935 204 DE-years Instrument transformers: 1 290 335 IT-years (1-phase units) Gas insulated switchgear: 88 971 GIS CB-bay-years # of failures # of components survey duraon Failure freq. = [year -1 ] Failure definions (IEC 60694 defs.) Major failure (MaF): “... failure of a switchgear and control gear which causes the cessaon of one or more of its fundamental funcons. A major failure will result in an immediate change in the system operang condions, e.g. the backup protecve equipment will be required to remove the fault, or will result in mandatory removal from service within 30 minutes for unscheduled maintenance.” Minor failure (MiF): “... failure of an equipment other than a major failure or any failure, even incomplete, of a construconal element or a sub-assembly which does not cause a major failure.” Major failure frequencies SF 6 single pressure circuit breakers: 0.30 (0.67) MaF / 100 CB-years Disconnectors and earthing switches: 0.21 MaF / 100 DE-years Instrument transformers: 0.053 MaF / 100 IT-years (1-phase units) Gas insulated switchgear: 0.37 (0.53) MaF / 100 GIS CB-bay-years

Upload: others

Post on 24-Jan-2022

3 views

Category:

Documents


0 download

TRANSCRIPT

Study Committee A3High Voltage Equipment

I������������ C������ �� L���� E������� S������Conseil International des Grands Réseaux Électriques

http://www.cigre.org

Failure Frequencies for High Voltage Circuit Breakers, Disconnectors, Earthing Switches, Instrument Transformers and Gas Insulated Switchgear

CIGRÉ working group A3.06 "Reliability of High Voltage Equipment": M. Runde, C. E. Sölver, A. Carvalho, M. L. Cormenzana, H. Furuta, W. Grieshaber, A. Hyrczak, D. Kopejtkova, J. G. Krone, M. Kudoke, D. Makareinis, J. F. Martins,

K. Mestrovic, I. Ohno, J. Östlund, K.-Y. Park, J. Patel, C. Protze, J. Schmid, J. E. Skog, B. Sweeney, F. Waite, B. Bergman, and S. Tsukao.

The CIGRÉ reliability survey

• Equipment covered (U ≥ 60 kV): • Circuit breakers (only single pressure SF6) • Disconnectors and earthing switches • Instrument transformers • GIS; including a “GIS practice survey”

• Failure and population data collected for the time period 2004 – 2007

• Both major and minor failures included

• 90 utilities from 30 countries participated by returning completed Excel-based questionnaires

• Six Technical Brochures containing all results under way

Failure frequency calculation

Example:Two failures over a four-year period in a population of 25 circuit breakers

Failure frequency: 2.0 failures / 100 CB-years

Surveyed service experience

SF6 circuit breakers: 281 090 CB-years

Disconnectors and earthing switches: 935 204 DE-years

Instrument transformers: 1 290 335 IT-years (1-phase units)

Gas insulated switchgear: 88 971 GIS CB-bay-years

# of failures# of components • survey duration

Failure freq. = [year-1]

Failure definitions (IEC 60694 defs.)

Major failure (MaF): “... failure of a switchgear and control gear which causes the cessation of one or more of its fundamental functions. A major failure will result in an immediate change in the system operating conditions, e.g. the backup protective equipment will be required to remove the fault, or will result in mandatory removal from service within 30 minutes for unscheduled maintenance.”

Minor failure (MiF): “... failure of an equipment other than a major failure or any failure, even incomplete, of a constructional element or a sub-assembly which does not cause a major failure.”

Major failure frequencies

SF6 single pressure circuit breakers: 0.30 (0.67) MaF / 100 CB-years

Disconnectors and earthing switches: 0.21 MaF / 100 DE-years

Instrument transformers: 0.053 MaF / 100 IT-years (1-phase units)

Gas insulated switchgear: 0.37 (0.53) MaF / 100 GIS CB-bay-years

Study Committee A3High Voltage Equipment

I������������ C������ �� L���� E������� S������Conseil International des Grands Réseaux Électriques

http://www.cigre.org

SF6 single pressure circuit breaker major failure frequecies

Disconnector and earthing switches combined failure frequencies

GIS failure frequenciesInstrument transformer failure frequencies

Six Technical Bruchures containing all results are in print

TB no. 509 – 514: “Final Report of the 2004 – 2007 International Enquiry on Reliability of High Voltage Equipment”

“Part 1: Summary and General Matters” “Part 2: SF6 Circuit Breakers”“Part 3: Disconnectors and Earthing Switches” “Part 4: Instrument Transformers”“Part 5: Gas Insulated Switchgear” “Part 6: GIS Practices”