BlazeFrame® product catalog

I N T E G R AT E D F I R E S T O P S Y S T E M S

S T R O N G E R T H A N S T E E LSM.

clarkdietrich.com/BlazeFrame

The technical content of this literature is effective 9/10/12 and supersedes all previous information.Pub. No. CD-BlazeFrame 9/12 clarkdietrich.com

What is BlazeFrame? BlazeFrame products are innovative steel framing profile/intumescent composites, that combine ease of installation, inspection, life safety and joint protection dependability into one unique product.

How does it work? Using a cured factory metered dosage intumescent material, BlazeFrame profiles provide fire stopping, smoke and sound dampening that is effective immediately after framing components are installed. When exposed to heat above 375° F, the intumescent material expands up to 35 times its size. This provides additional protection from heat and flame passage during a fire event.

What does it replace? BlazeFrame's factory metered dosage intumescent material eliminates elastomeric fire proofing caulks and spray. The cured intumescent tape eliminates VOC's and off gases associated with caulked spray fire proofing. With the intumescent tape factory applied it eliminates both overage and underage often associated with the messy caulks and sprays.

BlazeFrame Advantages:• Installed&inspectedas" jointframing"

(before obstructions)• Unaffectedbydirty,oily,wetorfreezing

conditions• Curedintumescenteffectiveimmediately

(no VOC)• Nofatiguetojointorsubstratematerialsforlife

of assembly

BlazeFrame Design Advantages

One to three hour assembly

BLAZEFRAME FIRE STOP DEEP LEG DEFLECTION

TRACK (DL2, DSL2)

STEEL STUD

1, 2, 3, LAYERSFOR 1, 2, 3 HR RATING

5/8” TYPE XGYPSUM WALLBOARD

CONCRETE DECK

2

The technical content of this literature is effective 9/10/12 and supersedes all previous information. The technical content of this literature is effective 9/10/12 and supersedes all previous information. Pub. No. CD-BlazeFrame 9/12clarkdietrich.com

Fire Stopping• UL2079Classifiedandlistedforupto3hr

assemblies• Protectionforupto3"overallmovement

capability(1-1/2"upand1-1/2"down)• Eliminatesfireproofingcaulksandsprays• ShaftwallAssembliescertifiedforusewithall

ULlisted"liner"boardsandfinishsidegypsumproducts

Sound Dampening• NVLAPcertifiedtoprovideuptoSTC62

(based on wall assembly)• Openunencumberedjoints(nocaulkrequired)• FluteddeckexposedwithonlyBlazeFrame

Deck PlugorFluteCoverSTC=50+

Smoke barrier-air leakage - IBC 2009 BlazeFrameassemblieshavebeenULClassified withthelowestpossibleL-Rating(lessthan1CFM/lft).

Seismic Requirements BlazeFrameisUL2079ClassifiedforClassIIICycling of 500 cycles at 30 cycles per minute of vertical movement which may be capable of meeting seismic design and building code requirements.

Code Compliance BlazeFrame joint protection complies with up to date building codes and is listed by Underwriters LaboratoriesInc.

UL2079 TestsforFireResistanceofBuildingJointSystemsASTME-1966 StandardTestMethodforFireResistiveJointSystemsASTME-814 StandardMethodofFireTestsofFireStopSystemsULCS115-M95 StandardMethodofFireTestsofFireStopSystemsASTME-119 EvaluationofaNon-LoadBearingWallAssemblywithaControlJointBackerASTME-2837 RatedWallAssembliesInstalledtoNon-RatedAssemblies(pending)

Expandedintumescentstripafterfiretest

BlazeFramedeflectiontrack&deckplugsinsoundtest

3

The technical content of this literature is effective 9/10/12 and supersedes all previous information.Pub. No. CD-BlazeFrame 9/12 clarkdietrich.com

M E TA L D E C K CO N D I T I O N

CO N C R E T E D E C K CO N D I T I O N

• Head of Wall assembly complete before studs are installed.

• Mineralwoolonlyneededforflutefill.

• Earlier,easier,andaccurateinspection.

• Clean transition from wall sheathing to substrate.

• Exposedandfinishedjointsarefireandsoundrated.

BLAZEFRAME FIRE STOP DEEP LEG DEFLECTION

TRACK (DL2, DSL2)

STEEL STUD

1, 2, 3, LAYERSFOR 1, 2, 3 HR RATING

5/8” TYPE XGYPSUM WALLBOARD

CONCRETE DECK

MINERAL WOOLFLUTE FILL

BLAZEFRAME FIRE STOP DEEP LEG

DEFLECTION TRACK(DL2, DSL2)

1, 2, 3, LAYERSFOR 1, 2, 3, HR

RATING

ATTACH GYPSUM PER UL DESIGN REQUIREMENT

STEEL STUD

BlazeFrame Design Advantages

4

The technical content of this literature is effective 9/10/12 and supersedes all previous information. The technical content of this literature is effective 9/10/12 and supersedes all previous information. Pub. No. CD-BlazeFrame 9/12clarkdietrich.com

B E A M P E N E T R AT I O N CO N D I T I O N

• Eliminatescontourcuttingofwallsheathing,caulks/sprays.

• Sprayfireproofingormineralwoolaretheeasyoptionforbeamcavityfill.

METAL PAN DECK

BLAZEFRAME FIRE STOP DEEP LEG DEFLECTION

TRACK (DL2)

STEEL STUD

ANGLE OR Z-CLIPCENTERED

5/8” TYPE XGYPSUM WALLBOARD

FIRE PROOFINGor MINERAL WOOL

5/8” TYPE XGYPSUM WALLBOARD

BLAZEFRAME OFFSET DEEP LEG DEFLECTION TRACK

(ODL2, ODSL2)

14GA STRAP / ANGLEOUTRIGGER

STEEL STUD

• Eliminatesz-clips,lathbasket,voidsinfireproofing.

• 14gaangleoutrigger/profilepreassembledpriortoinstallation.

PA R A L L E L O FF S E T CO N D I T I O N

5

BlazeFrame Sample Profiles

The technical content of this literature is effective 9/10/12 and supersedes all previous information.Pub. No. CD-BlazeFrame 9/12 clarkdietrich.com

*4”leglengthisnotavailablefor2-1/2”widesystem

*4”leglengthisnotavailablefor2-1/2”widesystem

DSL 2 (DEEP LEG - SLOT TED BOTH SIDES)

SL 1 (DEEP LEG - SLOT TED ONE SIDE)

Profile with two slotted legs w/ fire stop on both sides CompositeFireStop/Framingforuseinfireratedwallassemblies. Provides 100%unencumberedjointprotection.Accommodatesupto11/2”overallmovementwithUL2019LevelIIICertification.MinimumCP60coating.Legswithslotsspaced1”o.c.forpositiveattachmentofstudsperlistedassembliesinULFireResistanceDirectory.

Widths: 2-1/2",3-5/8",4",6"and8" Thicknesses: 33mils(20ga),43mils(18ga)and54mils(16ga)

Profile Leg Length (L)

Tape Width (I)

Slot Height (S)

Joint Protection

DSL 2 3.00” 1.00” 1.50” 0.75”DSLW 2 3.00” 1.25” 1.50” 1.00”DSLX 2 4.00” * 1.75” 2.00” 1.50”

Profile with one slotted leg and one solid leg w/ fire stop on slotted side CompositeFireStop/Framingforuseinfireratedwallassemblies. Provides 100%unencumberedjointprotection.Accommodatesupto11/2”overallmovementwithUL2019LevelIIICertification.MinimumCP60coating.Onelegwithslotsspaced1”o.c.forpositiveattachmentofstudsperlistedassembliesinULFireResistanceDirectory.

Widths: 2-1/2",3-5/8",4",6"and8" Thicknesses: 33mils(20ga),43mils(18ga)and54mils(16ga)

Profile Slotted Leg Length (L1)

Solid Leg Length (L2)

Tape Width (I)

Slot Height (S)

Joint Protection

SL 1 3.00” 2.00” 1.00” 1.50” 0.75”SLW 1 3.00” 2.00” 1.25” 1.50” 1.00”SLX 1 4.00” * 2.50” 1.75” 2.00” 1.50”

(L)

Width

(L)

(S)

(I)

(L)

.22”1.00”Fastener mid-height of exposed slot

(L2)

Width

(L1)(I)

(I)

6

The technical content of this literature is effective 9/10/12 and supersedes all previous information. The technical content of this literature is effective 9/10/12 and supersedes all previous information. Pub. No. CD-BlazeFrame 9/12clarkdietrich.com

(DL 1 Series)

(DL 2 Series)

*4”leglengthisnotavailablefor2-1/2”widesystem

DL (DEEP LEG - SOLID)

JR (J-RUNNER)

CompositeFireStop/Framingforuseinfireratedwallassemblies. Provides 100%unencumberedjointprotection.Accommodatesupto3”overallmovementwithUL2019LevelIIICertification.MinimumCP60coating.Twosolidlegssupporting“freefloating”studsperlistedassembliesinULFireResistanceDirectory.

Widths: 2-1/2",3-5/8",4",6"and8" Thicknesses: 33mils(20ga),43mils(18ga)and54mils(16ga)

(DL 1 Series) Profile with two solid legs w/ fire stop on one side (DL 2 Series) Profile with two solid legs w/ fire stop on both sides

Profile Leg Length (L)

Tape Width (I)

Joint Protection

DL 2.00” 1.00” 0.75”DLW 2.00” 1.25” 1.00”

DLX 2.50” 1.75” 1.50”DLZ 3.00” 2.25” 2.00”DLY 4.00” * 3.25” 3.00”

Profile with two solid legs w/ fire stop on one side CompositeFireStop/Framingforuseinupto3hrfireratedshaftwallassemblies.Provides100%unencumberedjointprotection.Accommodatesupto11/2”overallmovementwithUL2019LevelIIICertification.MinimumCP60coating.Oneleg(front)havingintumescentperlistedassembliesinULFireResistanceDirectory.

Widths: 2-1/2",4"and6" Thicknesses: 33mils(20ga),43mils(18ga)and54mils(16ga)

Profile Front Leg Length (FL)

Back Leg Length (BL)

Tape Width (I)

Joint Protection

JR 1 2.00” 3.00” 1.00” 0.75”JRW 1 2.00” 3.00” 1.25” 1.00”

JRX 1 2.00” 3.00” 1.75” 1.50”

(L) (L)(I)(I)

(BL)(FL)

(I)

Width

Width

7

BlazeFrame Sample Profiles

The technical content of this literature is effective 9/10/12 and supersedes all previous information.Pub. No. CD-BlazeFrame 9/12 clarkdietrich.com

ODL 2 (OFFSET DEEP LEG)

ODSL 2 (OFFSET DEEP SLOT TED LEG)

Profile with two solid legs w/ fire stop on both sides CompositeFireStop/Framingwith“offsetstep”accommodates1-1/4”thick fireproofing in head of wall and wall to wall (column) assemblies. (Other offset depths available to accommodate other sprayed thicknesses). Provides100%unencumberedjointprotection.Accommodatesupto2”overallmovementwithUL2079LevelIIICertification.MinimumCP60coating.TwosolidlegsperlistedassembliesinULFireResistanceDirectory.

Widths: 3-5/8",4",6"and8" Thicknesses: 33mils(20ga),43mils(18ga)and54mils(16ga)

Profile Lower Leg Length (L)

Tape Width (I)

Joint Protection

ODL 2 2.00” 1.00” 0.75”ODLW 2 2.00” 1.25” 1.00”

ODLX 2 2.50” 1.75” 1.50”ODLZ 2 3.00” 2.25” 2.00”

Profile with two slotted lower legs w/ fire stop on both sides CompositeFireStop/Framingwith“offsetstep”accommodates1-1/4”thick fireproofing in head of wall and wall to wall (column) assemblies. (Other offset depths available to accommodate other sprayed thicknesses). Provides100%unencumberedjointprotection.Accommodatesupto1-1/2”overallmovementwithUL2079LevelIIICertification.MinimumCP60coating.Twolegswithslotsspaced1”o.c.forpositiveattachmentofstudsperlistedassembliesinULFireResistanceDirectory.

Widths: 3-5/8",4",6"and8" Thicknesses: 33mils(20ga),43mils(18ga)and54mils(16ga)

Profile Lower Leg Length (L)

Tape Width (I)

Slot Height (S)

Joint Protection

ODSL 2 3.00” 1.00” 1.50” 0.75”ODSLW 2 3.00” 1.25” 1.50” 1.00”

ODSLX 2 4.00” 1.75” 2.00” 1.50”

Width

(L)0.75”0.75”

(1-1/4”)*

Width

(L)

0.75” 0.75”(1-1/4”)*

* Other offset step depths available

* Other offset step depths available

(I)

(I)

8

The technical content of this literature is effective 9/10/12 and supersedes all previous information. The technical content of this literature is effective 9/10/12 and supersedes all previous information. Pub. No. CD-BlazeFrame 9/12clarkdietrich.com

C JB (CONTROL JOINT BACKER) Profile for protection of control joints CompositeFireStop/ControlJointBackerforusetoprotectArchitecturaldesignjoints(optionalcontroljointovergap)forupto2hrratedassemblies.MinimumG40coating.Providesa metal profile which supports intumescent materials located inside and spanning gap between opposing drywall edge at control jointlocations.Alsoeliminatestheneedforasecondstudinthegypsum assembly.

Width: 3-1/4" Length: 10'-0" Thicknesses: 18mils(25ga) Packaging: 14Pcs./Ctn.

Profile Intumescent Width

Profile Width

Thickness

CJB-18 1.25" 3.25" .018"

FC (FLUTE COVER) Profile strap for under fluted decks Corrugated strap for horizontal use to span fluted areas of unprotected or protected metal decks in up to 2 hr rated assemblies. Profile attached to deck“valley”surfacesamax16”o.c.onbothsides.Profilesprovidea surface area for attachment of head of wall partition track profiles centered or offset underneath and parallel to deck fluted areas per listed assemblies in ULFireResistanceDirectory.

Sizes: 675(6-3/4”)or700(7”) Length: 10'-0" Thicknesses: 33mils (20ga)

1.50” 1.50”0.875” 0.875”

Width varies to match flute opening

0.56

3”

WallboardSteel Stud

093 Control Joint CJB - Control Joint Backer

Eliminates the need for a second stud in

the gypsum assembly

BLAZEFRAME COMPOSITE(DL2, DSL2)

BLAZEFRAME (FC)FLUTE COVER(continuous)

5/8” TYPE XGYPSUM WALLBOARD STEEL STUD

FLUTED DECK

9

The technical content of this literature is effective 9/10/12 and supersedes all previous information.Pub. No. CD-BlazeFrame 9/12 clarkdietrich.com

BLAZEFRAME COMPOSITETRACK/FIRE STOP

(DL1, SL1)

5/8” TYPE XGYPSUM WALLBOARD

CONCRETE DECK

STEEL STUD

BLAZEFRAME FIRE STOP DEEP LEG DEFLECTION

TRACK (DL2, DSL2)

STEEL STUD

1, 2, 3, LAYERSFOR 1, 2, 3 HR RATING

5/8” TYPE XGYPSUM WALLBOARD

CONCRETE DECK

Post Tension or Structural Concrete Overhead

PT-1HW-D-0498

Chase Wall Post Tension or Structural Flat Concrete

PT-2 HW-D-0505

METAL PAN DECK

BLAZEFRAME FIRE STOP DEEP LEG DEFLECTION

TRACK (DL2)

STEEL STUD

ANGLE OR Z-CLIPCENTERED

5/8” TYPE XGYPSUM WALLBOARD

FIRE PROOFINGor MINERAL WOOL

MINERAL WOOLFLUTE FILL

BLAZEFRAME FIRE STOP DEEP LEG

DEFLECTION TRACK(DL2, DSL2)

1, 2, 3, LAYERSFOR 1, 2, 3, HR

RATING

ATTACH GYPSUM PER UL DESIGN REQUIREMENT

STEEL STUD

Perpendicular Unprotected Deck (UD) – Mineral Wool Fill

UD-1 HW-D-0513

Head of Wall Beam Penetration SS-1

HW-D-0495

BlazeFrame Sample Details

10

The technical content of this literature is effective 9/10/12 and supersedes all previous information. The technical content of this literature is effective 9/10/12 and supersedes all previous information. Pub. No. CD-BlazeFrame 9/12clarkdietrich.com

BLAZEFRAME COMPOSITE(DL2, DSL2)

BLAZEFRAME (FC)FLUTE COVER(continuous)

5/8” TYPE XGYPSUM WALLBOARD STEEL STUD

FLUTED DECK

BLAZEFRAME COMPOSITETRACK/FIRE STOP

(DL2, DSL2)

FIRE PROOFING

5/8” TYPE XGYPSUM WALLBOARD

MINERAL WOOL

STEEL STUD

Centered Under Flute Unprotected Deck (UD) – Flute Cover

UD-6 HW-D-0544

Perpendicular Protected Deck (PD) – Mineral Wool Flute Fill

PD-12 HW-D-0513

Parallel Under Structural Support (Z-Clips)

SS-16 HW-D-0502

Wall to Wall Gypsum to Protected Steel (I-Beam)

VM-3Design Based on

WW-S-0055HW-D-0558

BLAZEFRAME COMPOSITETRACK/FIRE STOP

(DL2, DSL2)

5/8” TYPE XGYPSUM WALLBOARD

Z-CLIPS

STEEL STUD

STEEL COLUMN

BLAZEFRAME “OL” PROFILE(ODL2)

5/8” TYPE XGYPSUM WALLBOARD

FIRE PROOF COATING

11

The technical content of this literature is effective 9/10/12 and supersedes all previous information.Pub. No. CD-BlazeFrame 9/12 clarkdietrich.com

CONCRETE COLUMN / WALL

5/8” TYPE XGYPSUM WALLBOARD

STEEL STUD

BLAZEFRAME COMPOSITE TRACK / FIRESTOP

(DL2)

Wall to Wall Gypsum to Concrete Column/Wall

VM-1 WW-S-0055

5/8” TYPE XGYPSUM WALLBOARD

BLAZEFRAME COMPOSITETRACK / FIRE STOP

“OL” - SERIES(ODL2, ODSL2)

STEEL STUD 5/8” TYPE XGYPSUM WALLBOARD

BLAZEFRAME OFFSET DEEP LEG DEFLECTION TRACK

(ODL2, ODSL2)

14GA STRAP / ANGLEOUTRIGGER

STEEL STUD

5/8” TYPE XGYPSUM WALLBOARD

093 CONTROL JOINT(optional)

SHAFT LINER BOARD

BLAZEFRAME COMPOSITETRACK / FIRE STOP

(JR1)

CH, CT, OR I STUD

Parallel Under Structural Support (Offset Leg Profile)

SS-2 HW-D-0502

Edge of Structural Support with Angle (Offset Leg Profile)

SS-28 HW-D-0631

Hollow Steel Shape - Non RatedSS-21

Design Based on HW-D-0543 HW-D-0559

BlazeFrame Sample Details

12

The technical content of this literature is effective 9/10/12 and supersedes all previous information. The technical content of this literature is effective 9/10/12 and supersedes all previous information. Pub. No. CD-BlazeFrame 9/12clarkdietrich.com

Under UL G500 Series DesignVM-6

HW-D-0503

BLAZEFRAME COMPOSITE TRACK / FIRE STOP

(DL2, DSL2)

5/8” TYPE XGYPSUM WALLBOARD

FURRING CHANNEL

STEEL STUD

5/8” TYPE XGYPSUM WALLBOARD

Bottom of WallVM-12

BW-S-0021

5/8” TYPE XGYPSUM WALLBOARD

BLAZEFRAME COMPOSITETRACK / FIRE STOP

(DL2) CONCRETE FLOOR

STEEL STUD

Flat Strap PatchVertical Cavity Obstructions

ECA - End Cap AngleExterior Corner Application

FIELD MODIFIED - VERTICAL OBSTRUCTION

TOP VIEW SIDE VIEW

FASTEN FSP TO OUTERSURFACE OF TRACK LEG

BLAZEFRAME FSP(Flatstrap Patch)

TOP VIEW TOP VIEWINSERT ECA

SIDE VIEW INSERT ECA

ECA ATTACHED WITH FASTENER

INTERSECTING WALL BLAZEFRAME “BUTTED”

13

The technical content of this literature is effective 9/10/12 and supersedes all previous information.Pub. No. CD-BlazeFrame 9/12 clarkdietrich.com

CONCRETE DECK

BLAZEFRAME COMPOSITETRACK / FIRE STOP

(JR1)

3 LAYERS FOR3 HOUR RATING

CH, CT, OR I STUD

LINER BOARD

MINERAL WOOL

5/8” TYPE XGYPSUM WALLBOARD

BLAZEFRAMECOMPOSITE

TRACK / FIRE STOP(JR1)

FASTENER AT BOTTOMOF OBSTRUCTION

(when exists)CT, CH, OR I STUD

LINER BOARD

MINERAL WOOL

MINERAL WOOL orFIRE PROOFING

5/8” TYPE XGYPSUM WALLBOARD

093 CONTROL JOINT

5/8” TYPE XGYPSUM WALLBOARD

BLAZEFRAME “CJB”CONTROL JOINT BACKER

STEEL STUD5/8” TYPE X

GYPSUM WALLBOARD

BLAZEFRAME “CJB”CONTROL JOINT BACKER

093 CONTROL JOINT

STEEL STUD

Shaft Wall Post Tension or Structural Concrete

PT-3HW-D-0496

CJB - Control Joint Backer one side 1-hour

12033

Shaft Wall Perpendicular to Unprotected Deck

UD-10HW-D-0504

CJB - Control Joint Backer two sides 2-hour

12033

BlazeFrame Sample Details

14

The technical content of this literature is effective 9/10/12 and supersedes all previous information. The technical content of this literature is effective 9/10/12 and supersedes all previous information. Pub. No. CD-BlazeFrame 9/12clarkdietrich.com

UL Approvals

UL Control - R25833 (US)- 1, 2 and 3 hr designs - UL 2079 standard compliant

UL Listings

HW-D-0495 Protected Beam Penetration HW-D-0496 Under Flat Concrete (shaft wall) HW-D-0497 Parallel to Protected Beam (shaft wall) HW-D-0498 Under PT or Structural Concrete HW-D-0499 Parallel to Unprotected Fluted Metal Deck HW-D-0500 Perpendicular Unprotected Fluted Metal Deck HW-D-0501 Parallel to Beam (standard wall) HW-D-0502 Parallel & Edge Overlap Under Structural Support HW-D-0503 Under Layer “Type C” UL 500 Series Designs HW-D-0504 Under Unprotected Fluted Metal Deck (shaft wall) HW-D-0505 Under PT or Structural Concrete (chase wall) HW-D-0506 Under Fluted Metal Deck (chase wall) HW-D-0512 Perpendicular Protected Deck w/Fire Proofing Flute Fill HW-D-0513 Perpendicular Unprotected Deck w/Mineral Wool only Flute Fill HW-D-0543 Stair Shaft (093 Control Joint Optional) HW-D-0544 Parallel under Flute (Flute Cover Plate) HW-D-0558 Offset Leg Standard Wall Protected Roof Deck/Substrate HW-D-0559 Offset Leg Shaft Wall Protected Roof Deck/Substrate HW-D-0597 Parallel to Beam (Z-clip & Drywall Rip) HW-D-0631 Shaft Wall Parallel & Edge Overlap Under Structural Support HW-D-0632 PT or Structural Concrete Bare Slotted with Caulks HW-D-0633 Fluted Metal Deck Bare Slotted with Flute Plate/Caulks WW-S-0055 Vertical Wall to Wall Joint BW-S-0021 Bottom of Wall

Details shown are a limited sample of assemblies based on UL certified and listed assemblies. Additional assembly details, submittal sheets, and constructability designs are periodically added upon design and approval. Information can be viewed, downloaded, and printed from www.clarkdietrich.com/BlazeFrame.

Project Information

Name:

Address:

City/ST/ZIP:

Contractor Information

Name:

Contact:

Phone:

Fax:

Architect Information

Name:

Contact:

Phone:

Fax:

- ClarkDietrich products are manufactured from cold-formed steel. Steel is 100% recyclable, which helps divert debris from the waste

stream. The contribution to LEED must be calculated by the contractor based on weight or volume.

- ClarkDietrich’s steel products have a minimum of 25.5% post-consumer recycled content, and 6.8% pre-consumer. If you wish to

report a higher number for your project or seek Credit MR 5 please contact Technical Services at 888-437-3244 or visit www.clarkdietrich.com.

® (CJB)

“CJB” (Control Joint Backer)

Composite Fire Stop/Control Joint Backer for use to protect Architectural

design joints (optional control joint over gap) for up to 2 hr rated assemblies.

between opposing drywall edge at control joint locations. Also eliminates the

need for a second stud in the gypsum assembly.

Material:

Yield Strength: Grade 33ksi

Coating:

G40

18mils: 25 Gauge, 0.0188” Design Thickness, 0.0179“ Min. Thickness

Dimensions:

Width:

3-1/4”

Length:

10’-0”

Packaging:

14 Pieces/Carton

Intumescent

Width

Width

Gap

Width

Flange

Width

CJB-181.25”

3.25”.75”

1.25”

ASTM A1003, C955

WFCI 12033

is available @ www.clarkdietrich.com

CD-BlazeFrame-CJB © 08/12 ClarkDietrich Building Systems

Wallboard

Eliminates the need

for a second stud in

the gypsum assembly

Steel Stud

093 Control Joint

CJB - Control Joint Backer

Product Submittal Sheet

Technical Services: 888-437-3244

Engineering Services: 877-832-3206

Sales: 800-543-7140

clarkdietrich.com

Project InformationName: Address: City/ST/ZIP:

Contractor InformationName: Contact: Phone: Fax:

Architect InformationName: Contact: Phone: Fax:

- ClarkDietrich products are manufactured from cold-formed steel. Steel is 100% recyclable, which helps divert debris from the waste

stream. The contribution to LEED must be calculated by the contractor based on weight or volume.

- ClarkDietrich’s steel products have a minimum of 25.5% post-consumer recycled content, and 6.8% pre-consumer. If you wish to

report a higher number for your project or seek Credit MR 5 please contact Technical Services at 888-437-3244 or visit www.clarkdietrich.com.

Material: Yield Strength: Grade 33ksi for 33mils & 43mils, 50ksi for 54mils

Coating: CP60 (G90 available)

33mils: 20 Gauge, 0.0346” Design Thickness, 0.0329“ Min. Thickness

43mils: 18 Gauge, 0.0451” Design Thickness, 0.0428“ Min. Thickness

54mils: 16 Gauge, 0.0566” Design Thickness, 0.0538“ Min. Thickness

Dimensions: Inside width: Equal to the outside width of the stud

Widths (W): 3-5/8”, 4”, 6” and 8”

Track length: 10’-0”

Lower Leg Length (L)

Tape Width (I)

Slot Height (S)

Joint Protection

ODSL 2 3.00” 1.00” 1.50” 0.75”

ODSLW 2 3.00” 1.25” 1.50” 1.00”

ODSLX 2 4.00” * 1.75” 2.00” 1.50”

ASTM A1003, C955

UL2079, E814, E1966, E119

is available @ www.clarkdietrich.com

CD-BlazeFrame-ODSL2 © 08/12 ClarkDietrich Building Systems

Width (W)

(L)0.75” 0.75”

(1-1/4”) **

®

“ODSL 2” (Offset Slotted Leg)

Two offset slotted lower legs

Composite F

up to 1-1/2” thick in head of wall and wall to wall (column) assemblies. Pro-

vides 100% unencumbered joint protection. Accommodates up to 3” overall

legs with slots spaced 1”o.c. for positive attachment of studs per listed

assemblies in UL Fire Resistance Directory.

provides air, smoke and sound seals. When exposed to heat above 325

degrees Fahrenheit, the intumescent material expands up to 35 times its size.

* 4” leg length is not available for 2-1/2” wide system** Other offset step depths available

(I)

Product Submittal Sheet

Technical Services: 888-437-3244

Engineering Services: 877-832-3206Sales: 800-543-7140

clarkdietrich.com

Project InformationName: Address: City/ST/ZIP: Contractor Information

Name: Contact: Phone: Fax: Architect InformationName: Contact: Phone: Fax:

- ClarkDietrich products are manufactured from cold-formed steel. Steel is 100% recyclable, which helps divert debris from the waste

stream. The contribution to LEED must be calculated by the contractor based on weight or volume.

- ClarkDietrich’s steel products have a minimum of 25.5% post-consumer recycled content, and 6.8% pre-consumer. If you wish to

report a higher number for your project or seek Credit MR 5 please contact Technical Services at 888-437-3244 or visit www.clarkdietrich.com.

®

Composite Fire Stop/Framing for

100% unencumbered joint protection. Accommodates up to 1 1/2” overall

with slots spaced 1”o.c. for positive attachment of studs per listed assemblies

in UL Fire Resistance Directory.

provides air, smoke and sound seals. When exposed to heat above 325

degrees Fahrenheit, the intumescent material expands up to 35 times its size.

Material: Yield Strength: Grade 33ksi for 33mils & 43mils

Grade 50ksi for 54mils

Coating:

CP60 (G90 available)

33mils: 20 Gauge, 0.0346” Design Thickness, 0.0329“ Min. Thickness

43mils: 18 Gauge, 0.0451” Design Thickness, 0.0428“ Min. Thickness

54mils: 16 Gauge, 0.0566” Design Thickness, 0.0538“ Min. Thickness

Dimensions: Inside width: Equal to the outside width of the stud

Widths (W): 2-1/2”, 3-5/8”, 4”, 6” and 8”

Vertical slots: 0.22” wide & spaced every 1”o.c.

Track length: 10’-0”

Leg Length (L) Tape Width (I) Slot Height (S) Joint Protection

DSL 23.00”

1.00”1.50”

0.75”

DSLW 23.00”

1.25”1.50”

1.00”

DSLX 24.00” *

1.75”2.00”

1.50”ASTM A1003, C955UL2079, E814, E1966, E119

is available @ www.clarkdietrich.com

CD-BlazeFrame-DSL2 © 08/12 ClarkDietrich Building Systems

(L)

(W)

(L)

(S)

(I)

(L)

.22”1.00”

Fastener mid-height of exposed slot

* 4” leg length is not available for 2-1/2” wide system

Product Submittal Sheet

Technical Services: 888-437-3244

Engineering Services: 877-832-3206 Sales: 800-543-7140clarkdietrich.com

NEED TO SEND PRODUCT SUBMIT TALS?Build BlazeFrame Product Submittals for your next project. UseClarkDietrich'sSubmittalPro®ProductSubmittalSystemtocreateandsend a PDF package of BlazeFrame's product information and technical submittals based on your project's layout conditions.

Launch SubmittalPro® from clarkdietrich.com

CodeApprovals

15

CD-BlazeFrame 9/12 © ClarkDietrich Building Systems. The technical content of this literature is effective 9/10/12 and supersedes all previous information.

Turn to ClarkDietrich for a complete lineup of steel construction products and services nationwide:

Interior Framing∙Exterior Framing∙Interior Finishing∙Clips/Connectors∙Metal Lath/Accessories∙Engineering

9100 Centre Pointe Dr. Suite 210 West Chester, OH 45069

P 513.870.1100 F 513.870.1300

clarkdietrich.comClarkwestern Dietrich Building Systems LLC