HVAC LEGEND
SYMBOLS ABBREVIATIONS DESCRIPTIONS
SQ., RECT., OR ROUND DUCT SIZE AS NOTED
DUCT WITH ACOUSTICAL LINER
EXISTING DUCT OR EQUIPMENT TO REMAIN
EXISTING DUCT OR EQUIPMENT TO BE REMOVED
FLEXIBLE DUCT
CEILING DIFFUSER, SUPPLY
CEILING REGISTER, RETURN / EXHAUST
CD
CR / CE
SECTION THROUGH DUCT
DUCT DOWN
RECTANGULAR TO ROUND TRANSITION
MITERED DUCT ELBOW WITH TURNING VANES
1A
EFEQUIPMENT DESIGNATION AND NUMBER
SMOKE FIRE DAMPER WITH ACCESS DOOR
MANUAL VOLUME DAMPER, LOCKING QUADRANT TYPE FORROUND DUCT OR OPPOSED BLADE TYPE FOR RECT DUCT.
SFD
MVD
T THERMOSTAT
H HUMIDISTAT
DD DUCT DETECTOR
RS REMOTE SENSOR
T'STAT
CUBIC FEET OF AIR PER MINUTECFM
CFM SUPPLYCFMS
CFM RETURNCFMR
CFM EXHAUSTCFME
EXISTING(E) or EXIST.
NEW(N)
INDICATES RECTANGULAR DUCT SIZE: WIDTH x HEIGHT30"x10"
INDICATES ROUND DUCT SIZE: DIAMETER12"Ø
POINT OF CONNECTION
POINT OF DEMOLITION
POC
POD
THE TOTAL INSTALLATION SHALL COMPLY WITH ANY AND ALL REQUIREMENTS OF THE LEGALLY CONSTITUTED AUTHORITIES HAVINGJURISDICTION INCLUDING 2013 CBC (CALIFORNIA BUILDING CODE) AND 2013 CMC/CPC (CALIFORNIA MECHANICAL AND PLUMBING CODE).
THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID AND SHALL THOROUGHLY FAMILIARIZE HIMSELF WITH THE EXISTING CONDITIONSUNDER WHICH HE WILL BE REQUIRED TO WORK.
ALL INDICATED DIMENSIONS ARE APPROXIMATE AND ARE GIVEN FOR ESTIMATE PURPOSES ONLY. BEFORE PROCEEDING WITH THE WORKTHIS CONTRACTOR SHALL CAREFULLY CHECK AND VERIFY ALL DIMENSIONS, SIZES, REQUIRED CLEARANCES AND SHALL ASSUME FULLRESPONSIBILITY FOR THE FITTING OF ALL EQUIPMENT AND MATERIALS HEREIN REQUIRED TO OTHER PARTS OF THE WORK OF OTHERTRADES.
THE DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC TO THE EXTENT THAT ALL OFFSETS, BENDS, SPECIAL FITTINGS AND LOCATIONS ARE NOTEXACTLY LOCATED. ALL DUCTWORK DIMENSIONS SHOWN ON THE DRAWINGS ARE NET INSIDE DIMENSIONS. DO NOT FABRICATE DUCTWORKFROM THESE DRAWINGS. THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR SUPPLYING SHOP DRAWINGS WHICH REFLECT THEPROPOSED INSTALLATION. THE SHOP DRAWINGS MUST BE APPROVED BY THE ENGINEER PRIOR TO ANY SHEET METAL FABRICATION. THEMECHANICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ACCURATE AS-BUILT DRAWINGS AT THE COMPLETION OF THE PROJECT ANDSUBMITTING THEM TO THE ENGINEER AND OWNER.
IN THE PREPARATION OF THESE DOCUMENTS, CERTAIN ASSUMPTIONS ARE MADE REGARDING EXISTING CONDITIONS. SOME OF THESEASSUMPTIONS MAY NOT BE VERIFIABLE WITHOUT EXPENDING ADDITIONAL SUMS OF MONEY OR DESTROYING OTHERWISE ADEQUATE ORSERVICEABLE PORTIONS OF EXISTING BUILDINGS AND/OR EQUIPMENT. THEREFORE, THE ENGINEER SHALL NOT BE HELD RESPONSIBLEFOR ANY CHANGES OR ADDITIONAL COSTS INCURRED DUE TO EXISTING CONDITIONS.
THE CONTRACTOR SHALL COMPLY WITH ALL CONTRACT DOCUMENTS IN LAYING OUT HIS WORK AND EQUIPMENT. HE SHALL COORDINATETHE WORK OF THIS SECTION WITH THE WORK OF OTHER TRADES AND ALL JOB CONDITIONS.
THE INSTALLATION OF ACCESS PANELS OR OTHER INDICATING EQUIPMENT OR SPECIALTIES REQUIRING READING, ADJUSTMENT,INSPECTION, REPAIRS, REMOVAL OR REPLACEMENT SHALL BE CONVENIENTLY LOCATED WITH REFERENCE TO THE FINISHED BUILDING.
WHERE MATERIAL IS SHOWN ON THE DRAWINGS BUT NOT SPECIFIED, IT SHALL BE OF THE SAME TYPE AND QUALITY AS EXISTING MATERIAL.
PROVIDE MANUAL VOLUME DAMPERS AT UPSTREAM PORTION OF ALL TERMINAL AIR BRANCHES. THESE SHALL BE OF THE LOCKINGQUADRANT TYPE. WHERE LOCATED OVER SLOPED OR HARD CEILINGS, PROVIDE DURO-DYNE ANGLE GEAR DRIVE OR BOWDEN CABLECONTROL SYSTEM OR PROVIDE UNITED ENERTECH POWER/BALANCE SYSTEM. REMOTE PLATE LOCATIONS TO BE LOCATED AS DETERMINEDBY ARCHITECT..
PROVIDE MINIMUM 1" ACOUSTICAL LINING IN ALL DUCTWORK WITHIN 10 FEET OF ALL AIR MOVING EQUIPMENT. PROVIDE DURO-DYNEFLEXIBLE CONNECTION AT ALL DUCT AT EQUIPMENT LOCATIONS.
INSULATION THICKNESS FOR ENERGY PERFORMANCE SHALL BE BASED ON TITLE 24 ENERGY CODE AND REGULATIONS OR UNLESSOTHERWISE STATED ON FLOOR PLANS.
WHERE NOT SPECIFICALLY INDICATED OTHERWISE, ALL DUCTWORK AND EQUIPMENT SHALL BE SUPPORTED PER THE SMACNA GUIDELINESFOR SEISMIC RESTRAINT AND CURRENT APPLICABLE UNIFORM MECHANICAL CODE.
WHEN A FIRE ALARM SYSTEM WITH FULL COVERAGE SMOKE DETECTORS ARE PROVIDED, DUCT SMOKE DETECTORS MAY BE ELIMINATED.FIRE ALARM CONTRACTOR SHALL WIRE SMOKE/FIRE DAMPER ACTIVATORS TO AREA SMOKE DETECTORS.
TESTING, ADJUSTING, AND BALANCING (TAB) OF THE AIR CONDITIONING SYSTEMS AND RELATED ANCILLARY EQUIPMENT WILL BEPERFORMED BY A CERTIFIED, INDEPENDENT THIRD PARTY, AABC AGENCY PROCURED BY THE MECHANICAL CONTRACTOR. A COMPLETE AIRBALANCE REPORT TO BE SUBMITTED TO THE ADMINISTRATIVE AUTHORITY AND TO THE MECHANICAL ENGINEER AND APPROVED PRIOR TOFINAL PAYMENT.
DUCT SYSTEMS USED WITH BLOWER TYPE EQUIPMENT WHICH ARE PORTIONS ON THE HEATING, COOLING, ABSORPTION, EVAPORATIVECOOLING OR OUTDOOR AIR VENTILATION SYSTEM SHALL BE SIZED IN ACCORDANCE WITH CHAPTER 17 OF THE CALIFORNIA MECHANICALCODE.
UNLESS OTHERWISE STATED, MAXIMUM LENGTH FOR FLEXIBLE DUCTWORK SHALL NOT EXCEED SEVEN FEET (7'-0"). ALUMINUM FLEXDUCTWORK WILL NOT BE ALLOWED ON ANY PORTION OF THE DUCTWORK SYSTEM.
ANY SUBSTITUTION MADE BY THE CONTRACTOR THAT IS DIFFERENT FROM WHAT IS SPECIFIED ON THE DRAWINGS SHALL BE CLEARLYINDICATED ON THE SUBMITTAL AS TO ALL THAT IS BEING SUBSTITUTED.
DURING CONSTRUCTION, ALL DUCT AND OTHER AIR DISTRIBUTION COMPONENT OPENINGS SHALL BE COVERED WITH TAPE, PLASTIC OROTHER ACCEPTABLE MATERIAL TO REDUCE THE AMOUNT OF DUST OR DEBRIS WHICH MAY COLLECT IN THE SYSTEM.
PER ASHRAE 90.1 SECTION 6.4.4.2.1, DUCTWORK AND ALL PLENUMS WITH PRESSURE CLASS RATINGS SHALL BE CONSTRUCTED TO SEALCLASS A. AT A MINIMUM, ASHRAE 90.1 PRESCRIPTIVE REQUIREMENTS ARE REQUIRED PER GSA P-100 (2014) SECTIONS 1.4.5, 1.8.1 ANDTABLE 5.4 FOR MAJOR BUILDING ALTERATIONS.
MECHANICAL GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
ANCHORAGE AND BRACING NOTES
1. PIPES, DUCTS AND CONDUITS SHALL BE SUPPORTED AND BRACED PER THE SMACNA "GUIDELINES FOR SEISMIC RESTRAINTS OFMECHANICAL SYSTEMS AND PLUMBING SYSTEMS", THE "SUPERSTRUT SEISMIC RESTRAINT SYSTEM" FOR PIPES AND CONDUITS ONLY.
MECHANICAL SHEET INDEX
BASIS OF DESIGN
PROVIDE SERVICES OF MECHANICAL CONSTRUCTION DOCUMENT DESIGN AND SPECIFICATIONS FOR ANAHEIM HILLS ASC OFAPPROXIMATELY 3900.00 SQ. FT. NEW GENERATOR TO BE DESIGNED INTO EXISTING SYSTEM FOR OR ROOMS.
FILTER RACK SCHEDULE
5151 Shoreham Place, Suite #240San Diego, CA 92122Phone: 619.330.6043Fax: 909.890.3770
Email: [email protected]
DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS
REG
ISTE
RED
PROF
RE
ENI
GNE
ESSIONAL
ETA
TS
FO FILACO
AINR
M
No. 33209
E C HA N I CA L
NHOJNEVETS
M.
NOS
EXP. 9-30-2017
PROFESSIONAL STAMPS:
SH
EE
T T
ITLE
:
SHEET NUMBER:
PRIN
TED
:PA
TH:
DATE ISSUED:
DRAWN BY:
RE
VIS
ION
S:
PR
OJE
CT
NA
ME
PR
OJE
CT
NU
MB
ER
:15.0
04
1 2 3 4 5
MEDIC
AL A
RCHIT
ECTURE &
CONSULTIN
GRAYM
OND F
OX &
ASSOCIA
TES
1660 H
OTEL C
IRCLE N
ORTH S
TE 3
40 S
AN D
IEG
O C
A 9
2108
(619) 296-4
595
RA
YM
ON
DF
OX
.CO
M
6 7
AN
AH
EIM
HIL
LS
ASC
500 S
. ANAH
EIM
HIL
LS
RD.
STE. 128,1
29
ANAH
EIM
, CA 9
2807
J.P.
5/1
8/2
016 3
:52:1
5 P
MC:\
Use
rs\j
pete
rson.D
ESIG
NW
ESTEN
G\D
ocu
ments
\15-4
41 A
NAH
EIM
HIL
LS A
SC_M
P_CEN
TRAL_
jpete
rson.r
vt
15-441
M0.1
Issue Date
MECH
AN
I CAL L
EG
EN
DS, N
OTES &
SCH
ED
ULES
Sheet # Sheet Name
M0.1 MECHANICAL LEGENDS, NOTES & SCHEDULES
M1.1 MECHANICAL FLOOR PLAN
M2.1 MECHANICAL PIPING PLAN
M3.1 MECHANICAL DETAILS
M3.2 MECHANICAL CONTROLS
TYPE DESCRIPTION MFR. MODEL ACCESSORIES
6x6 CD CEILING DIFFUSER, MODULAR CORE, ALUMINUM KRUEGER 51240 FRAME 22 SURFACE MOUNT
6x6 CD CEILING DIFFUSER, MODULAR CORE, ALUMINUM KRUEGER 51240 FRAME 23 LAY-IN T-BAR PANEL
6x6 CR RETURN GRILLE, FIXED DEFLECTION, ALUMINUM KRUEGER 5810 FRAME 23 LAY-IN T-BAR PANEL
8x8 CD CEILING DIFFUSER, MODULAR CORE, ALUMINUM KRUEGER 51240 FRAME 23 LAY-IN T-BAR PANEL
8x8 CR RETURN GRILLE, FIXED DEFLECTION, ALUMINUM KRUEGER 5810 FRAME 23 LAY-IN T-BAR PANEL
10x10 CD CEILING DIFFUSER, MODULAR CORE, ALUMINUM KRUEGER 51240 FRAME 23 LAY-IN T-BAR PANEL
10x10 CR RETURN GRILLE, FIXED DEFLECTION, ALUMINUM KRUEGER 5810 FRAME 23 LAY-IN T-BAR PANEL
12x10 EG SIDE WALL EXHAUST GRILLE, ALUMINUM KRUEGER S585 HORIZONTAL BLADES
12x12 CD CEILING DIFFUSER, MODULAR CORE, ALUMINUM KRUEGER 51240 FRAME 23 LAY-IN T-BAR PANEL
12x12 CR RETURN GRILLE, FIXED DEFLECTION, ALUMINUM KRUEGER 5810 FRAME 23 LAY-IN T-BAR PANEL
14x14 CR RETURN GRILLE, FIXED DEFLECTION, ALUMINUM KRUEGER 5810 FRAME 23 LAY-IN T-BAR PANEL
16x16 CR RETURN GRILLE, FIXED DEFLECTION, ALUMINUM KRUEGER 5810 FRAME 23 LAY-IN T-BAR PANEL
PAT-2424-C-12R-L CEILING DIFFUSER, LAMI-VENT MODULE, ALUMINUM PRECISION AIR PAT-2424-C
SPLIT SYSTEM HEAT PUMPS SCHEDULE
AIR DISTRIBUTION SCHEDULE
FR
1HOUSING:
SIZE:
FILTERS:
OPTIONS:
CAMFIL MAGNA/PACK SIDE-ACCESS ABSOLUTE FILTER HOUSING
1W x 1/2H (28.50" x 14.38")
QTY - FILTER - SIZE1 - CAMFIL XH ABSOLUTE HIGH CAPACITY HEPA FILTER - 24x12x11.50
DIFFERENTIAL PRESSURE SWITCHFULLY INSULATEDGALVANIZEDDOUBLE WALL CONSTRUCTION
ALL PARTICULATE FILTERS SHALL COMPLY TO ASHRAE 52.2-2007 INCULDINGAPPENDIX J, FILTER EFFICIENCY SHALL BE MAINTAINED THROUGH OUT THEENTIRE LIFE OF THE FILTERS.
TYPE MARK MFR MODELUNIT
SERVED AIR FLOW
ELECTRICAL
WEIGHT LBS. ACCESSORIESPOWER VOLTAGE PHASE Hz MCA
H 1 NORTEC NH-EL 1/020 FC-3 850 CFM 800 W 208 V 3 60 Hz 30 A 65
H 2 NORTEC NH-EL 1/020 FC-4 850 CFM 800 W 208 V 3 60 Hz 30 A 65
HUMIDIFIER SCHEDULE
TYPE MARK MFR MODEL
AIR FLOW HEATINGCAPACITY
COOLING ELECTRICAL DATA
WEIGHT LBS. ACCESSORIESSUPPLY ESP TOTAL CAP SENSIBLE CAP VOLTAGE PHASE Hz FLA MCA MOCP
FC 1 CARRIER 42BHE16B6
FC 2 CARRIER 42BHE20K7
FC 3 AAON H3-BRB-3-A-141D-3B2 600 CFM 2.50 in-wg 49,000 Btu/h 38,390 Btu/h 33,230 Btu/h 460 V 3 60 Hz 19 A 23 A 25 A 624
FC 4 AAON H3-BRB-3-A-141D-3B2 600 CFM 2.50 in-wg 49,000 Btu/h 38,390 Btu/h 33,230 Btu/h 460 V 3 60 Hz 19 A 23 A 25 A 624
FC 5 MITSUBISHI MSY-GA24NA 550 CFM 22,000 Btu/h 208 V 1 60 Hz 1 A 0 A 0 A 37
CONDENSING UNIT SCHEDULE
SPLIT SYSTEM FAN COIL SCHEDULE
TYPE MARK MFR MODEL
COOLING DATA ELECTRICAL DATA WEIGHTLBS. ACCESSORIESTOTAL SENSIBLE SEER VOLTAGE PHASE Hz FLA MCA MOCP
CU 1 MITSUBISHI MUY-GA24NA 22,000 Btu/h 16,923 Btu/h 17.5 208 V 1 60 Hz 14.17 A 17 A 20 A 117
EXHAUST FAN SCHEDULE
TYPE MARK MFR MODEL
AIR FLOW
FAN RPM MOTOR HP
ELECTRICAL
WEIGHT LBS. ACCESSORIESCFM ESP VOLT PHASE Hz
EF 1 LOREN COOK GC-144 105 CFM 0.50 in-wg 1036 N/A 120 V 1 60 Hz 15 BACKDRAFT DAMPER, PAINTED ALUMINUM GRILLE
EF 2 LOREN COOK GC-144 75 CFM 0.50 in-wg 924 N/A 120 V 1 60 Hz 15 BACKDRAFT DAMPER, PAINTED ALUMINUM GRILLE
EF 3 LOREN COOK GC-144 55 CFM 0.50 in-wg 903 N/A 120 V 1 60 Hz 15 BACKDRAFT DAMPER, PAINTED ALUMINUM GRILLE
EF 4 LOREN COOK GC-144 95 CFM 0.50 in-wg 1028 N/A 120 V 1 60 Hz 15 BACKDRAFT DAMPER, PAINTED ALUMINUM GRILLE
EF 5 LOREN COOK SQI-B 800 CFM 0.50 in-wg 1215 1/6 120 V 1 60 Hz 150
EF 6 LOREN COOK SQI-B 800 CFM 0.50 in-wg 1215 1/6 120 V 1 60 Hz 150
EF 7 LOREN COOK GC-144 55 CFM 0.50 in-wg 903 N/A 120 V 1 60 Hz 15 BACKDRAFT DAMPER, PAINTED ALUMINUM GRILLE
EF 8 LOREN COOK GC-144 100 CFM 0.50 in-wg 1036 N/A 120 V 1 60 Hz 15 BACKDRAFT DAMPER, PAINTED ALUMINUM GRILLE
TYPE MARK MFR MODEL
AIR FLOW HEATINGCAPACITY
COOLING ELECTRICAL
WEIGHT LBS. ACCESSORIESSUPPLY ESP TOTAL SENSIBLE VOLTAGE PHASE Hz FLA MCA MOCP
HP 1 CARRIER 25HHA4036-5 22,300 Btu/h 33,400 Btu/h 23,380 Btu/h 208 V 3 60 Hz 11 A 13 A 20 A 218
HP 2 CARRIER 25HHA4036-5 22,300 Btu/h 33,400 Btu/h 23,380 Btu/h 208 V 3 60 Hz 11 A 13 A 20 A 218
HP 3 AAON CFA-004-A-0-3 600 CFM 0.00 in-wg 0 Btu/h 0 Btu/h 0 Btu/h 460 V 3 60 Hz 9 A 11 A 15 A 550
HP 4 AAON CFA-004-A-0-3 600 CFM 0.00 in-wg 0 Btu/h 0 Btu/h 0 Btu/h 460 V 3 60 Hz 9 A 11 A 15 A 550
33
22
11
A
A
A.5
A.5
B
B
C
C
C1
C1
D
D
D1
D1
E
E
F
F
G
G
WAITINGAREA100
RECEPTION/BUSINESS OFFICE
101
STAFF LOUNGE102
PATIENTTOILET
103
NON-RATEDCORRIDOR
104
MED. WASTE105
I.T.106
STAFFTOILET
108
STAFFDRESSING
109
RECOVERY110
NURSESTATION
114
PATIENTTOILET
111
J.C.112
NON-RATEDCORRIDOR
113
PRE-OP115
SUB-STERILEHALLWAY
117
STORAGE118
OR-1119
DIRTYUTILITY
120
CLEAN UTILITY121
PROCEDURELENS X
116
OR-2122
STORAGE123
MED GAS124
VAC.PUMP
125
UTILITY126
NON-RATEDCORRIDOR
107
PATIENTDISCHARGE
AREA
EMERGENCYEXIT ONLY
VVV
WAG OXYNO2N2
VV
VW
AG
OXY
NO2
N2
AP
FR
1
H
5
FC
1
CU
AP
FR
1
H
PAT-2424-C-12R-L
0 CFM
(TYP. OF 4)
(TYP. OF 4)
1
EF
2
EF
3
EF
4
EF
EXISTING EXHAUST
12x10 EG
400 CFM
(TYP. OF 2) 6
EF
5
EF
10x10 CD
300 CFM
10x10 CR
300 CFM
6x6 CD
70 CFM
6x6 CD
85 CFM
6x6 CR
70 CFM
8x8 CD
210 CFM
8x8 CD
210 CFM14x14 CR
500 CFM
6x6 CR
60 CFM
6x6 CD
60 CFM
8x8 CD
140 CFM
6x6 CD
80 CFM
8x8 CR
135 CFM
6x6 CD
50 CFM
8x8 CD
175 CFM
8x8 CR
175 CFM
8x8 CR
150 CFM
8x8 CR
190 CFM
6x6 CD
55 CFM
10x10 CR
220 CFM 10x10 CD
220 CFM
8x8 CR
100 CFM
8x8 CD
100 CFM
8x8 CD
190 CFM
8x8 CD
185 CFM
8x8 CD
190 CFM
12x12 CR
375 CFM
10x10 CR
160 CFM
6x6 CD
60 CFM
6x6 CR
50 CFM
6x6 CD
50 CFM
8x8 CD
100 CFM
8x8 CD
100 CFM
10x10 CR
200 CFM
8x8 CD
135 CFM
8x8 CD
100 CFM
12x12 CR
430 CFM12x12 CD
430 CFM6x6 CD
75 CFM
8x8 CD
150 CFM
6x6 CD
50 CFM
1
HP
2
HP
2
FC
PAT-2424-C-12R-L
0 CFM6x6 CR
30 CFM
6x6 CD
30 CFM
1
FC
7
EF
8
EF
2
H
1
H
16"ø14"ø12"ø12"ø
6"ø
8"ø
6"ø6"
ø 8x8 CR
140 CFM
20"ø20"ø20"ø18"ø
18"ø
16"ø 16"ø 16"ø 14"ø 14"ø 12"ø
12"ø
10"ø
8"ø
18"ø16"ø14"ø
14"ø14"ø20"x20" 12"ø12"ø 8"ø
12"ø
10"ø
10"ø 12"x8"
(E) STRUCTURAL BEAM
48"x
24"
1
1200 CFM
200 CFM
3
FC
4
FC
3
HP
4
HP
5151 Shoreham Place, Suite #240San Diego, CA 92122Phone: 619.330.6043Fax: 909.890.3770
Email: [email protected]
DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS
REG
ISTE
RED
PROF
RE
ENI
GNE
ESSIONAL
ETA
TS
FO FILACO
AINR
M
No. 33209
E C HA N I CA L
NHOJNEVETS
M.
NOS
EXP. 9-30-2017
PROFESSIONAL STAMPS:
SH
EE
T T
ITLE
:
SHEET NUMBER:
PRIN
TED
:PA
TH:
DATE ISSUED:
GENERAL NOTES
CONSTRUCTION NOTES
DRAWN BY:
RE
VIS
ION
S:
PR
OJE
CT
NA
ME
PR
OJE
CT
NU
MB
ER
:15.0
04
1 2 3 4 5
MEDIC
AL A
RCHIT
ECTURE &
CONSULTIN
GRAYM
OND F
OX &
ASSOCIA
TES
1660 H
OTEL C
IRCLE N
ORTH S
TE 3
40 S
AN D
IEG
O C
A 9
2108
(619) 296-4
595
RA
YM
ON
DF
OX
.CO
M
6 7
AN
AH
EIM
HIL
LS
ASC
500 S
. ANAH
EIM
HIL
LS
RD.
STE. 128,1
29
ANAH
EIM
, CA 9
2807
J.P.
TRUENORTH
#
5/1
8/2
016 3
:52:1
8 P
MC:\
Use
rs\j
pete
rson.D
ESIG
NW
ESTEN
G\D
ocu
ments
\15-4
41 A
NAH
EIM
HIL
LS A
SC_M
P_CEN
TRAL_
jpete
rson.r
vt
15-441
M1.1
Issue Date
MECH
AN
I CAL F
LO
OR P
LAN
3/16" = 1'-0"MECHANICAL FLOOR PLAN 1
FOR LINE TYPES, SYMBOLS & ABBREVIATIONS SEE LEGEND ON M0.1.
ALL SPIN-IN OR TAP TYPE DUCT CONNECTIONS SHALL BE PROVIDED WITH ANEXTRACTOR.
T-STATS SHALL NOT BE MOUNTED IN DIRECT LINE OF ANY SUPPLY DIFFUSER ORNEAR ANY HEAT REJECTION EQUIPMENT.
DUCT DIMENSIONS ARE INSIDE CLEAR, ADD AN ADDITIONAL 2" MINIMUM FOR R-8DUCT INSULATION. SIZES MAY CHANGE PER MANUFACTURE
ALL DUCTWORK SHALL BE HARD DUCT. FLEX DUCT MAY BE USED ONLY AT SUPPLY &RETURN OUTLETS AT A MAX. LENGTH OF 7'-0".
ALL VENTING SHALL HAVE A MIN. OF 10' CLEARANCE FROM ANY FORCED AIR INLET W/A MIN. OF 3' CLEARANCE ABOVE & A MIN OF 4' CLEARANCE FROM ANY PROPERTY LINEEXCEPT A PUBLIC WAY. PER SEC. 906
ALL DUCTWORK SHALL BE MOUNTED HIGH AND TIGHT TO ROOF STRUCTURE ASPOSSIBLE.
PROVIDE 1" ACOUSTICAL LINING IN ALL DUCTWORK WITHIN 10 FEET OF ALL AIRMOVING EQUIPMENT. PROVIDE DURO-DYNE FLEXIBLE CONNECTION AT ALL DUCT ATEQUIPMENT LOCATIONS.
CONTRACTOR SHALL COORDINATE DUCT RUNS WITH FIRE SPRINKLERCONTRACTOR.
ALL RESTROOM DOORS SHALL HAVE A 1" UNDERCUT.
CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR FOR BUILDING TOBE PURGED UPON COMPLETION AND PRIOR TO OCCUPANCY. FILTERS SHALL BEREPLACED BEFORE PURGE AND UPON COMPLETION OF PURGE CYCLE.
CONTRACTOR SHALL PATCH ALL ROOF PENETRATIONS AS NEED TO MAINTAINEXISTING ROOFING WARRANTY.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
1 WALL MOUNTED MAGNEHELIC GAUGE AT +60" A.F.F.
33
22
11
A
A
A.5
A.5
B
B
C
C
C1
C1
D
D
D1
D1
E
E
F
F
G
G
WAITINGAREA100
RECEPTION/BUSINESS OFFICE
101
STAFF LOUNGE102
PATIENTTOILET
103
NON-RATEDCORRIDOR
104
MED. WASTE105
I.T.106
STAFFTOILET
108STAFF
DRESSING109
RECOVERY110
NURSESTATION
114
PATIENTTOILET
111
J.C.112
NON-RATEDCORRIDOR
113
PRE-OP115
SUB-STERILEHALLWAY
117
STORAGE118
OR-1119
DIRTY UTILITY120
CLEAN UTILITY121
PROCEDURELENS X
116
OR-2122
STORAGE123 MED GAS
124
VAC.PUMP
125
UTILITY126
NON-RATEDCORRIDOR
107
PATIENTDISCHARGE
AREA
EMERGENCYEXIT ONLY
VVV
WAG OXYNO2N2
VV
VW
AG
OXY
NO2
N2
5
FC
1
CU
1
FC
2
FC
1
HP
2
HP
CU
3
CU
4
COND
CO
ND
CO
ND
COND
REF REF
REF
REF
REFREF
REF
RE
F
RE
F
5151 Shoreham Place, Suite #240San Diego, CA 92122Phone: 619.330.6043Fax: 909.890.3770
Email: [email protected]
DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS
REG
ISTE
RED
PROF
RE
ENI
GNE
ESSIONAL
ETA
TS
FO FILACO
AINR
M
No. 33209
E C HA N I CA L
NHOJNEVETS
M.
NOS
EXP. 9-30-2017
PROFESSIONAL STAMPS:
SH
EE
T T
ITLE
:
SHEET NUMBER:
PRIN
TED
:PA
TH:
DATE ISSUED:
GENERAL NOTES
CONSTRUCTION NOTES
DRAWN BY:
RE
VIS
ION
S:
PR
OJE
CT
NA
ME
PR
OJE
CT
NU
MB
ER
:15.0
04
1 2 3 4 5
MEDIC
AL A
RCHIT
ECTURE &
CONSULTIN
GRAYM
OND F
OX &
ASSOCIA
TES
1660 H
OTEL C
IRCLE N
ORTH S
TE 3
40 S
AN D
IEG
O C
A 9
2108
(619) 296-4
595
RA
YM
ON
DF
OX
.CO
M
6 7
AN
AH
EIM
HIL
LS
ASC
500 S
. ANAH
EIM
HIL
LS
RD.
STE. 128,1
29
ANAH
EIM
, CA 9
2807
J.P.
TRUENORTH
#
5/1
8/2
016 3
:52:1
9 P
MC:\
Use
rs\j
pete
rson.D
ESIG
NW
ESTEN
G\D
ocu
ments
\15-4
41 A
NAH
EIM
HIL
LS A
SC_M
P_CEN
TRAL_
jpete
rson.r
vt
15-441
M2.1
Issue Date
MECH
AN
I CAL P
IPIN
G P
LAN
3/16" = 1'-0"MECHANICAL PIPING PLAN 1
FOR LINE TYPES, SYMBOLS & ABBREVIATIONS SEE LEGEND ON M0.1.
ALL SPIN-IN OR TAP TYPE DUCT CONNECTIONS SHALL BE PROVIDED WITH ANEXTRACTOR.
CONTRACTOR SHALL COORDINATE PIPE RUNS WITH FIRE SPRINKLERCONTRACTOR.
CONTRACTOR SHALL PATCH ALL ROOF PENETRATIONS AS NEED TO MAINTAINEXISTING ROOFING WARRANTY.
1.
2.
3.
4.
12 ga. HANGER WIRELOOPED ANDTURNED AS SHOWN
1 1/2" LONG TEKSCREW
STRUCTURE
1/2"ø HANGERROD (TYP.)
2 1/2" x 2 1/2"x 16 ga.ANGLE BRACE (TYP.)
STRUCTURE
1 1/2" LONG TEKSCREW
1 1/2" LONG TEKSCREW
HANGER STRAP
DIAGONAL BRACE
DRILL IN ANCHORW/ MIN. 2"PENETRATION
SECURE UNISTRUT TO ROOF TRUSS W/ (1) TWO-HOLE CORNER ANGLE & 1/2"ø THRU BOLT INTOWEB FRAMING MEMBER (TYP)
SECURE ALL THREAD TOUNISTRUT W/ DBL. NUTSAND LOCKWASHERS.
UNISTRUT. SPAN MIN.OF 3 TRUSSES
3/8"ø ALL THREAD RODFAN COIL
UNISTRUT
SECURE ALL THREAD TOUNISTRUT W/ ABL. NUTSAND LOCKWASHERS.
2x2x16 ga. DIAGONAL "L"BRACE.
SIDE VIEW
PLAN VIEW
CEILING
FINISH FLOOR
WALL
3/4" PLYWOODBLOCKING INWALL
7' M
IN.
ATTACH FAN COIL TO WALL WITH(8) 1-1/2" SCREWS THRU FAN COILBACKING PLATE (BY MFR) ANDBLOCKING IN WALL
SECURE UNIT WITHCONC. DRIVE ANCHORS
FINISH GRADE
4" CONCRETE MOUNTINGPAD MIN 36" SQ AREA FOREACH CONDENSOR
HP
-
MOUNTING BRACKETBY EQUIP. MFR.1/2"ø HANGER ROD LENGTH
AS REQUIRED. (LENGTHSOVER 12" REQUIRE 45 DEG.
BRACING AT 2 OPPOSITECORNERS.)
(4) EACH UNIT. MAX. 2INCHES FROMCORNERS
EF
-
CENTER OFT-STAT
48"
TOP OFT-STAT
24"
46"
MOUNTING HEIGHT OVER OBSTRUCTION
HANGER SIZE
1" x 22 GA.
1" x 22 GA.
1" x 20 GA.
UP THRU 10"
11" TO 20"
21" TO 40"
DUCT SIZE
10'-0" O/C
10'-0" O/C
10'-0" O/C
MAX. SPACING
DUCT STRAP- SAME ASHANGER STRAP
3/8"∅MACHINE BOLT
HANGER STRAP- SEESCHEDULE BELOW
ROUND DUCT -SEE PLANS FORSIZE
2x2x16 GA. DIAGONAL "L"BRACE PER SMACNAGUIDELINES FOR SEISMICRESTRAINT. IF DISTANCE BELOWSUPPORTING STRUCTURALMEMBER IS LESS THAN 12",DIAGONAL BRACE MAY BEOMITTED
FOR CONNECTIONTO STRUCTURE -SEE
2" x 18 GA.
2" x 16 GA.
1/8" STEEL X 1-1/2"
UP THRU 10"
11" TO 20"
21" TO 40"
12'-0" O/C
12'-0" O/C
12'-0" O/C
HANGER SIZEDUCT SIZE MAX. SPACING
NOTE: PER 2010 CMC TABLE 6-7
MATERIAL
G.I. STEEL
G.I. STEEL
G.I. STEEL
G.I. STEEL
G.I. STEEL
G.I. STEEL
MATERIAL
HANGER STRAP SCHEDULEHORIZONTAL
1
1
1
-
1" MIN.
45
1" x 1/8" STRAP
1-1/8" x 1-1/8" x 1/8" ANGLE
1" x 1" x 1/8" ANGLE
UP THRU 18"
31" TO 48"
19" TO 30"
# 10 SMS (TYP.)
10'-0" O/C
10'-0" O/C
10'-0" O/C
2 x 2 x 16 GA.G.I. DIAGONALBRACE ALTERNATESIDES EVERYHANGER
G.I. DUCT HANGER- SEE SCHEDULEBELOW FOR SIZE
FOR CONNECTIONTO STRUCTURE -SEE DETAIL
TYPICAL SQUAREOR RECTANGULARDUCT
HANGER SIZEDUCT SIZE MAX. SPACING
VERTICAL
HORIZONTAL
HANGER SIZEDUCT SIZE MAX. SPACING
1" x 18 GA.
1" x 1/8"
1" x 18 GA.
UP THRU 24"
37" TO 48"
25" TO 36"
12'-0" O/C
12'-0" O/C
12'-0" O/C
NOTE: PER 2010 CMC TABLE 6-7
MATERIAL
G.I. STEEL
G.I. STEEL
G.I. STEEL
G.I. STEEL
G.I. STEEL
G.I. STEEL
MATERIAL
HANGER STRAP SCHEDULE
1
-
DURO DYNE MODEL KS-38
SET CONSISTS OF: ROUND ENDBEARING AND SQUARE ENDBEARING
MANUAL VOLUMEDAMPER SYMBOL
MVD-MANUALVOLUME DAMPER
FC UNIT, SEEMECH DWGS
SECONDARYCONDENSATE PAN
CEILING
TERMINATE SECONDARYCONDENSATE LINE W/ELBOW DN
2"
VENT FULL SIZE OFCOND. DRAIN.
ESCUTCHEON
2" MIN.
ESCUTCHEON
OR
COND. SLOPE TO DRAIN
COND. CONN. TO TAIL PCS WITH SLIPJOINT FITTING BELOW SINK. SEE FLOORPLANS FOR SIZES
S
-
L
-
INTERLOCKED UNITSCHEDULE
PROVIDE RELAYWHEREREQUIRED &INTERCONNECTTO HOT LEG OFEVAPORATORFAN MOTOR
120V-1ø -60HZ
NOTE:REFER TO WIRING NOTES FOR ADD'LINFORMATION.
PROGRAMMABLE T'STAT WITHFAN SET TO OPERATE DURING
OCCUPIED HOURS
24 V. CONTROL INTERLOCKWIRING BY MECHANICALCONTRACTOR
DUCT MOUNTEDSMOKE DETECTOR
N.O. RELAY
DISC. SW.
208V-3ø -60HZ
120V-1ø -60HZ
208V-3ø -60HZ
DISC. SW.
FC-1, HP-1, & EF-1,2,7,8
FC-2, HP-2, EF-3,4
FC-3, HP-3, EF-5
FC-4, HP-4, EF-6
DD
4
HP
-
FC
-
1
1
1
EF
-
23
1
1
T
5151 Shoreham Place, Suite #240San Diego, CA 92122Phone: 619.330.6043Fax: 909.890.3770
Email: [email protected]
DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS
REG
ISTE
RED
PROF
RE
ENI
GNE
ESSIONAL
ETA
TS
FO FILACO
AINR
M
No. 33209
E C HA N I CA L
NHOJNEVETS
M.
NOS
EXP. 9-30-2017
PROFESSIONAL STAMPS:
SH
EE
T T
ITLE
:
SHEET NUMBER:
PRIN
TED
:PA
TH:
DATE ISSUED:
DRAWN BY:
RE
VIS
ION
S:
PR
OJE
CT
NA
ME
PR
OJE
CT
NU
MB
ER
:15.0
04
1 2 3 4 5
MEDIC
AL A
RCHIT
ECTURE &
CONSULTIN
GRAYM
OND F
OX &
ASSOCIA
TES
1660 H
OTEL C
IRCLE N
ORTH S
TE 3
40 S
AN D
IEG
O C
A 9
2108
(619) 296-4
595
RA
YM
ON
DF
OX
.CO
M
6 7
AN
AH
EIM
HIL
LS
ASC
500 S
. ANAH
EIM
HIL
LS
RD.
STE. 128,1
29
ANAH
EIM
, CA 9
2807
J.P.
5/1
8/2
016 3
:52:2
0 P
MC:\
Use
rs\j
pete
rson.D
ESIG
NW
ESTEN
G\D
ocu
ments
\15-4
41 A
NAH
EIM
HIL
LS A
SC_M
P_CEN
TRAL_
jpete
rson.r
vt
15-441
M3.1
Issue Date
MECH
AN
I CAL D
ETAIL
S
CONNECTION TO STRUCTURE - WOOD 1
FAN COIL MOUNTING 2
DUCTLESS FAN COIL MOUNTING 3
HEAT PUMP MOUNTING 4
INLINE EXHAUST FAN MOUNTING 5
THERMOSTAT MOUNTING 6
DUCT SUPPORT - ROUND 7
DUCT SUPPORT - RECT. 8
MVD DETAIL 9
CONDENSATE - FC/LAV SINK 10
SPLIT SYSTEM WIRING 11
POINT NAME
ZONE TEMPERATURE
ZONE SETPOINT ADJUST
SUPPLY AIR HUMIDITY
PREFILTER DIFF. PRESSURE
AI
X
AO BI BO
HARDWARE POINTS
AV ALARM
SOFTWARE POINTS
SHOW ONGRAPHIC
MIXED AIR TEMPERATURE
BV LOOP SCHED TREND
X
FINAL FILTER DIFF. PRESSURE
X
X
X
X
X
X
X
X
X
X X
X
X
X
X
ZONE AIR HUMIDITY - RM (QTY 4)
COOLING STAGE 1
ZONE AIR TEMPERATURE - RM (QTY 4)
X
X
X
X
X
X
X
X
COOLING STAGE 2 X XX
COOLING STAGE 3 X XX
HEATING STATUS X XX
HUMIDIFIER STATUS X XX
ZONE OVERRIDE X XX
SUPPLY FAN VFD FAULT X XX
SUPPLY FAN STATUS X XX
SUPPLY FAN START/STOP X XX
HUMIDIFIER ENABLE
DEHUMIDIFICATION SETPOINT X XX
HUMIDIFIER SEPTOINT X XX
SCHEDULE XX
HEATING SETPOINT X XX
COOLING SETPOINT X XX
HIGH ZONE TEMP X
LOW ZONE TEMP X
SUPPLY FAN FAILURE X
PREFILTER CHANGE REQUIRED X
FINAL FILTER CHANGE REQUIRED X
HIGH ZONE AIR HUMIDITY X
LOW ZONE AIR HUMIDITY X
XX
SUPPLY AIR TEMPERATURE XX X
BI - Zone Override
AI - Zone Setpoint Adjust
Electric
AO - Heating PercentageDX
BO - Cooling Stage 1
BO - Cooling Stage 2
BO - Cooling Stage 3
M
CT
VFD
BO - Supply Fan Start/Stop
BI - Supply Fan Status
AO - Supply Fan VFD Speed
BI - Supply Fan VFD Fault
SA
AI - Supply Air Humidity
AO - Humidifier
BO - Humidifier Enable
H
STM
M
M
N.C.
OA
T
AI - Supply Air Temp
SF
T
AI - Zone Temp
AI - Zone Humidity
H
1. RTU-3 THRU RTU-5
Run Conditions - Scheduled:The unit shall run according to a user definable time schedule in the following modes:
• Occupied Mode: The unit shall maintain• A 67°F (adj.) cooling setpoint• A 63°F (adj.) heating setpoint.• Unoccupied Mode (night setback): The unit shall maintain• A 76°F (adj.) cooling setpoint.• A 60°F (adj.) heating setpoint.
Supply Fan:The supply fan shall run anytime the unit is commanded to run, unless shutdown on safeties.
Alarms shall be provided as follows:
• Supply Fan Failure: Commanded on, but the status is off.Zone Temperature Control:The controller shall provide the unit with the average zone temperature. The unit shall control its own DX cooling circuits andgas fired furnace to maintain zone temperature.The outside air dampers shall close when the unit is off.
Dehumidification:The controller shall measure the zone air humidity and override the cooling sequence to maintain zone air humidity at or below 60% RH(adj.). Dehumidification shall be enabled whenever the supply fan status is on.
Humidifier Control:The controller shall measure the zone air humidity and modulate the humidifier to maintain zone air humidity at or above 35% rh (adj.).
The humidifier shall be enabled whenever the supply fan status is on.The humidifier shall turn off whenever:
•
Supply air humidity rises from 90% rh to 95% rh (adj.).
•
OR on loss of supply fan status.
Zone Air Humidity:The controller shall monitor the zone air humidity of both operating rooms served by a respective unit and use as required for humiditycontrol.Alarms shall be provided as follows:
• High Zone Air Humidity: If the return air humidity is greater than 60% (adj.).• Low Zone Air Humidity: If the return air humidity is less than 35% (adj.).
Prefilter Differential Pressure Monitor:The controller shall monitor the differential pressure across the prefilter.Alarms shall be provided as follows:
• Prefilter Change Required: Prefilter differential pressure exceeds a user definable limit (adj.).Final Filter Differential Pressure Monitor:The controller shall monitor the differential pressure across the final filter.Alarms shall be provided as follows:
• Final Filter Change Required: Final filter differential pressure exceeds a user definable limit (adj.).Zone Setpoint Adjust:The occupant shall be able to adjust the zone temperature heating and cooling setpoints at the zone sensor.
Zone Unoccupied Override:A timed local override control shall allow an occupant to override the schedule and place the unit into an occupied mode for an adjustable period of time. Atthe expiration of this time, control of the unit shall automatically return to the schedule.
HL
AI - Pre Filter Static Pressure
HL
AI - Pre Filter Static Pressure
POINT NAME
OR SUITE STATIC PRESSURE
FAN STATUS
FAN START/STOP
AI
X
AO BI BO
HARDWARE POINTS
AV ALARM
SOFTWARE POINTS
SHOW ONGRAPHICBV LOOP SCHED TREND
X
X
X
X
X
X
X
X
FAN VFD SPEED XX X
FAN VFD FAULT XX X
VFD
BO - Fan Start/Stop
AO - Fan VFD Speed
BI - Fan VFD Fault
CTBI - Fan Status
EA
M
OR Suite Adjacent Cooridor
H L
AI - OR Suite Static Pressure
1. EF-1 THRU EF-3
Run Conditions - Scheduled:The unit shall interlocked to run while RTU-3 thru 5 are in operation:
Room Pressurization:Exhaust fan VFD to control speed to maintain +0.2 in.wc. positive pressure in O.R. suite relative to adjacent corridor.
5151 Shoreham Place, Suite #240San Diego, CA 92122Phone: 619.330.6043Fax: 909.890.3770
Email: [email protected]
DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS
REG
ISTE
RED
PROF
RE
ENI
GNE
ESSIONAL
ETA
TS
FO FILACO
AINR
M
No. 33209
E C HA N I CA L
NHOJNEVETS
M.
NOS
EXP. 9-30-2017
PROFESSIONAL STAMPS:
SH
EE
T T
ITLE
:
SHEET NUMBER:
PRIN
TED
:PA
TH:
DATE ISSUED:
DRAWN BY:
RE
VIS
ION
S:
PR
OJE
CT
NA
ME
PR
OJE
CT
NU
MB
ER
:15.0
04
1 2 3 4 5
MEDIC
AL A
RCHIT
ECTURE &
CONSULTIN
GRAYM
OND F
OX &
ASSOCIA
TES
1660 H
OTEL C
IRCLE N
ORTH S
TE 3
40 S
AN D
IEG
O C
A 9
2108
(619) 296-4
595
RA
YM
ON
DF
OX
.CO
M
6 7
AN
AH
EIM
HIL
LS
ASC
500 S
. ANAH
EIM
HIL
LS
RD.
STE. 128,1
29
ANAH
EIM
, CA 9
2807
J.P.
5/1
8/2
016 3
:52:2
1 P
MC:\
Use
rs\j
pete
rson.D
ESIG
NW
ESTEN
G\D
ocu
ments
\15-4
41 A
NAH
EIM
HIL
LS A
SC_M
P_CEN
TRAL_
jpete
rson.r
vt
15-441
M3.2
Issue Date
MECH
AN
I CAL C
ON
TRO
LS
OR SUITE ROOFTOP UNIT CONTROLS 1OR SUITE EXHAUST FAN CONTROLS 2
PLUMBING LEGEND AND SYMBOLSSYMBOL ABBREV. DESCRIPTION
DETAIL REFERENCE
SECTION REFERENCE
PLUMBING STACK OR RISER REFERENCE
EQUIPMENT REFERENCE
FILTERED WATER
SOFTENED / CONDITIONED COLD WATER
COLD WATER
HOT WATER
HOT WATER RETURN
POP-OFF DRAIN LINE OR HIDDEN WATER LINE
SOIL or WASTE BELOW GRADE (or FLOOR)
GREASE WASTE BELOW GRADE (or FLOOR)
COMBINATION WASTE AND VENT
ROOF & OVERFLOW DRAIN ABOVE & BELOW GRADE (or FLOOR)
STORM DRAIN
SOIL or WASTE ABOVE GRADE (or FLOOR)
PLUMBING VENT
CONDENSATE DRAIN
GAS LOW PRESSURE
GAS MEDIUM PRESSURE
LIQUID PROPANE GAS
AUTOMATIC FIRE SPRINKLER
RECLAIM WATER
COMPRESSED AIR
COMPRESSED AIR OUTLET
OXYGEN
NITROUS OXIDE
MEDICAL AIR
VACUUM
NITROGEN
CIRCUIT SETTER
SHUT OFF VALVE
SHUT OFF VALVE OR GAS COCK ON RISER
SWING CHECK VALVE
PRESSURE REDUCING VALVE
PRESSURE-TEMPERATURE RELIEF VALVE
REDUCED PRESSURE BACKFLOW PREVENTER
PIPE DOWN
PIPE UP
TEE DOWN
TEE UP
PIPE RISER & PIPE DROP (UP AND DOWN)
FLOOR CLEANOUT
WALL CLEANOUT
CLEANOUT PLUG
YARD CLEANOUT or CLEANOUT TO GRADE
CAP ON END OF PIPE
HOSE BIBB WITH VACUUM BREAKER
WATER HAMMER ARRESTOR & TRAP PRIMER
BALL VALVE
GAS REGULATOR
GAS COCK (or GAS STOP)
GAS SOLENOID
POINT OF CONNECTION
POINT OF DEMOLITION
ACCESS PANEL
ABOVE
BELOW
AMERICAN GAS ASSOCIATION
CONNECTION
CONTINUATION
EXISTING
NEW
DOWN
HANDICAPPED
INVERT ELEVATION
TYPICAL
UNLESS OTHERWISE NOTED
VENT THROUGH ROOF
WITH
PLUMBING FIXTURE UNIT
SECONDARY CONDENSATE
DETAIL No.
SHEET No.
STACK/RISER
ID. No.
EQUIPMENT
ID. No.
FW
SCW
CW
HW
HWR
S or W
GW
CWV
RD/OD
SD
S or W
V
COND
G
MPG
LPG
AS
RW
CA
CAO
OX
N2O
MA
VAC
N2
CS
SOV
SOV or GC
CV
PRV
PTR
RPBFP
DN
UP
DN
UP
FCO
WCO
CO
COTG
HB
WHA & TP
BV
GR
GC
GS
P.O.C.
P.O.D.
A.P.
ABV.
BEL.
A.G.A.
CONN
CONT
(E)
(N)
DN
H.C.
IE
(TYP)
U.O.N.
VTR
W/
FU
SEC COND
GW
CWV
RD/OD
SD
COND
G
MPG
LPG
AS
RW
CA
CAO
OX
N2O
MA
VAC
N2
AP-1
THE TOTAL INSTALLATION SHALL COMPLY WITH ANY AND ALL REQUIREMENTS OF THE LEGALLY CONSTITUTED AUTHORITIES HAVINGJURISDICTION INCLUDING 2013 CBC (CALIFORNIA BUILDING CODE) AND 2013 CMC/CPC (CALIFORNIA MECHANICAL AND PLUMBING CODE).
THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID AND SHALL THOROUGHLY FAMILIARIZE HIMSELF WITH THE EXISTING CONDITIONSUNDER WHICH HE WILL BE REQUIRED TO WORK.
ALL INDICATED DIMENSIONS ARE APPROXIMATE AND ARE GIVEN FOR ESTIMATE PURPOSES ONLY. BEFORE PROCEEDING WITH THEWORK THIS CONTRACTOR SHALL CAREFULLY CHECK AND VERIFY ALL DIMENSIONS, SIZES, REQUIRED CLEARANCES AND SHALL ASSUMEFULL RESPONSIBILITY FOR THE FITTING OF ALL EQUIPMENT AND MATERIALS HEREIN REQUIRED TO OTHER PARTS OF THE WORK OFOTHER TRADES.
THE DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC TO THE EXTENT THAT ALL OFFSETS, BENDS, SPECIAL FITTINGS AND LOCATIONS ARENOT EXACTLY LOCATED.
IN THE PREPARATION OF THESE DOCUMENTS, CERTAIN ASSUMPTIONS ARE MADE REGARDING EXISTING CONDITIONS. SOME OF THESEASSUMPTIONS MAY NOT BE VERIFIABLE WITHOUT EXPENDING ADDITIONAL SUMS OF MONEY OR DESTROYING OTHERWISE ADEQUATE ORSERVICEABLE PORTIONS OF EXISTING BUILDINGS AND/OR EQUIPMENT. THEREFORE, THE ENGINEER SHALL NOT BE HELD RESPONSIBLEFOR ANY CHANGES OR ADDITIONAL COSTS INCURRED DUE TO EXISTING CONDITIONS.
ITEMS RELATED TO PLUMBING UTILITIES AND/OR OTHER SERVICE(S); MATERIALS, LABOR, PERMITS, FEES, ETC., SHALL BE VERIFIED WITHTHE RESPECTIVE SERVING UTILITY COMPANY PRIOR TO SUBMISSION OF A BID. THE ACT OF SUBMITTING A BID SHALL CONSTITUTE FULLRESPONSIBILITY OF THE CONTRACTOR TO INSTALL SERVICE(S) IN COMPLIANCE WITH THE REQUIREMENTS OF THE SERVING UTILITYCOMPANY AND THE MECHANICAL ENGINEER. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CHARGES LEVIED BY THE SERVINGUTILITY COMPANY EXCEPTING THE FIRST BILLING DEPOSIT.
THE CONTRACTOR SHALL COMPLY WITH ALL CONTRACT DOCUMENTS IN LAYING OUT HIS WORK AND EQUIPMENT. HE SHALL COORDINATETHE WORK OF THIS SECTION WITH THE WORK OF OTHER TRADES AND ALL JOB CONDITIONS.
THE INSTALLATION OF ACCESS PANELS OR OTHER INDICATING EQUIPMENT OR SPECIALTIES REQUIRING READING, ADJUSTMENT,INSPECTION, REPAIRS, REMOVAL OR REPLACEMENT SHALL BE CONVENIENTLY LOCATED WITH REFERENCE TO THE FINISHED BUILDING.
ALL EQUIPMENT AND FIXTURES INSTALLED UNDER THIS CONTRACT SHALL BE HUNG OR ANCHORED IN ACCORDANCE WITH TITLE 24, TABLENO. 16 A-O.
THE INTENT OF THE DRAWINGS AND SPECIFICATIONS IS TO CONSTRUCT THE PROJECT IN ACCORDANCE WITH TITLE 24, CALIFORNIA CODEOF REGULATIONS.
WHERE MATERIAL IS SHOWN ON THE DRAWINGS BUT NOT SPECIFIED, IT SHALL BE OF THE SAME TYPE AND QUALITY AS EXISTINGMATERIAL.
THE FIRE PROTECTION CONTRACTOR SHALL PROVIDE ALL REQUIRED HYDRAULIC CALCULATIONS AND FIRE SPRINKLER HEAD LOCATION INACCORDANCE WITH NFPA 13 TO THE LOCAL FIRE DEPARTMENT FOR REVIEW AND APPROVAL OF THE FIRE PROTECTION SYSTEM.
TEST SYSTEM(S) IN ACCORDANCE WITH REQUIREMENTS OF THE GOVERNING AUTHORITIES.
ALL CLEANOUTS SHALL BE INSTALLED WHERE READILY ACCESSIBLE AND LOCATED AS PER CODE REQUIREMENTS THE CONTRACTORSHALL COORDINATE ALL CLEANOUT LOCATIONS WITH EQUIPMENT CABINETS, ETC. AND THE ARCHITECT PRIOR TO ANY INSTALLATION.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND REPAIRING ALL PAVED AREAS WHICH ARE EXCAVATED AND/OR DAMAGEDBY HIS OPERATIONS. IN ADDITION, THE CONTRACTOR SHALL RESTORE TO THEIR ORIGINAL CONDITION ALL PLANTED AREAS DAMAGED BYHIS OPERATIONS.
ALL CONNECTIONS TO EXISTING SERVICES SHALL BE MADE SUCH THAT INTERRUPTION TIME WILL BE AS SHORT AS POSSIBLE. THECONTRACTOR SHALL GIVE THE OWNERS REPRESENTATIVE SUFFICIENT NOTICE OF SUCH INTERRUPTIONS AND THE ACTUAL SHUT-DOWNTIME SHALL BE AT A TIME DESIGNATED BY THE OWNERS REPRESENTATIVE.
ALL EXTERIOR WATER SHUT-OFF VALVES BELOW GROUND SHALL BE INSTALLED IN YARD BOXES WITH COVERS CONSPICUOUSLY MARKED"WATER SHUT-OFF" RESPECTIVELY.
WHEN REQUIRED BY THE AUTHORITY HAVING JURISDICTION, POTABLE WATER SYSTEMS SHALL BE DISINFECTED AND FLUSHED PRIOR TOUSE BY WATER-CHLORINATION SOLUTION AND HAVE BACTERIOLOGICAL EXAMINATION MADE BY AN APPROVED AGENCY PER 2010 CPCSEC. 609.9.
PLUMBING PIPE, FITTINGS AND FIXTURES USED TO CONVEY OR DISPENSE WATER FOR HUMAN CONSUMPTION SHALL COMPLY WITH AB1953.
ANY SUBSTITUTION MADE BY THE CONTRACTOR THAT IS DIFFERENT FROM WHAT IS SPECIFIED ON THE DRAWINGS SHALL BE CLEARLYINDICATED ON THE SUBMITTAL AS TO ALL THAT IS BEING SUBSTITUTED.
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
PIPE MATERIAL SCHEDULE
PLUMBING SHEET INDEX
CALIFORNIA GREEN COMPLIANCE FORM
CALCULATIONS BASED ON CHAPTER 8 WORK SHEETS WS-1 & WS-2
LAVATORY FAUCET 0.5 0.5 0.25 MIN
FIXTURE TYPE DURATIONBASELINE FLOWRATE (GPM)
DESIGN FLOWRATE (GPM)
1
DAILY USES
15
OCCUPANTS
5.625
BASELINE GAL.PER DAY
5.625
DESIGN GAL.PER DAY
194.5625 141.3625TOTAL DAILY WATER USE (WU) =
155.65 113.09ALLOWABLE WATER USE =
42.56 -TOTAL WATER CONSUMPTION REDUCTION =
27%TOTAL WATER CONSUMPTION REDUCTION SAVINGS =
BASIS OF DESIGN
PLUMBING FIXTURE SCHEDULE
SYMBOLSPECIFICATIONS
*NO SUBSTITUTIONS WITHOUT ARCHITECTS APPROVALWASTE
CONNECTION SIZE:
VENTTRAPCW
RISERHW
RISER
WATERCLOSET: AMERICAN STANDARD "CADET" 2998.012, ADACOMPLIANT, 17-1/4" HIGH RIM, ELONGATED BOWL, TANK TYPE, (1.28)GPF, FLOOR MOUNTED. CHURCH PLASTIC SEAT MODEL 5324.019,ELONGATED, OPEN FRONT, WITH EXTERNAL CHECK HINGE, SCRATCHAND STAIN RESISTANT.
3" INT. 2" 1/2" -
WATER HEATER SCHEDULE
WH
1
MFR. & MODEL NO.:
CAPACITY:
RECOVERY:
ELECTRICAL:
WEIGHT:
A.O. SMITH DEL-40D-5
40 GALLONS
19 GPH @ 100°F
120V, 1PH, 60HZ, 5.0KW
125 LBS (EMPTY)
WC
1
COPPER L TUBECOLD WATERABV. GROUND
SOLDEREDCAST BRONZE/
WROUGHT COPPER
BALLGATE
CHECK125
PIPE MATERIAL& WEIGHT
SERVICETYPE OFJOINTS
PRESSUREFITTINGSMATERIAL
SHUT-OFFRATINGSPSI - SwP
VALVE
NOTE: ALL EXPOSED FUEL GAS PIPING SHALL BE PRIME AND PAINTED, COORDINATE COLOR WITH ARCHITECT.
COPPER K TUBECOLD WATER
BELOW GROUND TO5' OUTSIDE BUILDING
BRAZEDCAST BRONZE/
WROUGHT COPPERBALLGATE
125
SCHEDULE 80 PVCCOLD WATER
BELOW GROUNDBEYOND 5'-0"
SOLVENT-WELD PVC GATE125
COPPER L TUBEHOT WATER
ABV. GROUNDSOLDERED
CAST BRONZE/WROUGHT COPPER
BALLCHECK
125
STEEL 40, BLACKSTEEL 40, BLACK
POLYETHYLENE PIPINGSTAINLESS STEEL TUBING
FUEL GAS
SCREWEDWELDED
NO-HUB CAST IRONVENT NO-HUB N/A N/AN/A
SCHEDULE 40 ABSNO-HUB CAST IRON
WASTEM SOIL &ROOF DRAINS
ABOVE GROUND
SOLVENT-WELDNO-HUB
ABSN/A
N/AN/A
N/AN/A
COPPER M TUBECONDENSATE SOLDERED BRONZE N/A125
COPPER K TUBEMEDICAL GAS
AND AIR SYSTEMSBRAZED
CAST BRONZE/WROUGHT COPPER
BALL125
PER MANF.
MALL. IRONSTEEL WELD
STAINLESS STEEL TUBING
150150
PER MANF.
SQR. HEADCOCK
PER MANF.
COPPER L TUBENO-HUB CAST IRON
WASTEM SOIL &ROOF DRAINS
BELOW GROUND
SOLVENT-WELDNO-HUB
ABSN/A
N/AN/A
N/AN/A
PLUMBING PIPE INSULATION SCHEDULE
INSULATIONMEAN RATING
TEMPERATURE(°F)
250°
200°
REQUIRED INSULATION THICKNESS (IN.)
4 to < 8< 11.5 to <
41 to < 1.5
4.0
5.04.5
3.0
5.0
4.5
PIPE SIZE (IN. DIA.)
5.0
4.5
8 andlarger
5.0
4.5
CONDUCTIVITYRANGE
(in Btu-in/hr persqft/°F)
0.32 - 0.34
0.29 - 0.31
FLUIDTEMPERATURE
RANGE (°F)
ABOVE 350°
251° - 350°
Space Heating, Hot Water systems (steam, steam condensate and hot water) and Service Water Heating systems
150° 2.52.5 2.5 3.0 3.00.27 - 0.30201° - 250°
125° 1.51.5 2.0 2.0 2.00.25 - 0.29141° - 200°
100° 1.51.0 1.5 1.5 1.50.22 - 0.28105° - 140°
Space cooling systems (chilled water, refrigerant and brine)
75° 0.50.5 1.0 1.0 1.00.21 - 0.2740° - 60°
50° 1.51.0 1.5 1.5 1.50.20 - 0.26BELOW 40°
NOTE: WHERE INSULATED PIPING IS EXPOSED OUTDOORS, IT SHALL BE COVERED. COVER OUTDOOR EXPOSED INSULATEDPIPING WITH 0.016 INCH THICK CORRUGATED ALUMINUM JACKET. ALL VALVES SHALL BE PROVIDED WITH VALVE EXTENSIONS.
SINK: ELKAY DLR-2219-10 SINK IN BASE CABINET, PROVIDE RECESSEDWALL MOUNTED BOBRICK B-359 PAPER TOWEL DISPENSER, DRINKINGWATER ATTACHMENT WITH UNDER CABINET WATER FILTRATION SYSTEMAND GARBAGE DISPOSAL, EMERSON BADGER #1.
2" 1-1/2" 1-1/2" 1/2" 1/2"S
1
SINK: ELKAY LR-2522-6 SINK IN BASE CABINET, PROVIDE RECESSED WALLMOUNTED BOBRICK B-359 PAPER TOWEL DISPENSER. 2" 1-1/2" 1-1/2" 1/2" 1/2"
S
2
SINK: ELKAY DLR-1919-10 SINK IN BASE CABINET, PROVIDE RECESSEDWALL MOUNTED BOBRICK B-359 PAPER TOWEL DISPENSER. 2" 1-1/2" 1-1/2" 1/2" 1/2"
S
3
SINK: ZURN SURGEON SINK, Z5461 CONTRACTOR PROVIDED,CONTRACTOR INSTALLED WALL MOUNTED WITH WALL HANGERS WITHSINGLE HOLE GOOSENECK SPOUT AND KNEE ACTIVATED FAUCETCONTROLS.
2" 1-1/2" 1-1/2" 1/2" 1/2"S
4
LAVATORY: KOHLER "CHESAPEAKE" K-1728, WHITE VITREOUS CHINA,WALL HUNG LAVATORY W/ FAUCET HOLES ON 4" CENTERS. ZURNZ81000-XL-3M SINGLE HANDLE FAUCET W/ 0.5 GPM AERATOR, PROVIDEASSE 1070 APPROVED TMV SET TO 110°, GRID STRAINER DRAIN W/ 1-1/2" CAST BRASS P-TRAP WITH CHROME FINISH, ANGLE STOPS W/ RIGIDRISER. PROVIDE J.R. SMITH 0700 SERIES WALL CARRIER. ON ADACOMPLIANT PROVIDE TRUEBRO LAV GUARD PER ADA CODE 4.19.4
2" 1-1/2" 1-1/2" 1/2" 1/2"L
1
JANITOR SINK: FLORESTONE 96/24" MOP SINK. PROVIDE F.R.P. 48" A.F.F.,PROVIDE BOBRICK B-223X24" MOP HOLDER MOUNTED @ 60" A.F.F. 3" 3" 1-1/2" 1/2" 1/2"
JS
1
FLOOR SINK: JOSAM 49302 FLOOR SINK, 8" SQUARE TOP-MEDIUMRECEPTOR, 5-7/8" DEEP SUMP, ACID RESISTANT COATED INTERIOR ANDGRATE. PROVIDED WITH TRAP PRIMER CONNECTION FOR TP-1.
2" 2" 1-1/2" - -FS
1
PROVIDE SERVICES OF PLUMBING CONSTRUCTION DOCUMENT DESIGN AND SPECIFICATIONS FOR ANAHEIM HILLS ASC OFAPPROXIMATELY 3900.00 SQ. FT. NEW GENERATOR TO BE DESIGNED INTO EXISTING SYSTEM FOR OR ROOMS.
KITCHEN FAUCET 2.2 1.5 4 MIN 1 15 132 90
FLUSHOMETER TANK TYPEWATER CLOSETS MALE
1.6 1.28 1 FLUSH 1 7.5 12 9.6
FLUSHOMETER TANK TYPEWATER CLOSETS FEMALE
1.28 1 FLUSH 3 7.5 36 28.81.6
TRAP PRIMER: MIFAB. MODEL "M-500" 1/2" INLET AND 1/2" OUTLET WITHOPTIONAL DISTRIBUTION UNIT, MAY BE LOCATED AS INDICATED ONDRAWINGS OR AS REQUIRED BY CODE. UPC LISTED. PROVIDED WITH A12"X 12" ACCESS PANEL OR LARGER DEPENDING ON THE REQUIREDACCESS TO THE EQUIPMENT AND SHUT-OFF VALVE. (CONTRACTOR TOVERIFY).
- - - 1/2" -TP
1
GARBAGE DISPOSAL SCHEDULE
GD
1
MFR. & MODEL NO.:
CONSTRUCTION:
MOTOR:
RPM:
ELECTRICAL:
WEIGHT:
IN-SINK ERATOR EMERSON BADGER #1
GALVANIZED STEEL
1/3 HP QUIET DURA-DRIVE INDUCTION MOTOR
1725
120V, 1PH, 60HZ, 5.6 AMPS
12 LBS. 7 OZ.
CIRCULATION PUMP SCHEDULE
CP
1
MFR. & MODEL NO.:
CAPACITY:
CONSTRUCTION:
MOTOR:
ELECTRICAL:
WEIGHT:
ARMSTRONG "ASTRO" 30B
5 GPM @ 10' TDH
ALL BRONZE
80 WATTS
120V, 1PH, 60HZ
22 LBS
5151 Shoreham Place, Suite #240San Diego, CA 92122Phone: 619.330.6043Fax: 909.890.3770
Email: [email protected]
DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS
REG
ISTE
RED
PROF
RE
ENI
GNE
ESSIONAL
ETA
TS
FO FILACO
AINR
M
No. 33209
E C HA N I CA L
NHOJNEVETS
M.
NOS
EXP. 9-30-2017
PROFESSIONAL STAMPS:
SH
EE
T T
ITLE
:
SHEET NUMBER:
PRIN
TED
:PA
TH:
DATE ISSUED:
DRAWN BY:
RE
VIS
ION
S:
PR
OJE
CT
NA
ME
PR
OJE
CT
NU
MB
ER
:15.0
04
1 2 3 4 5
MEDIC
AL A
RCHIT
ECTURE &
CONSULTIN
GRAYM
OND F
OX &
ASSOCIA
TES
1660 H
OTEL C
IRCLE N
ORTH S
TE 3
40 S
AN D
IEG
O C
A 9
2108
(619) 296-4
595
RA
YM
ON
DF
OX
.CO
M
6 7
AN
AH
EIM
HIL
LS
ASC
500 S
. ANAH
EIM
HIL
LS
RD.
STE. 128,1
29
ANAH
EIM
, CA 9
2807
J.P.
5/1
8/2
016 3
:52:2
2 P
MC:\
Use
rs\j
pete
rson.D
ESIG
NW
ESTEN
G\D
ocu
ments
\15-4
41 A
NAH
EIM
HIL
LS A
SC_M
P_CEN
TRAL_
jpete
rson.r
vt
15-441
P0.1
Issue Date
PLU
MBIN
G L
EG
EN
DS, N
OTES &
SCH
ED
ULES
Sheet # Sheet Name
P0.1 PLUMBING LEGENDS, NOTES & SCHEDULES
P1.1 PLUMBING FLOOR PLAN - HOT & COLD WATER
P1.2 PLUMBING FLOOR PLAN - WASTE & VENT
P2.1 PLUMBING RISER DIAGRAM - COLD WATER
P2.2 PLUMBING RISER DIAGRAM - HOT WATER
P2.3 PLUMBING RISER DIAGRAM - WASTE & VENT
P3.1 PLUMBING DETAILS
33
22
11
A
A
A.5
A.5
B
B
C
C
C1
C1
D
D
D1
D1
E
E
F
F
G
G
WAITINGAREA100
RECEPTION/BUSINESS OFFICE
101
STAFF LOUNGE102
PATIENTTOILET
103
NON-RATEDCORRIDOR
104
MED. WASTE105
I.T.106
STAFFTOILET
108 STAFFDRESSING
109
RECOVERY110
NURSESTATION
114
PATIENTTOILET
111
J.C.112
NON-RATEDCORRIDOR
113
PRE-OP115
SUB-STERILEHALLWAY
117
STORAGE118
OR-1119
DIRTYUTILITY
120
CLEAN UTILITY121
PROCEDURELENS X
116
OR-2122
STORAGE123
MED GAS124
VAC.PUMP
125
UTILITY126
NON-RATEDCORRIDOR
107
PATIENTDISCHARGE
AREAEMERGENCY
EXIT ONLY
1
WC
1
L
1
S
1
GD
1
L
1
WC
1
JS
1
S
3
S
4
S
2
L
1
WC
1
FS
1
FS
1
FS
1
2
3
3
3
3
4
5
45
3
5
4
6
3/4"ø
1 1/2"ø1 1/4"ø
3/4"ø
3/4"ø
3/4"ø
3/4"ø
1"ø
3/4"ø
3/4"ø
1"ø
1"ø 1"ø
1"ø1 1/2"ø
1"ø
1 1/2"ø
2"ø
1 1/4"ø
1"ø
3/4"ø
CP
1
WH
1
5151 Shoreham Place, Suite #240San Diego, CA 92122Phone: 619.330.6043Fax: 909.890.3770
Email: [email protected]
DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS
REG
ISTE
RED
PROF
RE
ENI
GNE
ESSIONAL
ETA
TS
FO FILACO
AINR
M
No. 33209
E C HA N I CA L
NHOJNEVETS
M.
NOS
EXP. 9-30-2017
PROFESSIONAL STAMPS:
SH
EE
T T
ITLE
:
SHEET NUMBER:
PRIN
TED
:PA
TH:
DATE ISSUED:
GENERAL NOTES
CONSTRUCTION NOTES
DRAWN BY:
RE
VIS
ION
S:
PR
OJE
CT
NA
ME
PR
OJE
CT
NU
MB
ER
:15.0
04
1 2 3 4 5
MEDIC
AL A
RCHIT
ECTURE &
CONSULTIN
GRAYM
OND F
OX &
ASSOCIA
TES
1660 H
OTEL C
IRCLE N
ORTH S
TE 3
40 S
AN D
IEG
O C
A 9
2108
(619) 296-4
595
RA
YM
ON
DF
OX
.CO
M
6 7
AN
AH
EIM
HIL
LS
ASC
500 S
. ANAH
EIM
HIL
LS
RD.
STE. 128,1
29
ANAH
EIM
, CA 9
2807
J.P.
TRUENORTH
#
5/1
8/2
016 3
:52:2
4 P
MC:\
Use
rs\j
pete
rson.D
ESIG
NW
ESTEN
G\D
ocu
ments
\15-4
41 A
NAH
EIM
HIL
LS A
SC_M
P_CEN
TRAL_
jpete
rson.r
vt
15-441
P1.1
Issue Date
PLU
MBIN
G F
LO
OR P
LAN
- H
OT &
CO
LD
WATER
3/16" = 1'-0"PLUMBING FLOOR PLAN - HOT & COLD WATER 1
FOR LINE TYPES, SYMBOLS & ABBREVIATIONS SEE LEGEND ON P0.1.
FOR CONNECTION TO STRUCTURE & PIPE SUPPORT SEE DETAILS 1/P3.1 AND2/P3.1.
UNLESS NOTED ALL CW & HW RISERS FROM FIXTURE TO CEILING ARE 1/2", SEEFIXTURE SCHEDULE ON P0.1.
ROUTE HOT WATER LOOP AS CLOSE AS POSSIBLE TO ALL FIXTURES.
SEE FIXTURE SCHEDULE ON P0.1 FOR ADA & STANDARD RIM HEIGHTS FOR WC-1& U-1.
ALL VENTING SHALL HAVE A MIN. OF 10' CLEARANCE FROM ANY FORCED AIRINLET W/ A MIN. OF 3' CLEARANCE ABOVE & A MIN OF 4' CLEARANCE FROM ANYPROPERTY LINE EXCEPT A PUBLIC WAY PER CPC SEC. 906.
NEW OR REPAIRED POTABLE WATER SYSTEMS SHALL BE DISINFECTED PRIORTO USE, ACCORDING TO THE METHOD SET IN SECTION 609.9 OF THE CPC.
CONTRACTOR SHALL PATCH FLOORS, WALLS & CEILINGS TO MATCH NEWCONSTRUCTION PER ARCHITECTS SPECIFICATIONS.
ROOF DRAIN & PIPES ARE BASED ON TABLE 11 @ 3" OF RAIN FALL PER HOUR W/1/8" PIPE SLOPE.
COORDINATE EXACT LOCATION OF S.O.V., BACKFLOW DEVICE, WATER METER,GAS METER & GREASE INTERCEPTOR WITH ARCHITECT.
PRIOR TO CONSTRUCTION CONTRACTOR SHALL FIELD VERIFY FOR EXACT SIZE,LOCATION & INVERT ELEVATION OF EXISTING WASTE LINE & COORDINATE WITHPLUMBING ENGINEER FOR ANY CHANGES NEEDED.
SHUT-OFF VALVES SHALL BE PROVIDED ON ALL MAIN BRANCHES, RUNS TOORISERS AND WHERE SHOWN ON DRAWING. LOCATE SHUT-OFF VALVES OVER T-BAR CEILING WHEN POSSIBLE. PROVIDE ACCESS PANELS WHEN SHUT-OFFVALVES ARE LOCATED OVER HARD LID CEILINGS.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
1 CONTERTOP MOUNTED SWING AWAY EYE WASH SPEAKMAN #SE-927.
2 CONNECT (N) 2" CW LINE TO (E) 2" CW LINE.
3 3/4" CW & HW DOWN IN WALL TO SINK.
4 3/4" CW & HW DOWN IN WALL TO LAVATORY.
5 3/4" CW & HW DOWN IN WALL TO WATER CLOSET.
6 3/4" CW DOWN IN WALL TO REFRIGERATOR.
33
22
11
A
A
A.5
A.5
B
B
C
C
C1
C1
D
D
D1
D1
E
E
F
F
G
G
WAITINGAREA100
RECEPTION/BUSINESS OFFICE
101
STAFF LOUNGE102
PATIENTTOILET
103
NON-RATEDCORRIDOR
104
MED. WASTE105
I.T.106
STAFFTOILET
108STAFF
DRESSING109
RECOVERY110
NURSESTATION
114
PATIENTTOILET
111
J.C.112
NON-RATEDCORRIDOR
113
PRE-OP115
SUB-STERILEHALLWAY
117
STORAGE118
OR-1119
DIRTYUTILITY
120
CLEAN UTILITY121
PROCEDURELENS X
116
OR-2122
STORAGE123
MED GAS124
VAC.PUMP
125
UTILITY126
NON-RATEDCORRIDOR
107
PATIENTDISCHARGE
AREAEMERGENCY
EXIT ONLY
WC
1
L
1
S
1
GD
1
L
1
WC
1
JS
1
S
3
S
4
S
2
L
1
WC
1
FS
1
FS
1
FS
1
1
2
1
2
5151 Shoreham Place, Suite #240San Diego, CA 92122Phone: 619.330.6043Fax: 909.890.3770
Email: [email protected]
DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS
REG
ISTE
RED
PROF
RE
ENI
GNE
ESSIONAL
ETA
TS
FO FILACO
AINR
M
No. 33209
E C HA N I CA L
NHOJNEVETS
M.
NOS
EXP. 9-30-2017
PROFESSIONAL STAMPS:
SH
EE
T T
ITLE
:
SHEET NUMBER:
PRIN
TED
:PA
TH:
DATE ISSUED:
GENERAL NOTES
CONSTRUCTION NOTES
DRAWN BY:
RE
VIS
ION
S:
PR
OJE
CT
NA
ME
PR
OJE
CT
NU
MB
ER
:15.0
04
1 2 3 4 5
MEDIC
AL A
RCHIT
ECTURE &
CONSULTIN
GRAYM
OND F
OX &
ASSOCIA
TES
1660 H
OTEL C
IRCLE N
ORTH S
TE 3
40 S
AN D
IEG
O C
A 9
2108
(619) 296-4
595
RA
YM
ON
DF
OX
.CO
M
6 7
AN
AH
EIM
HIL
LS
ASC
500 S
. ANAH
EIM
HIL
LS
RD.
STE. 128,1
29
ANAH
EIM
, CA 9
2807
J.P.
TRUENORTH
#
5/1
8/2
016 3
:52:2
5 P
MC:\
Use
rs\j
pete
rson.D
ESIG
NW
ESTEN
G\D
ocu
ments
\15-4
41 A
NAH
EIM
HIL
LS A
SC_M
P_CEN
TRAL_
jpete
rson.r
vt
15-441
P1.2
Issue Date
PLU
MBIN
G F
LO
OR P
LAN
- W
ASTE &
VEN
T
3/16" = 1'-0"PLUMBING FLOOR PLAN - WASTE & VENT 1
FOR LINE TYPES, SYMBOLS & ABBREVIATIONS SEE LEGEND ON P0.1.
FOR CONNECTION TO STRUCTURE & PIPE SUPPORT SEE DETAILS 1/P3.1 AND2/P3.1.
UNLESS NOTED ALL CW & HW RISERS FROM FIXTURE TO CEILING ARE 1/2", SEEFIXTURE SCHEDULE ON P0.1.
ROUTE HOT WATER LOOP AS CLOSE AS POSSIBLE TO ALL FIXTURES.
SEE FIXTURE SCHEDULE ON P0.1 FOR ADA & STANDARD RIM HEIGHTS FOR WC-1& U-1.
ALL VENTING SHALL HAVE A MIN. OF 10' CLEARANCE FROM ANY FORCED AIRINLET W/ A MIN. OF 3' CLEARANCE ABOVE & A MIN OF 4' CLEARANCE FROM ANYPROPERTY LINE EXCEPT A PUBLIC WAY PER CPC SEC. 906.
NEW OR REPAIRED POTABLE WATER SYSTEMS SHALL BE DISINFECTED PRIORTO USE, ACCORDING TO THE METHOD SET IN SECTION 609.9 OF THE CPC.
CONTRACTOR SHALL PATCH FLOORS, WALLS & CEILINGS TO MATCH NEWCONSTRUCTION PER ARCHITECTS SPECIFICATIONS.
ROOF DRAIN & PIPES ARE BASED ON TABLE 11 @ 3" OF RAIN FALL PER HOUR W/1/8" PIPE SLOPE.
COORDINATE EXACT LOCATION OF S.O.V., BACKFLOW DEVICE, WATER METER,GAS METER & GREASE INTERCEPTOR WITH ARCHITECT.
PRIOR TO CONSTRUCTION CONTRACTOR SHALL FIELD VERIFY FOR EXACT SIZE,LOCATION & INVERT ELEVATION OF EXISTING WASTE LINE & COORDINATE WITHPLUMBING ENGINEER FOR ANY CHANGES NEEDED.
SHUT-OFF VALVES SHALL BE PROVIDED ON ALL MAIN BRANCHES, RUNS TOORISERS AND WHERE SHOWN ON DRAWING. LOCATE SHUT-OFF VALVES OVER T-BAR CEILING WHEN POSSIBLE. PROVIDE ACCESS PANELS WHEN SHUT-OFFVALVES ARE LOCATED OVER HARD LID CEILINGS.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
1 CONNECT (N) 4" WASTE LINE TO (E) 4" WASTE LINE.
2 CONNECT (N) 2" VENT LINE TO EXISTING 2" VENT LINE.
L-1(1 F.U.)
WC-1(5 F.U.)
WC-1(5 F.U.)
WC-1(5 F.U.)
S-1(2 F.U.)
REFRIG(.5 F.U.)
JS-1(2 F.U.)
L-1(1 F.U.)
S-3(2 F.U.)
S-4(2 F.U.)
S-4(2 F.U.)
S-2(2 F.U.)
3/4"ø(1 F.U.)
3/4"ø3/4"ø
1"ø
3/4"ø
3/4"ø
1"ø
1"ø(8.5 F.U.)
(6.5 F.U.)
(6 F.U.)
1"ø(9.5 F.U.)
(14.5 F.U.)
3/4"ø(5 F.U.)
(19.5 F.U.)
1 1/4"ø
1 1/4"ø
1 1/4"ø
(21.5 F.U.)1 1/4"ø
(22.5 F.U.)
(24.5 F.U.)1 1/2"ø
1 1/2"ø(28.5 F.U.)
3/4"ø
3/4"ø
1 1/2"ø(30.5 F.U.)
WH-1(23.5 F.U.)
1 1/4"ø(23.5 F.U.)
2"ø(54 F.U.)
(E) 2" COLD WATER MAIN
H-2H-1
VELOCITY FOR HOT WATER PIPING LESS THAN 5 FT. PER SECOND
PIPE SIZE IS BASED ON CHART A-4.1 @ 2.4 P.S.I. / 100 FT.
FIXTURE UNITS ARE BASED ON TABLE A-2.1 FROM APPENDIX A
5
3
3
2
53.5
10
L
WC
1
5
3
15
FIXTURE UNITS
3/4"
3"
4"
1-1/2"
2"
2-1/2"
1"
1-1/4"
SIZE
1/2"
TOTAL NEW FIXTURE UNITS
PIPE SIZE SCHEDULE
NUMBER TOTAL
FIXTURE UNITS (COLD)
FIXTURE UNIT
MAXIMUM SIZE FOR HOT WATER PIPING SHALL BE 1-1/2"
VELOCITY FOR COLD WATER PIPING LESS THAN 8 FT. PER SECOND
S
PLUMBING COLD WATER SIZING FORM
1743
747
46
158
380
12
24
5
1
1743
699 180
300
10
245
65
0
0
28
56
100
17
10
8.0
8.0
5.0
6.0
7.5
4.5
3.5
0
0 1.8
4.8
2.5
3.0
F. TANK F. VALVE GPM VELOCITY
30TOTAL GPM
1 WH 23.5 23.5
1 2 2JS
5151 Shoreham Place, Suite #240San Diego, CA 92122Phone: 619.330.6043Fax: 909.890.3770
Email: [email protected]
DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS
REG
ISTE
RED
PROF
RE
ENI
GNE
ESSIONAL
ETA
TS
FO FILACO
AINR
M
No. 33209
E C HA N I CA L
NHOJNEVETS
M.
NOS
EXP. 9-30-2017
PROFESSIONAL STAMPS:
SH
EE
T T
ITLE
:
SHEET NUMBER:
PRIN
TED
:PA
TH:
DATE ISSUED:
DRAWN BY:
RE
VIS
ION
S:
PR
OJE
CT
NA
ME
PR
OJE
CT
NU
MB
ER
:15.0
04
1 2 3 4 5
MEDIC
AL A
RCHIT
ECTURE &
CONSULTIN
GRAYM
OND F
OX &
ASSOCIA
TES
1660 H
OTEL C
IRCLE N
ORTH S
TE 3
40 S
AN D
IEG
O C
A 9
2108
(619) 296-4
595
RA
YM
ON
DF
OX
.CO
M
6 7
AN
AH
EIM
HIL
LS
ASC
500 S
. ANAH
EIM
HIL
LS
RD.
STE. 128,1
29
ANAH
EIM
, CA 9
2807
J.P.
5/1
8/2
016 3
:52:2
6 P
MC:\
Use
rs\j
pete
rson.D
ESIG
NW
ESTEN
G\D
ocu
ments
\15-4
41 A
NAH
EIM
HIL
LS A
SC_M
P_CEN
TRAL_
jpete
rson.r
vt
15-441
P2.1
Issue Date
PLU
MBIN
G R
ISER D
IAG
RAM
- C
OLD
WATER
COLD WATER RISER DIAGRAM 1NO SCALE
L-1(.75 F.U.)
S-1(1.5 F.U.)
JS-1(1.5 F.U.)
L-1(.75 F.U.)
L-1(.75 F.U.)
S-3(1.5 F.U.)
S-4(1.5 F.U.)
S-4(1.5 F.U.)
S-2(1.5 F.U.)
(.75 F.U.)
(3 F.U.)
(6.5 F.U.) (2.25 F.U.)
(5.25 F.U.)
(6.75 F.U.)
(9.75 F.U.)(11.25 F.U.)
WH-1(23.5 F.U.)
3/4"ø
3/4"ø
3/4"ø
3/4"ø
3/4"ø
3/4"ø
3/4"ø
3/4"ø
1"ø
1"ø
3/4"ø
3/4"ø
1"ø
1"ø
3/4"ø
5151 Shoreham Place, Suite #240San Diego, CA 92122Phone: 619.330.6043Fax: 909.890.3770
Email: [email protected]
DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS
REG
ISTE
RED
PROF
RE
ENI
GNE
ESSIONAL
ETA
TS
FO FILACO
AINR
M
No. 33209
E C HA N I CA L
NHOJNEVETS
M.
NOS
EXP. 9-30-2017
PROFESSIONAL STAMPS:
SH
EE
T T
ITLE
:
SHEET NUMBER:
PRIN
TED
:PA
TH:
DATE ISSUED:
DRAWN BY:
RE
VIS
ION
S:
PR
OJE
CT
NA
ME
PR
OJE
CT
NU
MB
ER
:15.0
04
1 2 3 4 5
MEDIC
AL A
RCHIT
ECTURE &
CONSULTIN
GRAYM
OND F
OX &
ASSOCIA
TES
1660 H
OTEL C
IRCLE N
ORTH S
TE 3
40 S
AN D
IEG
O C
A 9
2108
(619) 296-4
595
RA
YM
ON
DF
OX
.CO
M
6 7
AN
AH
EIM
HIL
LS
ASC
500 S
. ANAH
EIM
HIL
LS
RD.
STE. 128,1
29
ANAH
EIM
, CA 9
2807
J.P.
5/1
8/2
016 3
:52:2
7 P
MC:\
Use
rs\j
pete
rson.D
ESIG
NW
ESTEN
G\D
ocu
ments
\15-4
41 A
NAH
EIM
HIL
LS A
SC_M
P_CEN
TRAL_
jpete
rson.r
vt
15-441
P2.2
Issue Date
PLU
MBIN
G R
ISER D
IAG
RAM
- H
OT W
ATER
HOT WATER RISER DIAGRAM 1NO SCALE
CP-1
WC-1(4 F.U.)
4" W(5 F.U.)
1-1/2" V
2" W.C.O.
S-1(2 F.U.)
2" W
L-2(1 F.U.)
2" W
L-1(1 F.U.)
WC-1(4 F.U.)
4" W
4" W.C.O.
WC-1(4 F.U.)4" W
L-1(1 F.U.)
2" W
2" W.C.O.
JS-1(2 F.U.)
CONNECT (N) 4" WASTELINE TO (E) 4" WASTE LINE
2" W
2" W
FS-1(2 F.U.)
2" W
S-3(2 F.U.)
2" W
S-4(2 F.U.)
4" W
S-4(2 F.U.)
S-2(2 F.U.)
2" W
FS-1(2 F.U.)
2" W
FS-1(2 F.U.)
FS-1(2 F.U.)
CONNECT (N) 4" WASTELINE TO (E) 4" WASTE LINE
4" W(6 F.U.)
4" W(8 F.U.)
4" W(12 F.U.)
4" W(14 F.U.)
4" W(16 F.U.)
4" W(7 F.U.)
4" W(12 F.U.)
4" W(19 F.U.)
1-1/2" V
2" V
2" V
1-1/2" V
2" V
1-1/2" V
2" V
2" V
1-1/2" V
1-1/2" V
1-1/2" V
1-1/2" V
1-1/2" V1-1/2" V
1-1/2" V
1-1/2" V
1-1/2" V
2" V
2" V
2" V
3" V
NUMBER
DRAINAGE FIXTURE UNITS
FIXTURE UNIT TOTAL
3,600
1,380
48
256
600
16
32
2
1
FIXTURE UNITS
1-1/2"
6"
8"
3"
4"
5"
2"
2-1/2"
SIZE
1-1/4"
DFU VERTICAL
DRAINAGE PIPE SIZE SCHEDULE
2,640
720
35
216
428
8
14
1
1
DFU HORIZONTAL
PIPE SIZE IS BASED ON TABLE 7-5 FROM CPC
FIXTURE UNITS ARE BASED ON TABLE 7-3 FROM CPC
3
3
2
L
WC
1
4
3
12
5 S 2 2
PLUMBING WASTE SIZING FORM
35TOTAL NEW FIXTURE UNITS
1 JS 2
84 FD 2
25 S 2 105 S 2
5151 Shoreham Place, Suite #240San Diego, CA 92122Phone: 619.330.6043Fax: 909.890.3770
Email: [email protected]
DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS
REG
ISTE
RED
PROF
RE
ENI
GNE
ESSIONAL
ETA
TS
FO FILACO
AINR
M
No. 33209
E C HA N I CA L
NHOJNEVETS
M.
NOS
EXP. 9-30-2017
PROFESSIONAL STAMPS:
SH
EE
T T
ITLE
:
SHEET NUMBER:
PRIN
TED
:PA
TH:
DATE ISSUED:
DRAWN BY:
RE
VIS
ION
S:
PR
OJE
CT
NA
ME
PR
OJE
CT
NU
MB
ER
:15.0
04
1 2 3 4 5
MEDIC
AL A
RCHIT
ECTURE &
CONSULTIN
GRAYM
OND F
OX &
ASSOCIA
TES
1660 H
OTEL C
IRCLE N
ORTH S
TE 3
40 S
AN D
IEG
O C
A 9
2108
(619) 296-4
595
RA
YM
ON
DF
OX
.CO
M
6 7
AN
AH
EIM
HIL
LS
ASC
500 S
. ANAH
EIM
HIL
LS
RD.
STE. 128,1
29
ANAH
EIM
, CA 9
2807
J.P.
5/1
8/2
016 3
:52:2
7 P
MC:\
Use
rs\j
pete
rson.D
ESIG
NW
ESTEN
G\D
ocu
ments
\15-4
41 A
NAH
EIM
HIL
LS A
SC_M
P_CEN
TRAL_
jpete
rson.r
vt
15-441
P2.3
Issue Date
PLU
MBIN
G R
ISER D
IAG
RAM
- W
ASTE &
VEN
T
NO SCALEWASTE & VENT RISER DIAGRAM 1
1 1/2" LONG "TEK"SCREW
DIAGONAL BRACE
STRUCTURE
1" MIN.
1" MIN.1 1/2" LONG"TEK" SCREW
1/2"ø HANGERROD (TYP.) 2 1/2"x2 1/2"x16 GA
ANGLE BRACE (TYP.)
STRUCTURE
SCHEDULE 40 PVC & ABS DWV
STEEL PIPE FOR GAS
REFER TO SMACNA GUIDELINES IN SCHEDULE BELOW
SUPPORT EVERY JOINT. SUPPORT SHALL BE WITHIN 18 INCHES OF JOINT ON BOTH SIDES. (SUPPORT ALSO REQUIRED AT EACHHORIZONTAL JOINT CONNECTION.)
CAST IRON HUBLESS (NO HUB)
ALL PIPING 2-1/2" AND LARGER PER THE FOLLOWING SMACNA GUIDELINES
BRACING MAY BE OMITTED WHERE TOP OF PIPE IS 12" OR LESS FROM BOTTOM OF HANGER SUPPORT CONNECTED TO STRUCTURE
VERTICAL ANGLE ONLY REQUIRED WHEN ROD MAXIMUM LENGTH IS EXCEEDED.
COPPER TUBE & PIPE
37"1- & 2 15'-0" 3/8"
ALLOW FOR EXPANSION EVERY 30'-0".3
NOTES:
2
1
10'-0"10'-0"2-1/2
4
3
10'-0"10'-0"
10'-0" 10'-0"
A
3 thru 6 A
25"1/2"
5/8"
1/2"
31"
25"
1 thru 2 10'-0"4'-0"
A
4'-0" 10'-0"
1
1- thru 2
8'-0"8'-0"
10'-0" 10'-0"
6'-0" 6'-0"
3/8"
3/8"
37"
37"
3/8"
3/8"
3/8"
37"
37"
37"
BETWEEN SUPPORT
1 THRU 1/2
2
1_2
&3_4
10'-0"6'-0"
10'-0" 10'-0"
6'-0" 10'-0"
PIPE SIZEIN INCHES
MAXIMUM SPAN
HANGERS O.C.
HORIZ. VERT.
3/8"
3/8"
3/8"
37"
37"
37"
HANGER RODDIAMETER SIZE
MAX. LENGTHFOR RODS
3/8"1-1/2 x 1-1/2 x 18
ga @ 40'-0" O.C.1-1/2 x 1-1/2 x 18
ga @ 80'-0" O.C.1 x 1 x 18ga
1/2"
3/8"
3/8"
2 x 2 x 16ga
2 x 2 x 16ga
2 x 2 x 16ga2-1/2 x 2-1/2 x 16
ga @ 80'-0" O.C.
2-1/2 x 2-1/2 x 16ga @ 80'-0" O.C.
2-1/2 x 2-1/2 x 16ga @ 80'-0" O.C.
2-1/2 x 2-1/2 x 16ga @ 40'-0" O.C.
2-1/2 x 2-1/2 x 16ga @ 40'-0" O.C.
2-1/2 x 2-1/2 x 16ga @ 40'-0" O.C.
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
BOLTSIZE
1 x 1 x 18ga
1 x 1 x 18ga
1 x 1 x 18ga
1 x 1 x 18ga
1 x 1 x 18ga
3
1-1/2 x 1-1/2 x 18ga @ 80'-0" O.C.
1-1/2 x 1-1/2 x 18ga @ 80'-0" O.C.
1-1/2 x 1-1/2 x 18ga @ 80'-0" O.C.
2-1/2 x 2-1/2 x 16ga @ 80'-0" O.C.
1-1/2 x 1-1/2 x 18ga @ 80'-0" O.C.
1-1/2 x 1-1/2 x 18ga @ 40'-0" O.C.
1-1/2 x 1-1/2 x 18ga @ 40'-0" O.C.
1-1/2 x 1-1/2 x 18ga @ 40'-0" O.C.
1-1/2 x 1-1/2 x 18ga @ 40'-0" O.C.
2-1/2 x 2-1/2 x 16ga @ 40'-0" O.C.
1 x 1 x 18ga
1 x 1 x 18ga
(STIFFNER)
VERTICALHANGER ANGLE
1 x 1 x 18ga
1-1/2 x 1-1/2 x 18ga @ 80'-0" O.C.
1-1/2 x 1-1/2 x 18ga @ 80'-0" O.C.
1-1/2 x 1-1/2 x 18ga @ 80'-0" O.C.
LONGITUDINALANGLE BRACE
2
1-1/2 x 1-1/2 x 18ga @ 40'-0" O.C.
2-1/2 x 2-1/2 x 16ga @ 40'-0" O.C.
1-1/2 x 1-1/2 x 18ga @ 40'-0" O.C.
TRANSVERSEANGLE BRACE
1 2
1_2
&3_4
1_2
&3_4
THREADED HANGARROD. FOR SIZE ANDSPACING SEE
2
-
ADD VERTICAL ANGLESTIFFNER IF LENGTH ISGREATER THAN MAX.LENGTH SHOWN ON PIPESUPPORT SCHEDLE
NUT & WASHERTOP & BOTTOM
"B-LINE" - B3690ADJUSTABLE "J" HANGAR
PIPING. SEE PLANS FOR SIZEAND LOCATION
"B-LINE" B3162 PIPE SADDLE
TRANSVERSE ANGLE BRACE.ALTERNATIVE SIDES EVERY BRACE
FOR CONNECTION TOSTRUCTURE SEE
1
-
INSULATION WHEREAPPILES - SEEAPECIFICATIONS
AIR GAP
3/4" CW
SINK
3/4" HW
2" WASTE
WCO
1-1/2" VENT
1-1/2" TRAP
PROVIDE (2) 1/2"CAPPED TEES &(1) 1/2" S.O.V.FOR FUTUREREVERSE OSMOSISSYSTEM
GARBAGE DISPOSER
FAUCET
S
1
SINK
2" WASTE
WCO
1-1/2" VENT
1-1/2" TRAP
3/4" CW
3/4" HW
S.O.V.
5151 Shoreham Place, Suite #240San Diego, CA 92122Phone: 619.330.6043Fax: 909.890.3770
Email: [email protected]
DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS
REG
ISTE
RED
PROF
RE
ENI
GNE
ESSIONAL
ETA
TS
FO FILACO
AINR
M
No. 33209
E C HA N I CA L
NHOJNEVETS
M.
NOS
EXP. 9-30-2017
PROFESSIONAL STAMPS:
SH
EE
T T
ITLE
:
SHEET NUMBER:
PRIN
TED
:PA
TH:
DATE ISSUED:
DRAWN BY:
RE
VIS
ION
S:
PR
OJE
CT
NA
ME
PR
OJE
CT
NU
MB
ER
:15.0
04
1 2 3 4 5
MEDIC
AL A
RCHIT
ECTURE &
CONSULTIN
GRAYM
OND F
OX &
ASSOCIA
TES
1660 H
OTEL C
IRCLE N
ORTH S
TE 3
40 S
AN D
IEG
O C
A 9
2108
(619) 296-4
595
RA
YM
ON
DF
OX
.CO
M
6 7
AN
AH
EIM
HIL
LS
ASC
500 S
. ANAH
EIM
HIL
LS
RD.
STE. 128,1
29
ANAH
EIM
, CA 9
2807
J.P.
5/1
8/2
016 3
:52:2
8 P
MC:\
Use
rs\j
pete
rson.D
ESIG
NW
ESTEN
G\D
ocu
ments
\15-4
41 A
NAH
EIM
HIL
LS A
SC_M
P_CEN
TRAL_
jpete
rson.r
vt
15-441
P3.1
Issue Date
PLU
MBIN
G D
ETAIL
S
CONNECTION TO STRUCTURE 1
PIPING SUPPORT SCHEDULE 2
PIPE SUPPORT 3
SINK CONNECTION 4
SINK CONNECTION 5