  • Source changeover systemsCompact NSX100-630, Compact NS630b-1600, Compact INS/INV, Masterpact

    Low Voltage

    Catalogue2013

    313E0100.indd 1 15/04/2013 10:38:33

  • 313E0100.indd 2 15/04/2013 10:38:34

  • IEfficient energy management and continuity of service with source-changeover systemTo ensure continuity of service for critical applications, LV electrical installations need to be connected to at least two independent power sources:

    * The replacement source (R) can be: a second power source (with possibly different characteristics from the normal source) or an electrical generator

    1 A normal source (N)

    2And a replacement

    source (R)*used to supply energy to the installation when the normal source unavailable, or, for instance, when its quality and/or availability is no longer guaranteed.

    The source-changeover

    system switches the load (partly or fully) between these two sources.

    A few basics on source-changeover systems> A source-changeover system can be automated to manage transfers according to external conditions.

    > Switching from a main power source to a replacement source can be performed either manually or automatically.

    > A source-changeover system comprises circuit breakers, switch-disconnectors or contactors.

    313E.indb 1 09/04/2013 13:04:06

  • II

    to switch the load to meet your needs

    Automatic source-changeover system(or ATSE: Automatic Transfer Switching Equipment)

    An automatic controller may be added to a remote-operated source-changeover system. It is possible to automatically control source transfer according to programmed (dedicated controllers) or programmable (PLC) operating modes. These solutions ensure optimum energy management.

    3

    ApplicationsCommercial and service sector (operating rooms in hospitals, safety systems for buildings, computer rooms for banks and insurance companies, lighting and emergency lighting systems in malls, etc.), industry and infrastructure.

    System2 or 3 circuit breakers that may have different configurations, linked by an electrical interlocking system. A mechanical interlocking system protects against electrical malfunctions or incorrect manual operations, with an automatic control system (dedicated controllers or PLC).

    1 Manual source-changeover system (or MTSE: Manual Transfer Switching Equipment)The simplest way to switch the load. It is controlled manually by an operator. The time required to switch from the N source to R source can vary.

    ApplicationsBuildings and infrastructure where the need for continuity of service is significant but not a priority: offices, small and medium-sized businesses.

    System2 or 3 mechanically interlocked manually-operated circuit breakers or 2 switch-disconnectors.

    3ways

    Remote-operated source-changeover system(or RTSE: Remote Transfer Switching Equipment)

    The most commonly used system for devices with high ratings. No direct human intervention is required. Source-changeover is controlled electrically.

    2

    System2 or 3 circuit breakers that may have different configurations, linked by an electrical interlocking system. In addition, a mechanical interlocking system protects against electrical malfunctions or incorrect manual operations.

    ApplicationsIndustry (assembly lines, engine rooms on ships, critical auxiliaries in thermal powerstations, etc.); Infrastructure (port and railway installations, runway lighting systems, control systems on military sites, etc.).

    313E.indb 2 09/04/2013 13:04:06

  • III

    > MTSE range

    Compact INSFrom 40 A to 630 A

    > RTSE range

    Compact NSX From 100 A to 630 A

    Masterpact NT / NW From 630 A to 6300 A

    Whatever the system, you benefit from our expertise!

    Our expertise and support come together with the source-changeover system you choose for your LV electrical installation.With Compact INS, Compact NSX and Masterpact NT and NW, we offer a complete range of solutions, designed around key values:

    Maximum continuity of service> Energy availability is ensured whatever

    the external requirements (e.g. high power demand).

    > Maintenance and replacement of the sources (N or R) can be done with no interruption of service.

    You can maintain a continuous level of service and customer satisfaction.

    Optimized energy management> Transfer the load to a replacement source

    according to external requirements.> Manage power sources according to power

    quality and power costs.> Perform system regulation.> Switch to an emergency replacement source.You are no longer dependent on your power supply (and supplier)!

    Simplicity and reliability> Simple installation on LV switchboard.> Optimized size of the switchboard.> System based on pre-tested components.> Compliance with IEC 60947-6-1.

    Maximum safetyFor LV electrical installations where safety and continuity of service are critical for people and/or equipment such as hospitals, airports, banks, malls, etc.

    > ATSE range

    UA Controller Compact NSX From 100 A to 630 A

    313E.indb 3 09/04/2013 13:04:07

  • IV

    A source-changeover system is indispensable for applications that need a continuous supply of electric power (hospitals, airports, banks, government facilities, etc.). But a source-changeover system is also suitable for all LV electrical installations exposed to:> Nominal voltage loss or dip (when there is high demand for electric power)> Unpredictable power quality> Frequent power cuts.

    For critical applications in particularFor all others in general

    These factors, and many others, can damage the continuity of service of your electrical installation.For infrastructure managers, a source-changeover system gives direct economic benefi ts: it is possible to select your source based on power cost. In this case, the replacement source (R) is used as an alternative, more economical source.

    Managing energy ef cientlyPower CostSafety

    313E.indb 4 09/04/2013 13:04:11

  • 1Source-changeover systems Compact NSX100-630, Compact NS630b-1600, Compact INS/INV, Masterpact

    General content

    Presentation 2

    Functions and characteristics A-1

    Dimensions B-1

    Electrical diagrams C-1

    Catalogue numbers and order forms

    D-1

    313E.indb 1 09/04/2013 13:04:11

  • Presentation For maximum continuity of service...

    Incoming feeders and main LV switchboards1 normal source 1 replacement source

    2 sources with coupler on busbars

    2 normal sources1 replacement source

    Db1

    0153

    8.ep

    s

    Db1

    0153

    9.ep

    s

    Db1

    0154

    0.ep

    s

    QN QR QS1 QC QS2 QN1 QN2 QR0 0 0 0 0 0 0 01 0 1 0 1 1 1 0

    CurrentsFrom 630 to 6300 A.

    0 1 1 1 0 0 0 10 1 1 1 0 01 0 0 (1) 0 1 00 0 1 (1)

    (1) possible by forcing operation.

    Power distribution

    PD

    3903

    85_S

    E_R

    _35.

    eps Generator or permanent

    source

    Db1

    0154

    1.ep

    s QN QR Typical applications: b continuous production processes b operating rooms b computer rooms...

    0 01 00 1

    CurrentsFrom 250 to 3200 A.

    Loads

    PB

    1115

    56.e

    ps Generator or permanent source

    Generator or permanent source

    Db1

    0154

    1.ep

    s

    Db1

    0154

    4.ep

    s QN QR Typical applications: b large electrical installations (e.g. airports) b refrigeration units b special electricity tariffs b pumping stations...

    0 01 00 1

    CurrentsFrom 40 to 400 A.

    Db1

    0154

    3.ep

    s

    PB

    1051

    09.e

    ps

    2

    313E.indb 2 09/04/2013 13:04:13

  • Incoming feeders and main LV switchboards1 normal source 1 replacement source

    2 sources with coupler on busbars

    2 normal sources1 replacement source

    Db1

    0153

    8.ep

    s

    Db1

    0153

    9.ep

    s

    Db1

    0154

    0.ep

    s

    QN QR QS1 QC QS2 QN1 QN2 QR0 0 0 0 0 0 0 01 0 1 0 1 1 1 0

    CurrentsFrom 630 to 6300 A.

    0 1 1 1 0 0 0 10 1 1 1 0 01 0 0 (1) 0 1 00 0 1 (1)

    (1) possible by forcing operation.

    Power distribution

    PD

    3903

    85_S

    E_R

    _35.

    eps Generator or permanent

    source

    Db1

    0154

    1.ep

    s QN QR Typical applications: b continuous production processes b operating rooms b computer rooms...

    0 01 00 1

    CurrentsFrom 250 to 3200 A.

    Loads

    PB

    1115

    56.e

    ps Generator or permanent source

    Generator or permanent source

    Db1

    0154

    1.ep

    s

    Db1

    0154

    4.ep

    s QN QR Typical applications: b large electrical installations (e.g. airports) b refrigeration units b special electricity tariffs b pumping stations...

    0 01 00 1

    CurrentsFrom 40 to 400 A.

    ... in a wide range of applications

    3

    313E.indb 3 09/04/2013 13:04:14

  • Ecodial software is dedicated to LV electrical installation calculation in accordance with the IEC60364 international standard or national standards.

    This 4th generation, "Ecodial Advance Calculation 4", offers a new ergonomic and new features:

    p operating mode that allows easy calculation in case of installation with different type of sources (parallel transformers, back-up generators)

    p discrimination analysis associating curves checking and discrimination tables

    p direct access to protection settings including residual current protections

    p easy selection of alternate solutions or manual selection of a product.

    Ecodial

    TOOLS

    181E6000.indd 4 09/04/2013 14:05:54

  • A-1

    Source-changeover systems Compact NSX100-630, Compact NS630b-1600, Compact INS/INV, Masterpact

    Functions and characteristics

    Presentation 2

    Overview of solutions Manual source-changeover systems Compact INS/INV 40 to 630 A, Compact NSX100/630 A-2Manual source-changeover systems Compact NS and Masterpact NT/NW 630 A to 6300 A A-3Remote-operated source-changeover systems Compact NSX100/630, Compact NS630b/1600 A A-4Remote-operated source-changeover systems Masterpact NT/NW 630 A to 6300 A A-5

    Manual source-changeover systems Possible combinations A-6

    Remote-operated source-changeover systems Mechanical interlocking Compact NSX, Compact NS or Masterpact NT/NW A-10Mechanical interlocking Compact NS or Masterpact NT/NW A-11General characteristics Compact NSX A-12General characteristics Compact NS, Masterpact NT/NW A-13Mech. and elect. durability A-14Connection and insulation accessories for Compact NSX and INS y 630 A A-15Electrical interlocking A-16Standard configurations A-17

    Associated controllers Controller selection A-18Controller installation A-19BA controller A-20BA controller, Operating sequences A-21UA controller A-22UA controller, Operating sequences, Forced operation mode A-23UA controller, Operating sequences, Special-tariff mode A-24UA controller, Operating sequences , Test mode and automatic operation A-25

    Operating sequences IVE unit A-26BA/UA controller A-27

    COM communications option A-28

    Dimensions B-1Electrical diagrams C-1Catalogue numbers and order forms D-1

    313E.indb 1 09/04/2013 13:04:14

  • Functions and characteristics

    Range Compact CompactModels INS40 to INS80

    INS100 to INS160INS250 to INS630INV250 to INV630

    NSX100 to NSX250NSX400 to NSX630

    Rating (A) 40 to 160 100 to 630 100 to 630Type of device Switch-disconnectors with

    extended handlesSwitch-disconnectors N/H/L circuit breakers

    NA switch-disconnectors

    Manual source-changeover systemsInterlocking via toggles

    DB

    1265

    89.e

    ps

    Db1

    0154

    5.ep

    s

    2 devices side-by-side. 3 devices side-by-side.

    Interlocking via rotary handles

    DB

    1265

    90.e

    ps

    N

    2.4

    Db1

    0154

    6.ep

    s

    Db1

    0154

    7.ep

    s

    ONI

    OOFF

    ONI

    OOFF

    Db1

    0154

    8.ep

    s

    2 devices side-by-side.

    Interlocking via keylocks with captive keys

    DB

    1265

    88.e

    ps

    Db1

    0154

    9.ep

    s

    Db1

    0155

    0.ep

    s

    A number of different devices.

    Interlocking on a base plate

    DB

    1265

    87.e

    ps

    Db1

    0155

    1.ep

    s

    2 devices side-by-side.

    Complete source-changeover assemblies

    DB

    1265

    86.e

    ps

    DB

    4041

    70.e

    ps

    2 devices side-by-side.

    Overview of solutionsManual source-changeover systems Compact INS/INV 40 to 630 A, Compact NSX100/630

    A-2

    313E.indb 2 09/04/2013 13:04:16

  • Range Compact MasterpactModels NS630b to NS1600 NT06 to NT16 NW08 to NW63Rating (A) 630 to 1600 630 to 1600 800 to 6300 Type of device N/H/L circuit breakers

    NA switch-disconnectorsH1/L1 circuit breakersHA switch-disconnectors

    N1/H1/H2/H3/L1 circuit breakersNA/HA/HF switch-disconnectors

    Manual source-changeover systemsInterlocking via extended rotary handles

    DB

    1265

    90.e

    ps

    Db1

    0155

    3.ep

    s

    2 devices side-by-side.

    Interlocking via keylocks with captive keys

    DB

    1265

    88.e

    ps

    Db1

    0155

    4.ep

    s

    Opush O

    FF

    Ipush O

    N

    O OFFdischa

    rged

    Opush O

    FF

    Ipush O

    N

    O OFFdischa

    rged

    Db1

    0155

    5.ep

    s

    Db1

    0155

    6.ep

    s

    A number of different devices.

    Mechanical interlocking using connecting rods

    DB

    1265

    85.e

    ps

    OpushO

    FF

    IpushO

    N

    OOFFdischa

    rged

    OpushO

    FF

    IpushO

    N

    OOFFdischa

    rged

    Db1

    0155

    7.ep

    s

    (1)

    Db1

    0155

    8.ep

    s

    Db1

    0155

    9.ep

    s

    2 devices one above the other.

    Mechanical interlocking using cables

    DB

    1265

    84.e

    ps

    Db1

    0156

    0.ep

    s

    (1)

    (2)

    Db1

    0156

    1.ep

    s

    Db1

    0156

    2.ep

    s

    2 or 3 devices one above the other.

    DB

    1265

    83.e

    ps

    2 or 3 devices side-by-side.For this case and other cases, please consult us

    DB

    1265

    80.e

    ps

    (1) Implemented with NS630b to NS1600 electrically-operated devices only.(2) For source-changeover systems using cables, always respect the installation conditions specified on page A-13.

    Manual source-changeover systems Compact NS and Masterpact NT/NW 630 A to 6300 A

    A-3

    313E.indb 3 09/04/2013 13:04:19

  • Functions and characteristics

    Range CompactModels NSX100 to NSX630 NS630b to NS1600Rating (A) 100 to 630 630 to 1600Type of device N/H/L circuit breakers

    NA switch-disconnectorsN/H/L circuit breakersNA switch-disconnectors

    Remote-operated source-changeover systemMechanical interlocking on base plate + electrical interlocking

    DB

    1265

    87.e

    ps

    Db1

    0156

    3.ep

    s

    2 electrically-operated devices side-by-side combined with an electrical interlocking system.

    Mechanical interlocking using connecting rods + electrical interlocking

    DB

    1265

    85.e

    ps

    OpushO

    FF

    IpushO

    N

    OOFFdischa

    rged

    OpushO

    FF

    IpushO

    N

    OOFFdischa

    rged

    Db1

    0155

    7.ep

    s

    2 electrically-operated devices one above the other combined with an electrical interlocking system.

    Mechanical interlocking using cables + electrical interlocking

    DB

    1265

    81.e

    ps

    Db1

    0156

    0.ep

    s

    (1)

    2 electrically-operated devices one above the other combined with an electrical interlocking system.

    DB

    1265

    82.e

    ps

    2 electrically-operated devices side-by-side combined with an electrical interlocking system.

    Automatic source-changeover systemsRemote-operated source-changeover system combined with an automatic-control system

    DB

    1265

    81.e

    ps The automatic controller operates the devices depending on external parameters.

    BA: Simple controller that manages the changeover function.

    UA: Controller that also manages engine generator sets.

    UA150: UA controller with a communication option.

    DB

    4044

    39.e

    ps

    BA controller

    DB

    1265

    82.e

    ps

    DB

    4044

    40.e

    ps

    UA and UA150 controller

    (1) For source-changeover systems using cables, always respect the installation conditions specified on page A-13.

    Overview of solutionsRemote-operated source-changeover systems Compact NSX100/630, Compact NS630b/1600 A

    A-4

    313E.indb 4 09/04/2013 13:04:20

  • Range MasterpactModels NT06 to NT16 NW08 to NW63Rating (A) 630 to 1600 800 to 6300 Type of device H1/L1 circuit breakers

    HA switch-disconnectorsN1/H1/H2/H3/L1 circuit breakersNA/HA/HF switch-disconnectors

    Remote-operated source-changeover systemMechanical interlocking using connecting rods + electrical interlocking

    DB

    1265

    85.e

    ps

    Db1

    0155

    8.ep

    s

    Db1

    0155

    9.ep

    s

    2 electrically-operated devices side-by-side combined with an electrical interlocking system.

    Mechanical interlocking using cables + electrical interlocking

    DB

    1265

    84.e

    ps

    Db1

    0156

    1.ep

    s

    Db1

    0156

    2.ep

    s

    2 or 3 electrically-operated devices one above the other combined with an electrical interlocking system (1).

    DB

    1265

    83.e

    ps

    2 or 3 electrically-operated devices side-by-side combined with an electrical interlocking system (1).

    (2)

    Automatic source-changeover systemsRemote-operated source-changeover system combined with an automatic-control system

    DB

    1265

    81.e

    ps The automatic controller operates the devices depending on external parameters.

    BA: Simple controller that manages the changeover function.

    UA: Controller that also manages engine generator sets.

    UA150: UA controller with a communication option.

    DB

    4044

    39.e

    ps

    BA controller

    DB

    1265

    82.e

    ps

    DB

    4044

    40.e

    ps

    UA and UA150 controller

    (1) Three devices with Masterpact NW only.(2) For source-changeover systems using cables, always respect the installation conditions specified on page A-13. For other cases, please consult us.

    Remote-operated source-changeover systems Masterpact NT/NW 630 A to 6300 A

    A-5

    313E.indb 5 09/04/2013 13:04:21

  • Functions and characteristics

    A manual source-changeover system can be installed on two or three manually-operated and mechanically interlocked circuit breakers or switch-disconnectors.Interlocks prevent connection to both sources at the same time, even momentarily.

    All possibilities for manual source-changeover systems

    Type of device Type of interlocking for two devicesComplete assembly

    Keylock Direct rotary handle

    Extended rotary handle

    Compact switch-disconnectors

    INS40 to INS160 b

    INS250-100 to INS630 b b b r b r

    INV100 to 630 b b r b r r

    INS/INV630b to 2500 b Legend:r Possible but visible break function disabled.r 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system.

    Type of device Type of interlocking for two devicesToggle Keylock Direct rotary

    handleExtended rotary handle

    On base plate (toggle or direct extended rotary control)

    On base plate (motor mechanism)

    Compact fixed or withdrawable circuit breakers

    NSX100 to 250 b b b b p b b b b b b b b b b

    NSX400 to NS630 b b b b p b b b b b b b b b b

    NSX100 to 630 b b p b b p b b p b b b p b b b p

    NS630b to 1600 with rotary handle

    b b p b b b b

    Legend:b Fixed devices only.b Fixed or withdrawable devices.b Devices must be either both fixed or both withdrawable.p With NSX400/630 rotary handle interlocking system.p Possible with NSX400/630 base plate + NSX100-250 adaptation kit.p Devices equipped with rotary handles.

    Type of device Type of interlocking for either all fixed or all withdrawable devicesKeylock Cable-type,

    2 devices side-by-side

    Cable-type, 3 devices side-by-side

    Cable-type, 2 devices one above the other

    Cable-type, 3 devices one above another

    Rod-type, 3 devices one above another

    Compact fixed or withdrawable circuit breakers or swith-disconnectors, with motor mechanism NS630b to 1600 b b b bMasterpact fixed or withdrawable circuit breakers or swith-disconnectors, manual operation or with motor mechanism

    NT06 to 16 b b b b

    NW08 to 63 b b b b b b

    NT06 to NW63 b b b

    Manual source-changeover systemsPossible combinations

    A-6

    313E.indb 6 09/04/2013 13:04:21

  • Complete source-changeover assembly for two switch-disconnectorsAll possibilities for manual source-changeover systems

    DB

    4041

    70.e

    ps These assemblies provide an easy way to implement source changeover functions with:

    b a single 3-position rotary handle that controls the two switch-disconnectors (Normal source ON, OFF, Replacement source ON)

    b a smaller size, taking up less room in the switchboard.A complete source changeover assembly can be ordered with a single catalogue number.

    Normal N Replacement RINS250-100 INS250-160 INS200-200 INS250-250 INS320 INS400 INS500 INS630

    INS250-100Ratings 100 A b INS250-160Ratings 160 A b INS200-200Ratings 200 A b INS250-250Ratings 250 A b INS320Ratings 320 A b INS400Ratings 400 A b INS500Ratings 500 A b INS630Ratings 630 A b

    Interlocking of two or three toggle-controlled devicesPossible combinations of Normal and Replacement source circuit breakers

    Db1

    0156

    6.ep

    s Two devices can be interlocked using this system. Two identical interlocking systems can be used to interlock three devices installed side by side, in which case one device is in the ON position and the two others are in the OFF position. Devices must all have the same configuration, i.e. fixed, plug-in, withdrawable or drawout.The system is locked using one or two padlocks (shackle diameter 5 to 8 mm).Two interlocking system models are available for:

    b Compact NSX100 to 250 b Compact NSX400 to 630.

    Normal N Replacement RNSX100 NSX160 NSX250 NSX400 NSX630

    NSX100Ratings 16... 100 A b b b b b NSX160Ratings 80...160 A b b b b b NSX250Ratings 125...250 A b b b b b NSX400Ratings 150... 400 A b b b b b NSX630Ratings 630 A b b b b b

    Possible combinations

    A-7

    313E.indb 7 09/04/2013 13:04:21

  • Functions and characteristics

    Interlocking of a number of devices using keylocks (captive keys)Combination of Normal and Replacement devices

    Db1

    0156

    9.ep

    s All Compact and Masterpact circuit breakers and Compact switch-disconnectors from 100 to 6300 A with rotary handles or motor mechanisms can be interlocked.

    Interlocking is based on two identical keylocks with a single key and a keylock adapter (different for each device). This solution enables interlocking between two devices that are physically distant or that have very different characteristics, for example between a low and a medium-voltage device, or between Compact NSX circuit breakers and switch-disconnectors.A system of wall-mounted captive key boxes makes possible a large number of combinations between many devices.

    Interlocking of two devices with rotary handlesPossible combinations of Normal and Replacement source circuit breakers

    ONI

    OOFF

    ONI

    OOFF

    Db1

    0156

    8.ep

    s The direct or extended rotary handles are padlocked with the devices in the OFF position. The mechanism prevents simultaneous closing of the devices, but allows them to be opened.

    Normal N Replacement RCompact NSX100/630 (1) NSX100 NSX160 NSX250 NSX400 NSX630NSX100Ratings 16... 100 A b b b v v NSX160Ratings 80...160 A b b b v v NSX250Ratings 125...250 A b b b v v NSX400Ratings 160... 400 A v v v b b NSX630Ratings 630 A v v v b b v 250 A and 630 A ratings can be mixed by using NSX400/630 rotary handle interlocking

    system.

    Normal N Replacement RCompact NS630b/1600 (1) NS630b NS800 NS1000 NS1200 NS1600NS630bRatings 250... 630 A b b b b b NS800Ratings 320... 800 A b b b b b NS1000Ratings 400... 1000 A b b b b b NS1200Ratings 480... 1200 A b b b b b NS1600Ratings 640... 1600 A b b b b b

    (1) When mixing NSX100/250 and NSX400/630 circuit breakers, use the NSX400/630 interlocking system.

    Manual source-changeover systemsPossible combinations

    A-8

    313E.indb 8 09/04/2013 13:04:22

  • Interlocking of two devices with rotary handlesPossible combinations of Normal and Replacement source switch-disconnectors

    DB

    1077

    42.e

    ps The direct or extended rotary handles are padlocked with the devices in the OFF position. The mechanism prevents simultaneous closing of the devices, but allows them to be opened.

    Normal N Replacement RCompact INS (1) INS40 INS63 INS80 INS100 INS125 INS160INS40Ratings 40 A b b b b b b INS63Ratings 63 A b b b b b b INS80Ratings 80 A b b b b b b INS100Ratings 100 A b b b b b b INS125Ratings 125 A b b b b b b INS160Ratings 160 A b b b b b b

    (1) With extended rotary handles only.(2) Possible with INV, but visible-break function is significantly impaired.

    Normal N Replacement RCompact INS /INV (2) INS250-100/

    INV100INS250-160/INV160

    INS250-200/INV200

    INS250-250/INV250

    INS320/INV320

    INS400/INV400

    INS500/INV500

    INS630/INV630

    INS250-100/INV100Ratings 100 A b b b b v v v INS250-160/INV160Ratings 160 A b b b b INS250-200/INV200Ratings 200 A b b b b INS250-250/INV250Ratings 250 A b b b b v v INS320/INV320Ratings 320 A v v b b b b INS400/INV400Ratings 400 A b b b b INS500/INV500Ratings 500 A b b b b INS630/INV630 Ratings 630 A v v b b b b v 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system.

    Interlocking of two devices on a base platePossible combinations of Compact NSX Normal and Replacement source circuit breakers

    DB

    4148

    91.e

    ps A base plate is available for mechanical interlocking of two manually-operated Compact NSX100 to 630 circuit breakers or switch-disconnectors.Normal N Replacement R

    NSX100 NSX160 NSX250 NSX400 NSX630NSX100Ratings 16... 100 A b b b b b NSX160Ratings 80... 160 A b b b b b NSX250Ratings 125... 250 A b b b b b NSX400Ratings 150... 400 A b b b b b NSX630Ratings 630 A b b b b b

    Interlocking of a number of devices using keylocks (captive keys)Combination of Masterpact devices

    Db1

    0190

    3.ep

    s Interlocking uses two identical keylocks with a single key. This solution enables interlocking between two devices that are physically distant or that have significantly different characteristics.

    Possible combinations

    A-9

    313E.indb 9 09/04/2013 13:04:23

  • A-10

    Functions and characteristics

    Mechanical interlocking of two or three devices is used to create a remote-operated source-changeover system. A basic mechanical interlocking system enhances the reliability of system operation.

    Interlocking of two Compact NSX100 to 630 devices using a base plateA base plate designed for two Compact circuit breakers can be installed horizontally or vertically on a mounting rail. Interlocking is carried out on the base plate by a mechanism located behind the breakers. Access to the circuit breaker controls and trip units is conserved. Circuit breakers must be fixed or plug-in versions, with or without earth-leakage protection or measurement modules. The base plate and the circuit breakers are supplied separately.

    b Base plate for Compact NSX100 to 250 devicesThis base plate is intended for two Compact NSX100 to 250 devices.

    b Base plate for Compact NSX400 to 630 devicesThis base plate is intended for two Compact NSX400 to 630 devices. It may also be used, without any modifications, to interlock a fixed Compact NSX100 to 250 with a Compact NSX400 or 630 device.An adapter kit is required for plug-in versions of the Compact NSX100 to 250 devices.Compact NSX100 to 250 devices, in both fixed and plug-in versions, may be equipped with spreaders.

    PB

    1051

    06_5

    0.ep

    s

    Possible combinations of Normal and Replacement Compact NSX source circuit breakers

    Interlocking of two electrically-operated Compact NSX circuit breakers using a base plate. Normal N Replacement R

    NSX100 NSX160 NSX250 NSX400 NSX630NSX100Ratings 12,5... 100 A b b b b b NSX160Ratings 12,5...160 A b b b b b NSX250Ratings 12,5...250 A b b b b b NSX400Ratings 160... 400 A b b b b b NSX630Ratings 250... 630 A b b b b b

    DB

    1262

    68.e

    ps Interlocking of two Compact NS630b to 1600 or two Masterpact NT and NW devices using connecting rodsThe two devices must be mounted one above the other (either 2 fixed or 2 withdrawable/drawout devices).Combinations are possible between Compact NS630b to NS1600 devices and between Masterpact NT and Masterpact NW devices.InstallationThis function requires:

    b an adaptation fixture on the right side of each circuit breaker or switch-disconnector

    b a set of connecting rods with no-slip adjustments.The adaptation fixtures, connecting rods and circuit breakers or switch-disconnectors are supplied separately, ready for assembly by the customer.The maximum vertical distance between the fixing planes is 900 mm.

    Possible combinations of Normal and Replacement source circuit breakers

    Normal N Replacement RNS630b to NS1600

    NT06 to NT16 NW08 to NW40

    NW40b to NW63

    NS630b to NS1600Ratings 250... 1600 A b

    Interlocking of two Masterpact NT or NW circuit breakers using connecting rods.

    NT06 to NT16Ratings 250... 1600 A b b b NW08 to NW40Ratings 320... 4000 A b b b NW40b to NW63Ratings 4000... 6300 A b b b

    Remote-operated source-changeover systems Mechanical interlocking Compact NSX, Compact NS or Masterpact NT/NW

    313E.indb 10 09/04/2013 13:04:24

  • A-11

    PB

    1008

    42_6

    8_S

    E.e

    ps Interlocking of two Compact NS630b to 1600 or two Masterpact NT/NW or up to three Masterpact NW devices using cablesFor cable interlocking, the circuit breakers may be mounted one above the other or side-by-side.The interlocked devices may be fixed or drawout, three-pole or four-pole, and have different ratings and sizes.

    Interlocking between two devices (Compact NS630b to 1600 or Masterpact NT and NW)This function requires:

    b an adaptation fixture on the right side of each device b a set of cables with no-slip adjustments.

    The maximum distance between the fixing planes (vertical or horizontal) is 2000 mm.

    Interlocking between three devices (Masterpact NW only)This function requires:

    b a specific adaptation fixture for each type of interlocking, installed on the right side of each device

    b two or three sets of cables with no-slip adjustments.The maximum distance between the fixing planes (vertical or horizontal) is 1000 mm.

    InstallationThe adaptation fixtures, sets of cables and circuit breakers or switch-disconnectors are supplied separately, ready for assembly by the customer.Installation conditions for cable interlocking systems:

    b cable length: 2.5 m b radius of curvature: 100 mm b maximum number of curves: 3.

    Interlocking of two Masterpact circuit breakers using cables.

    Possible combinations of Normal and Replacement source circuit breakers

    Normal N Replacement RNS630b to NS1600

    NT06 to NT16 NW08 to NW40

    NW40b to NW63

    NS630b to NS1600Ratings 250... 1600 A b NT06 to NT16Ratings 250... 1600 A b b b NW08 to NW40Ratings 320... 4000 A b b b NW40b to NW63Ratings 4000... 6300 A b b b

    It is not possible to combine Compact NS630b to 1600 and Masterpact NT (or Masterpact NW) devices.All combinations of two Masterpact NT and Masterpact NW devices are possible, whatever the rating or size of the devices.

    Possible combinations of three device

    Normal N Replacement RNS630b to NS1600

    NT06 to NT16 NW08 to NW40

    NW40b to NW63

    NS630b to NS1600Ratings 250... 1600 ANT06 to NT16Ratings 250... 1600 ANW08 to NW40Ratings 320... 4000 A b b NW40b to NW63Ratings 4000... 6300 A b b

    Only Masterpact NW may be used for three-device combinations.

    Types of mechanical interlocking and combinationsSee page A-4 to page A-9.

    Mechanical interlocking Compact NS or Masterpact NT/NW

    313E.indb 11 09/04/2013 13:04:25

  • A-12

    Functions and characteristics

    Range Compact NSXTypes of devices NSX100 to NSX250 NSX400 to NSX630Types of circuit breakers N / H / L N / H / LSwitch-disconnector version NA NAMixing possibilities all devices all devices

    NS100 to NS250 NS100 to NS630N/H/L/NA N/H/L/NA fixed or plug-in fixed or plug-in

    Electrical characteristicsRating 15 to 250 A 15 to 630 AInsulating voltage Ui (V AC) 750 750 Positive break indication b b Number of poles(N and R devices must have the same number of poles)

    3, 4

    Electrical durability See page A-14Operating temperature -25 C to +70 C (50 C for 440 V - 60 Hz)Control characteristics

    Control voltage AC 48 V - 50 Hz 48 V - 50 Hz 110/130, 220/240, 380/440 V - 50/60 Hz 110/130, 220/240, 380/440 V - 50/60 Hz

    DC 24-250 V 24-250 VMaximum consumption AC 500 VA 500 VA

    DC 500 W 500 WMinimum switching time 800 ms 800 msInterlocking

    Mechanical (see page A-10)Electrical by diagram (without IVE) b b

    with IVE unit b b auxiliary contacts used by circuit breaker 1 OF + 1 SDE 1 OF + 1 SDE

    Protection and measurementOverload protection long time b b Short-circuit protection short time b b

    instantaneous b b Earth-fault protection b Zone selective interlocking (ZSI) b Earth-leakage protection by Vigi module b b

    by control unit by add-on Vigirex relay b b

    Current measurementsVoltage, frequency, power measurements, etc.Indication and control auxiliaries

    Available auxiliary indication contacts OF + SD (+ SDV) 3 OF + SD (+ SDV)Voltage releases MX shunt b b

    MN undervoltage b b Voltage presence indicator b b Voltage transformer b b Ammeter module b b Insulation monitoring module b b Source-changeover controller

    With permanent replacement source b BA controllerWith standby generator set b UA controllerRemote communication via bus

    Device status indicationsDevice remote controlTransmission of settings b b Indication and identification of protection status and alarms b b Transmission of measurements b b Installation and connection

    Fixed front connectedFixed rear connected b (long rear connections) b (long rear connections)Withdrawable, plug-in or drawout b (plug-in on base) b (plug-in on base)Installation and connection accessories

    Downstream coupling accessory b b Bare-cable connectors b b Terminal extensions b b Terminal shields and inter-phase barriers b Locking by padlock b b

    by keylock b b Front panel escutcheons b b

    Remote-operated source-changeover systems0 General characteristics Compact NSX

    Compact NS MasterpactNS630b to NS1600 NT06 to 16 NW08 to 63N / H / L N1 / H1 / H2 / H3 / L1 N1 / H1 / H2 / H3 / L1NA NA / HA / HF NA / HA / HFall devices all mixing possibilities all mixing possibilitiesNS630b to 1600 (fixed, drawout or fixed + drawout) (fixed, drawout or fixed + drawout) N/H/L/NA N1/H1/H2/H3/L1/NA/HA/HF N1/H1/H2/H3/L1/NA/HA/HFfixed or plug-in

    250 to 1600 A 600 to 1600 A 800 to 6300 A750 1000 1000

    b b 3, 4

    See page A-14-25 C to +70 C (50 C for 440 V - 60 Hz)

    48 to 415 V - 50/60 Hz 440 V - 60 Hz

    24-250 V 24-250 V 24-250 V180 VA 180 VA 180 VA180 W 180 W 180 W800 ms 800 ms 800 ms

    b b b b only with UA or BA only with UA or BA

    1 OF + 1 CE (+ SDE) 1 OF + 1 CE + 1 PF 1 OF + 1 CE + 1 PF

    b b b b b b b b b b b b b b b

    b b b b b b b b b

    b b

    2 OF + SD 2 OF + SD 2 OF + SD b b b b b b

    b b b b b b b b

    b BA controller b UA controller

    b b b

    b b b b b b b b b

    b (vertical or horizontal) b (vertical or horizontal) b (vertical or horizontal) b (drawout) b (drawout) b (drawout)

    b

    b b b b b b b b b b

    313E.indb 12 09/04/2013 13:04:25

  • A-13

    Range Compact NSXTypes of devices NSX100 to NSX250 NSX400 to NSX630Types of circuit breakers N / H / L N / H / LSwitch-disconnector version NA NAMixing possibilities all devices all devices

    NS100 to NS250 NS100 to NS630N/H/L/NA N/H/L/NA fixed or plug-in fixed or plug-in

    Electrical characteristicsRating 15 to 250 A 15 to 630 AInsulating voltage Ui (V AC) 750 750 Positive break indication b b Number of poles(N and R devices must have the same number of poles)

    3, 4

    Electrical durability See page A-14Operating temperature -25 C to +70 C (50 C for 440 V - 60 Hz)Control characteristics

    Control voltage AC 48 V - 50 Hz 48 V - 50 Hz 110/130, 220/240, 380/440 V - 50/60 Hz 110/130, 220/240, 380/440 V - 50/60 Hz

    DC 24-250 V 24-250 VMaximum consumption AC 500 VA 500 VA

    DC 500 W 500 WMinimum switching time 800 ms 800 msInterlocking

    Mechanical (see page A-10)Electrical by diagram (without IVE) b b

    with IVE unit b b auxiliary contacts used by circuit breaker 1 OF + 1 SDE 1 OF + 1 SDE

    Protection and measurementOverload protection long time b b Short-circuit protection short time b b

    instantaneous b b Earth-fault protection b Zone selective interlocking (ZSI) b Earth-leakage protection by Vigi module b b

    by control unit by add-on Vigirex relay b b

    Current measurementsVoltage, frequency, power measurements, etc.Indication and control auxiliaries

    Available auxiliary indication contacts OF + SD (+ SDV) 3 OF + SD (+ SDV)Voltage releases MX shunt b b

    MN undervoltage b b Voltage presence indicator b b Voltage transformer b b Ammeter module b b Insulation monitoring module b b Source-changeover controller

    With permanent replacement source b BA controllerWith standby generator set b UA controllerRemote communication via bus

    Device status indicationsDevice remote controlTransmission of settings b b Indication and identification of protection status and alarms b b Transmission of measurements b b Installation and connection

    Fixed front connectedFixed rear connected b (long rear connections) b (long rear connections)Withdrawable, plug-in or drawout b (plug-in on base) b (plug-in on base)Installation and connection accessories

    Downstream coupling accessory b b Bare-cable connectors b b Terminal extensions b b Terminal shields and inter-phase barriers b Locking by padlock b b

    by keylock b b Front panel escutcheons b b

    Compact NS MasterpactNS630b to NS1600 NT06 to 16 NW08 to 63N / H / L N1 / H1 / H2 / H3 / L1 N1 / H1 / H2 / H3 / L1NA NA / HA / HF NA / HA / HFall devices all mixing possibilities all mixing possibilitiesNS630b to 1600 (fixed, drawout or fixed + drawout) (fixed, drawout or fixed + drawout) N/H/L/NA N1/H1/H2/H3/L1/NA/HA/HF N1/H1/H2/H3/L1/NA/HA/HFfixed or plug-in

    250 to 1600 A 600 to 1600 A 800 to 6300 A750 1000 1000

    b b 3, 4

    See page A-14-25 C to +70 C (50 C for 440 V - 60 Hz)

    48 to 415 V - 50/60 Hz 440 V - 60 Hz

    24-250 V 24-250 V 24-250 V180 VA 180 VA 180 VA180 W 180 W 180 W800 ms 800 ms 800 ms

    b b b b only with UA or BA only with UA or BA

    1 OF + 1 CE (+ SDE) 1 OF + 1 CE + 1 PF 1 OF + 1 CE + 1 PF

    b b b b b b b b b b b b b b b

    b b b b b b b b b

    b b

    2 OF + SD 2 OF + SD 2 OF + SD b b b b b b

    b b b b b b b b

    b BA controller b UA controller

    b b b

    b b b b b b b b b

    b (vertical or horizontal) b (vertical or horizontal) b (vertical or horizontal) b (drawout) b (drawout) b (drawout)

    b

    b b b b b b b b b b

    General characteristics Compact NS, Masterpact NT/NW

    313E.indb 13 09/04/2013 13:04:26

  • A-14

    Functions and characteristics

    Compact INS switch-disconnectorsINS250-100 INS250-160 INS250-200 INS250

    Number of poles 3, 4 3, 4 3, 4 3, 4Conventional thermal current (A) lth at 60 C 100 160 200 250Rated operational current (A) Ie Electrical AC, 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A

    440-480 V 100 100 160 160 200 200 250 250660-690 V 100 100 160 160 200 200 250 250

    Durability (category A) (ON-CR-OR-CN cycles)

    Mechanical 15000 15000 15000 15000Electrical AC, 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A

    440-480 V 1500 1500 1500 1500 1500 1500 1500 1500660-690 V 1500 1500 1500 1500 1500 1500 1500 1500

    INS320 INS400 INS500 INS630Number of poles 3, 4 3, 4 3, 4 3, 4Conventional thermal current (A) lth at 60 C 320 400 500 630Rated operational current (A) Ie Electrical AC, 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A

    440-480 V 320 320 400 400 500 500 630 630660-690 V 320 320 400 400 500 500 630 630

    Durability (category A) (ON-CR-OR-CN cycles)

    Mechanical 10000 10000 10000 10000Electrical AC, 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A

    440-480 V 1500 1500 1500 1500 1500 1500 1500 1500660-690 V 1500 1500 1500 1500 1500 1500 1500 1500

    Compact NSX100-630, Compact NS630b-1600NSX100-250 NSX400-630 NS630b-

    NS1600Number of poles 3, 4 3, 4 3, 4Rated current In (A) 100 to 250 400 to 630 630 to 1600Mechanical durability (ON-CR-OR-CN cycles)

    20000 - 40000 - 50000

    15000 8000

    Electrical durability at In (ON-CR-OR-CN cycles) for y 440 V and 480 V NEMA (2)

    10000 - 20000 - 30000

    4000 - 6000 2000

    Electrical durability at In (ON-CR-OR-CN cycles) for U = 500 V to 690 V (2)

    5000 - 7500 - 10000 2000 - 3000 1500

    Masterpact NT06-NT16/NW08-NW63 (1)NT06-NT10

    NT12-NT16

    NW08-NW16

    NW20 NW25-NW40

    NW50-NW63

    Number of poles 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4Rated current In (A) 630 to

    16001250 to 1600

    800 to 1600

    2000 2500 to 4000

    5000 to 6300

    Mechanical durability (ON-CR-OR-CN cycles)

    8000 8000 10000 10000 10000 5000

    Electrical durability at In (ON-CR-OR-CN cycles) for y 440 V and 480 V NEMA (2)

    6000 6000 NT16: 3000

    10000 8000 5000 1500

    Electrical durability at In (ON-CR-OR-CN cycles) for U = 500 V to 690 V (2)

    3000 2000NT16: 1000

    10000 6000 2500 1500

    (1) Mechanical and electrical durability not applicable to Masterpact H3 and L versions.(2) Electrical durability tests carried out with a power factor of 0.8 as per IEC 947-2.Note: ON: opening of Normal source CR: closing of Replacement source OR: opening of Replacement source CN: closing of Normal source

    Remote-operated source-changeover systems Mech. and elect. durability Compact INS, Compact NSX, NS, Masterpact NT/NW

    313E.indb 14 09/04/2013 13:04:26

  • A-15

    1

    2

    3

    4

    DB

    4135

    68.e

    ps Downstream coupling accessoryThis accessory simplifies connection to bars and cables with lugs.It may be used to couple two circuit breakers (Compact NSX100 to 630) or switch-disconnectors (Compact INS/INV100 to 630) of the same size.Pitch between outgoing terminals:

    b Compact INS250 and INV100 to 250: 35 mm b Compact INS/INV320 to 630: 45 mm b Compact NSX100 to 250: 35 mm b Compact NSX400 to 630: 45 mm.

    For Compact NSX circuit breakers, the downstream coupling accessory can be used only with fixed versions.

    Connection and insulation accessoriesThe coupling accessory can be fitted with the same connection and insulation accessories as the circuit breakers and switch-disconnectors.

    Possible uses Downstream couplingPossible mounting

    Outgoing pitch (mm)

    Manual source-changeover systemsINS250 (100 to 250 A) with rotary handle b 35NSX100/250 with rotary handle b 35NSX100/250 on base plate with toggle control b 35INS400/630 (320 to 630 A) with rotary handle b 45NSX400/630 with rotary handle b 45

    1 Short terminal shields2 Terminals3 Interphase barriers4 Long terminal shields

    NSX400/630 on base plate with toggle control b 45Complete source-changeover assembly

    INS250 (100 to 250 A) b 35INS400/630 (320 to 630 A) b 45Remote-operated source-changeover systems

    NSX100/250 b 35NSX400/630 b 45

    Connection and insulation accessories for Compact NSX and INS y 630 A

    313E.indb 15 09/04/2013 13:04:27

  • A-16

    Functions and characteristics

    Electrical interlocking is used with a mechanical interlocking system. An automatic controller may be added to take into account information from the distribution system.

    Morover, the relays controlling the closing order to the Normal and Replacement circuit-breakers must be mechanically and/or electrically interlocked to prevent them from giving simultaneous closing commands.

    Electrical interlocking is carried out by an electrical control device.For Compact NSX up to 630 A, electrical interlocking is implemented by the IVE unit integrating control circuits and an external terminal block in accordance with the pages C-5 to C-4 of the chapter Electric diagrams of this catalogue. The integrated control circuits implement the time delays required for correct source transfer.For Compact NS630b to 1600 and Masterpact, this function can be implemented in one of two ways:

    b using the IVE unit b by an electrician based on the diagrams in accordance with the pages C-9 to C-14

    of the chapter Electric diagrams of this catalogue.

    Characteristics of the IVE unit b External connection terminal block: v inputs: circuit breaker control signals v outputs: status of the SDE contacts on the Normal and Replacement source

    circuit breakers. b 2 connectors for the two Normal and Replacement source circuit breakers: v inputs:

    - status of the OF contacts on each circuit breaker (ON or OFF) - status of the SDE contacts on the Normal and Replacement source circuit breakers

    v outputs: power supply for operating mechanisms. b Control voltage: v 24 to 250 V DC v 48 to 415 V 50/60 Hz - 440 V 60 Hz.

    The IVE unit control voltage must be same as that of the circuit breaker operating mechanisms.

    Db1

    0157

    3.ep

    s

    IVE unit.

    Necessary equipmentFor Compact NSX100 to 630, each circuit breaker must be equipped with:

    b a motor mechanism b an OF contact b an SDE contact.

    The components are supplied ready for assembly and the circuit breakers prewired. The prewiring must not be modified.

    For Compact NS630b to 1600, each circuit breaker must be equipped with: b a motor mechanism b an available OF contact b a CE connected-position contact (carriage switch) on withdrawable circuit breakers b an SDE contact.

    For Masterpact NT and NW, each circuit breaker must be equipped with: b a remote-operation system made up of: v MCH gear motor v MX or MN opening release v XF closing release v PF ready to close contact b an available OF contact b one to three CE connected-position contacts (carriage switches) on drawout

    circuit breakers (depending on the installation).

    Remote-operated source-changeover systemsElectrical interlocking

    313E.indb 16 09/04/2013 13:04:27

  • A-17

    Compact NS, Masterpact NT and NW Types of mechanical interlocking Possible combinations Typical electrical diagrams Diagram no.2 devices

    Db1

    0157

    4.ep

    s QN QR Compact NSX100 to 630:0 0 b electrical interlocking without emergency

    power off (EPO) auxiliaries: 512011771 0 v with EPO by MN 512011780 1 v with EPO by MX 51201179

    Compact NS630b to 1600: b electrical interlocking with lockout after fault: v permanent replacement source (with IVE) 51201183 v with EPO by MX (with IVE) 51201184 v with EPO by MN (with IVE) 51201185

    Masterpact NT and NW: b electrical interlocking with lockout after fault: v permanent replacement source (with IVE) 51201142 v with EPO by MX (with IVE) 51201143 v with EPO by MN (with IVE) 51201144 b automatic control with lockout after fault: v permanent replacement source (with IVE) 51156904 v engine generator set (with IVE) 51156905 b BA/UA controller (with IVE) 51156903

    Masterpact NW onlyTypes of mechanical interlocking Possible combinations Typical electrical diagrams Diagram no.3 devices: 2 Normal sources and 1 Replacement source

    Db1

    0157

    5.ep

    s QN1 QN2 QR b electrical interlocking:0 0 0 v without lockout after fault 511569061 1 0 v with lockout after fault 511569070 0 1

    3 devices: 2 Normal sources and 1 Replacement source with source selection

    Db1

    0157

    6.ep

    s QN1 QN2 QR b automatic control with engine generator set:0 0 0 v without lockout after fault (with MN) 511569081 0 0 v with lockout after fault (with MN) 511569090 0 11 1 00 1 0

    3 devices: 3 sources, only one device

    Db1

    0157

    7.ep

    s QS1 QS2 QS3 b electrical interlocking:0 0 0 v without lockout after fault 511569101 0 0 v with lockout after fault 511569110 1 00 0 1

    3 devices: 2 sources + 1 coupling

    Db1

    0157

    8.ep

    s QS1 QC QS2 b electrical interlocking:0 0 0 v without lockout after fault 511569121 0 1 v with lockout after fault 511569131 1 0 b automatic control with lockout after fault 511569140 1 11 0 0 (1)

    0 0 1 (1)

    (1) possible by forcing operation

    Lockout after fault option. This option makes it necessary to manually reset the device following fault tripping.

    Standard configurations

    313E.indb 17 09/04/2013 13:04:28

  • A-18

    Functions and characteristics

    By combining a remote-operated source-changeover system with an integrated BA or UA automatic controller, it is possible to automatically control source transfer according to user-selected sequences.These controllers can be used on source-changeover systems comprising 2 circuit breakers.For source-changeover systems comprising 3 circuit breakers, the automatic control diagram must be prepared by the installer as a complement to to diagrams provided in the electrical diagrams section of this catalogue.

    Controller BA UACompatible circuit breakers All Compact NS,

    Compact NSX and Masterpact circuit breakers

    4-position switchAutomatic operation b b Forced operation on Normal source b b Forced operation on Replacement source b b Stop (both Normal and Replacement sources off) b b Automatic operation

    Monitoring of the Normal source and automatic transfer b b Generator set startup control b Delayed shutdown (adjustable) of generator set b Load shedding and reconnection of non-priority circuits b Transfer to the Replacement source if one of the phases of the Normal phase is absent

    b

    TestBy opening the P25M circuit breaker supplying the controller b

    DB

    4038

    09.e

    ps By pressing the test button on the front of the controller b Indications

    Circuit breaker status indication on the front of the controller: on, off, fault trip

    b b

    Automatic mode indicating contact b b Other functions

    Selection of type of Normal source (single-phase or three-phase) (1)

    b

    Voluntary transfer to Replacement source (e.g. energy management commands)

    b b

    During peak-tariff periods (energy management commands) forced operation on Normal sourceif Replacement source not operational

    b

    Additional contact (not part of controller). Transfer to Replacement source only if contact is closed (e.g. used to test the frequency of UR).

    b b

    BA controller. Setting of maximum startup time for the replacement source b Options

    DB

    4038

    10.e

    ps Communication optionPower supply

    Control voltages (2) 110 V b b 220 to 240 V 50/60 Hz b b 380 to 415 V 50/60 Hz and 440 V 60 Hz

    b b

    Operating thresholdsUndervoltage 0.35 Un y voltage y 0.7 Un b b Phase failure 0.5 Un y voltage y 0.7 Un b Voltage presence voltage u 0.85 Un b b IP degree of protection (EN 60529) and IK degree of protection against external mechanical impacts (EN 50102)

    Front IP40 b b Side IP30 b b Connectors IP20 b b

    UA controller. Front IK07 b b Characteristics of output contacts (dry, volt-free contacts)

    Rated thermal current (A) 8Minimum load 10 mA at 12 VOutput contacts:Position of the Auto/Stop switch b b Load shedding and reconnection order b Generator set start order. b

    AC DCUtilisation category (IEC 947-5-1) AC12 AC13 AC14 AC15 DC12 DC13Operational current (A) 24 V 8 7 5 5 8 2

    48 V 8 7 5 5 2 -110 V 8 6 4 4 0.6 -220/240 V 8 6 4 3 - -250 V - - - - 0.4 -380/415 V 5 - - - - -440 V 4 - - - - -660/690 V - - - - - -

    (1) For example, 220 V single-phase or 220 V three-phase.(2) The controller is powered by the ACP control plate. The same voltage must be used for the ACP plate, the IVE unit and the circuit breaker operating mechanisms. If this voltage is the same as the source voltage, then the Normal and Replacement sources can be used directly for the power supply. If not, an isolation transformer must be used.

    Associated controllersController selection

    313E.indb 18 09/04/2013 13:04:28

  • A-19

    PB

    1008

    57_S

    E.e

    ps ACP control plateThe control plate provides in a single unit:

    b protection for the BA or UA controller with two highly limiting P25M circuit breakers (infinite breaking capacity) for power drawn from the AC source

    b control of circuit-breaker ON and OFF functions via two relay contactors b connection of the circuit breakers to the BA or UA controller via a built-in terminal

    block.Control voltages

    b 110 V 50/60 Hz. b 220 to 240 V 50/60 Hz. b 380 to 415 V 50/60 Hz and 440 V 60 Hz.

    The same voltage must be used for the ACP control plate, the controller and the circuit breaker operating mechanisms.InstallationConnection between the ACP control plate and the IVE unit may use:

    b wiring done by the installer b prefabricated wiring (optional).

    Installation of the BA and UA controllersThe BA and UA controllers may be installed in one of two manners:

    b directly mounted on the ACP control plate b mounted on the front panel of the switchboard b if the length of the connection between the controller and the control plate (ACP) is

    less than or equal to 1 m, the connecting cable ref. 29368 can be ordered as an optional extra. Cables longer than 1 m, but not longer than 2 m will be the responsibility of the installer.

    ACP control plate.

    DB

    1262

    69.e

    ps

    Mounting on the ACP control plate.

    DB

    1262

    70.e

    ps

    Mounting on the front panel of the switchboard.

    Controller installation

    313E.indb 19 09/04/2013 13:04:29

  • A-20

    Functions and characteristics

    The BA controller is used to create simple source-changeover systems that switch from one source to another depending on the presence of voltage UN on the Normal source.It is generally used to manage two permanent sources and can control Compact NS, Compact NSX and Masterpact NT/NW circuit breakers and switch-disconnectors.

    Operating modesA four-position switch may be used to select:

    b automatic operation b forced operation on the Normal source b forced operation on the Replacement source b stop (both Normal and Replacement sources off).

    Setting the time delaysTime delays are set on the front of the controller.t1. delay between detection that the Normal source has failed and the transmission of the order to open the Normal source circuit breaker (adjustable from 0.1 to 30 seconds).t2. delay between detection that the Normal source has returned and the transmission of the order to open the Replacement source circuit breaker (adjustable from 0.1 to 240 seconds).

    Circuit breaker commands and status indicationsThe status of the circuit breakers is indicated on the front of the controller.

    b ON, OFF, fault.A built-in terminal block may be used to connect the following input/output signals:

    b inputs: v voluntary order to transfer to source R (e.g. for special tariffs, etc.) v additional control contact (not part of the controller). Transfer to the Replacement

    source takes place only if the contact is closed (e.g. used to test the frequency of UR, etc.)

    b outputs: v indication of operation in automatic or stop mode via changeover contacts.

    TestIt is possible to test the operation of the BA controller by turning OFF (opening) the P25M circuit breaker for the Normal source and thus simulating a failure of voltage UN.

    DB

    4038

    41.e

    ps

    BA Controller

    DB

    4038

    38.e

    ps

    Front of the BA controller.

    Associated controllersBA controller

    313E.indb 20 09/04/2013 13:04:29

  • A-21

    Switch set to Auto (automatic operation and special-tariff mode) Switch set to the N position (forced operation on the Normal source)

    DB

    1265

    47.e

    ps

    DB

    1265

    48.e

    ps

    Switch set to the R position (forced operation on the Replacement source)

    Switch set to the Stop position

    DB

    1265

    49.e

    ps

    DB

    1265

    50.e

    ps

    KeyUN : Normal source voltageUR : Replacement source voltageN : Normal source circuit breakerR : Replacement source circuit breaker

    WAITING The system exits this mode when the operating mode is modified or when an external event occurs (e.g. failure or return of UN).

    The number sends to the indicated step when the condition is true.

    BA controller Operating sequences

    11

    313E.indb 21 09/04/2013 13:04:30

  • A-22

    Functions and characteristics

    The UA controller is used to create a source-changeover system integrating the following automatic functions:b transfer from one source to another depending on the presence of voltage UN on the Normal sourceb startup of an engine generator setb shedding and reconnection of non-priority circuitsb transfer to the Replacement source if one of the phases on the Normal source fails.The UA controller can control Compact NS, Compact NSX and Masterpact NT/NW devices.

    Operating modesA four-position switch may be used to select:

    b automatic operation b forced operation on the Normal source b forced operation on the Replacement source b stop (both Normal and Replacement sources off, then manual operation).

    Setting the time delaysTime delays are set on the front of the controller.t1. delay between detection that the Normal source has failed and the transmission of the order to open the Normal source circuit breaker (adjustable from 0.1 to 30 seconds).t2. delay between detection that the Normal source has returned and the transmission of the order to open the Replacement source circuit breaker (adjustable from 0.1 to 240 seconds).t3. delay following opening of QN with load shedding and before closing of QR (adjustable from 0.5 to 30 seconds).t4. delay following opening of QR with load reconnection and before closing of QN (adjustable from 0.5 to 30 seconds).t5. delay for confirmation that UN is present before shutting down the engine generator set (adjustable from 60 to 600 seconds).t6. delay before startup of the engine generator set (120 or 180 seconds).

    Commands and indicationsCircuit breaker status indications on the front of the controller:

    b ON, OFF, fault.A built-in terminal block may be used to connect the following input/output signals:

    b inputs: v voluntary order to transfer to source R (e.g. for special tariffs, etc.) v additional control contact (not part of the controller). Transfer to the Replacement

    source takes place only if the contact is closed (e.g. used to test the frequency of UR, etc.)

    b outputs: v control of an engine generator set (ON / OFF) v shedding of non-priority circuits v indication of operation in automatic mode via changeover contacts.

    Distribution-system settingsThree switches are used to:

    b select the type of Normal source, whether single-phase or three-phase (e.g. 240 V single-phase or 240 V three-phase)

    b select whether to remain (or not) on the Normal source if the Replacement source is not operational during operation on special tariffs

    b select the maximum permissible startup time for the engine generator set during operation on special tariffs (120 or 180 seconds).

    TestA pushbutton on the front of the controller may be used to test transfer from the Normal source to the Replacement source, then the return to the Normal source. The test lasts approximately three minutes.

    COM communications optionUsing the internal bus protocol, this option may be used to remote the following information:

    b circuit breaker status (ON, OFF, fault trip) b presence of the Normal and Replacement voltages b presence of an order for forced operation (e.g. special tariffs) b settings and configuration information b status of non-priority circuits (loads shed or not)

    b position of the switch (stop, auto, forced operation on the Normal source, forced operation on the Replacement source).

    DB

    4038

    42.e

    ps

    UA Controller

    DB

    4038

    37.e

    ps

    Front of the UA controller.

    Associated controllersUA controller

    313E.indb 22 09/04/2013 13:04:31

  • A-23

    Switch set to the R position (forced operation on the Replacement source) Switch set to the N position (forced operation on the Normal source)

    DB

    1265

    51.e

    ps

    DB

    1265

    52.e

    ps

    Switch set to the Stop position

    DB

    1265

    53.e

    ps

    WAITING The system exits this mode when the operating mode is modified or when an external event occurs (e.g. failure or return of UN).

    When the UA controller is not energised, the output for generator set startup is activated).

    KeyUN : Normal source voltageUR : Replacement source voltageN : Normal source circuit breakerR : Replacement source circuit breaker

    UA controller Operating sequences Forced operation mode

    313E.indb 23 09/04/2013 13:04:32

  • A-24

    Functions and characteristics

    Switch set to the Auto position (special-tariff mode)

    WAITING The system exits this mode when the operating mode is modified or when an external event occurs (e.g. failure or return of UN).

    When the UA controller is not energised, the output for generator set startup is activated).

    KeyUN : Normal source voltageUR : Replacement source voltageN : Normal source circuit breakerR : Replacement source circuit breakerB : Penalties accepted (N ON), i.e. B = 1

    1 The number sends to the indicated step when the condition is true.

    Associated controllersUA controllerOperating sequences Special-tariff mode

    DB

    1265

    54.e

    ps

    313E.indb 24 09/04/2013 13:04:32

  • A-25

    Switch set to the Auto position (automatic operation and test mode).

    DB

    1265

    55.e

    ps

    WAITING The system exits this mode when the operating mode is modified or when an external event occurs (e.g. failure or return of UN).

    When the UA controller is not energised, the output for generator set startup is activated).

    KeyUN : Normal source voltageUR : Replacement source voltageN : Normal source circuit breakerR : Replacement source circuit breaker B : Penalties accepted (N ON), i.e. B = 1(*) The test lasts 180 seconds.

    1 The number sends to the indicated step when the condition is true.

    UA controllerOperating sequences Test mode and automatic operation

    313E.indb 25 09/04/2013 13:04:33

  • A-26

    Functions and characteristics

    IVE unit

    Db1

    2659

    4.ep

    s

    SymbolsQN : Normal Compact circuit breaker equipped for remote operation (motor mechanism)QR : Replacement Compact circuit breaker equipped for remote operation (motor mechanism)ON : Circuit breaker QN opening orderOR : Circuit breaker QR opening orderIN : Circuit breaker QN closing orderIR : Circuit breaker QR closing orderL1 : Faulty Normal indication LEDL2 : Faulty Replacement indication LED

    KeyO: OFF (circuit open)I: ON (circuit closed

    : either ON or OFF.

    Note: following all trips (overload, short-circuit, earth-leakage fault, voluntary trip), a manual reset on the front of the motor mechanism is required.

    Operating sequences IVE unit

    313E.indb 26 09/04/2013 13:04:33

  • A-27

    BA controller

    Db1

    2659

    5.ep

    s

    InputsUN : Normal source voltageUR : Replacement source voltageKT : order for forced-operation on RKR : additional check before transfer

    OutputsQN : Normal source circuit breakerQR : Replacement source circuit breaker

    UA controller

    Db1

    2659

    9.ep

    s

    InputsUN : Normal source voltageUR : Replacement source voltageKT : order for forced-operation on RKR : additional check before transfer

    OutputsKG : order to the gensetSH : load-shedding orderQN : Normal source circuit breakerQR : Replacement source circuit breaker

    KeyO: OFF (circuit open)I: ON (circuit closed

    : either ON or OFF.

    ImportantIf UR is not ON when the transfer order is issued (KT or UN), the sequence is not carried out.If KR status is not ON when the transfer order is issued (KT or UN), the transfer sequence is carried out later when KR status becomes I.

    BA/UA controller

    313E.indb 27 09/04/2013 13:04:33

  • A-28

    Functions and characteristics

    RS 232, Ethernet

    RS 485

    DC150 dataconcentrator

    Communication interface

    Communication bus

    Devices

    MasterpactIVE MasterpactR

    N

    960019200

    JBus

    N1

    N2

    BBus

    5

    13

    913 7

    155

    13

    913 7

    15

    error24V

    OK

    error

    com. com.

    N1 N2

    DC150

    N

    Electrical-installation management

    DB

    4041

    57.e

    ps Communications option for Compact NS u 630 A and Masterpact NT/NWThe COM communications option is compatible with all the source-changeover systems for Compact NS630b-1600 and Masterpact NT/NW circuit breakers and switch-disconnectors.It can be used to remote status information. It may not be used to operate the circuit breakers (only possible locally on the front of the UA150 controller).Masterpact and Compact NS630b to 1600 circuit breakers and switch-disconnectors are compatible with the Modbus ECO COM option.Depending on the trip units or control units used, the COM option may also be used to analyse distribution-system parameters required for the operating and maintenance assistance.

    Circuit breaker communicationSwitch-disconnector

    Circuit breaker

    Compact NS630b-1600 status indicationsON / OFF b b Fault trip b Connected / disconnected position b b Masterpact NT/NW status indications

    ON / OFF b b Fault trip b Connected / disconnected position b b

    Operating and maintenance assistanceOperating and maintenance aids Modbus

    MeasurementCurrent A E P HVoltages, power... E P HFrequency P HPower quality: fundamental, harmonics HProgramming of demand metering E P HFault readingsType of fault A E P HInterrupted current P HWaveform captureOn faults HOn demand or programmed HHistories and logsTrip history E P HAlarm history P HEvent logs P HIndicatorsCounter operation A E P HContact wear P HMaintenance register P HNote: see the description of the Micrologic control units for further details on protection and alarms, measurements, waveform capture, histories, logs and maintenance indicators.

    COM communications option

    313E.indb 28 09/04/2013 13:04:36

  • A-29

    Controller UA150Status indications

    Normal sourceON / OFF b Circuit breaker ON b Fault trip (SDE) b Voltage presence b Replacement sourceCircuit breaker ON b Fault trip (SDE) b Voltage presence b Status of R voltage contact b ControllerAutomatic mode b Normal mode b Replacement mode b Stop mode b Testing b Replacement engine generator setGenset failure b Genset OFF b Genset ON b Shedding of non-priority circuits b Reconnection of non-priority circuits b Settings

    Time delay t1 for validation of UN absence b Time delay t2 for validation of UN return b Time delay t3 for wait between opening of N and closing of R b Time delay t4 for wait between opening of R and closing of N b Time delay t5 for wait between return of UN and order for genset shutdown b Time delay t6 for wait before declaring genset failure b Penalties accepted to avoid special tariff transfer b

    960019200

    JBus

    N1

    N2

    BBus

    5

    13

    913 7

    155

    13

    913 7

    15

    error24V

    OK

    error

    com. com.

    N1 N2

    DC150

    N

    DB

    4040

    74.e

    ps DC150 data concentratorThe DC150 data concentrator is designed to centralise the information provided by the communicating switchgear of the Digipact range and to make this information accessible to a supervisor or PLC under the MODBUS/JBUS protocol.

    Main characteristics b Power supply:

    110 V AC to 240 V AC115 V DC to 125 V DC.

    b Weight: 1.5 kg. b Installation: on panel with the DC150 box which must be earthed on metal part of

    the installation. b Over dimensions H x W x D (mm): 138.5 x 100 x 192.8.

    COM communications option

    313E.indb 29 09/04/2013 13:04:37

  • This international site allows you to access all the Schneider Electric Solution and Product information via :

    pcomprehensive descriptions p range data sheets pa download area pproduct selectors p ...

    You can also access the information dedicated to your business and get in touch with your Schneider Electric country support.

    schneider-electric.com

    TOOLS

    181E6100.indd 12 09/04/2013 14:06:21

  • B-1

    Source-changeover systems Compact NSX100-630, Compact NS630b-1600, Compact INS/INV, Masterpact

    Dimensions

    Presentation 2Functions and characteristics A-1

    Manual source-changeover systems Interlocking of direct rotary handles B-2Interlocking of extended rotary handles B-3Interlocking of toggles B-5Complete source-changeover assembly B-6Downstream coupling accessory B-7

    Remote-operated source-changeover systems Interlocking on a base plate B-9Interlocking using connecting rods B-13Interlocking using cables B-15IVE unit, BA and UA automatic controllers B-20

    Electrical diagrams C-1Catalogue numbers and order forms D-1

    313E.indb 1 09/04/2013 13:04:37

  • B-2

    Dimensions

    Compact NSX100 to 630Dimensions Front-panel cutout

    DB

    1266

    07.e

    ps

    DB

    1266

    08.e

    ps

    DB

    4044

    83.e

    ps

    Dimensions (mm) Type A B C D F G H J K L M N P

    NSX100/160/250 325 90 87.5 175 156 133 9.25 9 295 75.5 150 75 155NSX400/630 416 115 100 200 210 157 5 24.6 386 100 175 74.5 179

    Compact INS/INV250 - 100 to 250 / Compact INS/INV320/400/500/630Dimensions Front-panel cutout

    Db1

    0160

    9.ep

    s

    Db1

    0161

    0.ep

    s

    Db1

    0161

    1.ep

    s

    Dimensions (mm) Type A B C D F G H K L M N P

    INS/INV250 - 100/160/200/250 325 90 87.5 175 156 106 17.5 295 75.5 150 75 131INS/INV320/400/500/630 416 115 100 200 210 130 22.5 386 100 175 74.5 160.4Note: X and Y are the symmetry planes for a 3-pole device.

    Manual source-changeover systems Interlocking of direct rotary handles

    313E.indb 2 09/04/2013 13:04:38

  • B-3

    Compact NSX100 to 630Dimensions Front-panel cutout

    DB

    1266

    10.e

    ps

    DB

    1266

    08.e

    ps

    DB

    4044

    82.e

    ps

    Dimensions (mm) Type A B C D F G min G max H J P Q

    NSX100/160/250 325 90 87.5 175 156 171 600 9.25 9 25.5 25.5NSX400/630 416 115 100 200 210 195 600 5 24.6 30.8 30.8

    Compact INS40/63/80/100/125/160 / Compact INS/INV250 - 100 to 250 / Compact INS/INV320/400/500/630Dimensions Front-panel cutout

    Db1

    0161

    4.ep

    s

    Db1

    0161

    5.ep

    s

    Db1

    0775

    6.ep

    s

    Dimensions (mm) Type A B C D F G min G max H P Q

    INS40/63/80 325 90 87.5 175 156 155 396 0 25.5 25.5INS100/125/160 325 90 87.5 175 156 200 441 0 25.5 25.5INS/INV250 - 100/160/200/250 325 90 87.5 175 156 185 600 17.5 25.5 25.5INS320/400/500/630 416 115 100 200 210 204 600 22.5 30.8 30.8

    Interlocking of extended rotary handles

    313E.indb 3 09/04/2013 13:04:39

  • B-4

    Compact NS630b to 1600Dimensions

    Db1

    0161

    7.ep

    s

    DB

    1016

    18.e

    ps

    Front-panel cutout

    Db1

    0161

    9.ep

    s

    Dimensions (mm) Type A B C D F G min G max H J P Q R

    NS630b/800/1000/1200/1600 411 63.5 98 175 280 218 605 25 24 25.5 25.5 64

    Manual source-changeover systemsInterlocking of extended rotary handles

    Dimensions

    313E.indb 4 09/04/2013 13:04:39

  • B-5

    Compact NSX100 to 630Dimensions 3 poles 4 poles

    DB

    1266

    12.E

    PS

    DB

    1266

    13.E

    PS

    DB

    1266

    14.E

    PS

    Front-panel cutout 3 poles on left 4 poles on left

    Db1

    0162

    3.ep

    s

    Db1

    0162

    4.ep

    s

    Dimensions (mm) Type C2 C3 L L16 L17 L18 R2 R18 R19 P5 P

    NSX100/160/250 54 108 52.5 140 245 280 54 89 140 83 120NSX400/630 92.5 182 70 185 325 370 71.5 116.5 185 107 150

    Interlocking of toggles

    313E.indb 5 09/04/2013 13:04:40

  • B-6

    Assembly for INS250 - 100 to 250 / Assembly for INS320/400/500/630Dimensions

    Db1

    0162

    5.ep

    s

    Db1

    0162

    6.ep

    s

    Front-panel cutout

    Db1

    0162

    7.ep

    s

    Dimensions (mm) Type A B C D E F G H I J K L M N

    INS250 - 100/160/200/250 60.4 130.4 296 68 136 131 61.8 279.3 42 84 156 186.5 5.5 50INS320/400/500/630 82.5 175 395 102.5 205 155 87 383.7 64 128 210 213 8 50

    Dimensions of the complete source-changeover assembly with an extended handle

    Db1

    0165

    0.ep

    s

    Db1

    0165

    1.ep

    s

    DB

    1077

    43.e

    ps Dimensions (mm) Type A B C E K L M N

    INS250 - 100/160/200/250 60.4 130.4 295 136 156 138.5 631 50INS320/400/500/630 82.5 175 395 205 210 162.5 658 75

    Dimensions (mm) Type P Mmax Mmin Q

    INS250 - 100/160/200/250 100 567.5 195 64INS320/400/500/630 150 593 220.5 64

    Note: lines X and Y indicate the axes of symmetry of the switch-disconnector. Reference plane Z corresponds to the back of the switch-disconnector.

    Manual source-changeover systemsComplete source-changeover assembly

    Dimensions

    313E.indb 6 09/04/2013 13:04:41

  • B-7

    Compact NSX100 to NSX630 (only for Compact NSX fixed devices)Dimensions

    DB

    4132

    82.e

    ps

    DB

    4132

    79.e

    ps

    Dimensions Connection

    DB

    4132

    80.e

    ps

    = = = =

    = =

    DB

    4135

    69.e

    ps

    Dimensions (mm) Type G2 G3 G28 G29 G30 G52 K1 K2 K3 K4 K8 K9 K16

    NSX100/160/250 118 181.5 244.5 96 152.5 178 35 35 51 156 70 170 8NSX400/630 165.9 264.7 337.5 143.5 220.5 264.7 45 45 75 210 113.5 250.7 15

    Dimensions (mm) Type L28 L29 L30 L31 L32 L33 L34 L35 L36 L37 L39 L40 T

    NSX100/160/250 320 99.5 300 89.5 4.73 130.5 139.5 74.5 19.5 87.5 9.5 140 6NSX400/630 425 130 400 117.5 5.15 175.3 184.7 98.5 26 115 9.85 184.7 6

    Note: coupling accessory: only for changeover systems using fixed versions of Compact NSX circuit breakers.

    Downstream coupling accessory

    313E.indb 7 09/04/2013 13:04:42

  • B-8

    Compact INS250 - 100 to 250 / Compact INS320/400/500/630Dimensions

    DB

    4132

    86.e

    ps

    DB

    4132

    83.e

    ps

    DB

    4135

    67.e

    ps

    Dimensions Connection

    DB

    4132

    84.e

    ps

    = = = =

    = =

    DB

    4135

    70.e

    ps

    Dimensions (mm) Type G2 G3 G28 G29 G30 G52 K1 K2 K3 K4 K8 K9 K16

    INS250-100/160/200/250 105.5 169 232 83.5 140 165.5 35 35 51 156 57.5 157.5 25.5INS320/400/500/630 141 240.7 313 119 195.6 240 45 45 75 210 88.5 225.7 37.5

    Dimensions (mm) Type L28 L29 L30 L31 L32 L33 L34 L35 L36 L37 L39 L40 T

    INS250-100/160/200/250 320 83 300 72 12.8 130.5 139.5 74.5 21.5 70 8.5 140 6INS320/400/500/630 425 107.5 400 95 17.35 175.3 184.7 98.5 26 92.5 12.65 184.7 6

    Manual source-changeover systemsDownstream coupling accessory

    Dimensions

    313E.indb 8 09/04/2013 13:04:43

  • B-9

    Compact NSX100 to 250Dimensions, 3 or 4 poles Fixed device Withdrawable device

    DB

    4132

    87.e

    ps

    DB

    4132

    88.e

    ps

    DB

    1266

    19.E

    PS

    (*) Short terminal shields are mandatory.

    Vertical mounting Horizontal mounting

    Db1

    0163

    7.ep

    s

    Db1

    0163

    8.ep

    s

    Dimensions (mm) Type G50 G51 H20 H21 H22 H23 H42 H43 H44 H45 H46 K25 K35 K36

    NSX100/160/250 137.5 285 62.5 97 45.5 73 60 120 144.5 300 37 156 210.5 300NSX400/630 180 360 100 152 83 123 60 120 189 378 77 210 282.5 400

    Dimensions (mm) Type L31 L32 P7 P8 P9 P32 P33 P50 P52 P54 T9 T10 U

    NSX100/160/250 110.5 354 25 45 75 182 143 25 99.5 21 9 6 y 32NSX400/630 150.5 466 25 45 100 256 215 25 123 21 9 6 y 32

    Note: coupling accessory: only for changeover systems using fixed versions of Compact NSX circuit breakers.

    Remote-operated source-changeover systemsInterlocking on a base plate

    313E.indb 9 09/04/2013 13:04:44

  • B-10

    Compact NSX400 to 630Dimensions, 3 or 4 poles Fixed device

    DB

    4132

    89.e

    ps

    DB

    4132

    90.e

    ps

    Withdrawable device

    Note: coupling accessory: only for changeover systems using fixed versions of Compact NSX circuit breakers.

    DB

    1266

    22.E

    PS

    (*) Short terminal shields are mandatory.

    DimensionsVertical mounting Horizontal mounting

    Db1

    0163

    7.ep

    s

    Db1

    0163

    8.ep

    s

    Note: dimensions see page B-9.

    Remote-operated source-changeover systemsInterlocking on a base plate

    Dimensions

    313E.indb 10 09/04/2013 13:04:45

  • B-11

    Normal and Replacement source devices: NSX100 to NSX250Dimensions Front-panel cutout

    177145

    DB

    4132

    91.e

    ps

    NSX100to

    NSX250

    NSX100to

    NSX250

    77

    9595

    156

    47.5 47.5

    29.5

    DB

    4041

    34.e

    ps

    Normal and Replacement source devices: NSX400 to NSX630 Dimensions Front-panel cutout

    249217

    DB

    4133

    00.e

    ps

    NSX400to

    NSX630

    12763.5

    127

    127

    42

    210

    63.5

    NSX400to

    NSX630

    DB

    4041

    35.e

    ps

    Note for Compact NSX:For dimensions with the accessories (IP40 escutcheons and Vigi escutcheon protection collars), see Catalogue Compact.

    313E.indb 11 09/04/2013 13:04:46

  • B-12

    NSX400 to NSX630 as the Normal device, NSX100 to NSX250 as the Replacement deviceDimensions Front-panel cutout

    DB

    1266

    23.E

    PS

    NSX400to

    NSX630

    NSX100to

    NSX250

    DB

    4041

    36.e

    ps

    Remote-operated source-changeover systemsInterlocking on a base plate

    Dimensions

    313E.indb 12 09/04/2013 13:04:47

  • B-13

    Two Compact NS630b to NS1600 devices one above the otherFixed devices Withdrawable devices

    DB

    1077

    47.e

    ps

    Db1

    0165

    5.ep

    s

    Two Masterpact NT devices one above the other Fixed devices Withdrawable devices

    Db1

    0165

    6.ep

    s

    Db1

    0165

    5.ep

    s

    Interlocking using connecting rods

    313E.indb 13 09/04/2013 13:04:47

  • B-14

    Two Masterpact NW devices one above the otherFixed devices Withdrawable devices

    DB

    1077

    48.e

    ps

    DB

    1077

    49.e

    ps

    Remote-operated source-changeover systems Interlocking using connecting rods

    Dimensions

    313E.indb 14 09/04/2013 13:04:47

  • B-15

    Two Compact NS630b to NS1600 devices side-by-sideFixed devices Withdrawable devices

    Db1

    0166

    1.ep

    s

    Db1

    0166

    2.ep

    s

    Two Masterpact NT devices side-by-side Fixed devices Drawout devices

    Db1

    0166

    3.ep

    s

    Db1

    0166

    2.ep

    s

    Combination of two Masterpact NT and NW devices side-by-side Fixed devices Drawout devices

    Db1

    0166

    4.ep

    s

    DB

    4041

    47.e

    ps

    Interlocking using cables

    313E.indb 15 09/04/2013 13:04:48

  • B-16

    Two Masterpact NW devices side-by-sideFixed devices Drawout devices

    Db1

    0166

    6.ep

    s

    Db1

    0166

    7.ep

    s

    Three Masterpact NW devices side-by-side Fixed devices

    Db1

    0166

    8.ep

    s

    Drawout devices

    Db1

    0166

    9.ep

    sRemote-operated source-changeover systemsInterlocking using cables

    Dimensions

    313E.indb 16 09/04/2013 13:04:49

  • B-17

    Two Compact NS630b to NS1600 devices one above the otherFixed devices Withdrawable devices

    DB

    1077

    50.e

    ps

    Db1

    0167

    1.ep

    s

    Two Masterpact NT devices one above the other Fixed devices Drawout devices

    Db1

    0167

    2.ep

    s

    Db1

    0167

    1.ep

    s

    313E.indb 17 09/04/2013 13:04:49

  • B-18

    Two Masterpact NW devices one above the otherFixed devices Drawout devices

    DB

    1077

    51.e

    ps

    DB

    1077

    52.e

    ps

    Two Masterpact NT and NW devices one above the otherFixed devices Drawout devices

    DB

    1077

    53.e

    ps

    DB

    4041

    48.e

    ps

    Remote-operated source-changeover systemsInterlocking using cables

    Dimensions

    313E.indb 18 09/04/2013 13:04:50

  • B-19

    Three Masterpact NW devices one above the otherFixed devices Drawout devices

    DB

    1077

    54.e

    ps

    DB

    1077

    55.e

    ps

    Remote-operated source-changeover systemsInterlocking using cables

    Dimensions

    313E.indb 19 09/04/2013 13:04:50

  • B-20

    IVE unit

    Db1

    0167

    9.ep

    s

    Db1

    0167

    8.ep

    s

    ACP control plate and BA/UA controllers Door cutout for BA/UA controllers

    Db1

    0168

    0.ep

    s

    Db1

    0168

    1.ep

    s

    Db1

    0168

    2.ep

    s

    DB

    1016

    83.e

    ps

    (1) Cutout according DIN 43700 standard.

    Remote-operated source-changeover systemsIVE unit, BA and UA automatic controllers

    Dimensions

    313E.indb 20 09/04/2013 13:04:51

  • C-1

    Source-changeover systems Compact NSX100-630, Compact NS630b-1600, Compact INS/INV, Masterpact

    Presentation 2Functions and characteristics A-1Dimensions B-1

    Remote-operated source-changeover systems 2 Compact NSX100/630 devices C-22 Compact NSX100/630, NS630b/1600 or Masterpact NT/NW devices C-5

    Source-changeover systems with automatic controllers 2 Compact NSX100/630, NS630b/1600 or Masterpact NT/NW devices C-6Controller settings C-72 Compact NSX100/630, NS630b/1600 or Masterpact NT/NW devices C-8

    Remote-operated source-changeover systems 2 Compact NS630b/1600 devices C-92 Masterpact NT or NW devices C-123 Masterpact NW devices C-17

    Source-changeover systems with automatic controllers 2 Masterpact NT or NW devices C-26

    Catalogue numbers and order forms D-1

    Electrical diagrams

    313E.indb 1 09/04/2013 13:04:51

  • C-2

    Source-changeover system without automatic-control systemWithout auxiliaries for emergency off Local reset

    Db4

    0180

    5.ep

    s

    Db1

    0165

    9.ep

    s

    Voluntary remote reset

    Db1

    0166

    0.ep

    s

    Automatic reset

    (1) Prefabricated wiring: cannot be modified.

    LegendsQN Normal source Compact NSX equipped with motor mechanismQR Replacement source Compact NSX equipped with motor

    mechanismSDE fault-trip indication contactIVE electrical interlocking and terminal block unitMT motor mechanismOF2 breaker ON/OFF indication contactRN reset order for breaker QNRR reset order for breaker QR

    States permitted by mechanical interlocking systemNormal Replacement0 01 00 1Note: diagram shown with circuits de-energised, circuit breakers open and relays in normal position.

    Remote-operated source-changeover systems2 Compact NSX100/630 devicesDiagram no. 51201177

    Electrical diagrams

    313E.indb 2 09/04/2013 13:04:52

  • C-3

    Electrical diagrams

    Source-changeover system without automatic-control systemWith emergency off by MN release and automatic reset

    KA5 KA5

    KA5KA5

    DB

    4151

    14.e

    ps

    Automatic reset

    (1) Prefabricated wiring supplied.(2) Independent auxiliary source.

    LegendsQN Normal source Compact NSX equipped with

    motormechanismQR Replacement source Compact NSX equipped with motor

    mechanismMN undervoltage releaseOF2 breaker ON/OFF indication contactSDE fault-trip indication contactMT motor mechanismIVE electrical interlocking and terminal block unitBP emergency off button with latchingKA5 auxiliary relayF1 auxiliary power supply circuit breaker

    States permitted by mechanical interlocking systemNormal Replacement0 01 00 1Note: after a fault trip, the breaker must be reset manually by pressing its reset button. Diagram shown with circuits de-energised, circuit breakers open and relays in normal position.

    Remote-operated source-changeover systems 2 Compact NSX100/630 devicesDiagram no. 51201178

    313E.indb 3 09/04/2013 13:04:53

  • C-4

    Source-changeover system without automatic-control systemWith emergency off by MX release and automatic reset

    DB

    4151

    15.e

    ps

    Automatic reset

    (1) Prefabricated wiring supplied(2) This source can be: b the source present in the case of voltage monitoring b an independent source.

    In this case, the MX release must be