Low Voltage
Catalogue2013
313E0100.indd 1 15/04/2013 10:38:33
-
313E0100.indd 2 15/04/2013 10:38:34
-
IEfficient energy management and continuity of service with source-changeover systemTo ensure continuity of service for critical applications, LV electrical installations need to be connected to at least two independent power sources:
* The replacement source (R) can be: a second power source (with possibly different characteristics from the normal source) or an electrical generator
1 A normal source (N)
2And a replacement
source (R)*used to supply energy to the installation when the normal source unavailable, or, for instance, when its quality and/or availability is no longer guaranteed.
The source-changeover
system switches the load (partly or fully) between these two sources.
A few basics on source-changeover systems> A source-changeover system can be automated to manage transfers according to external conditions.
> Switching from a main power source to a replacement source can be performed either manually or automatically.
> A source-changeover system comprises circuit breakers, switch-disconnectors or contactors.
313E.indb 1 09/04/2013 13:04:06
-
II
to switch the load to meet your needs
Automatic source-changeover system(or ATSE: Automatic Transfer Switching Equipment)
An automatic controller may be added to a remote-operated source-changeover system. It is possible to automatically control source transfer according to programmed (dedicated controllers) or programmable (PLC) operating modes. These solutions ensure optimum energy management.
3
ApplicationsCommercial and service sector (operating rooms in hospitals, safety systems for buildings, computer rooms for banks and insurance companies, lighting and emergency lighting systems in malls, etc.), industry and infrastructure.
System2 or 3 circuit breakers that may have different configurations, linked by an electrical interlocking system. A mechanical interlocking system protects against electrical malfunctions or incorrect manual operations, with an automatic control system (dedicated controllers or PLC).
1 Manual source-changeover system (or MTSE: Manual Transfer Switching Equipment)The simplest way to switch the load. It is controlled manually by an operator. The time required to switch from the N source to R source can vary.
ApplicationsBuildings and infrastructure where the need for continuity of service is significant but not a priority: offices, small and medium-sized businesses.
System2 or 3 mechanically interlocked manually-operated circuit breakers or 2 switch-disconnectors.
3ways
Remote-operated source-changeover system(or RTSE: Remote Transfer Switching Equipment)
The most commonly used system for devices with high ratings. No direct human intervention is required. Source-changeover is controlled electrically.
2
System2 or 3 circuit breakers that may have different configurations, linked by an electrical interlocking system. In addition, a mechanical interlocking system protects against electrical malfunctions or incorrect manual operations.
ApplicationsIndustry (assembly lines, engine rooms on ships, critical auxiliaries in thermal powerstations, etc.); Infrastructure (port and railway installations, runway lighting systems, control systems on military sites, etc.).
313E.indb 2 09/04/2013 13:04:06
-
III
> MTSE range
Compact INSFrom 40 A to 630 A
> RTSE range
Compact NSX From 100 A to 630 A
Masterpact NT / NW From 630 A to 6300 A
Whatever the system, you benefit from our expertise!
Our expertise and support come together with the source-changeover system you choose for your LV electrical installation.With Compact INS, Compact NSX and Masterpact NT and NW, we offer a complete range of solutions, designed around key values:
Maximum continuity of service> Energy availability is ensured whatever
the external requirements (e.g. high power demand).
> Maintenance and replacement of the sources (N or R) can be done with no interruption of service.
You can maintain a continuous level of service and customer satisfaction.
Optimized energy management> Transfer the load to a replacement source
according to external requirements.> Manage power sources according to power
quality and power costs.> Perform system regulation.> Switch to an emergency replacement source.You are no longer dependent on your power supply (and supplier)!
Simplicity and reliability> Simple installation on LV switchboard.> Optimized size of the switchboard.> System based on pre-tested components.> Compliance with IEC 60947-6-1.
Maximum safetyFor LV electrical installations where safety and continuity of service are critical for people and/or equipment such as hospitals, airports, banks, malls, etc.
> ATSE range
UA Controller Compact NSX From 100 A to 630 A
313E.indb 3 09/04/2013 13:04:07
-
IV
A source-changeover system is indispensable for applications that need a continuous supply of electric power (hospitals, airports, banks, government facilities, etc.). But a source-changeover system is also suitable for all LV electrical installations exposed to:> Nominal voltage loss or dip (when there is high demand for electric power)> Unpredictable power quality> Frequent power cuts.
For critical applications in particularFor all others in general
These factors, and many others, can damage the continuity of service of your electrical installation.For infrastructure managers, a source-changeover system gives direct economic benefi ts: it is possible to select your source based on power cost. In this case, the replacement source (R) is used as an alternative, more economical source.
Managing energy ef cientlyPower CostSafety
313E.indb 4 09/04/2013 13:04:11
-
1Source-changeover systems Compact NSX100-630, Compact NS630b-1600, Compact INS/INV, Masterpact
General content
Presentation 2
Functions and characteristics A-1
Dimensions B-1
Electrical diagrams C-1
Catalogue numbers and order forms
D-1
313E.indb 1 09/04/2013 13:04:11
-
Presentation For maximum continuity of service...
Incoming feeders and main LV switchboards1 normal source 1 replacement source
2 sources with coupler on busbars
2 normal sources1 replacement source
Db1
0153
8.ep
s
Db1
0153
9.ep
s
Db1
0154
0.ep
s
QN QR QS1 QC QS2 QN1 QN2 QR0 0 0 0 0 0 0 01 0 1 0 1 1 1 0
CurrentsFrom 630 to 6300 A.
0 1 1 1 0 0 0 10 1 1 1 0 01 0 0 (1) 0 1 00 0 1 (1)
(1) possible by forcing operation.
Power distribution
PD
3903
85_S
E_R
_35.
eps Generator or permanent
source
Db1
0154
1.ep
s QN QR Typical applications: b continuous production processes b operating rooms b computer rooms...
0 01 00 1
CurrentsFrom 250 to 3200 A.
Loads
PB
1115
56.e
ps Generator or permanent source
Generator or permanent source
Db1
0154
1.ep
s
Db1
0154
4.ep
s QN QR Typical applications: b large electrical installations (e.g. airports) b refrigeration units b special electricity tariffs b pumping stations...
0 01 00 1
CurrentsFrom 40 to 400 A.
Db1
0154
3.ep
s
PB
1051
09.e
ps
2
313E.indb 2 09/04/2013 13:04:13
-
Incoming feeders and main LV switchboards1 normal source 1 replacement source
2 sources with coupler on busbars
2 normal sources1 replacement source
Db1
0153
8.ep
s
Db1
0153
9.ep
s
Db1
0154
0.ep
s
QN QR QS1 QC QS2 QN1 QN2 QR0 0 0 0 0 0 0 01 0 1 0 1 1 1 0
CurrentsFrom 630 to 6300 A.
0 1 1 1 0 0 0 10 1 1 1 0 01 0 0 (1) 0 1 00 0 1 (1)
(1) possible by forcing operation.
Power distribution
PD
3903
85_S
E_R
_35.
eps Generator or permanent
source
Db1
0154
1.ep
s QN QR Typical applications: b continuous production processes b operating rooms b computer rooms...
0 01 00 1
CurrentsFrom 250 to 3200 A.
Loads
PB
1115
56.e
ps Generator or permanent source
Generator or permanent source
Db1
0154
1.ep
s
Db1
0154
4.ep
s QN QR Typical applications: b large electrical installations (e.g. airports) b refrigeration units b special electricity tariffs b pumping stations...
0 01 00 1
CurrentsFrom 40 to 400 A.
... in a wide range of applications
3
313E.indb 3 09/04/2013 13:04:14
-
Ecodial software is dedicated to LV electrical installation calculation in accordance with the IEC60364 international standard or national standards.
This 4th generation, "Ecodial Advance Calculation 4", offers a new ergonomic and new features:
p operating mode that allows easy calculation in case of installation with different type of sources (parallel transformers, back-up generators)
p discrimination analysis associating curves checking and discrimination tables
p direct access to protection settings including residual current protections
p easy selection of alternate solutions or manual selection of a product.
Ecodial
TOOLS
181E6000.indd 4 09/04/2013 14:05:54
-
A-1
Source-changeover systems Compact NSX100-630, Compact NS630b-1600, Compact INS/INV, Masterpact
Functions and characteristics
Presentation 2
Overview of solutions Manual source-changeover systems Compact INS/INV 40 to 630 A, Compact NSX100/630 A-2Manual source-changeover systems Compact NS and Masterpact NT/NW 630 A to 6300 A A-3Remote-operated source-changeover systems Compact NSX100/630, Compact NS630b/1600 A A-4Remote-operated source-changeover systems Masterpact NT/NW 630 A to 6300 A A-5
Manual source-changeover systems Possible combinations A-6
Remote-operated source-changeover systems Mechanical interlocking Compact NSX, Compact NS or Masterpact NT/NW A-10Mechanical interlocking Compact NS or Masterpact NT/NW A-11General characteristics Compact NSX A-12General characteristics Compact NS, Masterpact NT/NW A-13Mech. and elect. durability A-14Connection and insulation accessories for Compact NSX and INS y 630 A A-15Electrical interlocking A-16Standard configurations A-17
Associated controllers Controller selection A-18Controller installation A-19BA controller A-20BA controller, Operating sequences A-21UA controller A-22UA controller, Operating sequences, Forced operation mode A-23UA controller, Operating sequences, Special-tariff mode A-24UA controller, Operating sequences , Test mode and automatic operation A-25
Operating sequences IVE unit A-26BA/UA controller A-27
COM communications option A-28
Dimensions B-1Electrical diagrams C-1Catalogue numbers and order forms D-1
313E.indb 1 09/04/2013 13:04:14
-
Functions and characteristics
Range Compact CompactModels INS40 to INS80
INS100 to INS160INS250 to INS630INV250 to INV630
NSX100 to NSX250NSX400 to NSX630
Rating (A) 40 to 160 100 to 630 100 to 630Type of device Switch-disconnectors with
extended handlesSwitch-disconnectors N/H/L circuit breakers
NA switch-disconnectors
Manual source-changeover systemsInterlocking via toggles
DB
1265
89.e
ps
Db1
0154
5.ep
s
2 devices side-by-side. 3 devices side-by-side.
Interlocking via rotary handles
DB
1265
90.e
ps
N
2.4
Db1
0154
6.ep
s
Db1
0154
7.ep
s
ONI
OOFF
ONI
OOFF
Db1
0154
8.ep
s
2 devices side-by-side.
Interlocking via keylocks with captive keys
DB
1265
88.e
ps
Db1
0154
9.ep
s
Db1
0155
0.ep
s
A number of different devices.
Interlocking on a base plate
DB
1265
87.e
ps
Db1
0155
1.ep
s
2 devices side-by-side.
Complete source-changeover assemblies
DB
1265
86.e
ps
DB
4041
70.e
ps
2 devices side-by-side.
Overview of solutionsManual source-changeover systems Compact INS/INV 40 to 630 A, Compact NSX100/630
A-2
313E.indb 2 09/04/2013 13:04:16
-
Range Compact MasterpactModels NS630b to NS1600 NT06 to NT16 NW08 to NW63Rating (A) 630 to 1600 630 to 1600 800 to 6300 Type of device N/H/L circuit breakers
NA switch-disconnectorsH1/L1 circuit breakersHA switch-disconnectors
N1/H1/H2/H3/L1 circuit breakersNA/HA/HF switch-disconnectors
Manual source-changeover systemsInterlocking via extended rotary handles
DB
1265
90.e
ps
Db1
0155
3.ep
s
2 devices side-by-side.
Interlocking via keylocks with captive keys
DB
1265
88.e
ps
Db1
0155
4.ep
s
Opush O
FF
Ipush O
N
O OFFdischa
rged
Opush O
FF
Ipush O
N
O OFFdischa
rged
Db1
0155
5.ep
s
Db1
0155
6.ep
s
A number of different devices.
Mechanical interlocking using connecting rods
DB
1265
85.e
ps
OpushO
FF
IpushO
N
OOFFdischa
rged
OpushO
FF
IpushO
N
OOFFdischa
rged
Db1
0155
7.ep
s
(1)
Db1
0155
8.ep
s
Db1
0155
9.ep
s
2 devices one above the other.
Mechanical interlocking using cables
DB
1265
84.e
ps
Db1
0156
0.ep
s
(1)
(2)
Db1
0156
1.ep
s
Db1
0156
2.ep
s
2 or 3 devices one above the other.
DB
1265
83.e
ps
2 or 3 devices side-by-side.For this case and other cases, please consult us
DB
1265
80.e
ps
(1) Implemented with NS630b to NS1600 electrically-operated devices only.(2) For source-changeover systems using cables, always respect the installation conditions specified on page A-13.
Manual source-changeover systems Compact NS and Masterpact NT/NW 630 A to 6300 A
A-3
313E.indb 3 09/04/2013 13:04:19
-
Functions and characteristics
Range CompactModels NSX100 to NSX630 NS630b to NS1600Rating (A) 100 to 630 630 to 1600Type of device N/H/L circuit breakers
NA switch-disconnectorsN/H/L circuit breakersNA switch-disconnectors
Remote-operated source-changeover systemMechanical interlocking on base plate + electrical interlocking
DB
1265
87.e
ps
Db1
0156
3.ep
s
2 electrically-operated devices side-by-side combined with an electrical interlocking system.
Mechanical interlocking using connecting rods + electrical interlocking
DB
1265
85.e
ps
OpushO
FF
IpushO
N
OOFFdischa
rged
OpushO
FF
IpushO
N
OOFFdischa
rged
Db1
0155
7.ep
s
2 electrically-operated devices one above the other combined with an electrical interlocking system.
Mechanical interlocking using cables + electrical interlocking
DB
1265
81.e
ps
Db1
0156
0.ep
s
(1)
2 electrically-operated devices one above the other combined with an electrical interlocking system.
DB
1265
82.e
ps
2 electrically-operated devices side-by-side combined with an electrical interlocking system.
Automatic source-changeover systemsRemote-operated source-changeover system combined with an automatic-control system
DB
1265
81.e
ps The automatic controller operates the devices depending on external parameters.
BA: Simple controller that manages the changeover function.
UA: Controller that also manages engine generator sets.
UA150: UA controller with a communication option.
DB
4044
39.e
ps
BA controller
DB
1265
82.e
ps
DB
4044
40.e
ps
UA and UA150 controller
(1) For source-changeover systems using cables, always respect the installation conditions specified on page A-13.
Overview of solutionsRemote-operated source-changeover systems Compact NSX100/630, Compact NS630b/1600 A
A-4
313E.indb 4 09/04/2013 13:04:20
-
Range MasterpactModels NT06 to NT16 NW08 to NW63Rating (A) 630 to 1600 800 to 6300 Type of device H1/L1 circuit breakers
HA switch-disconnectorsN1/H1/H2/H3/L1 circuit breakersNA/HA/HF switch-disconnectors
Remote-operated source-changeover systemMechanical interlocking using connecting rods + electrical interlocking
DB
1265
85.e
ps
Db1
0155
8.ep
s
Db1
0155
9.ep
s
2 electrically-operated devices side-by-side combined with an electrical interlocking system.
Mechanical interlocking using cables + electrical interlocking
DB
1265
84.e
ps
Db1
0156
1.ep
s
Db1
0156
2.ep
s
2 or 3 electrically-operated devices one above the other combined with an electrical interlocking system (1).
DB
1265
83.e
ps
2 or 3 electrically-operated devices side-by-side combined with an electrical interlocking system (1).
(2)
Automatic source-changeover systemsRemote-operated source-changeover system combined with an automatic-control system
DB
1265
81.e
ps The automatic controller operates the devices depending on external parameters.
BA: Simple controller that manages the changeover function.
UA: Controller that also manages engine generator sets.
UA150: UA controller with a communication option.
DB
4044
39.e
ps
BA controller
DB
1265
82.e
ps
DB
4044
40.e
ps
UA and UA150 controller
(1) Three devices with Masterpact NW only.(2) For source-changeover systems using cables, always respect the installation conditions specified on page A-13. For other cases, please consult us.
Remote-operated source-changeover systems Masterpact NT/NW 630 A to 6300 A
A-5
313E.indb 5 09/04/2013 13:04:21
-
Functions and characteristics
A manual source-changeover system can be installed on two or three manually-operated and mechanically interlocked circuit breakers or switch-disconnectors.Interlocks prevent connection to both sources at the same time, even momentarily.
All possibilities for manual source-changeover systems
Type of device Type of interlocking for two devicesComplete assembly
Keylock Direct rotary handle
Extended rotary handle
Compact switch-disconnectors
INS40 to INS160 b
INS250-100 to INS630 b b b r b r
INV100 to 630 b b r b r r
INS/INV630b to 2500 b Legend:r Possible but visible break function disabled.r 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system.
Type of device Type of interlocking for two devicesToggle Keylock Direct rotary
handleExtended rotary handle
On base plate (toggle or direct extended rotary control)
On base plate (motor mechanism)
Compact fixed or withdrawable circuit breakers
NSX100 to 250 b b b b p b b b b b b b b b b
NSX400 to NS630 b b b b p b b b b b b b b b b
NSX100 to 630 b b p b b p b b p b b b p b b b p
NS630b to 1600 with rotary handle
b b p b b b b
Legend:b Fixed devices only.b Fixed or withdrawable devices.b Devices must be either both fixed or both withdrawable.p With NSX400/630 rotary handle interlocking system.p Possible with NSX400/630 base plate + NSX100-250 adaptation kit.p Devices equipped with rotary handles.
Type of device Type of interlocking for either all fixed or all withdrawable devicesKeylock Cable-type,
2 devices side-by-side
Cable-type, 3 devices side-by-side
Cable-type, 2 devices one above the other
Cable-type, 3 devices one above another
Rod-type, 3 devices one above another
Compact fixed or withdrawable circuit breakers or swith-disconnectors, with motor mechanism NS630b to 1600 b b b bMasterpact fixed or withdrawable circuit breakers or swith-disconnectors, manual operation or with motor mechanism
NT06 to 16 b b b b
NW08 to 63 b b b b b b
NT06 to NW63 b b b
Manual source-changeover systemsPossible combinations
A-6
313E.indb 6 09/04/2013 13:04:21
-
Complete source-changeover assembly for two switch-disconnectorsAll possibilities for manual source-changeover systems
DB
4041
70.e
ps These assemblies provide an easy way to implement source changeover functions with:
b a single 3-position rotary handle that controls the two switch-disconnectors (Normal source ON, OFF, Replacement source ON)
b a smaller size, taking up less room in the switchboard.A complete source changeover assembly can be ordered with a single catalogue number.
Normal N Replacement RINS250-100 INS250-160 INS200-200 INS250-250 INS320 INS400 INS500 INS630
INS250-100Ratings 100 A b INS250-160Ratings 160 A b INS200-200Ratings 200 A b INS250-250Ratings 250 A b INS320Ratings 320 A b INS400Ratings 400 A b INS500Ratings 500 A b INS630Ratings 630 A b
Interlocking of two or three toggle-controlled devicesPossible combinations of Normal and Replacement source circuit breakers
Db1
0156
6.ep
s Two devices can be interlocked using this system. Two identical interlocking systems can be used to interlock three devices installed side by side, in which case one device is in the ON position and the two others are in the OFF position. Devices must all have the same configuration, i.e. fixed, plug-in, withdrawable or drawout.The system is locked using one or two padlocks (shackle diameter 5 to 8 mm).Two interlocking system models are available for:
b Compact NSX100 to 250 b Compact NSX400 to 630.
Normal N Replacement RNSX100 NSX160 NSX250 NSX400 NSX630
NSX100Ratings 16... 100 A b b b b b NSX160Ratings 80...160 A b b b b b NSX250Ratings 125...250 A b b b b b NSX400Ratings 150... 400 A b b b b b NSX630Ratings 630 A b b b b b
Possible combinations
A-7
313E.indb 7 09/04/2013 13:04:21
-
Functions and characteristics
Interlocking of a number of devices using keylocks (captive keys)Combination of Normal and Replacement devices
Db1
0156
9.ep
s All Compact and Masterpact circuit breakers and Compact switch-disconnectors from 100 to 6300 A with rotary handles or motor mechanisms can be interlocked.
Interlocking is based on two identical keylocks with a single key and a keylock adapter (different for each device). This solution enables interlocking between two devices that are physically distant or that have very different characteristics, for example between a low and a medium-voltage device, or between Compact NSX circuit breakers and switch-disconnectors.A system of wall-mounted captive key boxes makes possible a large number of combinations between many devices.
Interlocking of two devices with rotary handlesPossible combinations of Normal and Replacement source circuit breakers
ONI
OOFF
ONI
OOFF
Db1
0156
8.ep
s The direct or extended rotary handles are padlocked with the devices in the OFF position. The mechanism prevents simultaneous closing of the devices, but allows them to be opened.
Normal N Replacement RCompact NSX100/630 (1) NSX100 NSX160 NSX250 NSX400 NSX630NSX100Ratings 16... 100 A b b b v v NSX160Ratings 80...160 A b b b v v NSX250Ratings 125...250 A b b b v v NSX400Ratings 160... 400 A v v v b b NSX630Ratings 630 A v v v b b v 250 A and 630 A ratings can be mixed by using NSX400/630 rotary handle interlocking
system.
Normal N Replacement RCompact NS630b/1600 (1) NS630b NS800 NS1000 NS1200 NS1600NS630bRatings 250... 630 A b b b b b NS800Ratings 320... 800 A b b b b b NS1000Ratings 400... 1000 A b b b b b NS1200Ratings 480... 1200 A b b b b b NS1600Ratings 640... 1600 A b b b b b
(1) When mixing NSX100/250 and NSX400/630 circuit breakers, use the NSX400/630 interlocking system.
Manual source-changeover systemsPossible combinations
A-8
313E.indb 8 09/04/2013 13:04:22
-
Interlocking of two devices with rotary handlesPossible combinations of Normal and Replacement source switch-disconnectors
DB
1077
42.e
ps The direct or extended rotary handles are padlocked with the devices in the OFF position. The mechanism prevents simultaneous closing of the devices, but allows them to be opened.
Normal N Replacement RCompact INS (1) INS40 INS63 INS80 INS100 INS125 INS160INS40Ratings 40 A b b b b b b INS63Ratings 63 A b b b b b b INS80Ratings 80 A b b b b b b INS100Ratings 100 A b b b b b b INS125Ratings 125 A b b b b b b INS160Ratings 160 A b b b b b b
(1) With extended rotary handles only.(2) Possible with INV, but visible-break function is significantly impaired.
Normal N Replacement RCompact INS /INV (2) INS250-100/
INV100INS250-160/INV160
INS250-200/INV200
INS250-250/INV250
INS320/INV320
INS400/INV400
INS500/INV500
INS630/INV630
INS250-100/INV100Ratings 100 A b b b b v v v INS250-160/INV160Ratings 160 A b b b b INS250-200/INV200Ratings 200 A b b b b INS250-250/INV250Ratings 250 A b b b b v v INS320/INV320Ratings 320 A v v b b b b INS400/INV400Ratings 400 A b b b b INS500/INV500Ratings 500 A b b b b INS630/INV630 Ratings 630 A v v b b b b v 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system.
Interlocking of two devices on a base platePossible combinations of Compact NSX Normal and Replacement source circuit breakers
DB
4148
91.e
ps A base plate is available for mechanical interlocking of two manually-operated Compact NSX100 to 630 circuit breakers or switch-disconnectors.Normal N Replacement R
NSX100 NSX160 NSX250 NSX400 NSX630NSX100Ratings 16... 100 A b b b b b NSX160Ratings 80... 160 A b b b b b NSX250Ratings 125... 250 A b b b b b NSX400Ratings 150... 400 A b b b b b NSX630Ratings 630 A b b b b b
Interlocking of a number of devices using keylocks (captive keys)Combination of Masterpact devices
Db1
0190
3.ep
s Interlocking uses two identical keylocks with a single key. This solution enables interlocking between two devices that are physically distant or that have significantly different characteristics.
Possible combinations
A-9
313E.indb 9 09/04/2013 13:04:23
-
A-10
Functions and characteristics
Mechanical interlocking of two or three devices is used to create a remote-operated source-changeover system. A basic mechanical interlocking system enhances the reliability of system operation.
Interlocking of two Compact NSX100 to 630 devices using a base plateA base plate designed for two Compact circuit breakers can be installed horizontally or vertically on a mounting rail. Interlocking is carried out on the base plate by a mechanism located behind the breakers. Access to the circuit breaker controls and trip units is conserved. Circuit breakers must be fixed or plug-in versions, with or without earth-leakage protection or measurement modules. The base plate and the circuit breakers are supplied separately.
b Base plate for Compact NSX100 to 250 devicesThis base plate is intended for two Compact NSX100 to 250 devices.
b Base plate for Compact NSX400 to 630 devicesThis base plate is intended for two Compact NSX400 to 630 devices. It may also be used, without any modifications, to interlock a fixed Compact NSX100 to 250 with a Compact NSX400 or 630 device.An adapter kit is required for plug-in versions of the Compact NSX100 to 250 devices.Compact NSX100 to 250 devices, in both fixed and plug-in versions, may be equipped with spreaders.
PB
1051
06_5
0.ep
s
Possible combinations of Normal and Replacement Compact NSX source circuit breakers
Interlocking of two electrically-operated Compact NSX circuit breakers using a base plate. Normal N Replacement R
NSX100 NSX160 NSX250 NSX400 NSX630NSX100Ratings 12,5... 100 A b b b b b NSX160Ratings 12,5...160 A b b b b b NSX250Ratings 12,5...250 A b b b b b NSX400Ratings 160... 400 A b b b b b NSX630Ratings 250... 630 A b b b b b
DB
1262
68.e
ps Interlocking of two Compact NS630b to 1600 or two Masterpact NT and NW devices using connecting rodsThe two devices must be mounted one above the other (either 2 fixed or 2 withdrawable/drawout devices).Combinations are possible between Compact NS630b to NS1600 devices and between Masterpact NT and Masterpact NW devices.InstallationThis function requires:
b an adaptation fixture on the right side of each circuit breaker or switch-disconnector
b a set of connecting rods with no-slip adjustments.The adaptation fixtures, connecting rods and circuit breakers or switch-disconnectors are supplied separately, ready for assembly by the customer.The maximum vertical distance between the fixing planes is 900 mm.
Possible combinations of Normal and Replacement source circuit breakers
Normal N Replacement RNS630b to NS1600
NT06 to NT16 NW08 to NW40
NW40b to NW63
NS630b to NS1600Ratings 250... 1600 A b
Interlocking of two Masterpact NT or NW circuit breakers using connecting rods.
NT06 to NT16Ratings 250... 1600 A b b b NW08 to NW40Ratings 320... 4000 A b b b NW40b to NW63Ratings 4000... 6300 A b b b
Remote-operated source-changeover systems Mechanical interlocking Compact NSX, Compact NS or Masterpact NT/NW
313E.indb 10 09/04/2013 13:04:24
-
A-11
PB
1008
42_6
8_S
E.e
ps Interlocking of two Compact NS630b to 1600 or two Masterpact NT/NW or up to three Masterpact NW devices using cablesFor cable interlocking, the circuit breakers may be mounted one above the other or side-by-side.The interlocked devices may be fixed or drawout, three-pole or four-pole, and have different ratings and sizes.
Interlocking between two devices (Compact NS630b to 1600 or Masterpact NT and NW)This function requires:
b an adaptation fixture on the right side of each device b a set of cables with no-slip adjustments.
The maximum distance between the fixing planes (vertical or horizontal) is 2000 mm.
Interlocking between three devices (Masterpact NW only)This function requires:
b a specific adaptation fixture for each type of interlocking, installed on the right side of each device
b two or three sets of cables with no-slip adjustments.The maximum distance between the fixing planes (vertical or horizontal) is 1000 mm.
InstallationThe adaptation fixtures, sets of cables and circuit breakers or switch-disconnectors are supplied separately, ready for assembly by the customer.Installation conditions for cable interlocking systems:
b cable length: 2.5 m b radius of curvature: 100 mm b maximum number of curves: 3.
Interlocking of two Masterpact circuit breakers using cables.
Possible combinations of Normal and Replacement source circuit breakers
Normal N Replacement RNS630b to NS1600
NT06 to NT16 NW08 to NW40
NW40b to NW63
NS630b to NS1600Ratings 250... 1600 A b NT06 to NT16Ratings 250... 1600 A b b b NW08 to NW40Ratings 320... 4000 A b b b NW40b to NW63Ratings 4000... 6300 A b b b
It is not possible to combine Compact NS630b to 1600 and Masterpact NT (or Masterpact NW) devices.All combinations of two Masterpact NT and Masterpact NW devices are possible, whatever the rating or size of the devices.
Possible combinations of three device
Normal N Replacement RNS630b to NS1600
NT06 to NT16 NW08 to NW40
NW40b to NW63
NS630b to NS1600Ratings 250... 1600 ANT06 to NT16Ratings 250... 1600 ANW08 to NW40Ratings 320... 4000 A b b NW40b to NW63Ratings 4000... 6300 A b b
Only Masterpact NW may be used for three-device combinations.
Types of mechanical interlocking and combinationsSee page A-4 to page A-9.
Mechanical interlocking Compact NS or Masterpact NT/NW
313E.indb 11 09/04/2013 13:04:25
-
A-12
Functions and characteristics
Range Compact NSXTypes of devices NSX100 to NSX250 NSX400 to NSX630Types of circuit breakers N / H / L N / H / LSwitch-disconnector version NA NAMixing possibilities all devices all devices
NS100 to NS250 NS100 to NS630N/H/L/NA N/H/L/NA fixed or plug-in fixed or plug-in
Electrical characteristicsRating 15 to 250 A 15 to 630 AInsulating voltage Ui (V AC) 750 750 Positive break indication b b Number of poles(N and R devices must have the same number of poles)
3, 4
Electrical durability See page A-14Operating temperature -25 C to +70 C (50 C for 440 V - 60 Hz)Control characteristics
Control voltage AC 48 V - 50 Hz 48 V - 50 Hz 110/130, 220/240, 380/440 V - 50/60 Hz 110/130, 220/240, 380/440 V - 50/60 Hz
DC 24-250 V 24-250 VMaximum consumption AC 500 VA 500 VA
DC 500 W 500 WMinimum switching time 800 ms 800 msInterlocking
Mechanical (see page A-10)Electrical by diagram (without IVE) b b
with IVE unit b b auxiliary contacts used by circuit breaker 1 OF + 1 SDE 1 OF + 1 SDE
Protection and measurementOverload protection long time b b Short-circuit protection short time b b
instantaneous b b Earth-fault protection b Zone selective interlocking (ZSI) b Earth-leakage protection by Vigi module b b
by control unit by add-on Vigirex relay b b
Current measurementsVoltage, frequency, power measurements, etc.Indication and control auxiliaries
Available auxiliary indication contacts OF + SD (+ SDV) 3 OF + SD (+ SDV)Voltage releases MX shunt b b
MN undervoltage b b Voltage presence indicator b b Voltage transformer b b Ammeter module b b Insulation monitoring module b b Source-changeover controller
With permanent replacement source b BA controllerWith standby generator set b UA controllerRemote communication via bus
Device status indicationsDevice remote controlTransmission of settings b b Indication and identification of protection status and alarms b b Transmission of measurements b b Installation and connection
Fixed front connectedFixed rear connected b (long rear connections) b (long rear connections)Withdrawable, plug-in or drawout b (plug-in on base) b (plug-in on base)Installation and connection accessories
Downstream coupling accessory b b Bare-cable connectors b b Terminal extensions b b Terminal shields and inter-phase barriers b Locking by padlock b b
by keylock b b Front panel escutcheons b b
Remote-operated source-changeover systems0 General characteristics Compact NSX
Compact NS MasterpactNS630b to NS1600 NT06 to 16 NW08 to 63N / H / L N1 / H1 / H2 / H3 / L1 N1 / H1 / H2 / H3 / L1NA NA / HA / HF NA / HA / HFall devices all mixing possibilities all mixing possibilitiesNS630b to 1600 (fixed, drawout or fixed + drawout) (fixed, drawout or fixed + drawout) N/H/L/NA N1/H1/H2/H3/L1/NA/HA/HF N1/H1/H2/H3/L1/NA/HA/HFfixed or plug-in
250 to 1600 A 600 to 1600 A 800 to 6300 A750 1000 1000
b b 3, 4
See page A-14-25 C to +70 C (50 C for 440 V - 60 Hz)
48 to 415 V - 50/60 Hz 440 V - 60 Hz
24-250 V 24-250 V 24-250 V180 VA 180 VA 180 VA180 W 180 W 180 W800 ms 800 ms 800 ms
b b b b only with UA or BA only with UA or BA
1 OF + 1 CE (+ SDE) 1 OF + 1 CE + 1 PF 1 OF + 1 CE + 1 PF
b b b b b b b b b b b b b b b
b b b b b b b b b
b b
2 OF + SD 2 OF + SD 2 OF + SD b b b b b b
b b b b b b b b
b BA controller b UA controller
b b b
b b b b b b b b b
b (vertical or horizontal) b (vertical or horizontal) b (vertical or horizontal) b (drawout) b (drawout) b (drawout)
b
b b b b b b b b b b
313E.indb 12 09/04/2013 13:04:25
-
A-13
Range Compact NSXTypes of devices NSX100 to NSX250 NSX400 to NSX630Types of circuit breakers N / H / L N / H / LSwitch-disconnector version NA NAMixing possibilities all devices all devices
NS100 to NS250 NS100 to NS630N/H/L/NA N/H/L/NA fixed or plug-in fixed or plug-in
Electrical characteristicsRating 15 to 250 A 15 to 630 AInsulating voltage Ui (V AC) 750 750 Positive break indication b b Number of poles(N and R devices must have the same number of poles)
3, 4
Electrical durability See page A-14Operating temperature -25 C to +70 C (50 C for 440 V - 60 Hz)Control characteristics
Control voltage AC 48 V - 50 Hz 48 V - 50 Hz 110/130, 220/240, 380/440 V - 50/60 Hz 110/130, 220/240, 380/440 V - 50/60 Hz
DC 24-250 V 24-250 VMaximum consumption AC 500 VA 500 VA
DC 500 W 500 WMinimum switching time 800 ms 800 msInterlocking
Mechanical (see page A-10)Electrical by diagram (without IVE) b b
with IVE unit b b auxiliary contacts used by circuit breaker 1 OF + 1 SDE 1 OF + 1 SDE
Protection and measurementOverload protection long time b b Short-circuit protection short time b b
instantaneous b b Earth-fault protection b Zone selective interlocking (ZSI) b Earth-leakage protection by Vigi module b b
by control unit by add-on Vigirex relay b b
Current measurementsVoltage, frequency, power measurements, etc.Indication and control auxiliaries
Available auxiliary indication contacts OF + SD (+ SDV) 3 OF + SD (+ SDV)Voltage releases MX shunt b b
MN undervoltage b b Voltage presence indicator b b Voltage transformer b b Ammeter module b b Insulation monitoring module b b Source-changeover controller
With permanent replacement source b BA controllerWith standby generator set b UA controllerRemote communication via bus
Device status indicationsDevice remote controlTransmission of settings b b Indication and identification of protection status and alarms b b Transmission of measurements b b Installation and connection
Fixed front connectedFixed rear connected b (long rear connections) b (long rear connections)Withdrawable, plug-in or drawout b (plug-in on base) b (plug-in on base)Installation and connection accessories
Downstream coupling accessory b b Bare-cable connectors b b Terminal extensions b b Terminal shields and inter-phase barriers b Locking by padlock b b
by keylock b b Front panel escutcheons b b
Compact NS MasterpactNS630b to NS1600 NT06 to 16 NW08 to 63N / H / L N1 / H1 / H2 / H3 / L1 N1 / H1 / H2 / H3 / L1NA NA / HA / HF NA / HA / HFall devices all mixing possibilities all mixing possibilitiesNS630b to 1600 (fixed, drawout or fixed + drawout) (fixed, drawout or fixed + drawout) N/H/L/NA N1/H1/H2/H3/L1/NA/HA/HF N1/H1/H2/H3/L1/NA/HA/HFfixed or plug-in
250 to 1600 A 600 to 1600 A 800 to 6300 A750 1000 1000
b b 3, 4
See page A-14-25 C to +70 C (50 C for 440 V - 60 Hz)
48 to 415 V - 50/60 Hz 440 V - 60 Hz
24-250 V 24-250 V 24-250 V180 VA 180 VA 180 VA180 W 180 W 180 W800 ms 800 ms 800 ms
b b b b only with UA or BA only with UA or BA
1 OF + 1 CE (+ SDE) 1 OF + 1 CE + 1 PF 1 OF + 1 CE + 1 PF
b b b b b b b b b b b b b b b
b b b b b b b b b
b b
2 OF + SD 2 OF + SD 2 OF + SD b b b b b b
b b b b b b b b
b BA controller b UA controller
b b b
b b b b b b b b b
b (vertical or horizontal) b (vertical or horizontal) b (vertical or horizontal) b (drawout) b (drawout) b (drawout)
b
b b b b b b b b b b
General characteristics Compact NS, Masterpact NT/NW
313E.indb 13 09/04/2013 13:04:26
-
A-14
Functions and characteristics
Compact INS switch-disconnectorsINS250-100 INS250-160 INS250-200 INS250
Number of poles 3, 4 3, 4 3, 4 3, 4Conventional thermal current (A) lth at 60 C 100 160 200 250Rated operational current (A) Ie Electrical AC, 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A
440-480 V 100 100 160 160 200 200 250 250660-690 V 100 100 160 160 200 200 250 250
Durability (category A) (ON-CR-OR-CN cycles)
Mechanical 15000 15000 15000 15000Electrical AC, 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A
440-480 V 1500 1500 1500 1500 1500 1500 1500 1500660-690 V 1500 1500 1500 1500 1500 1500 1500 1500
INS320 INS400 INS500 INS630Number of poles 3, 4 3, 4 3, 4 3, 4Conventional thermal current (A) lth at 60 C 320 400 500 630Rated operational current (A) Ie Electrical AC, 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A
440-480 V 320 320 400 400 500 500 630 630660-690 V 320 320 400 400 500 500 630 630
Durability (category A) (ON-CR-OR-CN cycles)
Mechanical 10000 10000 10000 10000Electrical AC, 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A
440-480 V 1500 1500 1500 1500 1500 1500 1500 1500660-690 V 1500 1500 1500 1500 1500 1500 1500 1500
Compact NSX100-630, Compact NS630b-1600NSX100-250 NSX400-630 NS630b-
NS1600Number of poles 3, 4 3, 4 3, 4Rated current In (A) 100 to 250 400 to 630 630 to 1600Mechanical durability (ON-CR-OR-CN cycles)
20000 - 40000 - 50000
15000 8000
Electrical durability at In (ON-CR-OR-CN cycles) for y 440 V and 480 V NEMA (2)
10000 - 20000 - 30000
4000 - 6000 2000
Electrical durability at In (ON-CR-OR-CN cycles) for U = 500 V to 690 V (2)
5000 - 7500 - 10000 2000 - 3000 1500
Masterpact NT06-NT16/NW08-NW63 (1)NT06-NT10
NT12-NT16
NW08-NW16
NW20 NW25-NW40
NW50-NW63
Number of poles 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4Rated current In (A) 630 to
16001250 to 1600
800 to 1600
2000 2500 to 4000
5000 to 6300
Mechanical durability (ON-CR-OR-CN cycles)
8000 8000 10000 10000 10000 5000
Electrical durability at In (ON-CR-OR-CN cycles) for y 440 V and 480 V NEMA (2)
6000 6000 NT16: 3000
10000 8000 5000 1500
Electrical durability at In (ON-CR-OR-CN cycles) for U = 500 V to 690 V (2)
3000 2000NT16: 1000
10000 6000 2500 1500
(1) Mechanical and electrical durability not applicable to Masterpact H3 and L versions.(2) Electrical durability tests carried out with a power factor of 0.8 as per IEC 947-2.Note: ON: opening of Normal source CR: closing of Replacement source OR: opening of Replacement source CN: closing of Normal source
Remote-operated source-changeover systems Mech. and elect. durability Compact INS, Compact NSX, NS, Masterpact NT/NW
313E.indb 14 09/04/2013 13:04:26
-
A-15
1
2
3
4
DB
4135
68.e
ps Downstream coupling accessoryThis accessory simplifies connection to bars and cables with lugs.It may be used to couple two circuit breakers (Compact NSX100 to 630) or switch-disconnectors (Compact INS/INV100 to 630) of the same size.Pitch between outgoing terminals:
b Compact INS250 and INV100 to 250: 35 mm b Compact INS/INV320 to 630: 45 mm b Compact NSX100 to 250: 35 mm b Compact NSX400 to 630: 45 mm.
For Compact NSX circuit breakers, the downstream coupling accessory can be used only with fixed versions.
Connection and insulation accessoriesThe coupling accessory can be fitted with the same connection and insulation accessories as the circuit breakers and switch-disconnectors.
Possible uses Downstream couplingPossible mounting
Outgoing pitch (mm)
Manual source-changeover systemsINS250 (100 to 250 A) with rotary handle b 35NSX100/250 with rotary handle b 35NSX100/250 on base plate with toggle control b 35INS400/630 (320 to 630 A) with rotary handle b 45NSX400/630 with rotary handle b 45
1 Short terminal shields2 Terminals3 Interphase barriers4 Long terminal shields
NSX400/630 on base plate with toggle control b 45Complete source-changeover assembly
INS250 (100 to 250 A) b 35INS400/630 (320 to 630 A) b 45Remote-operated source-changeover systems
NSX100/250 b 35NSX400/630 b 45
Connection and insulation accessories for Compact NSX and INS y 630 A
313E.indb 15 09/04/2013 13:04:27
-
A-16
Functions and characteristics
Electrical interlocking is used with a mechanical interlocking system. An automatic controller may be added to take into account information from the distribution system.
Morover, the relays controlling the closing order to the Normal and Replacement circuit-breakers must be mechanically and/or electrically interlocked to prevent them from giving simultaneous closing commands.
Electrical interlocking is carried out by an electrical control device.For Compact NSX up to 630 A, electrical interlocking is implemented by the IVE unit integrating control circuits and an external terminal block in accordance with the pages C-5 to C-4 of the chapter Electric diagrams of this catalogue. The integrated control circuits implement the time delays required for correct source transfer.For Compact NS630b to 1600 and Masterpact, this function can be implemented in one of two ways:
b using the IVE unit b by an electrician based on the diagrams in accordance with the pages C-9 to C-14
of the chapter Electric diagrams of this catalogue.
Characteristics of the IVE unit b External connection terminal block: v inputs: circuit breaker control signals v outputs: status of the SDE contacts on the Normal and Replacement source
circuit breakers. b 2 connectors for the two Normal and Replacement source circuit breakers: v inputs:
- status of the OF contacts on each circuit breaker (ON or OFF) - status of the SDE contacts on the Normal and Replacement source circuit breakers
v outputs: power supply for operating mechanisms. b Control voltage: v 24 to 250 V DC v 48 to 415 V 50/60 Hz - 440 V 60 Hz.
The IVE unit control voltage must be same as that of the circuit breaker operating mechanisms.
Db1
0157
3.ep
s
IVE unit.
Necessary equipmentFor Compact NSX100 to 630, each circuit breaker must be equipped with:
b a motor mechanism b an OF contact b an SDE contact.
The components are supplied ready for assembly and the circuit breakers prewired. The prewiring must not be modified.
For Compact NS630b to 1600, each circuit breaker must be equipped with: b a motor mechanism b an available OF contact b a CE connected-position contact (carriage switch) on withdrawable circuit breakers b an SDE contact.
For Masterpact NT and NW, each circuit breaker must be equipped with: b a remote-operation system made up of: v MCH gear motor v MX or MN opening release v XF closing release v PF ready to close contact b an available OF contact b one to three CE connected-position contacts (carriage switches) on drawout
circuit breakers (depending on the installation).
Remote-operated source-changeover systemsElectrical interlocking
313E.indb 16 09/04/2013 13:04:27
-
A-17
Compact NS, Masterpact NT and NW Types of mechanical interlocking Possible combinations Typical electrical diagrams Diagram no.2 devices
Db1
0157
4.ep
s QN QR Compact NSX100 to 630:0 0 b electrical interlocking without emergency
power off (EPO) auxiliaries: 512011771 0 v with EPO by MN 512011780 1 v with EPO by MX 51201179
Compact NS630b to 1600: b electrical interlocking with lockout after fault: v permanent replacement source (with IVE) 51201183 v with EPO by MX (with IVE) 51201184 v with EPO by MN (with IVE) 51201185
Masterpact NT and NW: b electrical interlocking with lockout after fault: v permanent replacement source (with IVE) 51201142 v with EPO by MX (with IVE) 51201143 v with EPO by MN (with IVE) 51201144 b automatic control with lockout after fault: v permanent replacement source (with IVE) 51156904 v engine generator set (with IVE) 51156905 b BA/UA controller (with IVE) 51156903
Masterpact NW onlyTypes of mechanical interlocking Possible combinations Typical electrical diagrams Diagram no.3 devices: 2 Normal sources and 1 Replacement source
Db1
0157
5.ep
s QN1 QN2 QR b electrical interlocking:0 0 0 v without lockout after fault 511569061 1 0 v with lockout after fault 511569070 0 1
3 devices: 2 Normal sources and 1 Replacement source with source selection
Db1
0157
6.ep
s QN1 QN2 QR b automatic control with engine generator set:0 0 0 v without lockout after fault (with MN) 511569081 0 0 v with lockout after fault (with MN) 511569090 0 11 1 00 1 0
3 devices: 3 sources, only one device
Db1
0157
7.ep
s QS1 QS2 QS3 b electrical interlocking:0 0 0 v without lockout after fault 511569101 0 0 v with lockout after fault 511569110 1 00 0 1
3 devices: 2 sources + 1 coupling
Db1
0157
8.ep
s QS1 QC QS2 b electrical interlocking:0 0 0 v without lockout after fault 511569121 0 1 v with lockout after fault 511569131 1 0 b automatic control with lockout after fault 511569140 1 11 0 0 (1)
0 0 1 (1)
(1) possible by forcing operation
Lockout after fault option. This option makes it necessary to manually reset the device following fault tripping.
Standard configurations
313E.indb 17 09/04/2013 13:04:28
-
A-18
Functions and characteristics
By combining a remote-operated source-changeover system with an integrated BA or UA automatic controller, it is possible to automatically control source transfer according to user-selected sequences.These controllers can be used on source-changeover systems comprising 2 circuit breakers.For source-changeover systems comprising 3 circuit breakers, the automatic control diagram must be prepared by the installer as a complement to to diagrams provided in the electrical diagrams section of this catalogue.
Controller BA UACompatible circuit breakers All Compact NS,
Compact NSX and Masterpact circuit breakers
4-position switchAutomatic operation b b Forced operation on Normal source b b Forced operation on Replacement source b b Stop (both Normal and Replacement sources off) b b Automatic operation
Monitoring of the Normal source and automatic transfer b b Generator set startup control b Delayed shutdown (adjustable) of generator set b Load shedding and reconnection of non-priority circuits b Transfer to the Replacement source if one of the phases of the Normal phase is absent
b
TestBy opening the P25M circuit breaker supplying the controller b
DB
4038
09.e
ps By pressing the test button on the front of the controller b Indications
Circuit breaker status indication on the front of the controller: on, off, fault trip
b b
Automatic mode indicating contact b b Other functions
Selection of type of Normal source (single-phase or three-phase) (1)
b
Voluntary transfer to Replacement source (e.g. energy management commands)
b b
During peak-tariff periods (energy management commands) forced operation on Normal sourceif Replacement source not operational
b
Additional contact (not part of controller). Transfer to Replacement source only if contact is closed (e.g. used to test the frequency of UR).
b b
BA controller. Setting of maximum startup time for the replacement source b Options
DB
4038
10.e
ps Communication optionPower supply
Control voltages (2) 110 V b b 220 to 240 V 50/60 Hz b b 380 to 415 V 50/60 Hz and 440 V 60 Hz
b b
Operating thresholdsUndervoltage 0.35 Un y voltage y 0.7 Un b b Phase failure 0.5 Un y voltage y 0.7 Un b Voltage presence voltage u 0.85 Un b b IP degree of protection (EN 60529) and IK degree of protection against external mechanical impacts (EN 50102)
Front IP40 b b Side IP30 b b Connectors IP20 b b
UA controller. Front IK07 b b Characteristics of output contacts (dry, volt-free contacts)
Rated thermal current (A) 8Minimum load 10 mA at 12 VOutput contacts:Position of the Auto/Stop switch b b Load shedding and reconnection order b Generator set start order. b
AC DCUtilisation category (IEC 947-5-1) AC12 AC13 AC14 AC15 DC12 DC13Operational current (A) 24 V 8 7 5 5 8 2
48 V 8 7 5 5 2 -110 V 8 6 4 4 0.6 -220/240 V 8 6 4 3 - -250 V - - - - 0.4 -380/415 V 5 - - - - -440 V 4 - - - - -660/690 V - - - - - -
(1) For example, 220 V single-phase or 220 V three-phase.(2) The controller is powered by the ACP control plate. The same voltage must be used for the ACP plate, the IVE unit and the circuit breaker operating mechanisms. If this voltage is the same as the source voltage, then the Normal and Replacement sources can be used directly for the power supply. If not, an isolation transformer must be used.
Associated controllersController selection
313E.indb 18 09/04/2013 13:04:28
-
A-19
PB
1008
57_S
E.e
ps ACP control plateThe control plate provides in a single unit:
b protection for the BA or UA controller with two highly limiting P25M circuit breakers (infinite breaking capacity) for power drawn from the AC source
b control of circuit-breaker ON and OFF functions via two relay contactors b connection of the circuit breakers to the BA or UA controller via a built-in terminal
block.Control voltages
b 110 V 50/60 Hz. b 220 to 240 V 50/60 Hz. b 380 to 415 V 50/60 Hz and 440 V 60 Hz.
The same voltage must be used for the ACP control plate, the controller and the circuit breaker operating mechanisms.InstallationConnection between the ACP control plate and the IVE unit may use:
b wiring done by the installer b prefabricated wiring (optional).
Installation of the BA and UA controllersThe BA and UA controllers may be installed in one of two manners:
b directly mounted on the ACP control plate b mounted on the front panel of the switchboard b if the length of the connection between the controller and the control plate (ACP) is
less than or equal to 1 m, the connecting cable ref. 29368 can be ordered as an optional extra. Cables longer than 1 m, but not longer than 2 m will be the responsibility of the installer.
ACP control plate.
DB
1262
69.e
ps
Mounting on the ACP control plate.
DB
1262
70.e
ps
Mounting on the front panel of the switchboard.
Controller installation
313E.indb 19 09/04/2013 13:04:29
-
A-20
Functions and characteristics
The BA controller is used to create simple source-changeover systems that switch from one source to another depending on the presence of voltage UN on the Normal source.It is generally used to manage two permanent sources and can control Compact NS, Compact NSX and Masterpact NT/NW circuit breakers and switch-disconnectors.
Operating modesA four-position switch may be used to select:
b automatic operation b forced operation on the Normal source b forced operation on the Replacement source b stop (both Normal and Replacement sources off).
Setting the time delaysTime delays are set on the front of the controller.t1. delay between detection that the Normal source has failed and the transmission of the order to open the Normal source circuit breaker (adjustable from 0.1 to 30 seconds).t2. delay between detection that the Normal source has returned and the transmission of the order to open the Replacement source circuit breaker (adjustable from 0.1 to 240 seconds).
Circuit breaker commands and status indicationsThe status of the circuit breakers is indicated on the front of the controller.
b ON, OFF, fault.A built-in terminal block may be used to connect the following input/output signals:
b inputs: v voluntary order to transfer to source R (e.g. for special tariffs, etc.) v additional control contact (not part of the controller). Transfer to the Replacement
source takes place only if the contact is closed (e.g. used to test the frequency of UR, etc.)
b outputs: v indication of operation in automatic or stop mode via changeover contacts.
TestIt is possible to test the operation of the BA controller by turning OFF (opening) the P25M circuit breaker for the Normal source and thus simulating a failure of voltage UN.
DB
4038
41.e
ps
BA Controller
DB
4038
38.e
ps
Front of the BA controller.
Associated controllersBA controller
313E.indb 20 09/04/2013 13:04:29
-
A-21
Switch set to Auto (automatic operation and special-tariff mode) Switch set to the N position (forced operation on the Normal source)
DB
1265
47.e
ps
DB
1265
48.e
ps
Switch set to the R position (forced operation on the Replacement source)
Switch set to the Stop position
DB
1265
49.e
ps
DB
1265
50.e
ps
KeyUN : Normal source voltageUR : Replacement source voltageN : Normal source circuit breakerR : Replacement source circuit breaker
WAITING The system exits this mode when the operating mode is modified or when an external event occurs (e.g. failure or return of UN).
The number sends to the indicated step when the condition is true.
BA controller Operating sequences
11
313E.indb 21 09/04/2013 13:04:30
-
A-22
Functions and characteristics
The UA controller is used to create a source-changeover system integrating the following automatic functions:b transfer from one source to another depending on the presence of voltage UN on the Normal sourceb startup of an engine generator setb shedding and reconnection of non-priority circuitsb transfer to the Replacement source if one of the phases on the Normal source fails.The UA controller can control Compact NS, Compact NSX and Masterpact NT/NW devices.
Operating modesA four-position switch may be used to select:
b automatic operation b forced operation on the Normal source b forced operation on the Replacement source b stop (both Normal and Replacement sources off, then manual operation).
Setting the time delaysTime delays are set on the front of the controller.t1. delay between detection that the Normal source has failed and the transmission of the order to open the Normal source circuit breaker (adjustable from 0.1 to 30 seconds).t2. delay between detection that the Normal source has returned and the transmission of the order to open the Replacement source circuit breaker (adjustable from 0.1 to 240 seconds).t3. delay following opening of QN with load shedding and before closing of QR (adjustable from 0.5 to 30 seconds).t4. delay following opening of QR with load reconnection and before closing of QN (adjustable from 0.5 to 30 seconds).t5. delay for confirmation that UN is present before shutting down the engine generator set (adjustable from 60 to 600 seconds).t6. delay before startup of the engine generator set (120 or 180 seconds).
Commands and indicationsCircuit breaker status indications on the front of the controller:
b ON, OFF, fault.A built-in terminal block may be used to connect the following input/output signals:
b inputs: v voluntary order to transfer to source R (e.g. for special tariffs, etc.) v additional control contact (not part of the controller). Transfer to the Replacement
source takes place only if the contact is closed (e.g. used to test the frequency of UR, etc.)
b outputs: v control of an engine generator set (ON / OFF) v shedding of non-priority circuits v indication of operation in automatic mode via changeover contacts.
Distribution-system settingsThree switches are used to:
b select the type of Normal source, whether single-phase or three-phase (e.g. 240 V single-phase or 240 V three-phase)
b select whether to remain (or not) on the Normal source if the Replacement source is not operational during operation on special tariffs
b select the maximum permissible startup time for the engine generator set during operation on special tariffs (120 or 180 seconds).
TestA pushbutton on the front of the controller may be used to test transfer from the Normal source to the Replacement source, then the return to the Normal source. The test lasts approximately three minutes.
COM communications optionUsing the internal bus protocol, this option may be used to remote the following information:
b circuit breaker status (ON, OFF, fault trip) b presence of the Normal and Replacement voltages b presence of an order for forced operation (e.g. special tariffs) b settings and configuration information b status of non-priority circuits (loads shed or not)
b position of the switch (stop, auto, forced operation on the Normal source, forced operation on the Replacement source).
DB
4038
42.e
ps
UA Controller
DB
4038
37.e
ps
Front of the UA controller.
Associated controllersUA controller
313E.indb 22 09/04/2013 13:04:31
-
A-23
Switch set to the R position (forced operation on the Replacement source) Switch set to the N position (forced operation on the Normal source)
DB
1265
51.e
ps
DB
1265
52.e
ps
Switch set to the Stop position
DB
1265
53.e
ps
WAITING The system exits this mode when the operating mode is modified or when an external event occurs (e.g. failure or return of UN).
When the UA controller is not energised, the output for generator set startup is activated).
KeyUN : Normal source voltageUR : Replacement source voltageN : Normal source circuit breakerR : Replacement source circuit breaker
UA controller Operating sequences Forced operation mode
313E.indb 23 09/04/2013 13:04:32
-
A-24
Functions and characteristics
Switch set to the Auto position (special-tariff mode)
WAITING The system exits this mode when the operating mode is modified or when an external event occurs (e.g. failure or return of UN).
When the UA controller is not energised, the output for generator set startup is activated).
KeyUN : Normal source voltageUR : Replacement source voltageN : Normal source circuit breakerR : Replacement source circuit breakerB : Penalties accepted (N ON), i.e. B = 1
1 The number sends to the indicated step when the condition is true.
Associated controllersUA controllerOperating sequences Special-tariff mode
DB
1265
54.e
ps
313E.indb 24 09/04/2013 13:04:32
-
A-25
Switch set to the Auto position (automatic operation and test mode).
DB
1265
55.e
ps
WAITING The system exits this mode when the operating mode is modified or when an external event occurs (e.g. failure or return of UN).
When the UA controller is not energised, the output for generator set startup is activated).
KeyUN : Normal source voltageUR : Replacement source voltageN : Normal source circuit breakerR : Replacement source circuit breaker B : Penalties accepted (N ON), i.e. B = 1(*) The test lasts 180 seconds.
1 The number sends to the indicated step when the condition is true.
UA controllerOperating sequences Test mode and automatic operation
313E.indb 25 09/04/2013 13:04:33
-
A-26
Functions and characteristics
IVE unit
Db1
2659
4.ep
s
SymbolsQN : Normal Compact circuit breaker equipped for remote operation (motor mechanism)QR : Replacement Compact circuit breaker equipped for remote operation (motor mechanism)ON : Circuit breaker QN opening orderOR : Circuit breaker QR opening orderIN : Circuit breaker QN closing orderIR : Circuit breaker QR closing orderL1 : Faulty Normal indication LEDL2 : Faulty Replacement indication LED
KeyO: OFF (circuit open)I: ON (circuit closed
: either ON or OFF.
Note: following all trips (overload, short-circuit, earth-leakage fault, voluntary trip), a manual reset on the front of the motor mechanism is required.
Operating sequences IVE unit
313E.indb 26 09/04/2013 13:04:33
-
A-27
BA controller
Db1
2659
5.ep
s
InputsUN : Normal source voltageUR : Replacement source voltageKT : order for forced-operation on RKR : additional check before transfer
OutputsQN : Normal source circuit breakerQR : Replacement source circuit breaker
UA controller
Db1
2659
9.ep
s
InputsUN : Normal source voltageUR : Replacement source voltageKT : order for forced-operation on RKR : additional check before transfer
OutputsKG : order to the gensetSH : load-shedding orderQN : Normal source circuit breakerQR : Replacement source circuit breaker
KeyO: OFF (circuit open)I: ON (circuit closed
: either ON or OFF.
ImportantIf UR is not ON when the transfer order is issued (KT or UN), the sequence is not carried out.If KR status is not ON when the transfer order is issued (KT or UN), the transfer sequence is carried out later when KR status becomes I.
BA/UA controller
313E.indb 27 09/04/2013 13:04:33
-
A-28
Functions and characteristics
RS 232, Ethernet
RS 485
DC150 dataconcentrator
Communication interface
Communication bus
Devices
MasterpactIVE MasterpactR
N
960019200
JBus
N1
N2
BBus
5
13
913 7
155
13
913 7
15
error24V
OK
error
com. com.
N1 N2
DC150
N
Electrical-installation management
DB
4041
57.e
ps Communications option for Compact NS u 630 A and Masterpact NT/NWThe COM communications option is compatible with all the source-changeover systems for Compact NS630b-1600 and Masterpact NT/NW circuit breakers and switch-disconnectors.It can be used to remote status information. It may not be used to operate the circuit breakers (only possible locally on the front of the UA150 controller).Masterpact and Compact NS630b to 1600 circuit breakers and switch-disconnectors are compatible with the Modbus ECO COM option.Depending on the trip units or control units used, the COM option may also be used to analyse distribution-system parameters required for the operating and maintenance assistance.
Circuit breaker communicationSwitch-disconnector
Circuit breaker
Compact NS630b-1600 status indicationsON / OFF b b Fault trip b Connected / disconnected position b b Masterpact NT/NW status indications
ON / OFF b b Fault trip b Connected / disconnected position b b
Operating and maintenance assistanceOperating and maintenance aids Modbus
MeasurementCurrent A E P HVoltages, power... E P HFrequency P HPower quality: fundamental, harmonics HProgramming of demand metering E P HFault readingsType of fault A E P HInterrupted current P HWaveform captureOn faults HOn demand or programmed HHistories and logsTrip history E P HAlarm history P HEvent logs P HIndicatorsCounter operation A E P HContact wear P HMaintenance register P HNote: see the description of the Micrologic control units for further details on protection and alarms, measurements, waveform capture, histories, logs and maintenance indicators.
COM communications option
313E.indb 28 09/04/2013 13:04:36
-
A-29
Controller UA150Status indications
Normal sourceON / OFF b Circuit breaker ON b Fault trip (SDE) b Voltage presence b Replacement sourceCircuit breaker ON b Fault trip (SDE) b Voltage presence b Status of R voltage contact b ControllerAutomatic mode b Normal mode b Replacement mode b Stop mode b Testing b Replacement engine generator setGenset failure b Genset OFF b Genset ON b Shedding of non-priority circuits b Reconnection of non-priority circuits b Settings
Time delay t1 for validation of UN absence b Time delay t2 for validation of UN return b Time delay t3 for wait between opening of N and closing of R b Time delay t4 for wait between opening of R and closing of N b Time delay t5 for wait between return of UN and order for genset shutdown b Time delay t6 for wait before declaring genset failure b Penalties accepted to avoid special tariff transfer b
960019200
JBus
N1
N2
BBus
5
13
913 7
155
13
913 7
15
error24V
OK
error
com. com.
N1 N2
DC150
N
DB
4040
74.e
ps DC150 data concentratorThe DC150 data concentrator is designed to centralise the information provided by the communicating switchgear of the Digipact range and to make this information accessible to a supervisor or PLC under the MODBUS/JBUS protocol.
Main characteristics b Power supply:
110 V AC to 240 V AC115 V DC to 125 V DC.
b Weight: 1.5 kg. b Installation: on panel with the DC150 box which must be earthed on metal part of
the installation. b Over dimensions H x W x D (mm): 138.5 x 100 x 192.8.
COM communications option
313E.indb 29 09/04/2013 13:04:37
-
This international site allows you to access all the Schneider Electric Solution and Product information via :
pcomprehensive descriptions p range data sheets pa download area pproduct selectors p ...
You can also access the information dedicated to your business and get in touch with your Schneider Electric country support.
schneider-electric.com
TOOLS
181E6100.indd 12 09/04/2013 14:06:21
-
B-1
Source-changeover systems Compact NSX100-630, Compact NS630b-1600, Compact INS/INV, Masterpact
Dimensions
Presentation 2Functions and characteristics A-1
Manual source-changeover systems Interlocking of direct rotary handles B-2Interlocking of extended rotary handles B-3Interlocking of toggles B-5Complete source-changeover assembly B-6Downstream coupling accessory B-7
Remote-operated source-changeover systems Interlocking on a base plate B-9Interlocking using connecting rods B-13Interlocking using cables B-15IVE unit, BA and UA automatic controllers B-20
Electrical diagrams C-1Catalogue numbers and order forms D-1
313E.indb 1 09/04/2013 13:04:37
-
B-2
Dimensions
Compact NSX100 to 630Dimensions Front-panel cutout
DB
1266
07.e
ps
DB
1266
08.e
ps
DB
4044
83.e
ps
Dimensions (mm) Type A B C D F G H J K L M N P
NSX100/160/250 325 90 87.5 175 156 133 9.25 9 295 75.5 150 75 155NSX400/630 416 115 100 200 210 157 5 24.6 386 100 175 74.5 179
Compact INS/INV250 - 100 to 250 / Compact INS/INV320/400/500/630Dimensions Front-panel cutout
Db1
0160
9.ep
s
Db1
0161
0.ep
s
Db1
0161
1.ep
s
Dimensions (mm) Type A B C D F G H K L M N P
INS/INV250 - 100/160/200/250 325 90 87.5 175 156 106 17.5 295 75.5 150 75 131INS/INV320/400/500/630 416 115 100 200 210 130 22.5 386 100 175 74.5 160.4Note: X and Y are the symmetry planes for a 3-pole device.
Manual source-changeover systems Interlocking of direct rotary handles
313E.indb 2 09/04/2013 13:04:38
-
B-3
Compact NSX100 to 630Dimensions Front-panel cutout
DB
1266
10.e
ps
DB
1266
08.e
ps
DB
4044
82.e
ps
Dimensions (mm) Type A B C D F G min G max H J P Q
NSX100/160/250 325 90 87.5 175 156 171 600 9.25 9 25.5 25.5NSX400/630 416 115 100 200 210 195 600 5 24.6 30.8 30.8
Compact INS40/63/80/100/125/160 / Compact INS/INV250 - 100 to 250 / Compact INS/INV320/400/500/630Dimensions Front-panel cutout
Db1
0161
4.ep
s
Db1
0161
5.ep
s
Db1
0775
6.ep
s
Dimensions (mm) Type A B C D F G min G max H P Q
INS40/63/80 325 90 87.5 175 156 155 396 0 25.5 25.5INS100/125/160 325 90 87.5 175 156 200 441 0 25.5 25.5INS/INV250 - 100/160/200/250 325 90 87.5 175 156 185 600 17.5 25.5 25.5INS320/400/500/630 416 115 100 200 210 204 600 22.5 30.8 30.8
Interlocking of extended rotary handles
313E.indb 3 09/04/2013 13:04:39
-
B-4
Compact NS630b to 1600Dimensions
Db1
0161
7.ep
s
DB
1016
18.e
ps
Front-panel cutout
Db1
0161
9.ep
s
Dimensions (mm) Type A B C D F G min G max H J P Q R
NS630b/800/1000/1200/1600 411 63.5 98 175 280 218 605 25 24 25.5 25.5 64
Manual source-changeover systemsInterlocking of extended rotary handles
Dimensions
313E.indb 4 09/04/2013 13:04:39
-
B-5
Compact NSX100 to 630Dimensions 3 poles 4 poles
DB
1266
12.E
PS
DB
1266
13.E
PS
DB
1266
14.E
PS
Front-panel cutout 3 poles on left 4 poles on left
Db1
0162
3.ep
s
Db1
0162
4.ep
s
Dimensions (mm) Type C2 C3 L L16 L17 L18 R2 R18 R19 P5 P
NSX100/160/250 54 108 52.5 140 245 280 54 89 140 83 120NSX400/630 92.5 182 70 185 325 370 71.5 116.5 185 107 150
Interlocking of toggles
313E.indb 5 09/04/2013 13:04:40
-
B-6
Assembly for INS250 - 100 to 250 / Assembly for INS320/400/500/630Dimensions
Db1
0162
5.ep
s
Db1
0162
6.ep
s
Front-panel cutout
Db1
0162
7.ep
s
Dimensions (mm) Type A B C D E F G H I J K L M N
INS250 - 100/160/200/250 60.4 130.4 296 68 136 131 61.8 279.3 42 84 156 186.5 5.5 50INS320/400/500/630 82.5 175 395 102.5 205 155 87 383.7 64 128 210 213 8 50
Dimensions of the complete source-changeover assembly with an extended handle
Db1
0165
0.ep
s
Db1
0165
1.ep
s
DB
1077
43.e
ps Dimensions (mm) Type A B C E K L M N
INS250 - 100/160/200/250 60.4 130.4 295 136 156 138.5 631 50INS320/400/500/630 82.5 175 395 205 210 162.5 658 75
Dimensions (mm) Type P Mmax Mmin Q
INS250 - 100/160/200/250 100 567.5 195 64INS320/400/500/630 150 593 220.5 64
Note: lines X and Y indicate the axes of symmetry of the switch-disconnector. Reference plane Z corresponds to the back of the switch-disconnector.
Manual source-changeover systemsComplete source-changeover assembly
Dimensions
313E.indb 6 09/04/2013 13:04:41
-
B-7
Compact NSX100 to NSX630 (only for Compact NSX fixed devices)Dimensions
DB
4132
82.e
ps
DB
4132
79.e
ps
Dimensions Connection
DB
4132
80.e
ps
= = = =
= =
DB
4135
69.e
ps
Dimensions (mm) Type G2 G3 G28 G29 G30 G52 K1 K2 K3 K4 K8 K9 K16
NSX100/160/250 118 181.5 244.5 96 152.5 178 35 35 51 156 70 170 8NSX400/630 165.9 264.7 337.5 143.5 220.5 264.7 45 45 75 210 113.5 250.7 15
Dimensions (mm) Type L28 L29 L30 L31 L32 L33 L34 L35 L36 L37 L39 L40 T
NSX100/160/250 320 99.5 300 89.5 4.73 130.5 139.5 74.5 19.5 87.5 9.5 140 6NSX400/630 425 130 400 117.5 5.15 175.3 184.7 98.5 26 115 9.85 184.7 6
Note: coupling accessory: only for changeover systems using fixed versions of Compact NSX circuit breakers.
Downstream coupling accessory
313E.indb 7 09/04/2013 13:04:42
-
B-8
Compact INS250 - 100 to 250 / Compact INS320/400/500/630Dimensions
DB
4132
86.e
ps
DB
4132
83.e
ps
DB
4135
67.e
ps
Dimensions Connection
DB
4132
84.e
ps
= = = =
= =
DB
4135
70.e
ps
Dimensions (mm) Type G2 G3 G28 G29 G30 G52 K1 K2 K3 K4 K8 K9 K16
INS250-100/160/200/250 105.5 169 232 83.5 140 165.5 35 35 51 156 57.5 157.5 25.5INS320/400/500/630 141 240.7 313 119 195.6 240 45 45 75 210 88.5 225.7 37.5
Dimensions (mm) Type L28 L29 L30 L31 L32 L33 L34 L35 L36 L37 L39 L40 T
INS250-100/160/200/250 320 83 300 72 12.8 130.5 139.5 74.5 21.5 70 8.5 140 6INS320/400/500/630 425 107.5 400 95 17.35 175.3 184.7 98.5 26 92.5 12.65 184.7 6
Manual source-changeover systemsDownstream coupling accessory
Dimensions
313E.indb 8 09/04/2013 13:04:43
-
B-9
Compact NSX100 to 250Dimensions, 3 or 4 poles Fixed device Withdrawable device
DB
4132
87.e
ps
DB
4132
88.e
ps
DB
1266
19.E
PS
(*) Short terminal shields are mandatory.
Vertical mounting Horizontal mounting
Db1
0163
7.ep
s
Db1
0163
8.ep
s
Dimensions (mm) Type G50 G51 H20 H21 H22 H23 H42 H43 H44 H45 H46 K25 K35 K36
NSX100/160/250 137.5 285 62.5 97 45.5 73 60 120 144.5 300 37 156 210.5 300NSX400/630 180 360 100 152 83 123 60 120 189 378 77 210 282.5 400
Dimensions (mm) Type L31 L32 P7 P8 P9 P32 P33 P50 P52 P54 T9 T10 U
NSX100/160/250 110.5 354 25 45 75 182 143 25 99.5 21 9 6 y 32NSX400/630 150.5 466 25 45 100 256 215 25 123 21 9 6 y 32
Note: coupling accessory: only for changeover systems using fixed versions of Compact NSX circuit breakers.
Remote-operated source-changeover systemsInterlocking on a base plate
313E.indb 9 09/04/2013 13:04:44
-
B-10
Compact NSX400 to 630Dimensions, 3 or 4 poles Fixed device
DB
4132
89.e
ps
DB
4132
90.e
ps
Withdrawable device
Note: coupling accessory: only for changeover systems using fixed versions of Compact NSX circuit breakers.
DB
1266
22.E
PS
(*) Short terminal shields are mandatory.
DimensionsVertical mounting Horizontal mounting
Db1
0163
7.ep
s
Db1
0163
8.ep
s
Note: dimensions see page B-9.
Remote-operated source-changeover systemsInterlocking on a base plate
Dimensions
313E.indb 10 09/04/2013 13:04:45
-
B-11
Normal and Replacement source devices: NSX100 to NSX250Dimensions Front-panel cutout
177145
DB
4132
91.e
ps
NSX100to
NSX250
NSX100to
NSX250
77
9595
156
47.5 47.5
29.5
DB
4041
34.e
ps
Normal and Replacement source devices: NSX400 to NSX630 Dimensions Front-panel cutout
249217
DB
4133
00.e
ps
NSX400to
NSX630
12763.5
127
127
42
210
63.5
NSX400to
NSX630
DB
4041
35.e
ps
Note for Compact NSX:For dimensions with the accessories (IP40 escutcheons and Vigi escutcheon protection collars), see Catalogue Compact.
313E.indb 11 09/04/2013 13:04:46
-
B-12
NSX400 to NSX630 as the Normal device, NSX100 to NSX250 as the Replacement deviceDimensions Front-panel cutout
DB
1266
23.E
PS
NSX400to
NSX630
NSX100to
NSX250
DB
4041
36.e
ps
Remote-operated source-changeover systemsInterlocking on a base plate
Dimensions
313E.indb 12 09/04/2013 13:04:47
-
B-13
Two Compact NS630b to NS1600 devices one above the otherFixed devices Withdrawable devices
DB
1077
47.e
ps
Db1
0165
5.ep
s
Two Masterpact NT devices one above the other Fixed devices Withdrawable devices
Db1
0165
6.ep
s
Db1
0165
5.ep
s
Interlocking using connecting rods
313E.indb 13 09/04/2013 13:04:47
-
B-14
Two Masterpact NW devices one above the otherFixed devices Withdrawable devices
DB
1077
48.e
ps
DB
1077
49.e
ps
Remote-operated source-changeover systems Interlocking using connecting rods
Dimensions
313E.indb 14 09/04/2013 13:04:47
-
B-15
Two Compact NS630b to NS1600 devices side-by-sideFixed devices Withdrawable devices
Db1
0166
1.ep
s
Db1
0166
2.ep
s
Two Masterpact NT devices side-by-side Fixed devices Drawout devices
Db1
0166
3.ep
s
Db1
0166
2.ep
s
Combination of two Masterpact NT and NW devices side-by-side Fixed devices Drawout devices
Db1
0166
4.ep
s
DB
4041
47.e
ps
Interlocking using cables
313E.indb 15 09/04/2013 13:04:48
-
B-16
Two Masterpact NW devices side-by-sideFixed devices Drawout devices
Db1
0166
6.ep
s
Db1
0166
7.ep
s
Three Masterpact NW devices side-by-side Fixed devices
Db1
0166
8.ep
s
Drawout devices
Db1
0166
9.ep
sRemote-operated source-changeover systemsInterlocking using cables
Dimensions
313E.indb 16 09/04/2013 13:04:49
-
B-17
Two Compact NS630b to NS1600 devices one above the otherFixed devices Withdrawable devices
DB
1077
50.e
ps
Db1
0167
1.ep
s
Two Masterpact NT devices one above the other Fixed devices Drawout devices
Db1
0167
2.ep
s
Db1
0167
1.ep
s
313E.indb 17 09/04/2013 13:04:49
-
B-18
Two Masterpact NW devices one above the otherFixed devices Drawout devices
DB
1077
51.e
ps
DB
1077
52.e
ps
Two Masterpact NT and NW devices one above the otherFixed devices Drawout devices
DB
1077
53.e
ps
DB
4041
48.e
ps
Remote-operated source-changeover systemsInterlocking using cables
Dimensions
313E.indb 18 09/04/2013 13:04:50
-
B-19
Three Masterpact NW devices one above the otherFixed devices Drawout devices
DB
1077
54.e
ps
DB
1077
55.e
ps
Remote-operated source-changeover systemsInterlocking using cables
Dimensions
313E.indb 19 09/04/2013 13:04:50
-
B-20
IVE unit
Db1
0167
9.ep
s
Db1
0167
8.ep
s
ACP control plate and BA/UA controllers Door cutout for BA/UA controllers
Db1
0168
0.ep
s
Db1
0168
1.ep
s
Db1
0168
2.ep
s
DB
1016
83.e
ps
(1) Cutout according DIN 43700 standard.
Remote-operated source-changeover systemsIVE unit, BA and UA automatic controllers
Dimensions
313E.indb 20 09/04/2013 13:04:51
-
C-1
Source-changeover systems Compact NSX100-630, Compact NS630b-1600, Compact INS/INV, Masterpact
Presentation 2Functions and characteristics A-1Dimensions B-1
Remote-operated source-changeover systems 2 Compact NSX100/630 devices C-22 Compact NSX100/630, NS630b/1600 or Masterpact NT/NW devices C-5
Source-changeover systems with automatic controllers 2 Compact NSX100/630, NS630b/1600 or Masterpact NT/NW devices C-6Controller settings C-72 Compact NSX100/630, NS630b/1600 or Masterpact NT/NW devices C-8
Remote-operated source-changeover systems 2 Compact NS630b/1600 devices C-92 Masterpact NT or NW devices C-123 Masterpact NW devices C-17
Source-changeover systems with automatic controllers 2 Masterpact NT or NW devices C-26
Catalogue numbers and order forms D-1
Electrical diagrams
313E.indb 1 09/04/2013 13:04:51
-
C-2
Source-changeover system without automatic-control systemWithout auxiliaries for emergency off Local reset
Db4
0180
5.ep
s
Db1
0165
9.ep
s
Voluntary remote reset
Db1
0166
0.ep
s
Automatic reset
(1) Prefabricated wiring: cannot be modified.
LegendsQN Normal source Compact NSX equipped with motor mechanismQR Replacement source Compact NSX equipped with motor
mechanismSDE fault-trip indication contactIVE electrical interlocking and terminal block unitMT motor mechanismOF2 breaker ON/OFF indication contactRN reset order for breaker QNRR reset order for breaker QR
States permitted by mechanical interlocking systemNormal Replacement0 01 00 1Note: diagram shown with circuits de-energised, circuit breakers open and relays in normal position.
Remote-operated source-changeover systems2 Compact NSX100/630 devicesDiagram no. 51201177
Electrical diagrams
313E.indb 2 09/04/2013 13:04:52
-
C-3
Electrical diagrams
Source-changeover system without automatic-control systemWith emergency off by MN release and automatic reset
KA5 KA5
KA5KA5
DB
4151
14.e
ps
Automatic reset
(1) Prefabricated wiring supplied.(2) Independent auxiliary source.
LegendsQN Normal source Compact NSX equipped with
motormechanismQR Replacement source Compact NSX equipped with motor
mechanismMN undervoltage releaseOF2 breaker ON/OFF indication contactSDE fault-trip indication contactMT motor mechanismIVE electrical interlocking and terminal block unitBP emergency off button with latchingKA5 auxiliary relayF1 auxiliary power supply circuit breaker
States permitted by mechanical interlocking systemNormal Replacement0 01 00 1Note: after a fault trip, the breaker must be reset manually by pressing its reset button. Diagram shown with circuits de-energised, circuit breakers open and relays in normal position.
Remote-operated source-changeover systems 2 Compact NSX100/630 devicesDiagram no. 51201178
313E.indb 3 09/04/2013 13:04:53
-
C-4
Source-changeover system without automatic-control systemWith emergency off by MX release and automatic reset
DB
4151
15.e
ps
Automatic reset
(1) Prefabricated wiring supplied(2) This source can be: b the source present in the case of voltage monitoring b an independent source.
In this case, the MX release must be