Current Product Software Issues (last Updated 30/5/2001) Page 1 of 57 SOFTWARE LISTING FOR COMMANDER, SCREENMASTER & CLEARSPAN PRODUCTS Last Updated: April 2002 Introduction The following document shows the latest release of software and product history for all Commander and Screen Master products. Please click the option you require. Commander Products_Summary C100/C150/C160 L150/L160 Original C200 C200 Plus C250/V100/V250 Original C300 C300 Plus C310 C320 C350 C500 C1900 Original PR100 PR100 Plus SR100 SR250 PR250 Commander Configuration Editor ScreenMaster Products_Summary ScreenMaster 1000 ScreenMaster 2000 Datamanager ABB LTD – D&D Department Release. P. Evans

Upload: doquynh

Post on 10-Mar-2018

218 views

Category:

Documents


2 download

TRANSCRIPT

Current Product Software Issues (last Updated 30/5/2001) Page 1 of 39

SOFTWARE LISTING FOR COMMANDER, SCREENMASTER & CLEARSPAN PRODUCTS

Last Updated: April 2002

Introduction

The following document shows the latest release of software and product history for all Commander and Screen Master products. Please click the option you require.

Commander Products_Summary

C100/C150/C160L150/L160Original C200C200 PlusC250/V100/V250Original C300C300 PlusC310C320C350C500C1900Original PR100PR100 PlusSR100SR250PR250Commander Configuration Editor

ScreenMaster Products_Summary

ScreenMaster 1000ScreenMaster 2000Datamanager

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 2 of 39

Software History

C100C150C160L150/L160C200C250/V100/V250C300C310C320C350/C360C500C1900PR100SR100SR250MR100PR250ScreenMaster 1000ScreenMaster 2000Commander Configuration Editor

Clearspan Products Summary

PX100 (Mk2 processor board)PX100 (Mk3 processor board)PX105 (Mk3 processor board)

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 3 of 39

Commander Products Summary C100/C150/C160 View History

Part No. Issue Size DCN DescriptionC100/2001 9 PSD313 15890 StandardC150/2001 8 PSD313 15866 StandardC150/2001/SP02 7 PSD313 15866 Individual alarm hysteresis values. First issue based on

C150/2001/Iss 2. Current issue based on C150/2001/Iss 8.C100/2501/SP25 3 PSD313 15890 OEM version. First issue based on C100/2001/Iss 7.

Current issue based on C100/2001/ Iss 8.C150/2501/SP25 2 PSD313 15866 OEM version. First issue based on C150/2001/Iss 7.

Current issue based on C150/2001/Iss 8C160/2001 5 PSD313 15866 StandardC160/2501/SP25 2 PSD313 15866 OEM version. First issue based on C160/2001/Iss 4.

Current issue based on C160/2001/Iss 5.

L150/L160 View History

Part No. Issue Size DCN DescriptionL150/2001 7 PSD313 15866 Standard software for L150 and L160

Original C200

Part No. Issue Size DCN DescriptionC200/2001 3 512 14001 Standard (does not support serial communications)C200/2002 1 512 14001 Ramp/soak, totalizer C200/2101 3 512 14017 Standard with serial communicationsC200/2101/S 3 512 14017 Serial slaveC200/2102 3 512 14017 Ramp/soak, totalizerC200/2101/SP01 4 512 14104 Four local setpoints, selectable using two digital inputs or via the

front panel switchesC200/2201 5 512 15139 Standard with serial communicationsC200/2201/S 5 512 15139 Serial slaveC200/2202 5 512 15139 Ramp/soak, totalizer - battery backed ram added

C200 Plus View History

Part No. Issue Size DCN DescriptionC200/2301 4 512 15632 Standard C200 PlusC200/2301/S 4 512 15632 MODBUS Serial slaveC200/2302 4 512 15632 Ramp/soak, totalizer

C200/2301/SP02 1 512 14127 Control output scaled and displayed in user selectable range for auto/manual ratio/bias station

C250/V100/V250 View History

Part No. Issue Size DCN DescriptionC250/2001 5 PSD313 16153 Standard software for C250, V100 and V250.C250/2501/SP25 3 PSD313 16153 OEM version. First issue based on C250/2001/Iss 3.

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 4 of 39

Current issue based on C250/2001/Iss 5

Original C300

Part No. Issue Size DCN DescriptionC300/2001 4 512 13872 Original standard version which did not support the use of option boardsC300/2101 5 512 14045 Original standard version which supported the use of option boardsC300/2101/S 5 512 14045 Slave EPROM fitted on option boards

C300 Plus View History

Part No. Issue Size DCN DescriptionC300/2201 10 512 15882 Standard C300 PlusC300/2201/S 10 512 15882 Slave EPROM fitted on option boards, supports MODBUS

on serial boardC300/2202 10 512 15882 Custom linearizer (C301)C300/2203 7 512 15882 Extended ramp/soak (C302) - was SP04C300/2201/SP06 3 512 15882 Remote setpoint with independent engineering range.

First issue based on C300/2201/Iss 2. Current issue based on C300/2201Iss 10.

C300/2201/SP07 3 512 15882 Auto/manual station. First issue based on C300/2201/Iss 6. Current issue based on C300/2201 Iss 10.

C300/2501/SP25 2 512 15882 OEM version. First issue based on C300/2201/Iss 9.Current issue based on C300/2201 Iss 10.

C310 View History

Part No. Issue Size DCN DescriptionC310/2001 6 PSD313 15634 Standard software for C310 controller.C310/2501/SP25 1 PSD313 15190 OEM version, first issue based on C310/2001/Iss 6.

C320 View History

Part No. Issue Size DCN DescriptionC320/2001 4 PSD313 15642 Standard software for C320 controller.

C350 View History

Part No. Issue Size DCN DescriptionC350/2001 9 2001 16175 Standard software for C350 and C360 controllers.

C500 View History

Part No. Issue Size DCN DescriptionC500/2001 10 2001 16187 Standard software for C500 controller.C500/2501/SP25 10 2001 16187 OEM version based on C500/2001/Iss 10.

Note: C500/2501/SP25 iss 1 was based on C500/2001/Iss 5. C500/2501/SP25 iss 2 was based on C500/2001/Iss 6. C500/2501/SP25 issues 3 to 9 have never been released

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 5 of 39

C1900 View History

Part No. Issue Size DCN DescriptionC1900/2101 3 2001 16174 Standard software for C1900 recorder / recorder-controller.C1900/2101/S 3 512 16174 Slave EPROM fitted on option boards, supports MODBUS

on serial board.

Original PR100

Part No. Issue Size DCN DescriptionPR100/1001 1 TMS370 14004 Master CPU on-chip programPR100/1002 1 TMS370 14004 Secondary processor for use with mk1 processor boardsPR100/1102 2 TMS370 14401 Secondary processor for use with mk2 and CE version

processor boardsPR100/2001 12 1001 14403 1 trace (PR101) original versionPR100/2002 11 1001 14403 2 trace (PR102) original versionPR100/2003 13 1001 14403 3 trace (PR103) original versionPR100/2004 12 1001 14403 4 trace (PR104) original versionPR100/2005 11 1001 14403 5 trace (PR105) original versionPR100/2006 12 1001 14403 6 trace (PR106) original versionPR100/2006/SP01 2 1001 14149 Special pasteuriser event software for Samsomatic (uses

PR100/2006 issue 11 source code)

PR100 Plus View History

Part No. Issue Size DCN DescriptionPR100/1001 1 TMS370 14004 Master CPU on-chip programPR100/1102 2 TMS370 14401 Secondary processor for use with mk2 and CE version

processor boardsPR100/2101 6 2001 15635 Standard PR100 plusPR100/2101/SP01 4 2001 15635 Special pasteuriser event software for Samsomatic.

First issue based on PR100/2101 Iss 3. Current issue based on PR100/2101 Iss 6.

PR100/2101/SP04 6 2001 15635 FValue measurement for sterilisation.First issue based on PR100/2101 Iss 1. Current issue based on PR100/2101 Iss 6.

PR100/2101/SP11 4 2001 15635 Batch Number Printing Special.First issue based on PR100/2101 Iss 3. Current issue based on PR100/2101 Iss 6.

PR100/2501/SP25 1 2001 15190 OEM version, first issue based on PR100/2101/Iss 6

MR100 View History

Part No. Issue Size DCN DescriptionMR100/2101 4 2001 15635 Standard MR100MR100/2501/SP25 1 2001 15190 OEM version, first issue based on MR100/2101/Iss 4

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 6 of 39

SR100 View History

Part No. Issue Size DCN DescriptionSR100/2001A 5 2001 16045 Standard version with advanced functionalitySR100/2001A (sp01)

5 2001 16045 Samsomatic version with advanced functionality(special event markers on pens 1 & 4)

SR100/2001A (sp11)

5 2001 16045 Batch Number Printing version with advanced functionality

SR100/2501A 5 2001 16045 OEM version with advanced functionalitySR100/2001B 5 2001 16045 Standard version with basic functionalitySR100/2501B 5 OEM version with basic functionality

PR250 View History

Part No. Issue Size DCN DescriptionPR250/2001 11 4001 16188 Master EPROM for MR250 and PR250.PR250/2001S 11 512 16188 Serial Slave EPROM for MR250 and PR250.PR250/2501(SP25) 11 4001 16188 OEM version Master EPROM for MR250 and PR250.

SR250 View History

Part No. Issue Size DCN DescriptionSR250/2001 4 4001 16188 Master EPROM for SR250 A and B .SR250/2501 4 512 16188 Serial Slave EPROM for SR250 A and B .SR250/2001S 4 4001 16188 OEM version Master EPROM for SR250 A and B

Commander Configuration Editor View History

Part No. Issue Size DCN DescriptionC100/3000 10 3.5” disk 16026 PC Configuration tool for Commander Products.

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 7 of 39

ScreenMaster Products Summary

ScreenMaster 1000 View History

Part No. SoftwareIssue

SystemIssue

DCN Description

SM1000/2001 2001/5 1001/5 16254 Standard SM1000.

ScreenMaster 2000 View History

Part No. SoftwareIssue

SystemIssue

DCN Description

SM2000/2002 2002/9 1002/7 16255 Standard SM2000.

Datamanager

Iss DCN Date CommentsGR2000/3000 1 May ‘01 Introduction of Datamanager software.

2 16130 Oct ‘01 US date format accomodated Reverse engineering allowed for Print Preview/View/Hide problems corrected Digital tags corrected FTP Ethernet compatibility added

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 8 of 39

Software History

C100

Issue DCN Date CommentsC100/2001 1 15134 Dec 95 Introduction of standard software.

2 15261 Feb 96 Software version and issue now displayed on power up. Company standard sets the MODBUS address to 1 instead of 0. PC Configurator ID now set to spaces by the company standard. Auto-tune now goes to the ‘off’ state on completion instead of an

‘end’ state - this allows another auto-tune to be started without first selecting the ‘off’ state.

Pressing the auto/manual key now stops an auto-tune. With issue 1 software, when the hardware configuration is set to

custom (U), any relay or logic o/p set as a control output will not work - this fault has now been corrected.

When the remote setpoint value is read via MODBUS (regs 4 & 5, 43 & 44) ratio & bias are now applied to the value returned.

The cold junction temperature is now displayed to the nearest 0.1°C instead of 1°C.

Enhancements have been made to allow the PC test rig in production to test the display and option board lines.

In the commissioning level invalid frames are not displayed to simplify and speed up testing (eg relays that are not fitted).

An error message is now displayed in the calibration frames if a calibration fails.

3 15287 Apr 96 Corrections for direct acting control with integral action.4 15352 July 96 Control output would lock at 0% for long periods of time,

resulting in poor control - fault corrected. In heat only applications, the control output value changes when

switching from auto to manual mode if the overlap value does not equal 0% - fault corrected.

If an auto-tune is started in manual, it now places the controller in auto if the auto-tune is completed successfully.

If an error occurs during an auto-tune, the controller now goes to the configured output value as well as selecting manual mode.

5 15386 Oct 96 Non-volatile memory refreshed continually to accommodate new memory devices.

Square root linearizer modified to produce a linear response for the first 4% of the electrical range.

Correction made to ensure the input does not fail on power-up when configured with an offset electrical range and a non-zero filter value.

On power-up the alarm relays no longer energise momentarily if the alarm condition is active.

Individual hysteresis values are now available by selecting “U” as the hysteresis setting in the configuration level.

Improvements made to the start-up auto-tuning. Correction to prevent the output from locking at 0 or 100% for a

period of time following recovery from an input failure. Correct display of remote setpoint failure in the remote setpoint

selection frame.

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 9 of 39

Software History

C100 (continued)

Issue DCN Date CommentsC100/2001 6 15440 May 97 Switch de-bounce improved to prevent noise being interpreted as

a key-press. MODBUS communications fault corrected, whereby incomplete

messages of less than 3 characters were causing the instrument to reset.

Heat/Cool control interaction fault eliminated, whereby Output set to 0% in Manual - with certain parameter settings would remain at 0% when switched back to Auto.

7 15542 Jan 98 Local setpoint stored in NONVOL, without the need for scroll key operation.

Correction to ensure reliable operation in MOD30ML backup operation.

Introduction of PSD313.8 15866 Mar 99 Correction to analog output, in the event the analog input greatly

exceeds the retransmission range. MODBUS: correction to response in respect of Coils 7, 9, & 11. MODBUS: correction to response in respect of Register 16. Correction in respect of automatic NONVOL saves for output 1,

in order to improve EMC performance.9 15890 July 99 Correction to control output value upon recovery from an input

failure.

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 10 of 39

Software History

C150

Issue DCN Date CommentsC150/2001 1 15137 Dec 95 Introduction of standard software

2 15261 Aug 96 Software version and issue now displayed on power up. Company standard sets the MODBUS address to 1 instead of 0. PC Configurator ID now set to spaces by the company standard Average, maximum and minimum values can now be read via

MODBUS. Correction made to ensure Offset is displayed correctly when a 5

digit engineering range is selected. The cold junction temperature is now displayed to the nearest

0.1°C instead of 1°C. Enhancements have been made to allow the PC test rig in

production to test the display and option board lines. In the commissioning level invalid frames are not displayed to

simplify and speed up testing (eg: relays that are not fitted). An error message is now displayed in the calibration frames if a

calibration fails.3 15359 Sept 96 Correct display flicker with square root input.

Wrap output now remains energised until the total is reset, regardless of input value.

Correct dp position always displayed when the electrical units value is displayed.

Pressing the down key (as stated in the manual) displays the input value in electrical units.

4 15386 Oct 96 Non-volatile memory refreshed continually to accommodate new memory devices

Square root linearizer modified to produce a linear response for the first 4% of the electrical range

Correction made to ensure the input does not fail on power-up when configured with an offset electrical range and a none zero filter value

On power-up the alarm relays no longer energise momentarily if the alarm condition is active

Individual hysteresis values are now available by selecting “U” as the hysteresis setting in the configuration level

Correction made to ensure Relay 2 works correctly with code A = 2 or B and Relay 3 with code A = 5 or E

5 15440 May 97 Switch de-bounce improved to prevent noise being interpreted as a key-press.

MODBUS communications fault corrected, whereby incomplete messages of less than 3 characters were causing the instrument to reset.

6 15542 Jan 98 Local setpoint stored in NONVOL, without the need for scroll key operation.

Correction to ensure reliable operation in MOD30ML backup operation.

Introduction of PSD313.

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 11 of 39

Software History

C150 (continued)

Issue DCN Date CommentsC150/2001

7 15611 Jun 98 Totalizer accuracy improved for low count-rates.8 15866 Mar 99 Correction to analog output, in the event the analog input greatly

exceeds the retransmission range. MODBUS: correction to response in respect of Coils 7, 9, & 11. MODBUS: correction to response in respect of Register 16. Correction in respect of automatic NONVOL saves for output 1,

in order to improve EMC performance.

Software History

C160

Issue DCN Date CommentsC160/2001 1 15420 Apr 97 Introduction of standard software (wall mounted version of

C150 instrument).2 15434 Apr 97 Analog output object code corrected.

Correction to ensure instrument does not reset when MODBUS communications active.

3 15523 Oct 97 Alarm 2 and 3 hysteresis is now adjustable when custom alarm hysteresis is selected.

4 15535 Dec 97 Introduction of PSD313. Correction in respect of custom linearizer.

5 15866 Mar 99 Correction to analog output, in the event the analog input greatly exceeds the retransmission range.

MODBUS: correction to response in respect of Coils 7, 9, & 11. Correction in respect of NONVOL saves via SPI, in order to

improve EMC performance.

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 12 of 39

Software History

L150/L160

Issue DCN Date CommentsL150/2001 1 15420 Apr 97 Introduction of standard software (Level Measurement versions

of C150/C160).2 15434 Apr 97 Analog output object code corrected.

Correction to ensure instrument does not reset when MODBUS communications active.

3 15523 Oct 97 Marketing required changes to enhance product.4 15535 Dec 97 Introduction of PSD313.5 15592 Mar 98 Input filter operates when used with P850/60 1–10mA sensors.

Correction to span error calculation on 1–10mA input.6 15612 May 98 Correction to input calibration in respect of P861/P871 sensor.7 15866 Mar 99 Correction to analog output, in the event the analog input greatly

exceeds the retransmission range. MODBUS: correction to response in respect of Coils 7, 9, & 11. Correction in respect of NONVOL saves via SPI, in order to

improve EMC performance. Correction to ensure that an assigned offset value is applied to

the volume calculation as well as the level calculation

Software HistoryC200

Issue DCN Date CommentsC200/2301 1 14145 Oct 94 Introduction of C200 Plus software.

Alarm hysteresis fault corrected. Self-seeking setpoint fault on ramp/soak corrected. Power fail mode now supports manual/last feature as on 200R.

2 14402 Mar 95 Company standard now sets parity to none and the serial enable state to ON.

3 15267 Apr 96 If an auto-tune was performed that resulted in a Tune Caution, subsequent auto-tune initiations would cause the instrument to lock up in the auto-tune frame (displaying TUNE CAUT) - this fault has now been corrected.

When switching from manual to auto the control output remained at the last value if the PV was less than 40% or greater than 60% of the engineering range - this fault has now been corrected.

Correction made to MODBUS write multiple coils function. MODBUS function 15 added.

4 15632 Aug 98 Correction in respect of MODBUS parity. Correction to reject MODBUS messages of less than 6 chars. Correction to improve internal MODBUS message interchange.

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 13 of 39

Software HistoryC250/V100/V250

Issue DCN Date CommentsC250/2001 1 15524 Oct 97 Introduction of standard software (Covers C250, V100, and

V250 with the one version).2 15532 Dec 97 Correction to Level 5 configuration (couldn’t set up Baud Rate

and Parity for serial communications). Local setpoints for Outputs 1 and 2 were not being saved to non-

volatile memory.3 15545 Feb 98 Correction in respect of automatic NONVOL saves for outputs 1

and 2, and integral term values.4 15866 Mar 99 Correction to analog output, in the event the analog input greatly

exceeds the retransmission range. MODBUS: correction to response in respect of Coils 7 & 9. MODBUS: correction to response in respect of Register 16.

5 16153 V100/V250 Deadband.Resolution of deadband has been improved for combinations of high Proportional Band & small Engineering Range.

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 14 of 39

Software HistoryC300

Issue DCN Date CommentsC300/2201 1 14147 Nov 94 Introduction of C300 Plus software.

2 14402 Mar 95 Serial Parity now “None” as company standard Block check character frame does not appear Profile operation limits corrected.

3 14421 Apr 95 Enhancements made to MODBUS to prevent random corruption of the process variable when unit is continually interrogated via the MODBUS interface.

MODBUS function code 15 (force multiple coils) has been added.

Heat/cool operation corrected to allow correct operation with all permutations of control actions.

4 14508 Jun 95 Further enhancements to prevent corruption of the process variable when the unit is continually interrogated via the MODBUS interface.

CJ compensation corrected for E & N type thermocouples. Second setpoint can now be selected via MODBUS.

5 15114 Dec 95 Further corrections to prevent the process variable being affected by MODBUS operation.

Change to correction factor applied to mA inputs. Corrections made to auto start-up power fail mode.

6 15275 Sept 96 The alarm trip value limits for MODBUS write operations are now +/-4095 to allow the setting of both negative and positive alarm trip values.

The option board type is read from the option board micro-controller before the start of the executive cycle to ensure that it is valid before any functions are executed - this fault resulted in assignment of logic inputs 3 & 4 being corrupted.

7 15540 Dec 97 MODBUS message rejected if less than 6 bytes.8 15549 Feb 98 MODBUS message exchange between master & slave CPUs

retried if unsuccessful.9 15633 Aug 98 Correction to Motorised Valve operation.10 15882 May 99 Correction to Motorised Valve operation upon power-up in

manual mode. Correction to the addressing of A/M parameter via MODBUS

coil table, coil address #74. Auto/Manual Station version (SP07) only: correction to decimal

point info. used by process variable.

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 15 of 39

Software HistoryC310

Issue DCN Date CommentsC310/2001 1 Jun 95 Introduction of standard software.

2 14509 Jun 95 CJ Compensation corrected for E & N type thermocouples. Control relay now operates when isolated retransmission is

selected. Setpoint selection limits with MODBUS corrected.

3 15123 Jan 96 Now uses PSD312. Correction to enable odd/even parity to work on MODBUS

serial communications.4 15141 Jan 96 Correction to MODBUS operation with odd/even parity.5 15586 Feb 98 Re-introduction of PSD313.6 15634 Aug 98 Correction to Motorised Valve operation.

MODBUS message rejected if less than 6 bytes.

Software HistoryC320

Issue DCN Date CommentsC320/2001 1 15421 Mar 97 Introduction of standard software (Pasteuriser version of C310).

2 15516 Sept 97 Security lockout provided by digital input 2 terminals. Addition of retransmission of pressure-difference option.

3 15587 Feb 98 Introduction of PSD313.4 15642 Sept 98 Modification to prevent display flashing when Alarm A is

active.

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 16 of 39

Software HistoryC350/C360

Issue DCN Date CommentsC350/2001 1 15858 Nov 98 Introduction of standard software (C350 operation only).

Note that override code is “31”.2 15861 Dec 98 Introduction of standard software (C350 and C360 operation). 3 15871 Mar 99 Correction to operation of logic equation.

Correction to operation of maths functions. Correction to operation of PID under PV failure conditions. Correction to operation of MODBUS communications (C360). Override code changed to “1410”.

4 15892 Sept 99 Modifications to ensure effectiveness of auto-tune password. Modifications to ensure correct operation of deviation bargraph

and deviation alarms on controllers set-up for On/Off control. Analog outputs assigned to a control output will always operate

over a 0 – 100% engineering range. On indicator versions, control output saved to non-vol memory. Auto-tune now available on Cascade and Motorised Valve (Fb). A/M state and O/P level accessible via MODBUS on Cascade. Process variable alarms operate correctly even when the process

variable is not assigned to input 1 Heat/Cool outputs are set to correct “configured output” when

switching from Automatic to Manual control via digital signals, bumpless transfer occurs when returning to automatic control.

Global alarm acknowledge added. C355 now has Ramp-Soak (9 Programs, 30 segments) cf: C360.

5 16024 Jun 00 Polarity of Digital Outputs corrected for Time Proportioning control.

Fixed fault of Control Output going to the start of decade when switching from Manual to Auto mode. e.g. o/p would go from 67 to 60.

Corrected application of Output Slew Rate for Single Loop, Time Proportioning Templates.

Added Output Slew Rate to Cascade Templates with Feedback Motorized valve.

Modifications made to ensure bumpless transfer occurs when switching between PID terms

Modbus Coils 33-36 (Relay state) now work correctly Configuration download. Modifications to ensure that the

Control Type parameter is not corrupted when downloading from the PC configurator

6 16030 July 00 Motorised Valve Output with Feedforward templates now work correctly

Correction made to ensure that Boundless Output with Feedforward cannot be selected from the front panel.

7 16164 Sept 01 Additions made to allow for modbus access to floating point values

Correction to operation of rampsoak program,segment & time event states

8 16166 Sept 01 Modbus response time improved. SCI (Modbus) transmit & receive buffers increased in size SCI (Modbus) Message length check modified to reflect

increased receive buffer size9 16175 Nov 01 modifications to eliminate faulty (intermittent) communication

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 17 of 39

when using commander configuration editor modified to ensure correct operation of auto/manual station

when changing from auto to manual with configured o/p set to "LAST"

modified to ensure correct operation of motorised valve with feedback output type when setting the desired valve position via Modbus. (the same modification was made to C500 on 8/12/2000 - introduction of issue 8)

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 18 of 39

Software History C500

Issue DCN Date CommentsC500/2001 1 15538 Dec 97 Introduction of standard software.

Note that override code is “31”.2 15543 Jan 98 Correction to feed-forward “Multiply” function.

Boundless control deadband value limits corrected from (-999 to 9999) to (0 to 9999).

Correction to enable MODBUS parity to be selected as Odd or Even.

Low limit on 0 to 20 mA input range changed from 0 to -0.5 mA.

“Valve-Sticking” message eliminated when Boundless template selected.

Remote Ratio disabled when any template not requiring it is selected.

3 15550 Feb 98 Correction in respect of Analog Outputs where a range other than 4 - 20 mA is selected.

Correction to Alarm Acknowledge procedure so that alarms are displayed as per the Manual.

Setpoint high/low limits and Input adjust Span values now addressed by Company Standard.

Control Output display in manual corrected in order that “0” is not missed when adjusting from “+1” to “-1”.

Correction to Integral Control Action: was not functioning with process in Proportional Band and with Manual Reset values of 0% or greater than 90%.

Input Offset and Span Adjust do not start to change immediately the key is pressed, enabling operator to view the Input value before adjusting.

Default engineering range for the Remote Ratio Input has been changed from 0.000 - 1.000 to 0.000 - 9.999.

4 15588 Mar 98 Thermocouple and RTD measuring in degrees F - correction to prevent the units reverting to degrees C following power-reset.

Cascade / Dual output templates - correction to ensure control output responds to process changes.

Deviation alarm decimal point display - correction to ensure any PV decimal point changes are immediately updated here.

On/Off Hysteresis Decimal Point (Tune Level) - correction to ensure PV decimal point value is shown here.

Dual Output types with Cascade / Feed-forward - correction to ensure this invalid combination is not selectable.

5 15637 Nov 98 Correction to Remote Setpoint scaling. Correction to A/M switching with output slew rate function. Correction to retransmission calculation when inputs are failed. Correction to Manual Reset value (to prevent negative settings). Correction to MODBUS code to prevent display-flicker. Correction to resistance measurement for high resistance ranges. Correction to Motorised Valve actual valve position for non-zero

based ranges. …...…………………………………Issue 5 continued overleaf:

C500 continued overleaf ...

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 19 of 39

Software HistoryC500 (continued)

C500/2001 5 15637 Nov 98 ….………………………Issue 5 continued from previous page: Instruction Manual corrected to show that Control Deadband

value is in percent (not engineering units). Correction to Alarm Time Delay to work above 32 seconds. Correction to ensure Thermocouple input fail-state operates for

engineering ranges set to max. or min. dynamic limits. Correction to non-volatile memory checksum calculations,

ensuring all non-volatile devices are read at power-up, regardless of error condition.

Corrections to x128 gain span calibration limit. The code to enable the Watchdog timer in the 68HC11 CPU has

been removed. The devices are now pre-programmed. Approach Band limits changed from 0.1 – 30.0 to 0.1 100.0 Alternative PID algorithm available for processes with long lag-

times. Corrections to Startup Autotune. Factory test rig can now set the time (via MODBUS). Interrupts are disabled when reading the commissioning switch.

6 15895 Sept 99 Modifications in respect of Logic Equation operation in order to allow an equation to produce a latch-function.

Operation of Logic Equation “NOT”-operator corrected. PID corrected to ensure control output drives in the correct

direction under process variable failure conditions. Operation of Maths Functions corrected in respect of maths

result failure states. Analog O/P2 engineering range configuration frames do not

appear if output is assigned to a control output. Modifications to ensure correct operation of deviation alarms on

controllers set-up for On/Off control. Analog outputs assigned to a control output will always operate

over a 0 – 100% engineering range. On indicator versions, control output saved to non-vol memory. Auto-tune now available on Cascade and Motorised Valve (Fb). A/M state and O/P level accessible via MODBUS on Cascade. Process variable alarms operate correctly even when the process

variable is not assigned to input 1 Heat/Cool outputs are set to correct “configured output” when

switching from Automatic to Manual control via digital signals, bumpless transfer occurs when returning to automatic control.

Global alarm acknowledge added.7 16029 July 00 Polarity of Digital Outputs corrected for Time Proportioning

control. Fixed fault of Control Output going to the start of decade when

switching from Manual to Auto mode. e.g. o/p would go from 67 to 60.

Corrected application of Output Slew Rate for Single Loop, Time Proportioning Templates.

Added Output Slew Rate to Cascade Templates with Feedback Motorized valve.

Modifications made to ensure bumpless transfer occurs when switching between PID terms

Modbus Coils 33-36 (Relay state) now work correctly

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 20 of 39

Motorised Valve Output with Feedforward templates now work correctly

Correction made to ensure that Boundless Output with Feedforward cannot be selected from the front panel.

8 16038 Mar 00 Motorised valve with Feedback. Correction made to ensure that when a desired valve position is set via modbus, the valve is driven to the desired valve position.

9 16176 Nov 01 modified to reduce faulty (intermittent) communication when using commander configuration editor

modified to ensure correct operation of auto/manual station when changing from auto to manual with configured o/p set to "LAST"

10 16187 Feb 02 modified to eliminate faulty (intermittent) communication when using commander configuration editor

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 21 of 39

Software History C1900

Issue DCN Date CommentsC1900/2001 1 14252 Jul 94 Introduction of recorder only software.

2 14110 Aug 94 Introduction of controller software.3 14116 Aug 94 Introduction of advanced software features.4 14119 Sept 94 Correction to the output test ramp.

Process variable units now displayed in the operator page. Change made to prevent pen 2 colliding with the true time event

pen during calibration.5 14148 Feb 95 MODBUS serial communications introduced.

Square root linearizer fault corrected. Integral action fault corrected. Crystal frequency no longer altered by company standard

download on controllers (see issue 7). The analog test ramp is turned off automatically once the

security link is placed in the secure position.6 14411 Mar 95 PID fault when used with offset engineering ranges corrected.

RTD linearizer adjustment to two decimal places added.7 14420 Apr 95 Boiler control version introduced.

12MHz crystal (calibration) added. Co. standard reset of crystal to 8MHz on recorders corrected. MODBUS write to multiple coils added. Option limits increased for boiler control versions.

8 15115 Dec 95 Introduction of Dairy (pasteuriser) version software. Correction to reverse linearization for thermocouple inputs. Correction in PID software to allow a maths result to be used as

the process variable. Correction to enable scale adjustment of remote setpoint inputs. Correction in MODBUS s/w to reduce slave CPU time-out

period.9 15367 Aug 96 Filter window increased for RTD i/p’s to improve PID control.

Low ohms input no longer fails with 0 ohms applied. 4 - 20mA i/p with RTD linearizer no longer causes input failure. Square root input more stable with low input values. Correction to linearization with non-thermocouple input type

and thermocouple linearizer selected. Correction to fault-detect limits. Interaction problem with maths results corrected. Analog output now assigned to control output as company

standard on controller versions. Input failure on power-up with filter enabled corrected. With self-seeking setpoint the new start value is no longer saved

in the non-volatile memory. Power recovery options added for ramp/soak. Correction made to option type display. Type B security changed on pasteuriser versions to allow tune

parameters to ab accessed. Changes made to 0% offset control. Corrections made to boundless control.

C1900 continued overleaf ...

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 22 of 39

Software HistoryC1900 (continued)

Issue DCN Date CommentsC1900/2001 10 15416 Mar 97 Correction so that secondary divert source does not cause divert

relay to activate. Company Standard changes. Horizontal scroll into top-level frames now no longer produces

accidental “Auto-scroll”.11 15503 Jul 97 Enhancement of totalizer wrap operation.

Introduction of C1960 versions. Correction of soak-segment power-recovery fault. Improvement to retort-recovery operation. Improvement to security of crystal frequency.

12 15507 Jul 97 Correction to corruption of crystal frequency. Correction to corruption of main analog output calibration. Correction of configuration failure on controllers following

Company standard. Correction of C1950 Series Company Standard with respect to

setpoint limits13 15590 Mar 98 Correction to ensure switching from RETORT HOLD to

RETORT RAMP occurs when process variable reaches setpoint. Correction to ensure selection of Ramp/Soak programs using

digital signals is correctly displayed. C1951 & C1952 with optional Auxiliary Input module may now

trace that signal (via the Blue Pen). Correction to holdback hysteresis on non-C1960 versions. Correction in respect of MODBUS parity. Correction to reject MODBUS messages of less than 6 chars. Correction to improve internal MODBUS message interchange.

C1900/2101 1 15614 Jun 98 Deletion of 8MHz crystal option (12MHz only now). Inclusion of RTD linearizer option for HI_OHMS input type. Alternative messages to “Ad.FAIL” provided.

2 16162 Aug 01 Modified to ensure that the first soak segment of a program does not automatically become decremented by the soak time adjustment value following a power failure/recovery.

Correction to fault in maths block software - causing average values to become corrupted if 2 or more maths blocks configured for average

3 16174 Nov 01 Introduction of delayed high/low process alarms Introduction of "micrometer" adjustment on all pens Introduction of time events on standard ramp/soak controllers

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 23 of 39

Software HistoryPR100

Issue DCN Date CommentsPR100/2101 1 14407 Mar 95 Introduction of PR100 Plus software.

2 14437 Feb 96 Random disabling of auto-scroll corrected. Pen calibration limits increased. RTD accuracy improved by addition of a resistance/RTD

calibration facility. Date now printed with time when operator message printed. Alarms now detected if they occur during easy view operation. Changing the real time clock settings does not now result in

automatic time stamps failing. Corrections made to the German language scrolls. Provision of 3 pen colours for text printing on single and two

pen instruments.3 15298 May 96 Enhancements made to reduce the chance of the ‘over

configured’ message being displayed. Enhancements made to prevent the remaining paper value from

being corrupted. Changes to the French language scrolls.

4 15436 May 97 Correction to fanfold chart reload procedure; fanfold chart cannot be rewound.

Addition to rollchart reload operation: operating vertical scroll whilst rewind active allows user to jump to “RELOAD COMPLETE” if all paper has been rewound. QA complaint 816.

Operator level memory card frames: German translations added. Chart returns to correct place to resume recording following

Cue/Review. 1 sec wrap pulse issued when predetermined count reached

irrespective of wrap on/off setting.5 15584 Feb 98 512KB and 2MB Memory Cards now locating files at correct

User Area Address on the card. 4MB Memory Card format now corrected for FAT-12 operation. French translation of “Appending File” corrected. Wrap pulses will not time-out if wrap is disabled.

6 15635 Aug 98 Correction to Totaliser count-down operation. Correction to “NO AUTO PRINT” frame script.

7 19019 Mar 00 Automatic time,date & trace printing recovers after long periods with the chart stopped

Analogue i/p spike filter is not by-passed when overrange i/p is detected

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 24 of 39

Software History

SR100

Iss DCN Date CommentsSR100/2001ASR100/2501ASR100/2001A (sp01)SR100/2001A (sp11)SR100/2001BSR100/2501B

1 16001 Dec ‘99 Introduction of SR100 2 16015 Jan ‘00 Correction to positioning of chart scale values

Foreign language corrections3 16020 Mar ‘00 Automatic time,date & trace printing recovers after long

periods with the chart stopped Memory Card option included in configurator upload

4 16025 May ‘00 Foreign language corrections5 16045 Mar ‘01 Correction of "Batch Number: XXXX " message

(applies to SP11 only) After a memory card has been formatted datalogging

cannot be "started" until file header & channel headers have been written to the card.

The characters displayed to indicate event pen position on the display have been corrected "<---" & "--->"

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 25 of 39

Software HistoryMR100

Issue DCN Date CommentsMR100/2101 1 15372 Sept 96 Introduction of MR100 software.

2 15436 May 97 Correction to fanfold chart reload procedure; fanfold chart cannot be rewound.

Addition to rollchart reload operation: operating vertical scroll whilst rewind active allows user to jump to “RELOAD COMPLETE” if all paper has been rewound. QA complaint 816.

Operator level memory card frames: German translations added. Chart returns to correct place to resume recording following

Cue/Review. 1 sec wrap pulse issued when predetermined count reached

irrespective of wrap on/off setting.3 15584 Feb 98 Changes as PR100/2101/Iss.5; does not impact on any functions

in MR100 - update is part of general xR100 release.4 15635 Aug 98 Correction to Totaliser count-down operation.

Correction to “NO AUTO PRINT” frame script.5 19019 Mar 00 Automatic time,date & trace printing recovers after long periods

with the chart stopped Analogue i/p spike filter is not by-passed when overrange i/p is

detected

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 26 of 39

Software HistoryPR250 – Main Eprom Software

Iss DCN Date CommentsPR250/2001PR250/2501

1 15427 Apr 97 Introduction of PR250 software.2 15444 May 97 Correction made to NONVOL checksum calculation following

memory-card download function.3 15509 Aug 97 Automatic Scale Printing (MR250) corrected to allow all

enabled scales to be printed. User Languages: English, German, and French texts user-

selectable. All German and French scroll translations implemented.

Memory Card: Corrections in respect of: 2M-byte and 4M-byte card formats; data-logging scan rates greater than 255 seconds; appending to file on a card that is full.

Totalizer: Changes to Wrap and Reset operation. MODBUS: Additions to Coil and Holding Register tables in

respect of Totalizer function and additional Digital Signals.

4 15537 Dec 97 Various memory-card data-logging problems (date-change, zeros omitted, digital start, follow-on-files).

Memory-card download caused corruption of module types. Printing of channel values and totalizer values: operation was

inconsistent with the manual. Operating Page Totalizer value corruption corrected.

5 15604 Apr 98 Correction to retransmit received MODBUS messages that are “lost” between master and slave processors.

Correction to ensure MODBUS comms and Configurator comms messages of less than 6 characters are ignored.

Correction to MODBUS comms in respect of parity. Limit-address for RTD test status corrected. Company Standard for MODBUS baud rate set at 9600 baud.

6 15628 Jul 98 Correction to ensure scales printed following chart reload. Operation of restarting memory-card data-logging simplified. Correction to ensure CONFIG register programmed correctly.

7 15638 Aug 98 Correction of faults that result in loss of all slow text printing. Corrections to error in data-logging feature introduced for Iss 6.

8 16016 Feb 00 Logic Equation implementation modified to allow ‘latching’ operation.

dot position calculations modified to eliminate rounding errors that are generated if very large engineering ranges are used and to ensure that pen drives to correct position during overrange/underrange conditions

Automatic time,date & trace printing recovers after long periods with the chart stopped

Introduction of PR250/2501 at issue 89 16044 Mar ‘01 Correction to fault causing analogue input A1 to be driven to

9999 when maths result M1 is allocated to a print group10 16173 Jul 01 Modifiied to ensure totalizer values from totalizers 9 to 12 are

correctly logged to memory card 11 16188 Feb 02 Various changes to improve PC config comms reliability,

specifically with the setting of Port D1 (SCI Tx) data & data direction

Analog i/p software modified to ensure correct result is

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 27 of 39

calculated when calculating gain from a negative electrical range value

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 28 of 39

Software History

PR250 – Modbus Slave Eprom SoftwareIss DCN Date Comments

PR250/2001SPR250/2501S

1 15427 Apr 97 Introduction of PR250 software.2 15444 May 97 No change from PR250/2001S issue 13 15509 Aug 97 No change from PR250/2001S issue 24 15537 Dec 97 No change from PR250/2001S issue 35 15604 Apr 98 Modification to ensure compatibility with Genesis For Windows

modbus system software6 15628 Jul 98 No change from PR250/2001S issue 57 15638 Aug 98 No change from PR250/2001S issue 68 16016 Feb 00 No change from PR250/2001S issue 7

Introduction of PR250/2501S at issue 8 PR250/2001S iss 8 is identical to PR250/2501S iss 8

9 16044 Mar ‘01 No change from PR250/2001S issue 8 PR250/2001S iss 9 is identical to PR250/2501S iss 9

10 16173 Jul 01 No change from PR250/2001S issue 9 PR250/2001S iss 10 is identical to PR250/2501S iss 9

11 16188 Feb 02 No change from PR250/2001S issue 10 PR250/2001S iss 11 is identical to PR250/2501S iss 10

Software History

SR250 - Main Eprom Software

Iss DCN Date CommentsSR250/2001SR250/2501

1 16016 Feb 00 Introduction of SR250/2001 and SR250/2501 2 16044 Mar ‘01 Correction to fault causing analogue input A1 to be driven to

9999 when maths result M1 is allocated to a print group3 16173 Jul 01 Modifiied to ensure totalizer values from totalizers 9 to 12 are

correctly logged to memory card 4 16188 Feb 02 Various changes to improve PC config comms reliability,

specifically with the setting of Port D1 (SCI Tx) data & data direction

Analog i/p software modified to ensure correct result is calculated when calculating gain from a negative electrical range value

Software History

SR250 - Modbus Slave Eprom Software

Iss DCN Date CommentsSR250/2001SSR250/2501S

1 16016 Feb 00 Introduction of SR250 software. SR250/2001S iss 1 is identical to SR250/2501S iss 1

2 16044 Mar ‘01 No change from SR250/2001S issue 1 SR250/2001S iss 2 is identical to SR250/2501S iss 2

3 16173 Jul 01 No change from PR250/2001S issue 2 PR250/2001S iss 3 is identical to PR250/2501S iss 2

4 16188 Feb 02 No change from PR250/2001S issue 3

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 29 of 39

PR250/2001S iss 4 is identical to PR250/2501S iss 3

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 30 of 39

Software History

ScreenMaster 1000 Operating System and Application

Software Issue

System Issue

DCN Date Comments

SM1000/2001 2001/1 1001/1 16132 Nov 01

Introduction of SM1001 software.

2001/2 1001/2 16140 Jan 02

Improvements to operation of archiving feature specifically with respect to corruption of smartmedia cards on insertion/removal.

2001/3 1001/3 16143 Feb 02

Addition of User adjustable contrast control.

2001/4 1001/4 16149 Mar 02

Addition of HV Dairy i/p card (HVDIC) functionality.

In Historical mode, archiving is now suspended rather than being disabled.

Fault correction: Instrument did reset every 1hr 50mins with relay boards fitted.

Fault correction: Alarm ack for Alarm B did not work is Alarm A disabled.

Fault correction: In alarm event log menu’s, unconfigured alarms were not greyed out.

2001/5 1001/4 16254 Apr 02

Addition of Optional Ethernet/Webserver Functionality.

Addition of Optional Modbus Functionality. Fault correction: When archiving analog data with a

sample rate of greater than 5 seconds, the value in the archive file may be repeated a number of times when a new record is created in the internal data file.

Fault correction: When archiving Logs, some entries may be lost if the instrument is placed offline for enough time to accumulate at least 20 entries.

Fault correction: If archiving is configured for logs only (no data archiving), when archiving is put online the archive progress dialog box can remain on permanently.

Fault correction: The Reset Archiving command only resets Data archiving not Log archiving.

Fault correction: In archiving, when a History Dialog Box is displayed but a selection is not made for a long period of time the wrong data can be archived if all data is eventually selected.

Fault correction: On the High Voltage Digital Input Card (HVDIC) the relay polarity only works in positive mode.

Fault correction: The correct contrast setting fails to get set correctly on power-up.

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 31 of 39

ScreenMaster 1000 BootloaderSoftware

IssueDCN Date Comments

SM1000/4001 4001/1 16132 Nov 01

Introduction of SM1001 software.

4001/4 16254 Jan 02

Allows updating of OS and Application(SM1000/3001) via Ethernet.

Allows updating of OS and Application(SM1000/3001) via Smartmedia or Compact Flash cards

Note : Issues 2 and 3 of the Bootloader have not been formally released

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 32 of 39

ScreenMaster 2000 Operating System and Application

Software Issue

System Issue

DCN Date Comments

SM2000/2001 2001/2 1001/2 16109 Feb 01

Introduction of SM2001 software.

SM2000/2002 2002/2 1002/2 16114 Apr 01

Introduction of SM2002 software. Introduction of Maths Equations & Logic Editor. Introduction of Horizontal Chart View. Software efficiency improvements. Introduction of WinCE 3.0 operating system Problem Corrected:- unit did not always switch the

back light on.2002/3 1002/3 16115 Apr

01 Problem Corrected:- Hybrid module only partially

worked. Problem Corrected:- Maths & Logic archiving errors. Problem Corrected:- Rate alarms do not work

correctly. Problem Corrected:- Chart view Screen intervals

menu. Sometimes did not display correct information.2002/4 1002/3 16120 May

01 Problem Corrected:- If the time is changed backwards

the new time is sometimes not accepted. Problem Corrected:- Programming ‘objects’ don’t

support years greater than 2037.

2002/5 1002/3 16121 May 01

Problem Corrected:- the exit menu item was enabled in Instrument status. Now removed

2002/6 1002/4 16131 Oct 01

Introduction of German language support. Problem Corrected:-exiting configuration or power

down/up caused system clock to jump forward, most notable with long recording sample rates.

Improved trace resolution for low resolution ranges. Improved time for a step input change to be plotted

onto the trace. Problem Corrected:- Scrolling in HCV and using

Historical Goto can result in a temporary loss of trace information.

Problem Corrected:- reasons found for unit crashing when storage card is removed have been eliminated.

Introduction of Reset Archiving. Problem Corrected:- an o/p from a totalizer on a given

channel cannot be assigned as the source for that channel. If the source of a channel is an output from a totalizer then the channel cannot have a totalizer itself.

Problem Corrected:- stopped these characters \ / : * ? “ < > | º ² ³ Ω ˜ being used to make filename for archiving.

2002/7 1002/5 16133 Nov 01

Improvement to operation of analog inputs – failure of comms to analog i/p modules was causing all inputs to be displayed as –99.9

Improvement to handling of alternative languages – Language was being changed when configuration saved using “save” rather “save as current”

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 33 of 39

2002/8 1002/6 16139 Jan 02

Improvements to operation of archiving feature specifically with respect to corruption of smartmedia cards on insertion/removal.

2002/9 1002/7 16255 Apr 02

Addition of Optional Ethernet/Webserver Functionality.

Fault correction: When archiving analog data with a sample rate of greater than 5 seconds, the value in the archive file may be repeated a number of times when a new record is created in the internal data file.

Fault correction: When archiving Logs, some entries may be lost if the instrument is placed offline for enough time to accumulate at least 20 entries.

Fault correction: If archiving is configured for logs only (no data archiving), when archiving is put online the archive progress dialog box can remain on permanently.

Fault correction: The Reset Archiving command only resets Data archiving not Log archiving.

Fault correction: In archiving, when a History Dialog Box is displayed but a selection is not made for a long period of time the wrong data can be archived if all data is eventually selected.

Fault correction: On the High Voltage Digital Input Card (HVDIC) the relay polarity only works in positive mode.

Various corrections have been made to Modbus functionality as detailed below ;

a) Fails to respond to messages after receiving a large number of packets (5000+).

b) Resets when downloading a configuration to an ML using the same RS485 lines.

c) Does not respond to messages sent by a quick master. i.e. A master sends a packet and, upon receiving the response, sends another packet within 40mS, the SM fails to ‘see’ the second packet.

d) Fails to reply to up to 20% of messages received.

e) If the instrument is connected to a master at the time of power up, it immediately begins to miss messages.

f) At low baud rates the instrument is unable to read the maximum number of registers(120). At 1200 baud only ~ 65 registers can be read.

g) Excessive time consumption in the 100mS thread when communicating.

h) At low baud rates it is possible for traces not to be plotted when reading a large number of registers.

i) Good packets being thrown away due to error checking mechanism.

j) Modbus protocol not being adhered to (waiting 13.5 character times to signal an end of message).

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 34 of 39

ScreenMaster 2000 BootloaderSoftware

IssueDCN Date Comments

SM2000/4001 4001/1 16109 Feb 01

Introduction of SM2001 software.

4002/2 16114 Apr 01

Allows loading of larger flash image.

4002/4 16254 Jan 02

Allows updating of OS and Application(SM2000/3001) via Ethernet.

Allows updating of OS and Application(SM2000/3001) via Smartmedia or Compact Flash cards

Note : Issue 3 of the Bootloader has not been formally released

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 35 of 39

Software History

Commander Configuration Editor

Issue DCN Date CommentsC100/3000 1 15268 Apr 96 Introduction of C100/C150 configurator.

2 15356 July 96 Change made to avoid set-up problems on some PC’s. Prompts now start with a capital letter. Product code format in hardware window corrected. Correction to export to word to prevent program crashing. Corrections to alarm trip limits. Report preview corrections. Font selection limited to true type fonts.

3 15393 Nov 96 Correct loss of hardware assignments. Filename changed when new configuration is selected. File not found error no longer displayed on exit. Correct alarm limits always selected. Allows for independent hysteresis settings on alarms.

4 15429 Apr 97 MR250, PR250, L150, L160, C160 added. “Close” function added. Enhanced port detection to cater for laptops. Generally enhanced level of error checking.

5 15534 Dec 97 Correction to faulty PR250 download. Correction to L150/L160 faulty download in respect of custom

linearizer.6 15605 Apr 98 Correction of miscellaneous faults on C100, C150, L150, L160,

C160, MR250, PR250, V100, C250, and V250. Introduction of C500, C250, V100, and V250.

7 15630 Aug 98 Correction of miscellaneous faults on C150, MR250, PR250, C500, C250, and V250.

8 15862 Jan 99 C350 and C360: Forms added. C100 and C250: Direct Acting can now be set. C500: Motorised Valve information added to report. C500: Analog output 2 settings corrected. C500: Electrical High and Low values set to zero when THC

and RTD input types selected. C250: Now able to assign 2nd retransmission to control output . C500: Analog input 3 with resistance feedback restricted to 0 dp. L160: Totalizer removed from report. L150/L160: product-codes problems on start-up corrected. C350/C360 and C500: Analog output can now be freely

assigned when an analog control type is selected. MR250/PR250: 2 / 4 wire MODBUS options reversal corrected.

9 15865 Feb 99 German language options awaiting completion (and therefore disabled).

10 16028 Jun 00 CR100 added SR100A & SR100B added L160, C160 Custom Lineariser Breakpoint 13 fault corrected “X” Close removed from Custom Lineariser Analog inputs DP fault corrected Local/Remote Panel Key Enable and Alarm Acknowledge Front

Panel Key enable hidden on C360 Cascade with Dual Analog heat/cool faults corrected Motorised Deadband DP added to report

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 36 of 39

Print report from Icon set to only print selected contents C350 and C500 P&I terms 3&4 Slider bar corrected C355 forms added to C350

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 37 of 39

Clearspan Products Summary

PX100 (MK2 processor board)

Part No. Issue Size DCN Date Pens Description

PX100/2101 1 128 Sept 90 1 RelayPX100/2102 1 128 Sept 90 2 RelayPX100/2103 3 128 13860 Nov 92 3 Relay

PX100/2104 1 128 Sept 90 1 RTXPX100/2105 1 128 Sept 90 2 RTXPX100/2106 3 256 13860 Nov 92 3 RTX

PX100/2107 1 128 Sept 90 1 PID/TPX100/2108 1 256 Sept 90 2 PID/T

PX100/2111 1 128 Sept 90 1 PID/APX100/2112 1 256 Sept 90 2 PID/A

PX100/2113 1 128 Sept 90 1 Flow/AnPX100/2114 1 256 Sept 90 2 Flow/AnPX100/2115 3 256 13860 Nov 92 3 Flow/An

PX100/2116 1 128 Sept 90 1 RTX + Flow/AnPX100/2117 1 256 Sept 90 2 RTX + Flow/AnPX100/2118 3 256 13860 Nov 92 3 RTX + Flow/An

PX100/2119 1 128 Sept 90 1 Flow/FrequencyPX100/2120 1 256 Sept 90 2 Flow/ FrequencyPX100/2121 3 256 13860 Nov 92 3 Flow/ Frequency

PX100/2122 1 128 Sept 90 1 RTX + Flow/ FrequencyPX100/2123 1 256 Sept 90 2 RTX + Flow/ FrequencyPX100/2124 3 256 13860 Nov 92 3 RTX + Flow/ Frequency

PX100/2129 1 256 13391 Oct 91 2 %RHPX100/2130 3 256 13860 Nov 92 3 %RH

PX100/2201 1 128 Sept 90 1 Serial TransPX100/2202 1 256 Sept 90 2 Serial TransPX100/2203 3 256 13860 Nov 92 3 Serial Trans

PX100/2201S 2 128 13316 Sept 91 1 S - Serial Slaves also used on P100M VersPX100/2202S 2 128 13316 Sept 91 2 TPX100/2203S 1 128 13316 Sept 91 3 U

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 38 of 39

Clearspan Products Summary

PX100 (MK3 processor board)

Part No. Issue

Size DCN Date Pens Description

PX100/2301 1 128 14133 Mar 95 1 BasicPX100/2302 1 128 14133 Mar 95 2 BasicPX100/2303 1 256 14133 Mar 95 3 Basic

PX100/2304 1 128 14133 Mar 95 1 RetransmissionPX100/2305 1 128 14133 Mar 95 2 RetransmissionPX100/2306 1 256 14133 Mar 95 3 Retransmission

PX100/2307 1 128 14133 Mar 95 1 Time proportioning PIDPX100/2308 1 256 14133 Mar 95 2 Time proportioning PID

PX100/2311 1 128 14133 Mar 95 1 Analog PIDPX100/2312 1 256 14133 Mar 95 2 Analog PID

PX100/2313 1 128 14133 Mar 95 1 FlowPX100/2314 1 256 14133 Mar 95 2 FlowPX100/2315 1 256 14133 Mar 95 3 Flow

PX100/2316 1 128 14133 Mar 95 1 Flow + retransmissionPX100/2317 1 256 14133 Mar 95 2 Flow + retransmissionPX100/2318 1 256 14133 Mar 95 3 Flow + retransmission

PX100/2319 1 128 14133 Mar 95 1 Flow / frequencyPX100/2320 1 256 14133 Mar 95 2 Flow / frequencyPX100/2321 1 256 14133 Mar 95 3 Flow / frequency

PX100/2322 1 128 14133 Mar 95 1 Flow / frequency + retransmissionPX100/2323 1 256 14133 Mar 95 2 Flow / frequency + retransmissionPX100/2324 1 256 14133 Mar 95 3 Flow / frequency + retransmission

PX100/2330 1 256 14133 Mar 95 3 %RH

PX100/2401 1 128 14133 Mar 95 1 Serial communicationsPX100/2402 1 256 14133 Mar 95 2 Serial communicationsPX100/2403 1 256 14133 Mar 95 3 Serial communications

ABB LTD – D&D Department Release. P. Evans

Current Product Software Issues (last Updated 30/5/2001) Page 39 of 39

Clearspan Products Summary

PX105 (MK3 processor board)

Part No. Issue Size DCN Date Pens Description

PX105/2211 3 512 13891 Sept 93 1 + Relay O/PPX105/2212 3 512 13891 Sept 93 2 + Relay O/PPX105/2213 3 512 13891 Sept 93 3 + Relay O/P

PX105/2214 3 512 13891 Sept 93 1 + EventPX105/2215 3 512 13891 Sept 93 2 + Event

PX105/2216 3 512 13891 Sept 93 1 Serial communicationsPX105/2217 3 512 13891 Sept 93 2 Serial communicationsPX105/2218 3 512 13891 Sept 93 3 Serial communications

PX105/2241 3 512 13891 Sept 93 1 Time prop analog PIDPX105/2242 4 512 13891 Sept 93 2 Time prop analog PIDPX105/2243 4 512 13891 Sept 93 3 Time prop analog PID

PX105/2244 3 512 13891 Sept 92 1 Profile controlPX105/2245 4 512 13891 Sept 93 2 Profile control

PX105/2246 3 512 13891 Sept 93 1 Time prop analog PID + SerialPX105/2247 4 512 13891 Sept 93 2 Time prop analog PID + SerialPX105/2248 4 512 13891 Sept 93 3 Time prop analog PID + Serial

PX105/2251 3 512 13891 Sept 93 1 + Relay O/P - FlowPX105/2252 3 512 13891 Sept 93 2 + Relay O/P - FlowPX105/2253 3 512 13891 Sept 93 3 + Relay O/P - Flow

PX105/2256 3 512 13891 Sept 93 1 + Relay O/P + Serial - FlowPX105/2257 3 512 13891 Sept 93 2 + Relay O/P + Serial - FlowPX105/2258 3 512 13891 Sept 93 3 + Relay O/P + Serial - Flow

PX105/2292 3 512 13891 Sept 93 2 Relative humidityPX105/2293 3 512 13891 Sept 93 3 Relative humidity

PX105/2297 3 512 13891 Sept 93 2 Relative humidity + SerialPX105/2298 3 512 13891 Sept 93 3 Relative humidity + Serial