softswitch128 switching system - w. w. grainger...• softswitch® relay is rated for 16 a...
TRANSCRIPT
369-346b 1 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
System Overview
Softswitch128® is a switching system that is ideal for small to medium sized switching projects. A system consists of panels, control stations, occupancy sensors, and photocells. Softswitch128® panels contain Lutron’s one million cycle Softswitch® relay and the Softswitch128® Controller.
Softswitch128® is easy to install and simple to program. Softswitch128® also includes a CEC/Title24 approved astronomical time clock for system automation.
System Features
•Digitalcontrolforupto512circuits.
•Addupto32digitalcontrolstations(wallstationsandinterfaces) for multiple points of control.
•Uptosixteen(16)Softswitch128® panels may be used.
•AddtheSoftswitch128®ExpansionModule(XPS-E-120/277-FT)tothesystemforincreasedcontrolstationcapacity.Threelinksofupto32controlstationseach(96controlstationstotal)maybeaddedwiththeExpansionModulepresent.
•IntegratedCECTitle24listedastronomicaltimeclock.
•Lutron® Softswitch® technology for every switched output(resistive,inductiveandcapacitve)tofull16A.
•Softswitch® relays are rated for all light sources as well as AC general use motors.
•RS232interfaceavailable(OMX-RS232).
•Contactclosureinputandoutputdevicesavailable(OMX-IOandOMX-CCO-8).
•Keyswitchwallstationsavailable(NTOMX-KS).
•Normaloremergencypanelcapability.
•Softswitch128®panelisprewiredandpre-tested.
•Panelsfor120/277 V~,347 V~,and480 V~ applications. Contact a Lutron representative for details on347 V~and480 V~ switching.
•208 V~loadsarewiredphase-to-phasein120 V~ panels. See Lutron®ApplicationNote#102fordetails.
•Feed-through,branchcircuitbreaker,andrough-intypepanels are available.
Softswitch128®Panel
Softswitch128® Switching System
369-346b 2 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
Overview
The Softswitch128® Controller is used to configure the entire Softswitch128® system. The controller featuresanLCDuserinterfacetofacilitateprogramming all switching system and astronomical timeclock(ATC)parameters.
Features
•Programwallstationstorecalllightpatterns,totoggleanyswitchleg(s),toactivatedelay-to-offandtoactivate contact closures on a button by button basis.
•Integratedastronomicaltimeclock(ATC)automatesswitching and contact closure outputs with up to 500 user-definedeventswithin7dailyschedulesand40holidayschedules.Eachdaymayhave25events.
•ATCeventsautomaticallyselectpatterns,startafter-hoursmode,orendafter-hoursmode.
•Eventsmaybecopiedandpastedforfastprogramming.
•ATCeventsmaybetriggeredbytimeofdayorbyanoffset from sunrise or sunset.
•Systemlocationisprogrammablebyinternalcitydatabase or by specifying latitude and longitude.
•ATCautomaticallyadjustsforleapyearanddaylightsavingstime(whereapplicable).
•Programmableafter-hoursmodewithuser-selectable“blink warn” and user programmable refresh time.
•Twointegrateduser-configurablecontactclosureinputs.
•Overridecapabilityisavailableatthepanelforcontrols, timeclock, and switch legs.
•ControllerislocatedintheSoftswitch128® panel for easy access.
Softswitch128® Controller
Softswitch128® Controller
369-346b 3 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
Standards
•ULListed
•CSA
•NOM
• Seismic Certified Available1(TestMethodAC156.ReferenceOSHPDPreapprovalOSP-0215-10)
Power
•Inputpower:120/277 V~,347 V~2and480 V~2. Allvoltages50/60 Hz,phase-to-neutral.
•BranchCircuitBreakers:UL-ratedthermalmagnetic.AICratings: 120V~10,000A 277V~18,000A 347V~14,000A
•Lightningstrikeprotection:MeetsANSI/IEEEstandard62.41-1980.Canwithstandvoltagesurgesupto6000 V~andcurrentsurgesupto3000 A.
•10-yearpowerfailurememory:restoreslightingtolevels prior to power interruption.
Load Types (relay ratings)
•16ATungsten,120 V~
•16AACGeneralUse,100-347 V~
•16AElectricDischargeLamp(ballast)
•16AResistive,277 V~
•16AInductive,100to347 V~
•1/2HP,120 V~
•1HP,220to277 V~
Switching Modules (120 V~, 277 V~, 347 V~)
•Softswitch®relayisratedfor16Acontinuoususe,whichisthemaximumcontinuousloadfora20 AOvercurrentProtectionDevice(BranchBreaker).
•PatentedSoftswitch® circuit eliminates arcing at mechanical contacts when loads are switched. Extendsrelaylifetoanaverageof1,000,000cycles(on/off)forresistive,capacitiveorinductivesources.
•Relayismechanicallyheld.
Specifications
1 Contact your Lutron representative for details.2 ContactyourLutronrepresentativefordetailson347 V~and480 V~ switching.
Wiring
•Internal: Wired and tested by Lutron.
•System communications:lowvoltageIECPELV/NEC® Class 2 wiring connects Softswitch128® panels to control stations.
•Line (mains) voltage: feed and load wiring only (feed-throughSoftswitch128® panels also require a feed for the Softswitch128® controller).
Physical Design
•Enclosure:NEMA-Type1,IP-20protection;16U.S.gaugesteel.Indoorsonly.
•Weight: 27 lb(13 kg)forMinipanels 80 lb(37 kg)forStandardpanels
135 lb(62 kg)forLargepanels
150 lb(69 kg)forExtraLargepanels
•SeismicCertificationLimits:SDS=2.5g,z/h=1.0,IP=1.5.ContactLutronfordetails.
Mounting
•MiniandStandardsizepanels:surfacemountorrecessmountbetween16 in(40 cm)studs.
•LargeorExtraLargepanels:surfacemountonly.
Environment
•32to104 °F(0to40 °C). Relativehumiditylessthan90%non-condensing.
Short Circuit Current Ratings (otherratingsavailable)
Standard Panel Type V~ SCCR Rating
XPSFeed-through Panels(allsizes) 120/277 25,000A
XPSMainLug Panels(allsizes) 120/277 25,000A
Continued on next page...
369-346b 4 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
Softswitch128® Controller
•ConfiguresentireSoftswitch128® system.
•Twolowvoltage(15to24 V-) contact closure inputs, momentary or maintained, pull up or pull down.
•EmergencySensing.
•AstronomicalTimeClock.
•DigitalControlLink.
•MountedinSoftswitch128® panel.
Astronomical Time Clock (ATC)
•Capableofupto500events.
•7dailyschedulesand40holidayschedulesareavailable.
•25eventsperday.
•Holidayeventsareprogrammableoneyearinadvance.
•Holidayschedulesareprogrammabletorunforupto90days.
•ATClocationprogrammablebybuilt-incitydatabaseor by entering latitude and longitude, plus a sunrise or sunset offset to adjust for local geography.
•CECTitle24listed.
OMX-RS232
•InterfacestheSoftswitch128®systemtoaPC,touchscreen,orbuildingmanagementsystem(BMS).
•UseRS232stringstosetlightlevelsandenable/disabletime clock events.
•RefertoSoftswitch128® programming guide for more information and programming features.
OMX-AV
•5lowvoltagecontactclosureinputsand5outputs.
•Inputsmayselectpatterns,togglelights,oractivatedelay-to-off.
•Interfaceswithoccupancysensorsordaylightsensors(withrelay)toactivatepatternsorturnofflightsinanunoccupied space.
Specifications (continued)
•Contactclosureoutputsareactivatedbybuttonpresses, contact closure inputs, time clock events, or emergency status.
•SeeOMX-AVspecificationformounting,wiring,contact closure output ratings, and voltage limits.
NOTE: only the features listed are supported by Softswitch128®.
OMX-CCO-8
•Integratesthirdpartymotorizedwindowtreatmentsor A/V equipment.
•Outputsareactivatedbybuttonpresses,contactclosure inputs, time clock events or emergency status.
•SeeOMX-CCO-8productspecificationformounting,wiring and voltage limits.
Contact Closure Inputs
•TwoclosureinputsareavailableattheSoftswitch128® controller.
•Maybeconfiguredaspullupto15or24 V- (externallysupplied)orpulleddowntocommon.
•Programmableasmaintainedormomentary.
•Functionsareprogrammableoncontactclose,contact open or both.
Wall Stations
•OnetosevenbuttonseeTouch® and single button FOMXcontrolsareavailable.
•Buttonsareprogrammabletoselectpatterns,togglecircuitsoractivatedelay-to-off.
•ButtonsareprogrammedattheSoftswitch128® controller.
•Wallcontrolsarepoweredbyandcommunicateviathe Softswitch128®low-voltagecommunicationlink.
•SeespecificationsubmittalsforseeTouch® and FOMXwallstationsforwiringandmountingdetails.
•Keyswitchcontrolisalsoavailable.
369-346b 5 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
Numberof Circuits
Prefix
XPS24 - 1204ML - 20
Prefix
XPS(Softswitch128® panels)
Number of Circuits
Totalnumberofcircuits(switchlegs)inthepanel.
Voltage
Omitforfeed-throughpanels.
120(100to127 V~or208 V~ )
277(277 V~ )
3471(347 V~ )
Feed
FT(feed-throughpanels)
4ML(3phase4wirefeed)
3ML(1phase3wirefeed)
Breaker Rating
Omitforfeed-throughpanels.
20(20 Abranchcircuitbreakers;20 A branch circuit breakershavea16 A continuous load rating).
VoltageFeed
BreakerRating
Example Model Numbers
Example 1
Modelnumberfor120 V~ Softswitch128® panel with28circuitsandLutroninstalled20 A branch circuitbreakers:
XPS28-1204ML-20
Example 2
Modelnumberfor120/277 V~ Softswitch128® panelwith12circuitswithoutcircuitbreakers:
XPS12-FT
Example 3
Modelnumberfora120 V~ Softswitch128® panel with12circuitsand20 A branch circuit breakers andasplit-phasefeeder:
XPS12-1203ML-20
Example 4
Modelnumberfora347V~ Softswitch128® panel with 24 circuits with Lutron®installed20 A branch circuitbreakers:
ContactyourLutronRepresentative
How to Build a Model Number
1 Custom panel construction required, contact Lutron for model number and lead time.
369-346b 6 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
Wire Sizes
•14to10AWG(2.5to4.0mm()forFeedWiringandSwitchLegs(toloads).
•Power(Hot/Live)andSwitchedHot/LiveconnectdirectlytoTerminalBlockforSwitchLegs.
Feed-through Softswitch128® Panel Models(withoutbranchcircuitbreakers)
Mini Softswitch128® Dual-Voltage Feed-through Models for 120 V~, 277 V~, or 347 V~1
Standard Softswitch128® Dual-Voltage Feed-through Models for 120 V~, 277 V~, or 347 V~1
Panel Model Switch Legs Feed Type Maximum FeedXPS8-FT 8
Feed-through 20AXPS12-FT 12
XPS16-FT 16
Panel Model Switch Legs Feed Type Maximum FeedXPS20-FT 20
Feed-through 20A
XPS24-FT 24XPS28-FT 28XPS32-FT 32XPS36-FT 36XPS40-FT 40XPS44-FT 44XPS48-FT 48
1 Custom panel construction required, contact Lutron for model number and lead time.
369-346b 7 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
Wire Sizes for Switch Legs
•14to10 AWG(2.5to4.0 mm()
1 20 Abreaker,16 Acontinuousloadrating.2 Custom panel construction required, contact Lutron for model number and lead time.
Softswitch128® Panels with Branch Circuit Breakers
Standard Softswitch128® Panels with Circuit Breakers for 120 V~ (max. feed is 200 A)
Large Softswitch128® Panels with Circuit Breakers for 277 / 347 V~2 (max. feed is 250 A)
Large Softswitch128® Panels with Circuit Breakers for 120 V~ (max. feed is 225 A)
Extra Large Softswitch128® Panels with Circuit Breakers for 277 / 347 V~2 (max. feed is 300 A)
Model Prefix Switch Legs Feed Type Branch Breaker1
XPS8 83Ø4 Wor1Ø3 WMainLugAccepts 4 AWG(25 mm()to250 kcmil (mcm)(120 mm()
20A
XPS12 12XPS16 16XPS20 20XPS24 24XPS28 28
Model Prefix Switch Legs Feed Type Branch Breaker1
XPS8 83Ø4 WMainLugAccepts 4 AWG(25 mm()to 350 kcmil (mcm)(185 mm()
20A
XPS12 12XPS16 16XPS20 20XPS24 24XPS28 28
Model Prefix Switch Legs Feed Type Branch Breaker1
XPS32 32 3Ø4 Wor1Ø3 WMainLugAccepts 4 AWG(25 mm()to 250 kcmil (mcm)(120 mm()
20AXPS36 36
XPS40 40
XPS42 42
Model Prefix Switch Legs Feed Type Branch Breaker1
XPS32 32 3Ø4 WMainLugAccepts 4 AWG(25 mm()to 350 kcmil (mcm)(185 mm()
20AXPS36 36
XPS40 40
XPS42 42
369-346b 8 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
Type Standard GFI EPD AFI K HID SWNAIC Rating (kAIC) 10 22 42 65 10 22 10 10 10 10 10NumberofPoles 1 2 3 1 2 1 2 3 1 2 1 1 2 1 1 1 2 3 11 22
10A X X X X X X15A X X X X X X X X X X X X X X X X X X X20A X X X X X X X X X X X X X X X X X X X25A X X X X X X X X X X X X X X X X X X30A X X X X X X X X X X X X X X X X X X35A X X X40A X X X X X X X X X X45A X X X X50A X X X X X X X X X X60A X X X X X X70A X X X X80A X X X90A X X X100A X X X110A X X125A X X
120 V~and277 V~XPPanelswithbranchcircuitbreakersmaybeorderedwithgeneralusebreakerspopulatedinthepositionsavailableaftertheswitchingmoduleshavebeenpre-wired.Circuitbreakersforswitchedcircuitsmayalsobeselected;theoptionsare10,15,and20 Asingle-polecircuitbreakers.Thefollowing tables list available options.
Am
per
e R
atin
g
Type StandardAIC Rating (kAIC) 18 35 65NumberofPoles 1 2 3 1 2 3 1 2 3
15 X X X X X X X X X20 X X X X X X X X X25 X X X X X X X X X30 X X X X X X X X X35 X X X X X X X X X40 X X X X X X X X X45 X X X X X X X X X50 X X X X X X X X X60 X X X X X X X X X70 X X X X X X X X X80 X X X X X X90 X X X X X X100 X X X X X X110 X X X X X X125 X X X X
Am
per
e R
atin
g
ContactLutronIntegratedSystemsfordetailedorderinginformation.1 1PoleSWNBreakeroccupies2spaces2 2PoleSWNBreakeroccupies3spaces
Legend
GFI–GroundFaultCircuitInterrupter(6mA)EPD–EquipmentGroundFaultProtection
(30mA)AFI–ArcFaultInterrupterK–KeyOperatedHID–ForHighIntensityDischargeLightingSWN–SwitchNeutralBreaker
277 V~ Breaker Options
General Use Breakers
120 V~ Breaker Options
369-346b 9 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
2.21(56)
1.34(34)
2.21(56)
4.09(104)
15.13(384)
14.38 (365)
0.15(4)
4.15(105)
24.00(610)
10.75(273)
21.50(546)
8.00(203)
15.875(403)
24.50(622)
Mini Softswitch128® Panel Dimensions
Left Side View
Top View
Right Side View
Bottom View
Suggested Mounting Height
MountMiniSoftswitch128®ataheightof45 in (1140 mm),measuredfromfloortobottomofpanel foroptimalLCDviewing.
Alldimensionsshownas:in(mm)
Front View
Cover
369-346b 10 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
4.15 (105)
41.75 (1060)
2.69 (68)
2.43 (62)
15.875(403)
8.00(203)
14.375(365)
59.50 (1511)
2.43 (62)11.00(279)
15.125(394)
59.00(1499)
4.21(107)
0.150(4)
Standard Softswitch128® Panel Dimensions
Bottom View
Left Side View
Top View
Right Side View
Suggested Mounting Height
MountStandardSoftswitch128®ataheightof26 in (660 mm), measured from floor to bottom of panel for optimalLCDviewing.
Alldimensionsshownas:in(mm)
Front View
Cover
369-346b 11 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
6.30
0.15
(160)
3.34 (85)
45.0(1143)
18.50 (470)
63.00(1600)
22.75 (578)
22.0 (559)
2.50 (64)
23.50 (597)
63.50(1613)
(4)
6.1(155)
Large Softswitch128® Panel Dimensions
Left Side View Right Side View
Top View
Bottom View
Suggested Mounting Height
MountLargeSoftswitch128® at a height of 10 in(254 mm),measuredfromfloortobottomofpanelforoptimalLCDviewing.
Alldimensionsshownas:in(mm)
Front View
Cover
369-346b 12 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
6.30(160)
3.45 (88)
68.00(1727)
18.50 (470)
22.75 (578)
3.0 (76)
23.50 (597)
82.50(2096)
0.15(4)
6.1(155)
22.0 (559)
82.00(2083)
Extra Large Softswitch128® Panel Dimensions
Left Side View Right Side View
Top View
Bottom View
Suggested Mounting Height
MountExtraLargeSoftswitch128® at a height of7 in(178 mm),measuredfromfloortobottomofpanelforoptimalLCDviewing.
Alldimensionsshownas:in(mm)
Front View
Cover
369-346b 13 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
•Forindooruseonly!
•Consultdimensionspagesforpanelsize,conduitknockouts, and mounting holes.
•Mountwhereambienttemperatureis32to104 ºF (0to40 ºC).
•Panelsweighupto150 lb(68.5 kg).Reinforcewallstructure for weight and local codes.
•Mountpanelwhereaudiblenoiseisacceptable.(internalrelaysclick.)
•Mountpanelsoline(mains)voltagewiringisatleast6 ft(1.8 m) from sound or electronic equipment and wiring.
•Mountwithin7ºoftruevertical.
Surface Mounting
•Lutronrecommendsusing0.25 in(6 mm) mounting bolts.
•Leave1.25 in(32 mm) clearance on each side of panel for cover.
Recess Mounting
•Mounttowallstudbyscrewingthroughslotsincorners of panel.
•Mountpanelbetweenflushand0.125 in(32 mm) below finished wall surface.
DistributionPanel(ifpanelisfeed-through style).
FeedWiringand Switch Legs to loads
IEC PELV/NEC® Class 2 Wiring hereonly!Usethis location for proper voltage spacing.
FeedWiringand Switch
Legs
FeedWiringand Switch Legs to loads
FeedWiringand Switch
Legs
Front View Side View Front View Side View
DistributionPanel(ifpanelisfeed-through style).
Suggested Mounting Height
ForoptimumviewingoftheSoftswitch128® Controller, mount Softswitch128® panels at the recommended distancefromthefloor(measuredfromfloortobottomof panel).
Mounting for Softswitch128® Panels
Panel Size DistanceMiniandTUB16* 45in(1140mm)StandardandTUB48* 26in(660mm)Large 10in(254mm)ExtraLarge 7in(178mm)
IEC PELV/NEC® Class 2 Wiring hereonly!Usethis location for proper voltage spacing.
* Seepage16formoreinformation.
369-346b 14 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
HSH
HSH
HSH
HSH
H
NNN
H
HH
H
Ground
Ground
Do not wire tothese terminals
Neutral
277 V~
120 V~
Neutral
{ 120 V~120 V~
277 V~ControlFeed
120 V~ControlFeed
OR
H
NNN
H
HH
H
H
NNN
H
HH
H
H
NNN
H
HH
H
H
NNN
H
HH
H
Wire the Softswitch128®panelasshown.UseatroughwhentheSoftswitch128®Panelisnotadjacenttoadistributionpanel.SpliceNeutralsintrough.
Donotremovebypassjumpersuntilloadwiringisverified.
Leaving bypass jumpers installed allows Softswitch128® panels to be used to provide temporary lighting, until load wiring is verified.
XPSwitchingModule (4circuits)
Softswitch128® Controller
Hot
Neutral
Load
Switched Load Wiring
Each switched circuit requires a dedicated 20 A circuit breaker and feed wiring to/from a distribution panel.
Control Wiring Control wiring requires a dedicated feed and circuit
breaker.
Wire Sizes•14to10 AWG(2.5to4.0 mm2)forFeedWiringand
Switched Load Wiring.•Power(Hot/Live)andSwitchedHot/LiveconnectdirectlytoTerminalBlockforSwitchLegs.
Feed-through Softswitch128® Wiring Overview
GroundBus
CircuitBreaker
Control Circuit•Suppliespowerforinternaloperation.• Lutronrecommendsadedicated120 V~ or 277 V~,20 A,1phase2wirefeedtopowerthecontrol circuit in the panel.
• Ifcontrolcircuitistappedfromacircuitthatpowersarelayinthepanel,itdrawsamaximumof1.5 Atoward the total load for that circuit.
369-346b 15 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
HSH
HSH
HSH
HSH
Wire Sizes
Softswitch128® panel load center accepts the followingfeederwiresizes:
Wireswitchedloadsasshown:
Allloadwiringsizesmustbebetween14to10AWG(2.5to4.0mm2).
Softswitch128® Controller
SwitchedHot
Neutral MainFeeds:PhaseA,B,C andNeutral
XPSwitchingModule(4circuits)
Softswitch128® with Branch Circuit Breakers Wiring Overview
Donotremovebypassjumpersuntilloadwiringisverified.
Leaving bypass jumpers installed allows Softswitch128® panels to be used to provide temporary lighting until load wiring is verified.
GroundBus
NOTES
•For120 V~ and 277 V~ panels that have 28 or less switch legs, a dedicated 20 Abreakerisprovidedtopower the control circuit.
•For120 V~ and 277 V~ panels that have 32ormoreswitchlegs,thecontrol circuit is powered from circuitbreaker#1whichalsopowersrelay#1.Thecontrolcircuitcoulddrawamaximumof1.5 Atowardthetotalloadcapacity for that circuit.
Load
120 V~ 277 / 347 V~
4 AWG(25 mm2) to250 kcmil(mcm)(120 mm2)
4 AWG(25 mm2) to350 kcmil(mcm)(185 mm2)
369-346b 16 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
NOTES
•Emergency Power: The additional 18 AWG(0.75 mm() wireisa“sense”linefromterminal5ofanotherPanel.ThissenselineallowsanEmergency(Essential)LightingPanelto“sense”whenNormal(Non-Essential)powerislost.IfmorethanoneEmergencyLightingPanelneedstosensefromaspecificNormalPanel,adedicatedwirebetweeneachpairofNormal(Non-Essential)andEmergency(Essential)panelsmayberequired.
•Shield/Drain:Connectshieldingasshown.DonotconnecttoGround(Earth)orCircuitSelector.Connectthe bare drain wires and cut off the outside shield.
IECPELV/NEC® Class 2wiringlinkrequires:• Two12AWG(4.0mm2) conductors for control wiring.• Oneshielded,twistedpair18AWG(0.75mm2) for data link.
FOMX-1B
Softswitch128® Panel
SO-7BOMX-AV
2xContactClosureInputs
NOTE:LinkTerminators(LT-1)arerequiredatthestartand end of the Softswitch128® IECPELV/NEC® Class 2 link.LT-1’sareincludedwiththeSoftswitch128® panel.
OMX-CCO-8
Upto32devicesand16panels
Softswitch128® Controller Wiring Details
FortheIECPELV/NEC® Class 2 link, use GRX-CBL-46Lorequivalent.Thecableconsistsof:
•Two12 AWG(4.0 mm() wires.
•One22 AWG(0.34 mm() twisted shielded pair.
•One18 AWG(0.75 mm() wire for Emergency Sense.
Forcontactclosureinputwiringuse18 AWG(0.75 mm() orlarger.Keepwirerunslessthan500 ft(152 m).
Low-Voltage IEC PELV/NEC® Class 2 Wiring•Low-voltageIECPELV/NEC® Class 2 wiring is used for all system communications.
•Wiringmustbedaisy-chained.
•Low-voltagewiringmustruninaseparatetroughfromline(mains)voltage.
•Mustbelessthan2000 ft(600 m) long.
• InstallLinkTerminators(LT-1)atthestartandendoftheIECPELV/NEC® Class 2 Link.
1 LutronhasapprovedcablefromBelden,Liberty,Alpha,andSignature. Ask for Lutron®GRAFIKEye® Cable.
1 2 3 4D5 1 2 3 4
1:Common(black)2:V+(red)3:MUX(purple)4:MUX(white)D:Shield/Drain(bare)5:Sense(orange)(colorsasperGRX-CBL-46L1)
1:ContactClosure12:Common3:ContactClosure24:Common
Softswitch128® Controller(top)
369-346b 17 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
Mini Softswitch128® Rough-In Panels
(maximumfeedpercircuit:20A)
Standard Softswitch128® Rough-In Panels
(maximumfeedpercircuit:20A)
Wire Sizes
•14to10AWG(2.5to4.0mm()forFeedWiringand SwitchLegs(toloads).
•Power(Hot/Live)andSwitchedHot/Liveconnectdirectly toTerminalBlockforSwitchLegs.
Rough-In Softswitch128® Panels – Feed-through Only (withoutbranchcircuitbreakers)
Rough-inpanelsareorderedanddeliveredastwoparts:anemptytubandapre-wiredbaseplate.Thepre-wiredbaseplateincludesswitchingmodules,terminalblocks,Softswitch128® controller, power supply and panel cover.
Thefollowingtablesdetailthemodelnumbersforthetwocomponentsrequiredforavailablerough-inpanels.
SINT12-FT
SINT44-FT
Mini Baseplate Standard Baseplate
Switch Legs Tub Part Number
Baseplate Number (120/277 V~)
8 TUB16 SINT8-FT12 TUB16 SINT12-FT16 TUB16 SINT16-FT
Switch Legs Tub Part Number
Baseplate Number (120/277 V~)
20 TUB48 SINT20-FT24 TUB48 SINT24-FT28 TUB48 SINT28-FT32 TUB48 SINT32-FT36 TUB48 SINT36-FT40 TUB48 SINT40-FT44 TUB48 SINT44-FT48 TUB48 SINT48-FT
369-346b 18 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
2.21(56)
1.34(34)
2.21(56)
4.09(104)
15.13(384)
14.38 (365)
0.15(4)
54.15(105)
24.00(610)
10.75(273)
21.50(546)
8.00(203)
15.875(403)
24.50(622)
TUB16 Dimensions
Left Side View
Top View
Right Side View
Bottom View
Suggested Mounting Height
MountTUB16ataheightof45in(1140mm),measured from floor to bottom of panel for optimal LCDviewing.
Alldimensionsshownas:in(mm).
Front View
Cover
369-346b 19 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
4.15 (105)
41.75 (1060)
2.69 (68)
2.43 (62)
15.875(403)
8.00(203)
14.375(365)
59.50 (1511)
2.43 (62)11.00(279)
15.125(394)
59.00(1499)
4.21(107)
0.150(4)
TUB48 Dimensions
Bottom View
Left Side View
Top View
Right Side View
Suggested Mounting Height
MountTUB48ataheightof26in(660mm),measuredfromfloortobottomofpanelforoptimalLCDviewing.
Alldimensionsshownas:in(mm).
Front View
Cover
369-346b 20 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
Numberof Circuits
Prefix
XPS24 - 1A1B - 2774ML - 20 - CGP___ _
VoltageFeed
BreakerRating
How to Build a Model Number with 480 V~ Contactors
2-Pole4-Pole
CustomPanelSuffix
Prefix
XPS(Softswitch128® panels)
Number of Circuits
Totalnumberofcircuits(switchlegs)inthe panelnotincluding480V~.
2-Pole (A)
Totalnumberof2-pole30Acontactorsin the panel.
4-Pole (B)
Totalnumberof4-pole30Acontactorsin the panel.
Voltage
277(277V~ )
Omitforfeed-throughpanels.
Feed
FT(feed-throughpanels)4ML(3phase4wirefeeders)
Breaker Rating
Omitforfeed-throughpanels.20(20Abranchcircuitbreakers;20Abranchcircuitbreakershavea16Acontinuousloadrating).
Custom Panel Suffix
Indicatespanelwithspecialoptions. Contact Lutron for specific options.
•Availableinlargeenclosuresizeonly.
•Branchcircuitbreakerandfeed-throughmodelsareavailable.
•Contactorsprovidedin2poleand4pole,30Amaximum.
Softswitch128® Panels with 480 V~ Contactors
369-346b 21 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
Large Softswitch128® Feed-through Models for 277 V~ and 480 V~ Contactors1
Wire Sizes
•14to10AWG(2.5to4.0mm()forFeedWiringandSwitchLegs(toloads).
•Power(Hot/Live)andSwitchedHot/LiveconnectdirectlytoTerminalBlockforSwitchLegs.
Feed-through Softswitch128® Panels with 480 V~ Contactors(withoutbranchcircuitbreakers)
1 Contact Lutron for lead time.
Model Prefix Switch Legs 2-Pole 4-Pole Feed Type Maximum Feed
XPS8 8
8ContactorsMaximum Feed-through 277V~ 20A
XPS12 12XPS16 16XPS20 20XPS24 24XPS28 28XPS32 32XPS36 36XPS40 40XPS44 44XPS48 48
369-346b 22 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
Wire Sizes
•14to10AWG(2.5to4.0mm()
Large Softswitch128® Panels with Circuit Breakers for 277 V~ (max. feed is 250 A) and 480 V~ Contactors1
Branch Circuit Breaker Softswitch128® Panels with 480 V~ Contactors
Large Softswitch128® Panels with Circuit Breakers for 277 V~ (max. feed is 250 A) and 480 V~ Contactors with 2-Pole Breakers2 to Power the 480 V~ load1
1 Contact Lutron for lead time.2 Each480V~ pole requires a 2 pole breaker. The Softswitch®panelhasa30positionloadcenter.
Model Prefix Switch Legs 2-Pole 4-Pole Feed Type
XPS8 8 5ContactorMaximum3Ø4WMainLugAccepts 4 AWG (25 mm() to 250 kcmil (mcm)(120 mm()
XPS12 12 5ContactorMaximumXPS16 16 5ContactorMaximumXPS20 20 5ContactorMaximumXPS24 24 1ContactorMaximumXPS28 28 1ContactorMaximum
Model Prefix Switch Legs 2-Pole 4-Pole Feed Type
XPS8 8 5ContactorMaximum (20PoleMaximum)
3Ø4WMainLugAccepts 4 AWG (25 mm() to 250 kcmil (mcm)(120 mm()
XPS12 12 5ContactorMaximum (8PoleMaximum)
XPS16 16 5ContactorMaximum (6PoleMaximum)
XPS20 20 5ContactorMaximum (4PoleMaximum)
XPS24 24 1ContactorMaximum (2PoleMaximum)
XPS28 28 1ContactorMaximum (1PoleMaximum)
369-346b 23 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
HSH
HSH
HSH
HSH
HSH
HSH
HSH
HSH
H
NNN
H
HH
H
Ground
Ground
Do not wire tothese terminals
Neutral
277 V~
120 V~
Neutral
{ 120 V~120 V~
277 V~ControlFeed
120 V~ControlFeed
OR
H
NNN
H
HH
H
XPSwitchingModule (4circuits)
Hot
Neutral
Load
Switched Load Wiring
Each switched circuit requires a dedicated 20 Amax.circuitbreakerand feed wiring to/from a distribution panel.
Control Wiring
Control wiring requires a dedicated feed and circuit breaker.
GroundBus
CircuitBreaker
480 V~ Contactor Softswitch128® Panels, Feed-through Wiring Overview(withoutbranchcircuitbreakers)
480 V~ Control Wiring
The contactors need to be wiredtoanXPoutput.
480 V~ Contactor Load Wiring
Each contactor circuit requires a dedicated2-pole277 V~30 A max.circuitbreaker.
Hot
Neutral
Hot
Wire the Softswitch128®panelasshown.UseatroughwhentheSoftswitch128®Panelisnotadjacenttoadistributionpanel.SpliceNeutralsintrough.
Load
Softswitch128® Controller
369-346b 24 08.08.12
Power EquipmentSoftswitch128®Switching Systems
® PageSPECIFICATION SUBMITTALJob Name:
Job Number:
Model Numbers:
HSH
HSH
HSH
HSH
480 V~ Contactor Softswitch128® Panels with Branch Circuit BreakersLoad Wiring OverviewWire the Softswitch128® panel as shown.
Softswitch128® Controller
SwitchedHot
Neutral
Load
MainFeeds:PhaseA,B,C andNeutral
XPSwitchingModule(4circuits)
DoNotRemovebypassjumpers until load wiring is verified.
Leaving bypass jumpers installed allows Softswitch128® panels to be used to provide temporary lighting until load wiring is verified.
GroundBus
480V~ Contactor
480 V~ Contactor Load Wiring
Each contactor circuit requires adedicated2-pole277V~ 30 Acircuitbreaker.The2-polebreaker could be installed in the Softswitch128® panel or in a distribution panel by others.
480 V~ Control Wiring
The contactors need to be wiredtoanXPoutput.
Hot
Load