smoke detector sensitivity testing - cfaa alarm articles and researc… · standard = bs 5839 part...
TRANSCRIPT
SMOKE DETECTOR – A fire detector designed to operate
when the concentration of airborne combustion products
exceed a predetermined level.
SMOKE DETECTOR SENSITIVITY – The relative degree of
response of a smoke detector expressed in %/foot
obscuration. A high sensitivity detector responds to a lower
concentration of smoke while a low sensitivity detector
responds to a high concentration of smoke under identical
fire test conditions.
OBSCURATION – The unit of measurement where smoke
has an effect on visibility. Expressed in %/foot.
Ionization
First type (Invented in 1941’s by Swiss physicist
Walter Jaeger ,Dr. Ernst Meili)
Best at detecting:
Incipient stage (invisibly small particles)
Fast flaming fires (smaller particle size - 0.01-0.4
micron range)
Dark or Black smoke
Photoelectric
Later technology
Best at detecting:
Slow smouldering fires (larger particle size - 0.4-
10.0 micron range)
Light coloured white/grey smoke
Radio active material -
(Americium-241)
Ionization Chamber and
reference chamber
Electrical Source
Positive and Negative plates
The radio active material
generates ‘Alpha’ particles,
which ‘Ionize’ (“to knock an
electron off of”) the air in the
chamber. The free electron
(negative charge) and the
atom with a missing electron
(positive charge) are attracted
to the oppositely charged
metal plates. The detector
senses a small electrical
current between these two
plates.
Smoke particles entering
the chamber attach to the
ions reducing the current flow.
The detector senses the drop
in current between the plates
and triggers the alarm.
Light Source
Lens to collimate light into a
beam
Photoelectric Sensor
Smoke particles entering the
dark Chamber, ‘Scatters’ light
directing it to the sensor cell,
which increases the voltage
generated by the cell.
Increase in voltage triggers
the alarm.
Optical Smoke Detector
1: Optical chamber
2: Cover
3: Case moulding
4: Photodiode (detector)
5: Infrared LED
Smoke detectors where installed properly and maintained
within their listed sensitivity ranges have proven to be
effective in saving lives and property.
However, smoke detectors become less reliable with time,
due to aging of their electronic components and
environmental conditions, making it even more important to
test the detectors in accordance with the CAN/UL-S536-04
” Inspection and Testing of Fire Alarm Systems”.
Detector sensitivity
after 4 years field exploration
Sensitivity [%/m]
# D
ete
cto
rs
Production
limits
Detector sensitivity
after revision process
Sensitivity [%/m]
# D
ete
cto
rs
Production
limits
10 – 30%
out of the limits
Optical components
after 4 years field exploration
Optical components
after revision process
NIST 2008,
•The Smoke Detector Operability Survey:
“Engineering Laboratory Analysis found that there was a
correlation between the occurrence of
nuisance alarms and the sensitivity of the alarm”,
FIRE INCIDENT STUDY NATIONAL SMOKE DETECTOR
PROJECT 1995:
“U.S. EXPERIENCE WITH SMOKE ALARMS AND OTHER
FIRE DETECTION/ALARM EQUIPMENT 2007”
“Nuisance alarms were the leading cause of disabled
alarms”.
“Problems associated with smoke alarm age may
include “sensitivity drift,” which refers to a shift in the range
of visibility obscuration or particulate density that will activate
the smoke alarm. Such a shift can mean either an
increase in nuisance activations (if sensitivity increases) or a
decreased ability to react promptly to real fires (if sensitivity
decreases)”.
“Since 1997, U.S. fire departments have responded to
more false alarms than real fires”.
“More than one-third of New Zealand households in a
smoke alarm installation program had problems with
nuisance alarms”.
SMOKE ALARMS IN U.S. HOME FIRES – NFPA MARTY
AHRENS 2009
“Foreign objects such as dust, dirt or insects can increase
sensitivity, as can fire products”.
“NIST study found that accumulation of cigarette smoke
could trigger smoke alarms”.
ALBERTA FIRE CODE 2006:
6.3.1.2. Inspection and Testing
1) Fire alarm systems shall be inspected and
tested in conformance with CAN/ULC-S-536, “Inspection
and Testing of Fire Alarm Systems.”
Testing Evolution - CAN/ULC-S536-82
4.4.1 A – Every reasonable effort shall be made to test all components
required in this subsection. In the event that some components cannot
reasonable be made accessible, a list of such components and their
location shall be included in the report. However, all such components
shall be tested at least once every three years.
4.4 – Yearly Testing
4.4.1 Every year the following tests shall be conducted and if a fault is
established appropriate corrective action shall be taken:
F – Each automatic alarm initiating device shall be tested for its
intended function in accordance with the manufacturer’s instructions;
Testing Evolution - CAN/ULC-S536-86
NOTE: A cleaning schedule for smoke detectors, based on the
environmental conditions prevailing and the results of clause 5.3.6.6,
should be established and maintained.
5.3.6.5 Inspect and test the smoke detectors in accordance with the
manufacturer’s recommendations.
5.3.6.6 Smoke detectors shall be tested for operability and the
required sensitivity.
Testing Evolution - CAN/ULC-S536-97
6.6.4 – Smoke Detectors
6.6.4.1.1 – Each smoke detector shall be visually inspected for
cleanliness. Where required, cleaning shall be in accordance with the
manufacturer’s recommendations.
6.6.4.1.2 – Each smoke detector sensitivity value shall be tested to
confirm that it is within its rated operating range, using the
manufacturer’s recommended test equipment.
6.6.4.1.3 – Each smoke detector whose sensitivity is not within the
required operating range shall be cleaned, retested in accordance with
clause 6.6.4.1.2 and if still not within its rated sensitivity, replaced with
compatible smoke detector.
6.6.4.1.5 – Each smoke detector shall be tested for operation by
introducing smoke or simulated smoke to the detector chamber.
5.7.4.1.3 Each smoke detector shall be tested to confirm that it is
within its rated operating range using a test method described in Clause
5.7.4.1.6. (Refer to Appendix E3.1, Field Device Testing-Legends and
Notes.)
Testing Evolution - CAN/ULC-S536-04
5.7.4 Smoke Detectors
5.7.4.1.1 Each smoke detector shall be visually inspected for
cleanliness. When required, cleaning shall be in accordance with the
manufacturer’s recommendations.
5.7.4.1.2 Each smoke detector shall be tested for operation by
introducing smoke or simulated smoke to the detecting chamber in
accordance with the manufacturer’s instructions.
5.7.4.1.4 A smoke detector whose sensitivity is not within the
required operating range shall be cleaned, retested in accordance with
Clause 5.7.4.1.3, and if still not within its rated sensitivity, replaced with a
compatible smoke detector. (Refer to Appendix E3.1, Field Device Testing-
Legends and Notes.)
5.7.4.1.6 Acceptable methods of determining the smoke detector
sensitivity are:
A Manufacturer’s recommended test instrument, equipment, or
method;
B Installed control units or transponders designed to test the
sensitivity of individual smoke detectors; or
C Calibrated instruments that provide the operation as described in
CAN/ULC-S529, Standard for Smoke Detectors for Fire Alarm
Systems, for the purpose of testing smoke detector sensitivity.
Testing Evolution - CAN/ULC-S536-04
5.7.4.1.5 Each smoke detector sensitivity measurement and if
applicable, the cleaning date shall be recorded on the individual device
record. (Refer to Appendix E3.1, Field Device Testing-Legends and
Notes.)
Allowable smoke detector sensitivity is established by
Underwriters Laboratories Canada (ULC) and have their
performance verified by Fire Tests.
All smoke detectors are required
to respond to the same Test Fires.
Nearly all smoke detectors installed in Canada are by:
•EDWARDS SYSTEMS TECHNOLOGIES (EST)
•SIMPLEX-GRINNELL
•SIEMENS BUILDING TECHNOLGIES
•SYSTEM SENSOR
Why test detector function and sensitivity?
Detector sensitivity can, and does, drift. Over-sensitivity
leads to false alarms, under-sensitivity to late alarms - or no
alarms. The need for functional testing through introducing a
smoke type stimulus is well recognised:
“Since stimulus of the sensing element through introduction
of the phenomena or surrogate phenomena which the
detectors are designed to detect forms part of the test(s),
use of a test button or a test magnet (for example) or
compliance with 45(i) (confirmation of analogue values) does
not satisfy the recommendations..”
BS 5839 1: 2002 45.3 (Note 4)
“The detectors shall be tested in place to ensure smoke
entry into the sensing chamber and an alarm response.
Testing with smoke or listed aerosol...shall be permitted as
acceptable test methods...”
USA NFPA 72 2000 Table 10.4.2.2 13.g.1 “Each smoke detector shall be tested for operation by
introducing smoke or simulated smoke into the detecting
chamber...”
CAN/ULC - S-536-04, 5.7.4.1.2
But the requirement for sensitivity checks is also clear in
national standards:
“....tests shall be performed to ensure that each smoke
detector is within its listed and marked sensitivity range...”
USA NFPA 72 2000 Table 10.4.2.2 13.g.1
“....each detector shall be tested to confirm that it is within its
rated operating range...”
CAN/ULC - S536-04, 5.7.4.1.3
Soiling Level vs. Sensitivity Level
Contrary to North America, the European approach is to evaluate
the level of soiling in the detector, which is nothing more than the
inverse of testing remaining sensitivity
Standard = DIN 14675/A1 + VDE 0833-1
DIN 14675/A1:2006 Paragraph 11.5.3 (see notes)
Fire detectors are to be exchanged or overhauled according to the
manufacturer’s specifications. This must be documented in the
operation log book.
w/o Drift Compensation – test with gas every year and replace
on failure or after 5 years with new or factory refurbished unit.
with Drift Compensation – test with gas every year and replace
on failure or after 8 years with new or factory refurbished unit.
Non-monitored – test with gas every year and replace on failure
or after 6 years with new or factory refurbished unit.
Monitored – test with gas every year and replace on failure or
after 8 years with new or factory refurbished unit.
Standard = NF / CNPP
Non-monitored or Monitored – test with gas every year and
replace on failure or after 4 years with new or factory refurbished
unit.
Standard = BS 5839 Part 1
Non-monitored or Monitored – test with gas and measure
sensitivity every year replace on failure with new unit. Testing can
involve using complex testing equipment, whereby the detector is
exposed to a defined smoke concentration. The concentration is
slowly increased, until the device goes into alarm, thereby
establishing the sensitivity.
Testing must in some cases even be witnessed!
Non-monitored or Monitored – test with gas and measure
sensitivity every year replace on failure with new unit.
KNOWLEDGE
Education limited within Alberta
Information can be difficult to source
EQUIPMENT
Specialized
COST
Increases time required when done in conformance with
CAN/ULC Standards.
NEWER SMOKE DETECTORS
Addressable: real time monitoring/diagnostics reporting
directly to the fire alarm control panel.
Some detectors look for fire signature, not just smoke, can
require specialized knowledge to test correctly.
Can utilize drift compensation technology
Conventional: easier testing with information available.
Variety of methods:
Obscuration
Voltage
Diagnostic LED’S
Can utilize drift compensation technology
OLDER SMOKE DETECTORS
Conventional: Information may be difficult to source.
Specialized testing equipment required.
Continued testing with smoke or aerosol over time or incorrectly
used may contribute to detectors either becoming more or less
sensitive over time.
NUISANCE /FALSE ALARMS
DELAYED ALARM SIGNAL
NO ALARM SIGNAL AT ALL
Require better education for those qualified under the AFC, IE
CFAA Fire Alarm Technology Program.
Require fire alarm Testing and Inspections in conformance with the
CAN/ULC-S536-04 ‘Inspection and Testing of Fire Alarm Systems’.
Including smoke detector sensitivity testing,
Where smoke detector sensitivity testing is not done in
conformance with Clause 5.7.4.1.6. A – C, that smoke detector
shall be replaced with a new smoke detector within 5 years.
WHY?
Smoke detectors do drift outside of their listed smoke detector
sensitivity range, introducing smoke into the chamber and seeing
the detector alarm, does not prove that it is still operating within it’s
designed parameters and will work in a real fire condition to detect
the products of combustion when required!
QUESTIONS?