Circuit-breakers LZM1, 2, 3, 4 and switch-disconnectors LN1, 2, 3, 4up to 1600 A
Reliably and safely controlling, switching and managing power, in industry, in buildings and in machine construction. Enabled by innovative protection concepts.
Circuit-breaker series LZM1 to LZM4,switch-disconnectors LN1 to LN4- just 4 compact frame sizes - available as 3 and 4-pole device- now also up to 1600 A- fl exible mounting using modular function groups- full rated current at 50 °C ambient temperature- switch suitable for world-wide use
Page 6, page 18
Standard/trip-indicating auxiliary contact from the Titan range- reduced number of variants and stockholding requirement- simple front installation at the same position- simple clip-on feature saves mounting costs- attractively priced identical parts from the control circuit
device range
Page 42
Door coupling rotary handles- identical drilling template for all
variants- innovative automatic centring- axis support for long-term reliable
operation - side-wall operation ensuring space-
saving main switch installation
Page 54
Remote operators- common functional concept of all
variants- low closing delays 60 ms to 100 ms- locking and sealing features provide
security
Page 64
Moeller SK1230-1177GB
Circuit-breakers, switch-disconnectors from 15 to 1600 A
Contents 1
Cir
cuit
-bre
aker
s, s
wit
ch-d
isco
nn
ecto
rs
up
to
160
0 A
Page
System overview
Circuit-breakers, switch-disconnectors 2
Technical overview 4
Ordering
Circuit-breaker thermo-magnetic release, 3-pole
6
Circuit-breaker, fi xed overload releases, 3 pole
8
Circuit-breaker, electronic releases, 3 pole
10
Circuit-breaker thermo-magnetic release, 4-pole
12
Circuit-breaker, fi xed overload releases, 4 pole
14
Circuit-breakers, electronic releases, 4 pole
16
Switch-disconnectors, 3 pole 18
Switch-disconnectors, 4 pole 18
Connection types 20
Plug-in units 40
Withdrawable units 41
Auxiliary contact with screw terminals 42
Undervoltage release with screw terminals
44
Undervoltage release, off-delayed 49
Shunt release with screw terminals 50
Door coupling rotary handles 54
Rotary handles 56
Page
Rotary handles with door interlock 57
Main switch assembly kit 58
Accessories 60
Mechanical interlock 62
Multi-function device adapter 63
Accessories 64
Insulated enclosures 66
Residual-current release frequency response
68
Engineering
Selectivity: incoming circuit-breaker, outgoing circuit-breaker
70
MCB, backup protection 74
Direction of blow-out, minimum clearances, tube cable lugs
75
Auxiliary switches, trip-indicating auxiliary contacts
76
Mechanical interlock for (door-coupling) rotary handle
77
Mechanical interlock for remote operator, residual-current relay
78
Sizes 1, 2: tripping characteristics 79
Size 3: tripping characteristics 80
Size 4: tripping characteristics 81
Sizes 1, 2, 3: let-through characteristics 82
Size 2: residual-current release frequency response
84
Page
Technical data
Circuit-breaker 86
Switch-disconnectors 90
Temperature infl uence 91
Effective power loss 93
Terminal capacities 94
Auxiliary contact 96
Equipping with auxiliary contacts, time differences
97
Undervoltage release, shunt release, 98
Remote operator, capacitor units 99
Residual current relay 100
Residual current release 102
Dimensions
Size 1: basic units 104
Size 1: accessories 105
Size 2: basic units 113
Size 2: accessories 114
Size 3: basic units 125
Size 3: accessories 126
Size 4: basic units 135
Size 4: accessories 136
2Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
System overviewCircuit-breakers, switch-disconnectors
18
13
14
6 8
75
24
25
15
12
11
19
17
21
20 16
23
9
10
1
4
23
LZM
3
http://catalog.moeller.net Moeller SK1230-1177GB
System overviewCircuit-breakers, switch-disconnectors
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Basic units
Circuit-breaker 1Rated uninterrupted current up to 1600 ASwitching capacity 16, 25, 36, 50 kA at 415 VAdjustable releases for overload and short-circuitAdjustable time selectivityEarth-fault protectionProtection of systems, cables, motors, generators3 and 4 pole versions,IEC/EN 60947a page 6
Switch-disconnector 1Rated uninterrupted current up to 1600 ARemotely tripped switch-disconnector with undervoltage or shunt release3 and 4 pole versions, IEC/EN 60947a page 18
Add-on functions
Standard auxiliary contact (HIN) 13Switching with the main contacts. Used for indication and interlock functions.a page 42
Trip-indicating auxiliary contact (HIA) 13General trip indication '+', when tripped by voltage release, overload release or short-circuit releasea page 42
Early-make auxiliary contacts 24For interlocking and load shedding circuits, as well as for early make of the undervoltage release in main switch/Emergency-stop applicationsa page 42
Voltage release 24Undervoltage releaseNon-delayedOFF-delayedShunt releasea page 44
Delay unit for undervoltage release 25a page 49
Rear drive 14a page 60
Door coupling rotary handle 16, 18Lockable
With door interlocka page 54
Main switch rotary handle for side panel mounting
15
a page 58
Extension shaft 17Can be cut to required length.a page 54
Rotary handle 19Lockablea page 56
Remote operator 22For remote switching of circuit-breakers and switch-disconnectorsa page 64
Toggle lever interlock device 23a page 61
Mounting accessories
Control circuit terminal 8For two terminals at top or bottomLZM1 a page 23LZM2 a page 27LZM3 a page 31LZM4 a page 39
Tunnel terminals for Al and Cu cable 6Standard with control circuit terminalLZM1 a page 21LZM2 a page 25LZM3 a page 31LZM4 a page 37
Box terminals 7Standard version of frame size 1 assembled within the circuit-breaker enclosureLZM1 a page 21LZM2 a page 25LZM3 a page 29
Terminal cover 4Protection against direct contact where cable lugs, busbars or tunnel terminals are usedLZM1 a page 23LZM2 a page 27LZM3 a page 32LZM4 a page 39
Terminal cover, knockout 3LZM1 a page 23LZM2 a page 27LZM3 a page 32LZM4 a page 39
Clip plate 10NZM1-XC35 for 35 mm top-hat railNZM2-XC75 for 75 mm top-hat raila page 61
Rear connection 11LZM1 a page 21LZM2 a page 25LZM3 a page 31LZM4 a page 37
Plug-in and withdrawable unit 9a page 40
Insulating surround 21For use with toggle lever, rotary drive and remote operator protruding from the enclosurea page 61
External warning plate/designation label 20a page 60
Spacer 12a page 61
IP2X protection against contact with a finger
2
For box terminalsLZM1 a page 23LZM2 a page 27LZM3 a page 32
IP2X protection against contact with a finger
5
For barrierLZM1 a page 23LZM2 a page 27LZM3 a page 32
LZM
4
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Technical overview Technical overviewCircuit-breaker, switch-disconnector, 3/4-pole
CiWian
Ii
A
x Ir 2 – 12 x In
5
LZM1, LZM2, LZM3, LZM4
Circ
uit-
brea
kers
, sw
itch
-dis
RateAdjuAdjuDela
Ambmin.
Eco
Bas
Com
Nor
Not
SwWithand VDE
Rate
TypRateRate
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Circuit-breaker, switch-disconnector, 3/4-pole
rcuit-breakerth main switch characteristics to IEC/EN 60204 d isolating characteristics to IEC/EN 60947
d uninterrupted current Iu = Rated current In stable overload release Ir stable short-circuit release Ii yed short-circuit release Isd
Thermomagnetic releases Electronic releasesSystem and cable protection Systems, cable, selectivity and generator protectionIu Iu Ir Ii Iu Iu Ir Isd
A A A A A A A A
ient temperature at 100% Iu/max. -25/+50 °C
20 0.8 – 1 x In 350 0.5 – 1 x In 2 – 102532
40 8 – 10 x In
50 6 – 10 x In6380100125
160 160 LZM1: 8x In6 – 10 x In 200
250300 320
400 400500
630800100012501600
nomic switching capacity LZME1-A…400/415 V kA/cos v 18 0.25
ic switching capacity LZMB1-A… LZMB2-A…400/415 V kA/cos v 25 0.25 25 0.25
fort switching capacity LZMC1-A… LZMC2-A… LZMC3-A… LZMC3-…E…400/415 V kA/cos v 36 0.25 36 0.25 36 0.25 36 0.25
mal switching capacity LZMN3-A… LZMN3-…E… LZMN4-…E…400/415 V kA/cos v 50 0.25 50 0.25 50 0.25
es The stated switching capacity values are rated ultimate short-circuit breaking capacities (Icu)
itch-disconnector main switch characteristics to IEC/EN 60204 VDE 0113 isolating characteristics to IEC/EN 60947, 0660 without overload and short-circuit release
d uninterrupted current Iu = rated current In63 – 160 160 – 250 400 – 630 630 – 1600
e N can be triggered with U/A voltage release LN1-… LN2-… LN3-… LN4-…d short-circuit making capacity Icm kA 2.8 5.5 25 53d short-time withstand current Icw (1s-Ieff) kA 2 3.5 12 25
LZM1, LZM2, LZM3, LZM4
6
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Ordering OrderingCircuit-breaker, thermo-magnetic release, 3 pole
acity Hz
Pricesee price list
Std. pack Notes
1 off IEC/EN 60947-2Adjustable overload releases Ir• 0.8 – 1 x In (ex-works 0.8 x In)Adjustable short-circuit releases Ii• 6 – 10 x In (ex-works 6 x In)
– LZM...-A40-I: 8 – 10 x In (ex-works 8 x In)Fixed short-circuit release Ii• 350 A at In = 20 – 32 A• 1280 A at In = 160 A (LZM1)
1 off
1 off
7
LZM....1, LZM...2,LZM...3
Circ
uit-
brea
kers
, sw
itch
-dis
Prot3
Not
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Circuit-breaker, thermo-magnetic release, 3 pole
Economic switching capacity 18 kA at 415 V 50/60 Hz
Basic switching capacity 25 kA at 415 V 50/60 Hz
Comfort switching capacity 36 kA at 415 V 50/60 Hz
Normal switching cap50 kA at 415 V 50/60
Rated current = rated uninterrupted current
Setting range Part no.Article no.
Pricesee price list
Part no.Article no.
Pricesee price list
Part no.Article no.
Pricesee price list
Part no.Article no.
Overload releases Short-circuit releases
In = Iu Ir Ii
A A A
ection of systems and cables pole
Terminals standard, terminal screws as accessories20 15…20 350 LZME1-A20-I
111808LZMB1-A20-I111848
LZMC1-A20-I111888
25 20…25 350 LZME1-A25-I111809
LZMB1-A25-I111849
LZMC1-A25-I111889
32 25…32 350 LZME1-A32-I111810
LZMB1-A32-I111850
LZMC1-A32-I111890
40 32…40 320…400 LZME1-A40-I111811
LZMB1-A40-I111851
LZMC1-A40-I111891
50 40…50 300…500 LZME1-A50-I111812
LZMB1-A50-I111852
LZMC1-A50-I111892
63 50…63 380…630 LZME1-A63-I111813
LZMB1-A63-I111853
LZMC1-A63-I111893
80 63…80 480…800 LZME1-A80-I111814
LZMB1-A80-I111854
LZMC1-A80-I111894
100 80…100 600…1000 LZME1-A100-I111815
LZMB1-A100-I111855
LZMC1-A100-I111895
125 100…125 750…1250 LZME1-A125-I111816
LZMB1-A125-I111856
LZMC1-A125-I111896
160 125…160 1280 LZME1-A160-I111817
LZMB1-A160-I111857
LZMC1-A160-I111897
Terminal screws standard, terminals as accessories160 125…160 960…1600 LZMB2-A160-I
111922LZMC2-A160-I111938
200 160…200 1200…2000 LZMB2-A200-I111923
LZMC2-A200-I111939
250 200…250 1500…2500 LZMB2-A250-I111924
LZMC2-A250-I111940
300 240…300 1500…2500 LZMB2-A300-I111925
LZMC2-A300-I111941
Terminal screws standard, terminals as accessories320 250…320 1920…3200 LZMC3-A320-I
111954LZMN3-A320-I111966
400 320…400 2400…4000 LZMC3-A400-I111955
LZMN3-A400-I111967
500 400…500 3000…5000 LZMC3-A500-I111956
LZMN3-A500-I111968
es Notes for terminals a 21
I
LZM...1, LZM...2, LZM...3
8
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Ordering OrderingCircuit-breaker, fixed overload releases, 3 pole
60947-2ble overload releases Ir 1 x In (ex-works 0.8 x In)ort-circuit release Ii In at In = 20/25/32 A (LZM1)A at In = 160 A (LZM1)A at In = 300 A (LZM2)
9
LZM...1, LZM...2
Circ
uit-
brea
kers
, sw
itch
-dis
Prot3
Not
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Circuit-breaker, fixed overload releases, 3 pole
Economic switching capacity 18 kA at 415 V 50/60 Hz
Basic switching capacity 25 kA at 415 V 50/60 Hz
Comfort switching capacity 36 kA at 415 V 50/60 Hz
Rated current = rated uninterrupted current
Setting range Part no.Article no.
Pricesee price list
Part no.Article no.
Pricesee price list
Part no.Article no.
Pricesee price list
Std. pack Notes
Overload releases Short-circuit releases
In = Iu Ir Ii
A A A
ection of systems and cables pole
Terminals standard, terminal screws as accessories20 15…20 350 LZME1-ASF20-I
111678LZMB1-ASF20-I111838
LZMC1-ASF20-I111878
1 off IEC/EN Adjusta• 0.8 –Fixed sh• 10 x• 350 A• 1280 • 2500
25 20…25 350 LZME1-ASF25-I111679
LZMB1-ASF25-I111839
LZMC1-ASF25-I111879
32 25…32 350 LZME1-ASF32-I111800
LZMB1-ASF32-I111840
LZMC1-ASF32-I111880
40 32…40 400 LZME1-ASF40-I111801
LZMB1-ASF40-I111841
LZMC1-ASF40-I111881
50 40…50 500 LZME1-ASF50-I111802
LZMB1-ASF50-I111842
LZMC1-ASF50-I111882
63 50…63 630 LZME1-ASF63-I111803
LZMB1-ASF63-I111843
LZMC1-ASF63-I111883
80 63…80 800 LZME1-ASF80-I111804
LZMB1-ASF80-I111844
LZMC1-ASF80-I111884
100 80…100 1000 LZME1-ASF100-I111805
LZMB1-ASF100-I111845
LZMC1-ASF100-I111885
125 100…125 1250 LZME1-ASF125-I111806
LZMB1-ASF125-I111846
LZMC1-ASF125-I111886
160 125…160 1280 LZME1-ASF160-I111807
LZMB1-ASF160-I111847
LZMC1-ASF160-I111887
Terminal screws standard, terminals as accessories160 125…160 1600 LZMB2-ASF160-I
111918LZMC2-ASF160-I111934
1 off
200 160…200 2000 LZMB2-ASF200-I111919
LZMC2-ASF200-I111935
250 200…250 2500 LZMB2-ASF250-I111920
LZMC2-ASF250-I111936
300 240…300 2500 LZMB2-ASF300-I111921
LZMC2-ASF300-I111937
es Notes for terminals a 21
I
LZM...1, LZM...2
10
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Ordering OrderingCircuit-breaker, electronic releases, 3 pole
Notes
IEC/EN 60947-2
Adjustable overload releases Ir• 0.5 – 1 x In (ex-works 0.8 x In)
R.m.s. value measurement and “thermal memory”
Adjustable short-circuit releases Ii• LZM...3-AE250/400-I: 2 – 11 x In (ex-works 6 x In)• LZM...3-AE630-I: 2 – 8 x In (ex-works 6 x In)• LZM...4-AE...-I: 2 – 12 x In (ex-works 6 x In)
IEC/EN 60947-2
Adjustable overload releases Ir• 0.5 – 1 x In (ex-works 0.8 x In)
R.m.s. value measurement and “thermal memory”
Adjustable time delay setting to overcome current peaks tr• 2 … 20 s with 6 x Ir as well as infinity (without overload release) (ex-factory 10 s)
Adjustable delayed short-circuit releases Isd• 2 – 10 x Ir (ex-works 6 x Ir)
– LZM…3-VE630-I: 1.5 – 7 x Ir (ex-works 6 x Ir)
Adjustable delay time tsd• Steps: 0, 20, 60, 100, 200, 300, 500, 750, 1000 ms (ex-works 0 ms)
Adjustable non-delayed short-circuit releases Ii• LZM2 fixed 12 x In• LZM…3-VE400-I: 2 – 11 x In (ex-works 6 x In)• LZM…3-VE630-I: 2 – 8 x In (ex-works 6 x In)• LZM…4-VE…-I: 2 – 12 x In (ex-works 12 x In)i2t constant function• LZM3, LZM4 switched (ex-works OFF)
11
LZM...2, LZM...3, LZM...4
Circ
uit-
brea
kers
, sw
itch
-dis
Prot3 po
Syst3 po
Not
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Circuit-breaker, electronic releases, 3 pole
Comfort switching capacity 36 kA at 415 V 50/60 Hz
Normal switching capacity 50 kA at 415 V 50/60 Hz
Rated current = rated uninterrupted current
Setting range Part no.Article no.
Pricesee price list
Part no.Article no.
Pricesee price list
Std. pack
Overload releases
Short-circuit releases
Non-delayed Delayed short-circuit release
In = Iu Ir Ii Isd
A A A A
ection of systems and cablesleTerminal screws standard, terminals as accessories
630 315…630 1260…5040 LZMC3-AE630-I111957
LZMN3-AE630-I111969
1 off
800 400…800 1600…9600 LZMN4-AE800-I111978
1000 500…1000 2000…12000 LZMN4-AE1000-I111979
1250 630…1250 2500…15000 LZMN4-AE1250-I111980
1600 800…1600 3200…19200 LZMN4-AE1600-I111981
ems and cable protection, selectivity and generator protectionleTerminal screws standard, terminals as accessories
160 LZMC2-VE160-I111942
250 LZMC2-VE250-I111943
400 LZMC3-VE400-I111958
LZMN3-VE400-I111970
1 off
630 315…630 1260…5040 472…4410 LZMC3-VE630-I111959
LZMN3-VE630-I111971
800 400…800 1600…9600 800…8000 LZMN4-VE800-I111982
1000 500…1000 2000…12000 1000…10000 LZMN4-VE1000-I111983
1250 630…1250 2500…15000 1250…12500 LZMN4-VE1250-I111984
1600 800…1600 3200…19200 1600…16000 LZMN4-VE1600-I111985
es Notes for terminals a 29
I I
LZM...2, LZM...3, LZM...4
12
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Ordering OrderingCircuit-breaker, thermomagnetic release, 4 pole
acity Hz
Pricesee price list
Std. pack Notes
1 off IEC/EN 60947-2
Adjustable overload releases Ir• 0.8 – 1 x In (ex-works 0.8 x In)
Setting on neutral pole implemented via the main pole setting Ir of the main pole.
Adjustable short-circuit releases Ii• 6 – 10 x In (ex-works 6 x In)
– LZM…-A40-I: 8 – 10 x In (ex-works 8 x In)
Fixed short-circuit release Ii• 350 A at In = 20 – 32 A• 1280 A at In = 160 A (LZM1)
LZM..1-4-A…• With 100 % overload and short-circuit protection in 4th poleLZM..2-4-A…• With 60 % overload and short-circuit protection in 4th pole
1 off
I 1 off
I
I
13
LZM...1, LZM...2, LZM...3
Circ
uit-
brea
kers
, sw
itch
-dis
Prot4 po
T
T
T
Not
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Circuit-breaker, thermomagnetic release, 4 pole
Ecconomic switching capacity 18 kA at 415 V 50/60 Hz
Basic switching capacity 25 kA at 415 V 50/60 Hz
Comfort switching capacity 36 kA at 415 V 50/60 Hz
Normal switching cap50 kA at 415 V 50/60
Rated current = rated uninterrupted current
Setting range Part no.Article no.
Pricesee price list
Part no.Article no.
Pricesee price list
Part no.Article no.
Pricesee price list
Part no.Article no.Overload
releasesNeutral conductor
Short-circuit releases
In = Iu Ir Ir Ii
A A A A
ection of systems and cablesleerminals standard, terminal screws as accessories
20 15…20 15…20 350 LZME1-4-A20-I111828
LZMB1-4-A20-I111868
LZMC1-4-A20-I111908
25 20…25 20…25 350 LZME1-4-A25-I111829
LZMB1-4-A25-I111869
LZMC1-4-A25-I111909
32 25…32 25…32 350 LZME1-4-A32-I111830
LZMB1-4-A32-I111870
LZMC1-4-A32-I111910
40 32…40 32…40 320…400 LZME1-4-A40-I111831
LZMB1-4-A40-I111871
LZMC1-4-A40-I111911
50 40…50 40…50 300…500 LZME1-4-A50-I111832
LZMB1-4-A50-I111872
LZMC1-4-A50-I111912
63 50…63 50…63 380…630 LZME1-4-A63-I111833
LZMB1-4-A63-I111873
LZMC1-4-A63-I111913
80 63…80 63…80 480…800 LZME1-4-A80-I111834
LZMB1-4-A80-I111874
LZMC1-4-A80-I111914
100 80…100 80…100 600…1000 LZME1-4-A100-I111835
LZMB1-4-A100-I111875
LZMC1-4-A100-I111915
125 100…125 100…125 750…1250 LZME1-4-A125-I111836
LZMB1-4-A125-I111876
LZMC1-4-A125-I111916
160 125…160 125…160 1280 LZME1-4-A160-I111837
LZMB1-4-A160-I111877
LZMC1-4-A160-I111917
erminal screws standard, terminals as accessories160 125…160 80…100 960…1600 LZMB2-4-A160/100-I
111930LZMC2-4-A160/100-I111948
200 160…200 100…125 1200…2000 LZMB2-4-A200/125-I111931
LZMC2-4-A200/125-I111949
250 200…250 125…160 1500…2500 LZMB2-4-A250/160-I111932
LZMC2-4-A250/160-I111950
300 240…300 160…200 1500…2500 LZMB2-4-A300/200-I111933
LZMC2-4-A300/200-I111951
erminal screws standard, terminals as accessories320 250…320 200…250 1920…3200 LZMC3-4-A320/200-I
111960LZMN3-4-A320/200-111974
400 320…400 240…300 2400…4000 LZMC3-4-A400/250-I111961
LZMN3-4-A400/250-111975
500 400…500 250…320 3000…5000 LZMC3-4-A500/320-I111962
LZMN3-4-A500/320-111976
es Notes for terminals a 21
I
LZM...1, LZM...2, LZM...3
14
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Ordering OrderingCircuit-breaker, fixed overload releases, 4 pole
0947-2
le overload releases Ir x In (ex-works 0.8 x In)
n neutral pole implemented via the main pole setting Ir of the main pole.
rt-circuit release Iinat In = 20/25/32 A (LZM1) at In = 160 A (LZM1) at In = 300 A (LZM2)
-A…00 % overload and short-circuit protection in 4th pole-A…0 % overload and short-circuit protection in 4th pole
15
LZM…1, LZM…2
Circ
uit-
brea
kers
, sw
itch
-dis
Prot4 po
T
T
Not
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Circuit-breaker, fixed overload releases, 4 pole
Economic switching capacity 18 kA at 415 V 50/60 Hz
Basic switching capacity 25 kA at 415 V 50/60 Hz
Comfort switching capacity 36 kA at 415 V 50/60 Hz
Rated current = rated uninterrupted current
Setting range Part no.Article no.
Pricesee price list
Part no.Article no.
Pricesee price list
Part no.Article no.
Pricesee price list
Std. pack
NotesOverload releases
Neutral conductor
Short-circuit releases
In = Iu Ir Ir Ii
A A A A
ection of systems and cablesleerminal standard, terminals screws as accessories
20 15…20 15…20 350 LZME1-4-ASF20-I111818
LZMB1-4-ASF20-I111858
LZMC1-4-ASF20-I111898
1 off IEC/EN 6
Adjustab• 0.8 – 1
Setting o
Fixed sho• 10 x I• 350 A • 1280 A• 2500 A
LZM..1-4• With 1LZM..2-4• With 6
25 20…25 20…25 350 LZME1-4-ASF25-I111819
LZMB1-4-ASF25-I111859
LZMC1-4-ASF25-I111899
32 25…32 25…32 350 LZME1-4-ASF32-I111820
LZMB1-4-ASF32-I111860
LZMC1-4-ASF32-I111900
40 32…40 32…40 400 LZME1-4-ASF40-I111821
LZMB1-4-ASF40-I111861
LZMC1-4-ASF40-I111901
50 40…50 40…50 500 LZME1-4-ASF50-I111822
LZMB1-4-ASF50-I111862
LZMC1-4-ASF50-I111902
63 50…63 50…63 630 LZME1-4-ASF63-I111823
LZMB1-4-ASF63-I111863
LZMC1-4-ASF63-I111903
80 63…80 63…80 800 LZME1-4-ASF80-I111824
LZMB1-4-ASF80-I111864
LZMC1-4-ASF80-I111904
100 80…100 80…100 1000 LZME1-4-ASF100-I111825
LZMB1-4-ASF100-I111865
LZMC1-4-ASF100-I111905
125 100…125 100…125 1250 LZME1-4-ASF125-I111826
LZMB1-4-ASF125-I111866
LZMC1-4-ASF125-I111906
160 125…160 125…160 1280 LZME1-4-ASF160-I111827
LZMB1-4-ASF160-I111867
LZMC1-4-ASF160-I111907
erminal screws standard, terminals as accessories160 125…160 80…100 1600 LZMB2-4-ASF160/100-I
111926LZMC2-4-ASF160/100-I111944
1 off
200 160…200 100…125 2000 LZMB2-4-ASF200/125-I111927
LZMC2-4-ASF200/125-I111945
250 200…250 125…160 2500 LZMB2-4-ASF250/160-I111928
LZMC2-4-ASF250/160-I111946
300 240…300 160…200 2500 LZMB2-4-ASF300/200-I111929
LZMC2-4-ASF300/200-I111947
es Notes for terminals a 25
I
LZM…1, LZM…2
16
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Ordering OrderingCircuit-breakers, electronic releases, 4 pole
Notes
IEC/EN 60947-2Adjustable overload releases Ir• 0.5 – 1 x In (ex-works 0.8 x In)Setting on neutral pole implemented via the main pole setting Ir of the main pole.R.m.s. value measurement and “thermal memory”
Adjustable short-circuit releases Ii• LZM...3-AE630-I: 2 – 8 x In (ex-works 6 x In)• LZM...4-4-AE...-I: 2 – 12 x In (ex-works 6 x In)
LZM...-4-AE.../...-I• With 60 % overload and short-circuit protection in 4th pole
IEC/EN 60947-2Adjustable overload releases Ir• 0.5 – 1 x In (ex-works 0.8 x In)Setting on neutral pole implemented via the main pole setting Ir of the main pole.R.m.s. value measurement and “thermal memory”
Adjustable delayed short-circuit releases Isd• 2 – 10 x Ir (ex-works 6 x Ir)
– LZM…3-VE630-I: 1.5 – 7 x Ir (ex-works 6 x Ir)
Adjustable delay time tsd• Steps: 0, 20, 60, 100, 200, 300, 500, 750, 1000 ms (ex-works 0 ms)
Adjustable short-circuit releases Ii• LZM2: fixed 12 x In• LZM...3-4-VE400-I: 2 – 11 x In (ex-works 6 x In)• LZM...3-4-VE630-I: 2 – 8 x In (ex-works 6 x In)• LZM...4-4-VE...-I: 2 – 12 x In (ex-works 12 x In)
i2t constant function (ex-works OFF)• LZM2 fixed OFF• LZM3, LZM4 switched (ex-works OFF)
LZM...-4-AE.../...-I• With 60 % overload and short-circuit protection in 4th pole
17
LZM…2, LZM…3, LZM…4
Circ
uit-
brea
kers
, sw
itch
-dis
Prot4 po
T
Syst4 po
T
Not
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Circuit-breakers, electronic releases, 4 pole
Comfort switching capacity 36 kA at 415 V 50/60 Hz
Normal switching capacity 50 kA at 415 V 50/60 Hz
Rated current = rated uninterrupted current
Setting range Part no.Article no.
Pricesee price list
Part no.Article no.
Pricesee price list
Std. packOverload releases Short-circuit
releasesNon-delayed
Delayed short-circuit release
In = Iu Ir Ii Isd
A A A A
ection of systems and cablesleerminal screws standard, terminals as accessories
630 315…630 1260…5040 LZMC3-4-AE630/400-I111963
LZMN3-4-AE630/400-I111977
1 off
800 400…800 1600…9600 LZMN4-4-AE800/500-I111986
1000 500…1000 2000…12000 LZMN4-4-AE1000/630-I111987
1250 630…1250 2500…15000 LZMN4-4-AE1250/800-I111988
1600 800…1600 3200…19200 LZMN4-4-AE1600/1000-I111989
ems and cable protection, selectivity and generator protectionleerminal screws standard, terminals as accessories
160 80…160 1920 160…1600 LZMC2-4-VE160/100-I111952
1 off
250 125…250 3000 250…2500 LZMC2-4-VE250/160-I111953
400 200…400 800…4400 400…4000 LZMC3-4-VE400/250-I111964
LZMN3-4-VE400/250-I111972
630 315…630 1260…5040 472…4410 LZMC3-4-VE630/400-I111965
LZMN3-4-VE630/400-I111973
800 400…800 1600…9600 800…8000 LZMN4-4-VE800/500-I111990
1000 500…1000 2000…12000 1000…10000 LZMN4-4-VE1000/630-I111991
1250 630…1250 2500…15000 1250…12500 LZMN4-4-VE1250/800-I111992
1600 800…1600 3200…19200 1600…16000 LZMN4-4-VE1600/1000-I111993
es Notes for terminals a 29
I I
LZM…2, LZM…3, LZM…4
18Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
OrderingSwitch-disconnectors 3 pole, 4 pole
3 switch positions I, +, 0; can be tripped remotely with shunt/undervoltage release3 pole 4 pole
Rated current = rated uninterrupted current
Short-circuit protection max. fuse gL-characteristic
Part no.Article no.
Pricesee price list
Part no.Article no.
Pricesee price list
Std. pack
In = IuA A gL
Switch-disconnectorsTerminals standard, terminal screws as accessories
63 125 LN1-63-I111994
LN1-4-63-I111998
1 off
100 125 LN1-100-I111995
LN1-4-100-I111999
125 125 LN1-125-I111996
LN1-4-125-I112000
160 160 LN1-160-I111997
LN1-4-160-I112001
Terminal screws standard, terminals as accessories160 250 LN2-160-I
112002LN2-4-160-I112005
1 off
200 250 LN2-200-I112003
LN2-4-200-I112006
250 250 LN2-250-I112004
LN2-4-250-I112007
400 630 LN3-400-I112008
LN3-4-400-I112010
630 630 LN3-630-I112009
LN3-4-630-I112011
800 1600 LN4-800-I112012
LN4-4-800-I112016
1000 1600 LN4-1000-I112013
LN4-4-1000-I112017
1250 1600 LN4-1250-I112014
LN4-4-1250-I112018
1600 1600 LN4-1600-I112015
LN4-4-1600-I112019
Notes Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113Isolating characteristics to IEC/EN 60947-3 and VDE 0660Protection against accidental contact according to IEC 100Notes for terminals a 21
LN1…, LN2…, LN3…, LN4…
19
http://catalog.moeller.net Moeller SK1230-1177GB
Notes
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
20
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Ordering OrderingConnection types
t no.icle no. when ered separately
Pricesee price list
Std. pack Notes
M1-XKC015
1 off Standard connection with all switches LZM1 and LN1.Conversion kit for circuit-breaker with screw connection.Type contains parts for a 3 or 4-pole switch side.Fitted within the switch housingM1-4-XKC
0751 off
M1-XKS019
1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers. Fitted outside the switch housingMounting of the cover NZM1(-4)-XKSA obligatory (supplied).
M1-4-XKS725
1 off
M1-XKA730
1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.A standard with control circuit terminal for 1 x 0.75 – 2.5 mm2 (18 – 14 AWG) or 2 x 0.75 – 1.5 mm2 (18 – 14 AWG) copper conductors.Fitted outside the switch housingUse with flexible and highly flexible conductors ferrules. Maximum specified cross-section can only be connected when stranded and without ferrules.Mounting of the cover NZM1(-4)-XKSA obligatory (supplied).
M1-4-XKA731
1 off
M1-XKR734
1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
M1-4-XKR737
1 off
21
LZM1
Circ
uit-
brea
kers
, sw
itch
-dis
BoxStan
Scre
Tun
Con
Not
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Connection types
ParArtord
Max. cable connection area
For use with Terminal capacities Terminal capacitiesType of conductor AWG/kcmil Cu strip (number of segments
x width x segment thickness)
Copper busbar width x thickness
mm2 mm mm
terminaldard equipment
LZM1(-4)LN1(-4)
Three- and four-pole Cu cable 1 x 10 – 701)
2 x 6 – 251 x 8 – 2/02 x 9 – 4
2 x 9 x 0.89 x 9 x 0.8
NZ260
NZ267
w connectionLZM1(-4)LN1(-4)
Three- and four-pole Copper cable lugs Aluminium cable lug
1 x 10 – 702 x 6 – 251 x 10 – 352 x 10 – 35
1 x 8 – 2/02 x 9 – 41 x 8 – 22 x 8 – 2
min. 12 x 5max. 16 x 5
NZ260
min. 12 x 5max. 16 x 5
NZ266
nel terminalLZM1(-4)LN1(-4)
Three- and four-pole Copper cableAl cable
1 x 16 – 95 1 x 6 – 3/0–
NZ266NZ266
nection on rear– LZM1(-4)
LN1(-4)Three- and four-pole Copper cable lugs
Aluminium cable lug
1 x 2.5 – 252 x 2.5 – 251 x 10 – 352 x 10 – 35
F 12 x 5F 16 x 5
NZ266NZ266
es 1) Up to 240 mmB can be connected depending on the cable manufacturer.
10
12
7o 6.5
16
14.5
LZM1
22
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Ordering OrderingConnection types
tains parts for two terminal locations located at top or bottom for 3 or 4-pole circuit-breakers. as standard with tunnel terminalf protection IP1XK cannot be combined with NZM1(-4)-XIPK IP2X protection against contact with a finger.
r thickness of the control terminals:K = 2 mmS = 2 mm
tains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.n against direct contact where cable lugs, busbars or tunnel terminals are usedd in kit with tunnel terminals or screw connection terminals.f protection IP1X on the connection side when using insulated conductor material.
tains parts for a terminal located at top or bottom for 3 or 4 pole circuit-breakers.ment of the protection against direct contact (simple finger protection).
tains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.ment of the protection against direct contact to IP2X.n when reaching into the cable connection area with the connection of cables in the box terminal.e combined with NZM-XSTK control circuit terminal.
tains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.ment of the protection against direct contact to IP2X.
LZM1
23
Circui
t-br
eake
rs, s
wit
ch-d
is
Con
Cov
Term
For
IP2XFor
For
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Connection types
Part no.Article no. when ordered separately
Pricesee price list
Max. cable connection area
For use with Terminal capacities Std. pack NotesType of conductor AWG/kcmil
mm2
trol circuit terminal– LZM1(-4)
LN1(-4)Three- and four-pole Screw connection 1 x 0.75 – 2.5
2 x 0.75 – 1.51 x 18 – 14 2 x 18 – 16
NZM1-XSTS260150
1 off Type conIncludedDegree oNZM-XSTHeight oNZM-XSTNZM-XST
– Box terminal NZM-XSTK266739
1 off
er– LZM1(-4)
LN1(-4)3 pole NZM1-XKSA
2600211 off Type con
ProtectioContaineDegree o
– 4 pole NZM1-4-XKSA266741
1 off
inal cover, knockout
box terminals– LZM1
LN13-pole NZM1-XKSFA
1007801 off Type con
Enhance– LZM1-4
LN1-44 pole NZM1-4-XKSFA
1007811 off
protection against contact with a fingerbox terminals
– LZM1LN1
3 pole NZM1-XIPK266744
1 off Type conEnhanceProtectioCannot b
– LZM1-4LN1-4
4 pole NZM1-4-XIPK266745
1 off
cover NZM1(-4)-XKSA– LZM1
LN13 pole NZM1-XIPA
2667481 off Type con
Enhance– LZM1-4
LN1-44 pole NZM1-4-XIPA
2667491 off
LZM1
24
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Ordering OrderingConnection types
rt no.ticle no. when ordered parately
Pricesee price list
Std. pack
Notes
M2-160-XKC2240
1 off Type suffix and type contain parts for a circuit-breaker side at top or bottom for 3 or 4 pole circuit-breakers.Conversion kit for circuit-breaker with screw connection.Fitted within the switch housingO = for fitting at the topU = for fitting at the bottomUe f 525 V AC:• Use cover NZM2(4)-XKSA.Use ferrules with flexible and highly flexible conductors. Max. cross section shown can only be connected when flexible and without ferrules.
M2-250-XKC2244
M2-4-160-XKC6755
M2-4-250-XKC6756
M2-XKS0030
1 off Type contains parts for a terminal located at top or bottom for 3 or 4 pole circuit-breakers.Standard connection with all LZM2 circuit-breakers.Conversion kit for circuit-breaker with box terminal.Use special cable lug narrow version, a 27Fitted within the switch housingIf a busbar is used, insulation (400 mm) e.g sleeving and a NZM2(-4)-XKSA cover are required.Ue f 525 V AC:• For all other connection material a NZM2(-4)-XKSA
shroud must be used.
M2-4-XKS6750
1 off
M2-XKA1457
1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.A standard with control circuit terminal for 1 x 0.75 – 2.5 mm2 (18 – 14 AWG) or 2 x 0.75 – 1.5 mm2 (18 – 16 AWG) copper conductors.Fitted outside the switch housingUse with flexible and highly flexible conductors ferrules. Maximum specified cross-section can only be connected when stranded and without ferrules.Mounting of the cover NZM2(-4)-XKSA obligatory (supplied).
M2-4-XKA1458
1 off
M2-XKR6765
1 off Type suffix and type contain parts for a circuit-breaker side at top or bottom for 3 or 4-pole circuit-breakers.O = for fitting at the topU = for fitting at the bottom
M2-4-XKR6768
25
LZM2
Circ
uit-
brea
kers
, sw
itch
-dis
Box
Scre
Stan
Tun
Con
Whe
Not
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Connection types
Max. cable connection area
For use with Terminal capacities Terminal capacities Part no.Article no. when ordered with basic unit
Pricesee price list
PaArse
Type of conductor
Terminal capacities
AWG/kcmil Cu strip (number of segments x width x segment thickness)
Copper busbar width x thickness
mm2 mm mm
terminalLZM2(-4)LN2(-4)
Three- and four-pole
Copper conductorsCu cable
1 x 4 – 1852 x 4 – 70
1 x 11 – 3502 x 12 – 2/0
f 2 x 9 x 0.8 +NZM2-160-XKCO262218
NZ26
+NZM2-160-XKCU262223+NZM2-250-XKCO262242
NZ26
+NZM2-250-XKCU262243+NZM2-4-160-XKCO266751
NZ26
+NZM2-4-160-XKCU266753+NZM2-4-250-XKCO266752
NZ26
+NZM2-4-250-XKCU266754
w connection
dard equipmentLZM2(-4)LN2(-4)
Three- and four-pole
Copper cable lugs
Aluminium cable lug
1 x 4 – 1852 x 4 – 701 x 10 – 502 x 10 – 50
1 x 11 – 3/02 x 121 x 8 – 1/02 x 8 – 1/0
f 2 x 16 x 0.8 f 16 x 5 NZ26
NZ26
nel terminalLZM2(-4)LN2(-4)
Three- and four-pole
Copper cableAl cable
1 x 16 … 1851 x 16 … 185
1 x 6 – 350–
NZ27
NZ27
nection on rear
n using cable lugs without NZM3(-4)-XKSA cover, they must be insulated.LZM2(-4)LN2(-4)
Three- and four-pole
Copper cable lugs
Aluminium cable lug
1 x 4 – 1852 x 4 – 701 x 10 – 502 x 10 – 50
f 2 x 16 x 0.8F 6 x 24 x 0.5
f 16 x 5F 20 x 5
+NZM2-XKRO266763
NZ26
+NZM2-XKRU266764
NZ26
+NZM2-4-XKRO266766+NZM2-4-XKRU266767
es 1) Up to 240 mmB can be connected depending on the cable manufacturer.
15
18
8o 8.5
24
20.5
LZM2
26
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Ordering OrderingConnection types
d. ck
Notes
off Type contains parts for two terminal locations located at top or bottom for 3 or 4-pole circuit-breakers.Included as standard with tunnel terminalDegree of protection IP1XNZM-XSTK cannot be combined with NZM2(-4)-XIPK IP2X protection against contact with a finger.Height or thickness of the control circuit terminals:NZM-XSTK = 2 mmNZM-XSTS = 2 mm
off
off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.Protection against direct contact where cable lugs, busbars or tunnel terminals are usedDegree of protection IP1X on the connection side when using insulated conductor material.off
off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.Enhancement of the protection against direct contact (simplified protection against contact with a finger).
off
off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.Enhancement of the protection against direct contact to IP2X.Protection when reaching into the cable connection area with the connection of cables in the box terminal.With 2 conductors minimum cross-section 25 mm2.Cannot be combined with NZM-XSTK control circuit terminal.
off
off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.Enhancement of the protection against direct contact to IP2X.
off
off Type contains a cable lug for 3-pole or 4-pole switches.Special cable lug, narrow style
LZM2
27
Circui
t-br
eake
rs, s
wit
ch-d
is
Con
Cov
Con
IP2XFor
For
Cop
Whe
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Connection types
Max. cable connection area
For use with Terminal capacities Part no.Article no. when ordered separately
Pricesee price list
StpaType of conductor Terminal capacities AWG/kcmil Copper busbar
width x thicknessmm
mm2
trol circuit terminalLZM2(-4)LN2(-4)
Three- and four-pole
Screw connection 1 x 0.75 – 2.52 x 0.75 – 1.5
1 x 18 – 14 2 x 18 – 16
NZM2-XSTS260156
1
LZM2(-4)LN2(-4)
Three- and four-pole
Box terminal 1 x 0.75 – 2.52 x 0.75 – 1.5
1 x 18 – 14 2 x 18 – 16
NZM-XSTK266739
1
erLZM2LN2
3 pole NZM2-XKSA260038
1
LZM2-4LN2-4
4 pole NZM2-4-XKSA266770
1
nection cover, knockoutLZM2LN2
3 pole NZM2-XKSFA104640
1
LZM2-4LN2-4
4 pole NZM2-4-XKSFA104641
1
protection against contact with a fingerbox terminals
LZM2LN2
3 pole NZM2-XIPK266773
1
LZM2-4LN2-4
4 pole NZM2-4-XIPK266774
1
covers NZM2(-4)-XKSA or NZM2(-4)LZM2LN2
3 pole NZM2-XIPA266777
1
LZM2-4LN2-4
4 pole NZM2-4-XIPA266778
1
per cable lug
n using cable lugs without NZM3(-4)-XKSA cover, they must be insulated.95 mm2 LZM2(-4)
LN2(-4)Three- and four-pole
KS95-NZM7059775
3
120 mm2 KS120-NZM7059776
150 mm2 KS150-NZM7059777
185 mm2 NZM2-XKS185260032
LZM2
28
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Ordering OrderingConnection types
Pricesee price list
Part no.Article no. when ordered separately
Pricesee price list
Std. pack Notes
NZM3-XKC260042
1 off Type suffix and type contain parts for a circuit-breaker side at top or bottom for 3 or 4-pole circuit-breakers.Conversion kit for circuit-breaker with screw connection.Fitted within the switch housingO = for fitting at the topU = for fitting at the bottomUe f 525 V AC:• Use NZM3(-4)-XKSA cover.Use with flexible and highly flexible conductors ferrules, note the max. terminal capacity when using ferrules.
NZM3-4-XKC266783
NZM3-XKS260039
1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.Standard connection with all LZM3 circuit-breakers and LN3 switch-disconnectors.Conversion kit for circuit-breaker with box terminal.Use special cable lugs narrow version, a 32Fitted within the switch housingWhen a busbar is used insulation is required (400 mm) e.g. using heat shrink and a shroud NZM3(-4)-XKSA.Ue f 525 V AC:A shroud NZM3(-4)-XKSA must be used with all other connection types.
NZM3-4-XKS266780
1 off
NZM3-XKV70100514
1 off Type contains parts for a terminal located at top or bottom for 3 or 4 pole circuit-breakers.Central drill holes, e.g. for up to 2 cable lugs per phase.Can be fitted to circuit-breaker with screw terminationPhase isolator supplied.Distance between pole centres with NZM3(-4)-XKV70: 70 mmDrill hole available for control cable.Connection terminals NZM3(-4)-XK300 and NZM3(-4)-XK22X21 can be installed.
NZM3-4-XKV70100515
1 off
29
LZM3
Circ
uit-
brea
kers
, sw
itch
-dis
Box
Scre
Con
Not
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Connection types
Max. cable connection area
Rated current1)
For use with Terminal capacities Terminal capacities Part no.Article no. when ordered with basic unit
In Type of conductor
Terminal capacities
AWG/kcmil Cu strip (number of segments x width x segment thickness)
Copper busbar width x thickness
A mm2 mm mm
terminalmax. 500400 UL/CSA
LZM3(-4)LN3(-4)
Three- and four-pole
Copper conductorsCu cable
1 x 35 – 2402 x 16 – 120
1 x 2 – 500 min. 6 x 16 x 0.8max. 20 x 24 x 0.5ormax. 11 x 21 x 1
+NZM3-XKCO262246+NZM3-XKCU262245
630 1 x 35 – 2402 x 16 – 120
1 x 2 – 500 min. 6 x 16 x 0.8max. 20 x 24 x 0.5ormax. 11 x 21 x 1
+NZM3-4-XKCO266781+NZM3-4-XKCU266782
w connection630 LZM3(-4)
LN3(-4)Three- and four-pole
Copper cable lugs
Aluminium cable lug
1 x 16 – 2402 x 16 – 2401 x 10 – 1202 x 10 – 120
1 x 4 – 3502 x 350
10 x 32 x 1.0+ 5 x 32 x 1.0
30 x 10+ 30 x 5
max. 400
nection width extension630 LZM3(-4)
LN3(-4)Three- and four-pole
Copper cable lugs
Aluminium cable lug
2 x 300 2 x 500 (2 x) 10 x 50 x 1.0 (2 x) 10 x 50
es 1) The following applies for the rated current: The values have been determined conform to IEC/EN 60947 (switchgear standard) and generally relate to the max. defined cross-sections and are intended for the purpose of orientation.
16
25
15
o 10.5
32
LZM3
30
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Ordering OrderingConnection types
Pricesee price list
Part no.Article no. when ordered separately
Pricesee price list
Std. pack
Notes
NZM3-XK300100782
1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.Only in conjunction with connection width extension NZM3(-4)-XKV70.Use with flexible and highly flexible conductors ferrules.Standard with control circuit terminal for 1 x 0.75 – 2.5 mm2 or 2 x 0.75 – 1.5 mm2 copper conductors.
NZM3-4-XK300100783
1 off
NZM3-XK22X21100784
1 off
NZM3-4-XK22X21100785
1 off
NZM3-XKA1271459
1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.A standard with control circuit terminal for 1 x 0.75 – 2.5 mm2 (18 – 14 AWG) or 2 x 0.75 – 1.5 mm2 (18 – 16 AWG) copper conductors.Fitted outside the switch housingUse with flexible and highly flexible conductors ferrules. Maximum specified cross-section can only be connected when stranded and without ferrules.Mounting of the cover NZM3(-4)-XKSA obligatory (supplied).
NZM3-4-XKA1271460
1 off
NZM3-XKA2271461
1 off
NZM3-4-XKA2271462
1 off
NZM3-XKR266792
1 off Type suffix and type contain parts for a circuit-breaker side at top or bottom for 3 or 4-pole circuit-breakers.O = for fitting at the topU = for fitting at the bottom
NZM3-4-XKR266795
1 off
NZM3/4-XSTS266797
1 off Type contains parts for two terminal locations located at top or bottom for 3 or 4 pole circuit-breakers.Included as standard with tunnel terminalDegree of protection IP1XHeight or thickness of the control circuit terminalsNZM-XSTS = 2 mm
NZM-XSTK266739
1 off
LZM3
31
Circui
t-br
eake
rs, s
wit
ch-d
is
Term
Tun
Con
not
Con
Not
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Connection types
Max. cable connection area
Rated current1)
For use with Terminal capacities Terminal capacities Part no.Article no. when ordered with basic unit
Type of conductor
Terminal capacities
AWG/kcmil Cu strip (number of segments x width x segment thickness)
Copper busbar width x thickness
In
A mm2 mm mm
inals for connection width extensionmax. 500 LZM3, LN3 3 pole Cu cable 1 x 120 – 300
LZM3-4, LN3-4 4 pole
630 LZM3, LN3 3 pole (2 x) 11 x 21 x 1.0
LZM3-4, LN3-4 4 pole (2 x) 11 x 21 x 1.0
nel terminal– max. 350 LZM3(-4)
LN3(-4)Three- and four-pole
Copper conductorsCu cableAl conductorsAl cable
1 x 16 – 1852) 1 x 6 – 350–
– max. 630 1 x 50 – 2402 x 50 – 240
1 x 0 – 5002 x 0 – 500
nection on rear
UL/CSA approvedmax. 630 LZM3(-4)
LN3(-4)Three- and four-pole
Copper cablesCu cable
1 x 16 – 2402 x 16 – 240
+NZM3-XKRO266790+NZM3-XKRU266791+NZM3-4-XKRO266793+NZM3-4-XKRU266794
max. 500 – – 1 x 10 – 1202 x 10 – 120
min.6 x 16 x 0.8Max. 10 x 32 x 1.0
Min. 20 x 5Max. 30 x 10
trol circuit terminal– LZM3(-4)
LN3(-4)Three- and four-pole
Screw connection
1 x 0.75 – 2.52 x 0.75 – 1.5
1 x 18 – 14 2 x 18 – 16
– LZM3(-4)LN3(-4)
Box terminal
es 1) The following applies for the rated current: The values have been determined conform to IEC/EN 60947 (switchgear standard) and generally relate to the max. defined cross-sections and are intended for the purpose of orientation.The engineering standards which apply in each case must be observed.
20.5
22.5
LZM3
32
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Ordering OrderingConnection types
or bottom for 3 or 4-pole circuit-breakers.re cable lugs, busbars or tunnel terminals are used.
e when using insulated conductor material.
or bottom for 3 or 4 pole circuit-breakers.
nnel terminal, NZM3(-4)-XKR connection on rear.gs, busbars or braid.
or bottom for 3 or 4-pole circuit-breakers.ntact to (simplified protection against contact with a finger).
or bottom for 3 or 4-pole circuit-breakers.ntact to IP2X.ion area with the connection of cables in the box terminal.
2.cuit terminal.
or bottom for 3 or 4-pole circuit-breakers.ntact to IP2X.
itches.
LZM3
33
Circui
t-br
eake
rs, s
wit
ch-d
is
Cov
Pha
Con
IP2X
For
Cop
Whe
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Connection types
Max. cable connection area
For use with Part no.Article no. when ordered separately
Pricesee price list
Std. pack Notes
er– – LZM3(-4)
LN3(-4)3 pole NZM3-XKSA
2600451 off Type contains parts for a terminal located at top
Insulation/protection against direct contact wheIncluded in set with tunnel terminalsDegree of protection IP1X on the connection sid
– – 4 pole NZM3-4-XKSA266801
1 off
se isolator– – LZM3(-4)
LN3(-4)3 pole NZM3-XKP
1005121 off Type contains parts for a terminal located at top
Included with the connection width extension.Cannot be combined with the NZM3(-4)-XKA tuInsulation protection with connection of cable lu
– – 4 pole NZM3-4-XKP100513
1 off
nection cover, knockout– – LZM3(-4)
LN3(-4)3 pole NZM3-XKSFA
1046421 off Type contains parts for a terminal located at top
Enhancement of the protection against direct co– – 4 pole NZM3-4-XKSFA
1046431 off
protection against contact with a finger– LZM3(-4)
LN3(-4)3 pole NZM3-XIPK
2668041 off Type contains parts for a terminal located at top
Enhancement of the protection against direct coProtection when reaching into the cable connectWith 2 conductors minimum cross-section 70 mmCannot be combined with NZM-XSTK control cir
4 pole NZM3-4-XIPK266805
1 off
cover NZM3(-4)-XKSA– LZM3(-4), LN3(-4) 3 pole NZM3-XIPA
2668081 off Type contains parts for a terminal located at top
Enhancement of the protection against direct co
– 4 pole NZM3-4-XIPA266809
1 off
per cable lug
n using cable lugs without NZM3(-4)-XKSA cover, they must be insulated.185 mm2 – LZM3(-4), LN3(-4)
LZM4(-4), LN4(-4)3 and 4 pole NZM3-XKS185
2600403 off Type contains a cable lug for 3-pole or 4-pole sw
Special cable lug, narrow style
900 mm2 – 3 and 4 pole NZM3-XKS240260041
3 off
LZM3
34
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Ordering OrderingConnection types
o. no. when d separately
Pricesee price list
Std. pack Notes
off Double hole fitting for M10 screws with 25 mm clearance.Use special cable lug narrow version.Ue f 525 V or cross-section > 185 mm2: Use of shroud NZM4(-4)-XKSA required.
off
-XKM14
1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.For M10 screws. Can be enlarged for M12 screws.Use special cable lug narrow version.Can be fitted to circuit-breaker with screw terminationInsulation through NZM4(-4)-XKSA cover or NZM4(-4)-XKP phase separator necessary
-4-XKM15
1 off
-XKM20
1 off
-4-XKM21
1 off
-XKM2S-
1
1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.Insulation through cover NZM4(-4)-XKSA or phase isolator NZM4(4)-XKP necessary.-4-XKM2S-
2
1 off
-XKM2S-
3
1 off
-4-XKM2S-
4
1 off
-XKV951
1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.Five way holes, e.g. for up to 9 cable lugs per phase.Can be fitted to circuit-breaker with screw terminationPhase isolator supplied.Distance between pole centres with NZM4(-4)-XKV95: 95 mmInstallation conditions for current transformer up to 130 mm width with 80 mm busbar width.Distance between pole centres with NZM4-XKV110: 107.5 mmInstallation conditions for current transformer up to 135 mm width with 80 mm busbar width.Distance between pole centres with NZM4-4-XKV120: 122 mmInstallation conditions for current transformer up to 164 mm width with 80 mm busbar width.4 mm drilled holes for control circuit terminal available.
-XKV1103
1 off
-4-XKV952
1 off
-4-XKV1204
1 off
35
LZM4
Circ
uit-
brea
kers
, sw
itch
-dis
Scre
Stan
Mod
Con
Not
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Connection types
Max. cable connection area Rated current1)
For use with Terminal capacities Terminal capacities Part nArticleordereType of
conductorTerminal capacities
AWG/kcmil Cu strip (number of segments x width x segment thickness)
Copper busbar width x thickness
In
A mm2 mm mm
w connection
dard equipment2-hole max. 1250 LZM4(-4)
LN4(-4)Three- and four-pole
Cu cable lugs 1 x 120 – 1854 x 50 – 185
1 x 250 – 3504 x 0 – 350
(2 x) 10 x 50 x 1.0 (2 x) 50 x 10
1600
ule plateSingle hole
max. 1250 LZM4, LN4 3 pole Copper cable lugs
1 x 120 – 3002 x 95 – 300
1 x 250 – 6002 x 000 – 600
(2 x) 10 x 40 x 1.0(2 x) 10 x 50 x 1.0
(2 x) 40 x 10(2 x) 50 x 10
NZM426681
LZM4-4LN4-4
4 pole NZM426681
Double hole
max. 1400 LZM4, LN4 3 pole Copper cable lugs
2 x 95 – 1854 x 35 – 1854 x 50
2 x 000 – 3504 x 2 – 350
NZM426682
LZM4-4LN4-4
4 pole NZM426682
Double hole
max. 1250 LZM4, LN4 3 pole Copper cable lugs
2 x 95 – 300 2 x 000 – 600 NZM4125028447
LZM4-4LN4-4
4 pole NZM4125028447
max. 1600 LZM4, LN4 3 pole Copper cable lugs
2 x 95 – 300 2 x 000 – 500 NZM4160028447
LZM4-4LN4-4
4 pole 2 x 95 – 300 2 x 000 – 500 NZM4160028447
nection width extensionmax. 1600 LZM4, LN4 3 pole Cu cable lugs 4 x 300
6 x 95 – 2404 x 6006 x 000 … 500
min. 10 x 50 x 1.0 max. (2 x) 80 x 10 NZM428159NZM428159
LZM4-4LN4-4
4 pole NZM428159NZM428159
es 1) The following applies for the rated current: The values have been determined conform to IEC/EN 60947 (switchgear standard) and generally relate to the max. defined cross-sections and are intended for the purpose of orientation.
25
50
20
o10.5o10.5
LZM4
36
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Ordering OrderingConnection types
. when parately
Pricesee price list
Std. pack Notes
B 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.Conversion kit for circuit-breaker with screw connection.Insulation through cover NZM4(-4)-XKSA or phase isolator NZM4(4)-XKP necessary.With switch mpunting on conductive mounting plates use of the shroud NZM4(-4)-XKSA necessary (supplied item).
XKB 1 off
A 1 off Type contains parts for a terminal located at top or bottom for 3 or 4 pole circuit-breakers.A standard with control circuit terminal for 1 x 0.75 … 2.5 mm2 (18 … 14 AWG) or 2 x 0.75 … 1.5 mm2 (18 … 16 AWG) copper conductors.Can be fitted to circuit-breaker with screw terminationUse ferrules with flexible and highly flexible conductors. Max. cross section shown can only be connected when flexible and without ferrules.Use of the NZM4(-4)-XKSA cover obligatory(supplied).
XKA 1 off
R 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.Can also be retrofitted:NZM4...-XKM... module plate or NZM4-...-XKV... connection width extension
XKR 1 off
off
LZM4
37
Circui
t-br
eake
rs, s
wit
ch-d
is
Flat
Tun
Con
Not
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Connection types
Max. cable connection area Rated current1)
For use with Terminal capacities
Terminal capacities Part no.Article noordered se
In Type of conductor
Terminal capacities
AWG/kcmil Cu strip (number of segments x width x segment thickness)
Copper busbar width x thickness
A mmmm2 mm
cable terminal– max. 1100 LZM4, LN4 3 pole min.6 x 16 x 0.8
max. (2 x) 10 x 32 x 1.0NZM4-XK266829
– LZM4-4LN4-4
4 pole min.6 x 16 x 0.8max. (2 x) 10 x 32 x 1.0
NZM4-4-266831
nel terminal– max. 1400 LZM4, LN4 3 pole Copper
conductorsCu cableAl conductorsAl cable
1 x 50 – 2404 x 50 – 2401 x 50 – 2404 x 50 – 240
1 x 0 – 5004 x 0 – 5001 x 0 – 5004 x 0 – 500
NZM4-XK266836
– LZM4-4LN4-4
4 pole NZM4-4-266837
nection on rear– max. 1250 LZM4(-4)
LN4(-4)Three- and four-pole
Copper cable lugs
Aluminium cable lug
1 x 120 – 1852 x 95 – 1854 x 35 – 1851 x 1852 x 70 – 1854 x 50 – 185
(2 x) 10 x 50 x 1.0 (2 x) 50 x 10 NZM4-XK266842NZM4-4-266843
– 1600 –
es 1) The following applies for the rated current: The values have been determined conform to IEC/EN 60947 (switchgear standard) and generally relate to the max. defined cross-sections and are intended for the purpose of orientation.
22.5
LZM4
38
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Ordering OrderingConnection types
tains parts for two terminal locations located at top or bottom for 3 or 4 pole circuit-breakers. as standard with tunnel terminalf protection IP1Xr thickness of the control circuit terminalsS = 2 mm
tains parts for a terminal located at top or bottom for 3 or 4 pole circuit-breakers.n against direct contact where cable lugs, busbars, flat cable terminals or tunnel terminals are used.dule plates, flat braid terminals and tunnel terminals included in the kit.ing insulated conductor material to degree of protection: IP1X.
tains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.ment of the protection against direct contact to (simplified protection against contact with a finger).
tains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers. with the connection width extension.e combined with the tunnel terminal NZM4(-4)-XKA, connection NZM4-XKR on rear.n protection where cable lugs, busbars, module plates or flat cable terminals are used.
tains a cable lug for 3-pole or 4-pole switches.able lug, narrow style
LZM4
39
Circui
t-br
eake
rs, s
wit
ch-d
is
Con
Cov
Con
Pha
Cab
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Connection types
Max. cable connection area For use with Terminal capacities Part no.Article no. when ordered separately
Pricesee price list
Std. pack Notes
Type of conductor Terminal capacities
AWG/kcmil
mm2
trol circuit terminal– LZM3(-4)
LN3(-4)Three- and four-pole
Screw connection 1 x 0.75 – 2.52 x 0.75 – 1.5
1 x 18 – 14 2 x 18 – 16
NZM3/4-XSTS266797
1 off Type conIncludedDegree oHeight oNZM-XST
er– LZM4
LN43 pole NZM4-XKSA
2668461 off Type con
ProtectioWith moWhen us
– LZM4-4LN4-4
4 pole NZM4-4-XKSA266847
nection cover, knockout– LZM4
LN43 pole NZM4-XKSFA
2921931 off Type con
Enhance– LZM4-4
LN4-44 pole NZM4-4-XKSFA
292194
se isolators– LZM4
LN43 pole NZM4-XKP
2815951 off Type con
IncludedCannot bInsulatio
– LZM4-4LN4-4
4 pole NZM4-4-XKP281596
le lug185 mm2 LZM3(-4)
LZM4(-4)LN3(-4)LN4(-4)
3 and 4 pole NZM3-XKS185260040
3 off Type conSpecial c
900 mm2 NZM3-XKS240260041
LZM4
40Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
OrderingPlug-in units
For use with Number of poles Part no.Article no. when ordered with basic unit
Pricesee price list
Part no.Article no. when ordered separately
Pricesee price list
Std. pack
Notes
Plug-in and withdrawable units
For circuit-breakers LZM and switch-disconnectors LN Plug-in adapter elementsCompleteOnly in combination with circuit-breaker
Terminal screws standard, terminals as accessoriesLZM2LN2
3 pole +NZM2-XSV266697
1 off Inmax. at: 20 °C: 250 A40 °C: 230 A (LZM...2-...)Mounting position: vertical, 90° right, 90° leftOrder control circuit plug unit separately!
LZM2-4LN2-4
4 pole +NZM2-4-XSV266698
Socketse.g. for reserved slotsRetrofit of circuit-breaker with plug-in module.Terminal screws standard, terminals as accessories
LZM2LN2
3 pole NZM2-XSVS266699
1 off
LZM2-4LN2-4
4 pole NZM2-4-XSVS266700
Removable moduleFits socket baseOnly in combination with circuit-breaker
LZM2LN2
3 pole +NZM2-XSVE266701
1 off
LZM2-4LN2-4
4 pole +NZM2-4-XSVE266702
Control circuit plug unitLZM2(-4)LN2(-4)
for auxiliary contact, shunt/undervoltage release
NZM2-XSVHI266705
1 off –
LZM2(-4)LN2(-4)
for remote operator NZM2-XSVR266706
–
NZM2-XSV…
41
http://catalog.moeller.net Moeller SK1230-1177GB
OrderingWithdrawable units
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
For use with Number of poles
Part no.Article no. when ordered with basic unit
Pricesee price list
Part no.Article no. when ordered separately
Pricesee price list
Std. pack
Notes
Withdrawable unit with control circuit plug unit
For circuit-breakers LZM and switch-disconnectors LNWithdrawable unit with auxiliary plug-in adapterCompleteOnly in combination with circuit-breaker
Terminal screws standard, terminals as accessoriesLZM3LN3
3 pole +NZM3-XAV266707
1 off Inmax. at:20 °C: 605 A (LZM3), 1600 A (LZM4)40 °C: 550 A (LZM3), 1500 A (LZM4)
Mounting position LZM3: vertical, 90 ° left LZM4: vertical
3 positionsConnected, test, disconnected The 3 positions are indicated mechanically.
Additionally, auxiliary contacts are use for remote signalling. An optional M22-(C)K01normally closed contact or M22-(C)K10 normally open contact per positionAlso see the RMQ-Titan control circuit device range in the Main Catalogue
All connections of auxiliary switches (HIA, HIN, HIV) and voltage releases to the control circuit plug units are already present.
LZM3-4LN3-4
4 pole +NZM3-4-XAV266708
LZM4LN4
3 pole +NZM4-XAV266709
LZM4-4LN4-4
4 pole +NZM4-4-XAV266710
Socket basee.g. for reserved slotsRetrofit of circuit-breaker with withdrawable carrier.
Terminal screws standard, terminals as accessoriesLZM3LN3
3 pole NZM3-XAVS266711
1 off
LZM3-4LN3-4
4 pole NZM3-4-XAVS266712
LZM4LN4
3 pole NZM4-XAVS266713
LZM4-4LN4-4
4 pole NZM4-4-XAVS266714
Withdrawable carrierLZM3LN3
3 pole +NZM3-XAVE266715
1 off
LZM3-4LN3-4
4 pole +NZM3-4-XAVE266716
LZM4LN4
3 pole +NZM4-XAVE266717
LZM4-4LN4-4
4 pole +NZM4-4-XAVE266718
NZM3-XAV…
42
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Ordering OrderingAuxiliary contact with screw terminals
tes Notes
r Std. pack:22-(C)K... : d. pack = 20 off
The following can be clipped into the switches:• LZM1- one standard auxiliary contact• LZM2 - up to 2 standard auxiliary contacts M22-(C)K… • LZM3 and LZM4 - up to 3 standard auxiliary contacts M22-(C)K… Any combinations of the auxiliary contact types ispossible.Marking on switch: HIN
Not in conjunction with NZM…-XU… undervoltage release or NZM…-XA… shunt releaseEarly make with switch on and switch off (manual actuation): approx. 20 ms
Not in conjunction with undervoltage release NZM…-XU, shunt release NZM…-XA… or remote operator NZM…-XR…Early make with switch on (manual actuation): approx. 90 ms
r Std. pack:22-(C)K... : d. pack = 20 off
The following can be clipped into the switches:• LZM1 - one trip-indicating auxiliary switch• LZM2 - one M22-(C)K… trip-indicating auxiliary switch• LZM3 - one M22-(C)K… trip-indicating auxiliary switch• LZM4 - up to two M22-(C)K… trip-indicating auxiliary switchesAny combinations of the auxiliary contact types is possible. Marking on switch: HIALabeling in FI-Block: HIAFI.
If the trip-indicating auxiliary contact in the fault-current block is used, the N/C contacts operates as a N/O contact and the N/C contact operates as an N/O contact (circuit symbol)
43
LZM, M22-…
Circ
uit-
brea
kers
, sw
itch
-dis
AuxStanSwitUsed
EarlFor appl
TripGendue
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Auxiliary contact with screw terminals
For use with Auxiliary contacts: f = safety function, by positive opening to IEC/EN 60947-5-1
Contact sequence
Part no.Article no. when ordered separately
Pricesee price list
Part no.Article no. when ordered separately
Pricesee price list
Std. pack No
N/O = Normally open
N/C = Normally closed
iliary contactsdard auxiliary contact (HIN)ching with the main contacts for indicating and interlocking tasks
LZM1(-4), 2(-4), 3(-4), 4(-4)LN1(-4), 2(-4), 3(-4), 4(-4)
1 N/O M22-K10216376
M22-CK10216384
20 off FoMSt
1 N/C f M22-K01216378
M22-CK01216385
20 off
With 3 m connection cable instead of screw termination.
LZM1(-4), 2(-4), 3(-4), 4(-4)LN1(-4), 2(-4), 3(-4), 4(-4)
1 N/O 1 N/C f M22-CK11107940
20 off
2 N/O M22-CK20107898
2 N/C f M22-CK02107899
y-make auxiliary contactinterlocking and load shedding circuits, as well as for early make of the undervoltage release in main switch/Emergency-Stop ications
With clamp terminal on the left-hand switch side.
LZM1(-4)LN1(-4)
2 N/O NZM1-XHIV259426
1 off
With clamp terminal on the right-hand switch side.
2 N/O NZM1-XHIVR292195
With 3 m connection cable instead of screw termination.
2 N/O NZM1-XHIVL259432
LZM2(-4), 3(-4)LN2(-4), 3(-4)
2 N/O NZM2/3-XHIV259430
LZM4(-4)LN4(-4)
2 N/O NZM4-XHIV266172
indicating auxiliary contact (HIA), (HIAFI)eral trip indication '+', when tripped by voltage release, overload release, short-circuit release or by the residual-current release to residual-current.
LZM1(-4), 2(-4), 3(-4), 4(-4)LN1(-4), 2(-4), 3(-4), 4(-4)
1 N/O M22-K10216376
M22-CK10216384
20 off FoMSt
1 N/C f M22-K01216378
M22-CK01216385
With 3 m connection cable instead of screw termination.
LZM1(-4), 2(-4), 3(-4), 4(-4)LN1(-4), 2(-4), 3(-4), 4(-4)
1 N/O 1 N/C f M22-CK11107940
2 N/O M22-CK20107898
2 N/C f M22-CK02107899
1.X3
1.X4
1.X1
1.X2
1.X3
1.X4
1.X1
1.X2
1.X3
1.X4
1.X3
1.X4
1.X1
1.X2
1.X1
1.X2
3.13 3.23
3.14 3.24
3.13 3.23
3.14 3.24
3.13 3.23
3.14 3.24
3.13 3.23
3.14 3.24
3.13 3.23
3.14 3.24
4.X3
4.X4
4.X1
4.X2
4.X3
4.X4
4.X1
4.X2
4.X3
4.X4
4.X3
4.X4
4.X1
4.X2
4.X1
4.X2
LZM, M22-…
44Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
OrderingUndervoltage release with screw terminal
For use with Rated control voltage Part no.Article no. when ordered separately
Pricesee price list
Std. pack NotesUs
V
Undervoltage releasesWithout auxiliary contactNon-delayed disconnection of LZM circuit-breakers or LN switch-disconnectors when the control voltage sinks below 35 – 70% US.For use with Emergency-Stop devices in conjunction with Emergency-Stop button.
With clamp terminal on the left-hand switch side.
LZM1(-4)LN1(-4)
24 V 50/60 Hz NZM1-XU24AC259434
1 off When the undervoltage release is de-energized, accidental contact with the main contacts of the switch during attempts to switch on, is safely prevented .
Undervoltage release cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XA... shunt release.
110 V – 130 V 50/60 Hz NZM1-XU110-130AC259440
208 V 240 V 50/60 Hz NZM1-XU208-240AC259442
380 V – 440 V 50/60 Hz NZM1-XU380-440AC259444
480 V – 525 V 50/60 Hz NZM1-XU480-525AC259446
600 V 50/60 Hz NZM1-XU600AC259448
12 V DC NZM1-XU12DC259450
24 V DC NZM1-XU24DC259452
110 V – 130 V DC NZM1-XU110-130DC259458
220 V – 250 V DC NZM1-XU220-250DC259460
With 3 m connection cable instead of screw termination.
LZM1(-4)LN1(-4)
24 V 50/60 Hz NZM1-XUL24AC259462
1 off
110 V – 130 V 50/60 Hz NZM1-XUL110-130AC259468
208 V 240 V 50/60 Hz NZM1-XUL208-240AC259471
380 V – 440 V 50/60 Hz NZM1-XUL380-440AC259473
480 V – 525 V 50/60 Hz NZM1-XUL480-525AC259475
600 V 50/60 Hz NZM1-XUL600AC259477
12 V DC NZM1-XUL12DC259479
24 V DC NZM1-XUL24DC259481
110 V 130 V DC NZM1-XUL110-130DC259487
220 V – 250 V DC NZM1-XUL220-250DC259489
D1
D2
U <
D1
D2
U <
LZM1
45
http://catalog.moeller.net Moeller SK1230-1177GB
OrderingUndervoltage release with screw terminal
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
For use with Rated control voltage Part no.Article no. when ordered separately
Pricesee price list
Std. pack NotesUs
V
Undervoltage releasesWithout auxiliary contactNon-delayed disconnection of LZM circuit-breakers or LN switch-disconnectors when the control voltage sinks below 35 – 70% US.For use with Emergency-Stop devices in conjunction with Emergency-Stop button.
LZM2(-4), LN2(-4)LZM3(-4), LN3(-4)
24 V 50/60 Hz NZM2/3-XU24AC259491
1 off When the undervoltage release is de-energized, accidental contact with the main contacts of the switch during attempts to switch on, is safely prevented .
Undervoltage release cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XA... shunt release.
110 V – 130 V 50/60 Hz NZM2/3-XU110-130AC259497
208 V 240 V 50/60 Hz NZM2/3-XU208-240AC259499
380 V – 440 V 50/60 Hz NZM2/3-XU380-440AC259501
480 V – 525 V 50/60 Hz NZM2/3-XU480-525AC259503
600 V 50/60 Hz NZM2/3-XU600AC259505
12 V DC NZM2/3-XU12DC259507
24 V DC NZM2/3-XU24DC259509
110 V 130 V DC NZM2/3-XU110-130DC259515
220 V – 250 V DC NZM2/3-XU220-250DC259517
LZM4(-4)LN4(-4)
24 V 50/60 Hz NZM4-XU24AC266189
1 off
110 V – 130 V 50/60 Hz NZM4-XU110-130AC266192
208 V – 240 V 50/60 Hz NZM4-XU208-240AC266193
380 V – 440 V 50/60 Hz NZM4-XU380-440AC266194
480 V – 525 V 50/60 Hz NZM4-XU480-525AC266195
600 V 50/60 Hz NZM4-XU600AC266196
12 V DC NZM4-XU12DC266203
24 V DC NZM4-XU24DC266204
110 V – 130 V DC NZM4-XU110-130DC266207
220 V – 250 V DC NZM4-XU220-250DC266208
D1
D2
U <
D1
D2
U <
LZM2/3…, LZM4
46Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
OrderingUndervoltage release with screw terminal
For use with
Rated control voltage Part no.Article no. when ordered separately
Pricesee price list
Std. pack Notes
Us
V
Undervoltage releasesWith two early-make auxiliary contactsFor interlocking and load-shedding circuits, as well as for early-make of the undervoltage release in main-switch applications.
With clamp terminal on the left-hand switch side.
LZM1(-4)LN1(-4)
24 V 50/60 Hz NZM1-XUHIV24AC259531
1 off When the undervoltage release is de-energized, accidental contact with the main contacts of the switch during attempts to switch on is safely prevented.Early-make of the auxiliary contacts with on and off switching (manual operation): approx. 20 ms.Undervoltage releases cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XA... shunt release.
110 V – 130 V 50/60 Hz NZM1-XUHIV110-130AC259537
208 V – 240 V 50/60 Hz NZM1-XUHIV208-240AC259539
380 V – 440 V 50/60 Hz NZM1-XUHIV380-440AC259541
480 V – 525 V 50/60 Hz NZM1-XUHIV480-525AC259543
12 V DC NZM1-XUHIV12DC259545
24 V DC NZM1-XUHIV24DC259547
110 V – 130 V DC NZM1-XUHIV110-130DC259553
220 V – 250 V DC NZM1-XUHIV220-250DC259555
With 3 m connection cable instead of screw termination.
LZM1(-4)LN1(-4)
24 V 50/60 Hz NZM1-XUHIVL24AC259557
1 off
110 V – 130 V 50/60 Hz NZM1-XUHIVL110-130AC259563
208 V – 240 V 50/60 Hz NZM1-XUHIVL208-240AC259565
380 V – 440 V 50/60 Hz NZM1-XUHIVL380-440AC259567
480 V – 525 V 50/60 Hz NZM1-XUHIVL480-525AC259569
12 V DC NZM1-XUHIVL12DC259571
24 V DC NZM1-XUHIVL24DC259573
110 V – 130 V DC NZM1-XUHIVL110-130DC259579
220 V – 250 V DC NZM1-XUHIVL220-250DC259581
LZM2(-4)LZM3(-4)LN2(-4)LN3(-4)
24 V 50/60 Hz NZM2/3-XUHIV24AC259583
1 off When the undervoltage release is de-energized, accidental contact with the main contacts of the switch during attempts to switch on is safely prevented.Early-make of the auxiliary contacts with on and off switching (manual operation): approx. 20 ms.Cannot be used in conjunction with NZM...-XR... remote operator.Undervoltage releases cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XA... shunt release.
110 V – 130 V 50/60 Hz NZM2/3-XUHIV110-130AC259589
208 V – 240 V 50/60 Hz NZM2/3-XUHIV208-240AC259591
380 V – 440 V 50/60 Hz NZM2/3-XUHIV380-440AC259594
480 V – 525 V 50/60 Hz NZM2/3-XUHIV480-525AC259598
12 V DC NZM2/3-XUHIV12DC259600
24 V DC NZM2/3-XUHIV24DC259602
110 V – 130 V DC NZM2/3-XUHIV110-130DC259608
220 V – 250 V DC NZM2/3-XUHIV220-250DC259610
D1 3.13
3.14D2
D1 3.13
3.14D2
D1 3.13
3.14D2
LZM1, LZM2/3
47
http://catalog.moeller.net Moeller SK1230-1177GB
OrderingUndervoltage release with screw terminal
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
For use with Rated control voltage Part no.Article no. when ordered separately
Pricesee price list
Std. pack Notes
Us
V
Undervoltage releasesWith two early-make auxiliary contacts
For interlocking and load-shedding circuits, as well as for early-make of the undervoltage release in main-switch applications.
LZM4(-4)LN4(-4)
24 V 50/60 Hz NZM4-XUHIV24AC266217
1 off When the undervoltage release is de-energized, accidental contact with the main switches of the switch during attempts to switch on is safely prevented.Early-make of the auxiliary contacts with switch on (manual operation): approx. 90 ms.Cannot be used in conjunction with NZM...-XR... remote operator.Undervoltage releases cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XA... shunt release.
110 V – 130 V 50/60 Hz NZM4-XUHIV110-130AC266220
208 V – 240 V 50/60 Hz NZM4-XUHIV208-240AC266221
380 V – 440 V 50/60 Hz NZM4-XUHIV380-440AC266222
480 V – 525 V 50/60 Hz NZM4-XUHIV480-525AC266223
12 V DC NZM4-XUHIV12DC266231
24 V DC NZM4-XUHIV24DC266232
110 V – 130 V DC NZM4-XUHIV110-130DC266235
220 V – 250 V DC NZM4-XUHIV220-250DC266236
D1 3.13
3.14D2
LZM4
48Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
OrderingUndervoltage release with screw terminal
For use with Rated control voltage Part no.Article no. when ordered separately
Pricesee price list
Std. pack
Us
V
Undervoltage releasesWith two separate early-make auxiliary contacts
Coil connection wired to clamp terminal, auxiliary switch connections wired with 3 m loose connection cables
LZM1(-4), LN1(-4) 24 V 50/60 Hz NZM1-XUHIV20KL24AC284388
1 off
110 V – 130 V 50/60 Hz NZM1-XUHIV20KL110-130AC284389
208 V – 240 V 50/60 Hz NZM1-XUHIV20KL208-240AC284400
24 V DC NZM1-XUHIV20KL24DC284387
Coil connection with 3 m loose connection cables, auxiliary switch connections wired to clamp terminal
LZM1(-4), LN1(-4) 24 V 50/60 Hz NZM1-XUHIV20LK24AC284402
1 off
110 V – 130 V 50/60 Hz NZM1-XUHIV20LK110-130AC284403
208 V … 240 V 50/60 Hz NZM1-XUHIV20LK208-240AC284404
24 V DC NZM1-XUHIV20LK24DC284401
Coil connection with 3 m loose connection cables, auxiliary switch connections wired to clamp terminal
LZM2(-4), LN2(-4)LZM3(-4), LN3(-4)
24 V 50/60 Hz NZM2/3-XUHIV20LK24AC285291
1 off
110 V – 130 V 50/60 Hz NZM2/3-XUHIV20LK110-130AC284407
208 V – 240 V 50/60 Hz NZM2/3-XUHIV20LK208-240AC284408
24 V DC NZM2/3-XUHIV20LK24DC284405
Contacts 3.23 and 3.24 with separate 3 m connection cables.LZM4(-4), LN4(-4) 24 V 50/60 Hz NZM4-XUHIV2024AC
2662441 off
110 V – 130 V 50/60 Hz NZM4-XUHIV20110-130AC266247
208 V 240 V 50/60 Hz NZM4-XUHIV20208-240AC266248
380 V – 440 V 50/60 Hz NZM4-XUHIV20380-440AC266249
24 V DC NZM4-XUHIV2024DC266258
Notes When the undervoltage release is de-energized, accidental contact with the main switches of the switch during attempts to switch on is safely prevented.Early-make of the auxiliary contacts with on and off switching (manual operation): approx. 20 ms.Cannot be used in conjunction with NZM...-XR... remote operator.Undervoltage releases cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XA... shunt release.
3.23
3.24
3.13
3.14D2
D1
3.23
3.24
3.13
3.14D2
D1
3.23
3.24
3.13
3.14D2
D1
3.23
3.24
3.13
3.14D2
D1
LZM1, LZM2/3…, LZM4
49
http://catalog.moeller.net Moeller SK1230-1177GB
OrderingUndervoltage releases, off-delayed
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
For use with Part no.Article no. when ordered separately
Pricesee price list
Std. pack Notes
Undervoltage releases, off-delayed
Combination of separate delay unit and special tripping device.Delay unitVoltage dips of less than the setting between 0.06 – 16 s do not cause disconnection of the NZM circuit-breaker or N switch-disconnector.
LZM1(-4), 2(-4), 3(-4), 4(-4)LN1(-4), 2(-4), 3(-4), 4(-4)
50/60 Hz220 V – 240 V380 V – 440 V480 V – 550 V
DC/AC24 V
UVU-NZM260154
1 off Adjustable delay time 70 ms – 4 s.With additional capacitor up to 16 s.A special tripping device is required.Cannot be installed simultaneously with NZM...-XHIV... or NZM...-XA... shunt release.Delay unit for separate installation (Fixing: top-hat rail or screws).For other operating voltages use control transformer.
Special tripping deviceFor combination with separate delay unitWithout auxiliary contacts
NZM1-X… with 3 m separate connection cables instead of screw terminal, NZM2, 3 , 4 with screw terminal
LZM1(-4), LN1(-4) NZM1-XUVL271607
1 off UVU-NZM delay unit is additionally required.Cannot be installed simultaneously with separate NZM...-XHIV early-make auxiliary contact or NZM...-XA... shunt release.
LZM2(-4), LN2(-4)LZM3(-4), LN3(-4)
NZM2/3-XUV259527
LZM4(-4), LN4(-4) NZM4-XUV266588
With 2 early-make auxiliary contactsNZM1-X… with 3 m separate connection cables instead of screw terminal, NZM2, 3 , 4 with screw terminal
LZM1(-4), LN1(-4) NZM1-XUVHIVL271608
1 off Cannot be used in conjunction with NZM...-XR... remote operator.UVU-NZM delay unit is additionally required.Cannot be installed simultaneously with separate NZM...-XHIV early-make auxiliary contact or NZM...-XA... shunt release.LZM1, 2, 3: Early-make of the auxiliary contacts with on and off switching (manual operation): approx. 20 ms.LZM4: Early-make of the auxiliary contacts with switch on (manual operation): approx. 90 ms.
LZM2(-4), LN2(-4)LZM3(-4), LN3(-4)
NZM2/3-XUVHIV259684
LZM4(-4), LN4(-4) NZM4-XUVHIV266596
With 2 separately operating early-make auxiliary contactsNZM1-X… with 3 m separate connection cables instead of screw terminal, NZM2(3)(4)-X… with screw terminal, contact 3.23 and 3.24 with 3 m separate connection cables.
LZM1(-4), LN1(-4) NZM1-XUVHIV20L271609
1 off Cannot be used in conjunction with NZM...-XR... remote operator.UVU-NZM delay unit is additionally required.Cannot be installed simultaneously with separate NZM...-XHIV early-make auxiliary contact or NZM...-XA... shunt release.LZM1, 2, 3: Early-make of the auxiliary contacts with on and off switching (manual operation): approx. 20 ms.LZM4: Early-make of the auxiliary contacts with switch on (manual operation): approx. 90 ms.
LZM2(-4), LN2(-4)LZM3(-4), LN3(-4)
NZM2/3-XUVHIV20259688
LZM4(-4), LN4(-4) NZM4-XUVHIV20266604
D1
D2
U
D1 3.13
3.14D2
U
3.23
3.24
3.13
3.14D2
D1
LZM1, LZM2/3..., LZM4
50Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
OrderingShunt releases with screw terminal
For use with
Rated control voltage Part no.Article no. when ordered separately
Pricesee price list
Std. pack
Notes
Us
V
Shunt releasesWithout auxiliary contactSwitches are tripped by a voltage pulse or by the application of uninterrupted voltage.
With clamp terminal on the left-hand switch side.
LZM1(-4)LN1(-4)
12 V AC/DC NZM1-XA12AC/DC259706
1 off When the undervoltage release is de-energized, accidental contact with the main contacts of the switch during attempts to switch on, is safely prevented.
Shunt release cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XU... undervoltage release.
24 V AC/DC NZM1-XA24AC/DC259708
110 V – 130 V AC/DC NZM1-XA110-130AC/DC259724
208 V – 250 V AC/DC NZM1-XA208-250AC/DC259726
380 V – 440 V AC/DC NZM1-XA380-440AC/DC259728
With 3 m connection cable instead of screw termination.
LZM1(-4)LN1(-4)
12 V AC/DC NZM1-XAL12AC/DC259734
1 off
24 V AC/DC NZM1-XAL24AC/DC259736
110 V – 130 V AC/DC NZM1-XAL110-130AC/DC259742
208 V – 250 V AC/DC NZM1-XAL208-250AC/DC259744
380 V – 440 V AC/DC NZM1-XAL380-440AC/DC259746
Without auxiliary contactSwitches are tripped by a voltage pulse or by the application of uninterrupted voltage.
LZM2(-4)LZM3(-4)LN2(-4)LN3(-4)
12 V AC/DC NZM2/3-XA12AC/DC259752
1 off When the undervoltage release is de-energized, accidental contact with the main contacts of the switch during attempts to switch on, is safely prevented.
Shunt release cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XU... undervoltage release.
24 V AC/DC NZM2/3-XA24AC/DC259754
110 V – 130 V AC/DC NZM2/3-XA110-130AC/DC259760
208 V – 250 V AC/DC NZM2/3-XA208-250AC/DC259763
380 V – 440 V AC/DC NZM2/3-XA380-440AC/DC259766
LZM4(-4)LN4(-4)
12 V AC/DC NZM4-XA12AC/DC266446
1 off
24 V AC/DC NZM4-XA24AC/DC266447
110 V – 130 V AC/DC NZM4-XA110-130AC/DC266450
208 V – 250 V AC/DC NZM4-XA208-250AC/DC266451
380 V – 440 V AC/DC NZM4-XA380-440AC/DC266452
C1
C2
C1
C2
C1
C2
C1
C2
LZM1, LZM2/3, LZM4
51
http://catalog.moeller.net Moeller SK1230-1177GB
OrderingShunt releases with screw terminal
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
For use with Part no.Article no. when ordered separately
Pricesee price list
Std. pack Notes
Shunt releasesCapacitor unit 230 V 50/60 Hzin conjunction with NZM...-XA2082-50AC/DC shunt releaseEnclosure: degree of protection IP20
LZM1(-4)LZM2(-4)LZM3(-4)LZM4(-4)LN1(-4)LN2(-4)LN3(-4)LN4(-4)
NZM-XCM229413
1 off Enables the safe use of circuit-breakers as mesh network circuit-breakers in the range from 0 … 110 % Un with constant switch-off time of 40 ms.If the mains voltage is absent, the installed capacitor supplies power for actuating the shunt release for at least 12 hours.The configuration of the capacitor unit is undertaken independently of the circuit-breaker.Connect NZM-XCM to the power feed side.
Design note: Connect a standard auxiliary contact as N/O in series with the shunt release!Standard auxiliary contact not included as standard.
For use with
Rated control voltage
Part no.Article no. when ordered separately
Pricesee price list
Std. pack
Notes
Us
V
Shunt releasesWithout auxiliary contactsFor mesh-network circuit-breakersFor intermittent operationMaximum on time = 1 sOperating range 10 – 110 % Us
LZM3(-4)LN3(-4)
230 V AC NZM3-XA-230AC-MNS274097
1 off Cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XU... undervoltage release.
Intermittent operation guaranteed by series connection of an M22-(C)K10 make contact.The maximum operating time of the shunt release for mesh network circuit-breaker is 1 s.
LZM4(-4)LN4(-4)
230 V AC NZM4-XA-230AC-MNS274138
1 off
C1
C2
a Reverse-power relay contact-S11 Remote offQ Standard auxiliary contact-Q1 Shunt release
1.13
1.14
C1
C2-Q1
L1 (L+)
QHIN
-S110
NZM...-XA...-MNS
M22-...K10
N (L-, L2)
a
C1
C2
LZM...-X...
52Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
OrderingShunt releases with screw terminal
For use with
Rated control voltage Part no.Article no. when ordered separately
Pricesee price list
Std. pack
Notes
Us
V
Shunt releasesWith early-make auxiliary contactNot in combination with remote operator.
With clamp terminal on the left-hand switch side.
LZM1(-4)LN1(-4)
12 V AC/DC NZM1-XAHIV12AC/DC259772
1 off When the shunt release is energized, accidental contact with the main contacts of the switch during attempts to switch on is safely prevented.Early-make of the auxiliary contact with on and off switching (manual operation): approx. 20 ms.Shunt release cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XU... undervoltage release.
24 V AC/DC NZM1-XAHIV24AC/DC259774
110 V – 130 V AC/DC NZM1-XAHIV110-130AC/DC259780
208 V – 250 V AC/DC NZM1-XAHIV208-250AC/DC259782
380 V – 440 V AC/DC NZM1-XAHIV380-440AC/DC259784
With 3 m connection cable instead of screw termination.
LZM1(-4)LN1(-4)
12 V AC/DC NZM1-XAHIVL12AC/DC259790
1 off
24 V AC/DC NZM1-XAHIVL24AC/DC259792
110 V – 130 V AC/DC NZM1-XAHIVL110-130AC/DC259798
208 V – 250 V AC/DC NZM1-XAHIVL208-250AC/DC259800
380 V – 440 V AC/DC NZM1-XAHIVL380-440AC/DC259802
With early-make auxiliary contactLZM2(-4)LZM3(-4)LN2(-4)LN3(-4)
12 V AC/DC NZM2/3-XAHIV12AC/DC259808
1 off When the shunt release is energized, accidental contact with the main contacts of the switch during attempts to switch on is safely prevented.Early-make of the auxiliary contact with on and off switching (manual operation): approx. 20 ms.Cannot be used in conjunction with NZM...-XR... remote operator.Shunt release cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XU... undervoltage release.
24 V AC/DC NZM2/3-XAHIV24AC/DC259810
110 V – 130 V AC/DC NZM2/3-XAHIV110-130AC/DC259816
208 V – 250 V AC/DC NZM2/3-XAHIV208-250AC/DC259818
380 V – 440 V AC/DC NZM2/3-XAHIV380-440AC/DC259820
LZM4(-4)LN4(-4)
12 V AC/DC NZM4-XAHIV12AC/DC266470
1 off
24 V AC/DC NZM4-XAHIV24AC/DC266471
110 V – 130 V AC/DC NZM4-XAHIV110-130AC/DC266474
208 V – 250 V AC/DC NZM4-XAHIV208-250AC/DC266475
380 V – 440 V AC/DC NZM4-XAHIV380-440AC/DC266476
C1
C2
3.13
3.14
C1
C2
3.13
3.14
C1
C2
3.13
3.14
C1
C2
3.13
3.14
LZM1, LZM2/3, LZM4
53
http://catalog.moeller.net Moeller SK1230-1177GB
OrderingShunt releases with screw terminal
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
For use with
Rated control voltage
Part no.Article no. when ordered separately
Pricesee price list
Std. pack
Us
V
Shunt releasesFor mesh-network circuit-breakersFor intermittent operationMaximum on time = 1 sOperating range 10 – 110 % Us
With early-make auxiliary contact
LZM3(-4)LN3(-4)
230 V AC NZM3-XAHIV-230AC-MNS274141
1 off
230 V AC NZM4-XAHIV-230AC-MNS274143
1 off
Notes Cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XU... undervoltage release.Cannot be used in conjunction with NZM...-XR... remote operator.
Intermittent operation guaranteed by series connection of a N/O contact M22-(C)K10 (standard auxiliary contact).The maximum operating time of the shunt release for mesh network circuit-breaker is 1 s.LZM3: Early-make of the auxiliary contact with on and off switching (manual operation): approx. 20 ms.LZM4: Early-make of the auxiliary contact with switch on (manual operation): approx. 90 ms.
C1
C2
3.13
3.14
C1
C2
3.13
3.14
NZM...-XAHIV-...
54
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Ordering OrderingDoor coupling rotary handles
Extremely narrow fittingsPart no.Article no.
Pricesee price list
Std. pack Notes
ckted in the locked OFF ositionsodified such that it feated from the sing a screwdriver, in the unlocked ON
be opened in OFFD(V)-60
um shaft length
haft supporte combined with DZ additional handle
arning plate/on label can be n
NZM1-XTVD-0279392
1 off Door interlock• Not defeated in the locked OFF
and ON positions• Can be modified such that it can
be defeated from the outside using a screwdriver, when it is in the unlocked ON position.
• Door can be opened in OFFNZM...-XTVD(V)-0• For extremely narrow fittings• With special short extension
shaft• Cannot be combined with
NZM...-XDZ additional handle• External warning plate/
designation label can be clipped on
NZM2-XTVD-0279393
NZM3-XTVD-0279394
NZM4-XTVD-0279395
NZM1-XTVDV-0279396
NZM2-XTVDV-0279397
NZM3-XTVDV-0279398
NZM4-XTVDV-0279399
cktable in the locked ion.odified such that it feated from the sing a screwdriver, in the unlocked ON
be opened in OFFDVR-60
um shaft length
haft supporte combined with DZ additional handle
arning plate/on label can be n
NZM1-XTVDVR-0279400
1 off Door interlock• Not defeatable in the locked OFF
position.• Can be modified such that it can
be defeated from the outside using a screwdriver, when it is in the unlocked ON position.
• Door can be opened in OFFNZM...-XTVDVR-0• For extremely narrow fittings• With special short extension
shaft• Cannot be combined with
NZM...-XDZ additional handle• External warning plate/
designation label can be clipped on
NZM2-XTVDVR-0279401
NZM3-XTVDVR-0279402
NZM4-XTVDVR-0279403
55
LZM1, LZM2, LZM3, LZM4
Circ
uit-
brea
kers
, sw
itch
-dis
Doo
ComAn aDegStan
Red
Exte
Not
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Door coupling rotary handles
For a max. shaft length of 60 mmFor use with Part no.
Article no.Pricesee price list
Std. pack Notes Part no.Article no.
Pricesee price list
Std. pack Notes
r coupling rotary handle
plete including rotary drive and coupling partsdditional extension shaft is necessary with the NZM...-XT(V)D(V)(R)(-60) types.
ree of protection IP66dard, black/grey
Lockable on the 0 position on the handle using up to 3 padlocks. With door interlock
LZM1(-4), LN1(-4) NZM1-XTVD260166
1 off Door interlock• Not defeated in the locked
OFF and ON positions• Can be modified such that it
can be defeated from the outside using a screwdriver, when it is in the unlocked ON position.
• Door can be opened in OFFNZM...-XTVD(V)• External warning plate/
designation label can be clipped on
NZM1-XTVD-60271504
1 off Door interlo• Not defea
and ON p• Can be m
can be deoutside uwhen it isposition.
• Door canNZM...-XTV• For maxim
60 mm• Without s• Cannot b
NZM...-X• External w
designaticlipped o
LZM2(-4), LN2(-4) NZM2-XTVD260168
NZM2-XTVD-60271505
LZM3(-4), LN3(-4) NZM3-XTVD260170
NZM3-XTVD-60271506
LZM4(-4), LN4(-4) NZM4-XTVD266614
NZM4-XTVD-60271507
Lockable on the handle on the switch using up to 3 padlocks. Can be locked in 0 position on the handle, with adequate modification also in I position. With door interlock. Lockable in the 0 position
LZM1(-4), LN1(-4) NZM1-XTVDV260172
NZM1-XTVDV-60271508
LZM2(-4), LN2(-4) NZM2-XTVDV260174
NZM2-XTVDV-60271509
LZM3(-4), LN3(-4) NZM3-XTVDV260176
NZM3-XTVDV-60271510
LZM4(-4), LN4(-4) NZM4-XTVDV266616
NZM4-XTVDV-60271511
-yellow for Emergency-StopLockable on the handle on the switch using up to 3 padlocks. Lockable in 0 position on handle. With door interlock. Lockable in the 0 position
LZM1(-4), LN1(-4) NZM1-XTVDVR260178
1 off Door interlock• Not defeatable in the
locked OFF position.• Can be modified such that it
can be defeated from the outside using a screwdriver, when it is in the unlocked ON position.
• Door can be opened in OFFNZM...-XTVDVR• External warning plate/
designation label can be clipped on
NZM1-XTVDVR-60271512
1 off Door interlo• Not defea
OFF posit• Can be m
can be deoutside uwhen it isposition.
• Door canNZM...-XTV• For maxim
60 mm• Without s• Cannot b
NZM...-X• External w
designaticlipped o
LZM2(-4), LN2(-4) NZM2-XTVDVR260180
NZM2-XTVDVR-60271513
LZM3(-4), LN3(-4) NZM3-XTVDVR260182
NZM3-XTVDVR-60271514
LZM4(-4), LN4(-4) NZM4-XTVDVR266618
NZM4-XTVDVR-60271515
nsion shaftMax. mounting depth: 400 mm
LZM1(-4), LN1(-4)LZM2(-4), LN2(-4)
NZM1/2-XV4261232
1 off Can be cut to required length
LZM3(-4), LN3(-4)LZM4(-4), LN4(-4)
NZM3/4-XV4261234
Max. mounting depth: 600 mm
LZM1(-4), LN1(-4)LZM2(-4), LN2(-4)
NZM1/2-XV6260191
LZM3(-4), LN3(-4)LZM4(-4), LN4(-4)
NZM3/4-XV6260193
es Circuit-breaker can also be installed in a lying position 90 ° left/right, with the handle still in the same position.
LZM1, LZM2, LZM3, LZM4
56Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
OrderingRotary handles
For use with Part no.Article no. when ordered separately
Pricesee price list
Std. pack
Notes
Rotary handle on circuit-breaker
Complete with rotary driveStandard, black/grey
Lockable on the 0 position on the switch using up to 3 padlocks.
LZM1(-4), LN1(-4) NZM1-XDV260125
1 off NZM1(2)(3)-X…: Can also be combined with insulating surround.MODAN handle position detection by wire release can be retrofitted.LZM2(-4), LN2(-4) NZM2-XDV
260127
LZM3(-4), LN3(-4) NZM3-XDV260129
LZM4(-4), LN4(-4) NZM4-XDV266608
Lockable on the 0 position on the handle using up to 3 padlocks.
LZM1(-4), LN1(-4) NZM1-XDVG285247
1 off Can also be combined with insulating surround.
LZM2(-4), LN2(-4) NZM2-XDVG285248
Red-yellow for Emergency-StopLockable on the 0 position on the switch using up to 3 padlocks.
LZM1(-4), LN1(-4) NZM1-XDVR260135
1 off NZM1(2)(3)-X…: Can also be combined with insulating surround.MODAN handle position detection by wire release can be retrofitted.LZM2(-4), LN2(-4) NZM2-XDVR
260137
LZM3(-4), LN3(-4) NZM3-XDVR260140
LZM4(-4), LN4(-4) NZM4-XDVR266610
Lockable on the 0 position on the handle using up to 3 padlocks.
LZM1(-4), LN1(-4) NZM1-XDVGR285249
Can also be combined with insulating surround.
LZM2(-4), LN2(-4) NZM2-XDVGR285280
Notes Circuit-breaker can also be installed in a lying position 90 ° left/right, with the handle still in the same position.
NZM…-XDV…
57
http://catalog.moeller.net Moeller SK1230-1177GB
OrderingRotary handles with door interlock
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
For use with Part no.Article no. when ordered separately
Pricesee price list
Std. pack
Notes
Rotary handle on switch with door interlock
Complete with rotary drive and insulating surroundStandard, black/grey
Lockable on the 0 position on the handle using up to 3 padlocks, can also be modified for the I position. Also available with door interlock e.g. for MCC service distribution.
LZM1(-4), LN1(-4) NZM1-XDTV260131
1 off Door interlock• In the ON position, can be defeated from
the outside using a 1 mm pin• Not defeated in the locked OFF and ON
positions• Door can be opened in OFF• Can only be switched ON when the door
is closed
LZM2(-4), LN2(-4) NZM2-XDTV260133
Red-yellow for Emergency-Stop
Lockable on the 0 position on the handle using up to 3 padlocks. Also available with door interlock e.g. for MCC service distribution
LZM1(-4), LN1(-4) NZM1-XDTVR260142
1 off
LZM2(-4), LN2(-4) NZM2-XDTVR260144
Rotary handle
Divergent to normal IEC handles: Door opening only possible with active rotation beyond the 0 position.Complete with rotary drive and insulating surround
Standard, black/greyLockable on the 0 position on the handle using up to 3 padlocks. Also available with door interlock e.g. for MCC service distribution.
LZM1(-4), LN1(-4) NZM1-XDTV-NA271453
1 off Door interlock• In the ON position, can be defeated from
the outside using a 1 mm pin• Not defeated in the locked OFF and ON
positions• Door opening only possible with active
rotation beyond the 0 position.• Can only be switched ON when the door
is closed• Cannot be combined with mechanical
interlock
LZM2(-4), LN2(-4) NZM2-XDTV-NA271454
Red-yellow for Emergency-StopLockable on the 0 position on the handle using up to 3 padlocks. Also available with door interlock e.g. for MCC service distribution.
LZM1(-4), LN1(-4) NZM1-XDTVR-NA271455
LZM2(-4), LN2(-4) NZM2-XDTVR-NA271456
Notes Circuit-breaker can also be installed in a lying position 90 ° left/right, with the handle still in the same position.
NZM...-XDTV...
58Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
OrderingMain switch assembly kit
Type For use with Part no.Article no. when ordered separately
Pricesee price list
Std. pack
Main switch assembly kit
Equipment supplied:• Rotary door-coupling handle• NZM...-XV4 extension shaft• External warning plate/designation label in German/English• Black and yellow flashFor enhanced protection against direct contact on the incomer side, IP2X protection against contact with a finger can be ordered a 23Other external warning plates/designation labels can be clipped on.
With black door coupling rotary handleLockable on the 0 position on the handle using up to 3 padlocks, can also be modified for the I position. With door interlock.
LZM1(-4), LN1(-4) NZM1-XHB266626
1 off
LZM2(-4), LN2(-4) NZM2-XHB266627
LZM3(-4), LN3(-4) NZM3-XHB266628
LZM4(-4), LN4(-4) NZM4-XHB271779
With red door coupling rotary handle for using switch as Emergency-Stop device according to IEC/EN 602041Lockable on the 0 position on the handle using up to 3 padlocks. Lockable door as additional feature, locking facility on circuit-breaker in 0 position.
LZM1(-4), LN1(-4) NZM1-XHBR266632
LZM2(-4), LN2(-4) NZM2-XHBR266633
LZM3(-4), LN3(-4) NZM3-XHBR266634
LZM4(-4), LN4(-4) NZM4-XHBR271842
Main switch assembly kit for side panel mounting
Actuation of the switch on the control panel side wallSwitch mounting on mounting plateEquipment supplied:• Door coupling rotary handle• NZM...-XV4 extension shaft• External warning plate/designation label in German/English• Black and yellow flashFor enhanced protection against direct contact on the incomer side, IP2X protection against contact with a finger can be ordered a 23Other external warning plates/designation labels can be clipped on.
Standard, black/greyLockable on the 0 position on the handle using up to 3 padlocks, can also be modified for the I position.
For operation on the left
LZM1(-4), LN1(-4) NZM1-XS-L266641
1 off
LZM2(-4), LN2(-4) NZM2-XS-L266642
LZM3(-4), LN3(-4) NZM3-XS-L266643
LZM4(-4), LN4(-4) NZM4-XS-L289806
For operation on the right
LZM1(-4), LN1(-4) NZM1-XS-R266644
LZM2(-4), LN2(-4) NZM2-XS-R266645
LZM3(-4), LN3(-4) NZM3-XS-R266646
LZM4(-4), LN4(-4) NZM4-XS-R289807
Red-yellow for Emergency-StopLockable on the 0 position on the handle using up to 3 padlocks.
For operation on the left
LZM1(-4), LN1(-4) NZM1-XSR-L266653
LZM2(-4), LN2(-4) NZM2-XSR-L266654
LZM3(-4), LN3(-4) NZM3-XSR-L266655
LZM4(-4), LN4(-4) NZM4-XSR-L289808
For operation on the right
LZM1(-4), LN1(-4) NZM1-XSR-R266656
LZM2(-4), LN2(-4) NZM2-XSR-R266657
LZM3(-4), LN3(-4) NZM3-XSR-R266658
LZM4(-4), LN4(-4) NZM4-XSR-R289809
NZM...-XHB..., NZM...-XS...
59
http://catalog.moeller.net Moeller SK1230-1177GB
OrderingMain switch assembly kit
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Type For use with Part no.Article no. when ordered separately
Pricesee price list
Std. pack
Main switch assembly kit for side panel mounting with mounting bracket
For direct mounting of circuit-breaker and handle in the side wall of the control cabinetEquipment supplied:• Door coupling rotary handle• Mounting bracket• Special short extension shaft• External warning plate/designation label in German/English• Black and yellow flashFor enhanced protection against direct contact on the incomer side, IP2X protection against contact with a finger can be ordered a 23Other external warning plates/designation labels can also be clipped on.Standard, black/grey
Can be locked in 0 position, with adequate modification also in I position. Narrowest minimum clearance between enclosure side plates of control panel and circuit-breaker is defined by mounting bracket. Extensions cannot be used.
For operation on the left
LZM1(-4), LN1(-4) NZM1-XSM-L266663
1 off
For operation on the left
LZM2(-4), LN2(-4) NZM2-XSM-L266664
For operation on the right
LZM1(-4), LN1(-4) NZM1-XSM-R266665
For operation on the right
LZM2(-4), LN2(-4) NZM2-XSM-R266666
Red-yellow for Emergency-StopLockable in 0 position on handle. Narrowest minimum clearance between enclosure side plates of control panel and circuit-breaker is defined by mounting bracket. Extensions cannot be used.
For operation on the left
LZM1(-4), LN1(-4) NZM1-XSRM-L266671
1 off
For operation on the left
LZM2(-4), LN2(-4) NZM2-XSRM-L266672
For operation on the right
LZM1(-4), LN1(-4) NZM1-XSRM-R266673
For operation on the right
LZM2(-4), LN2(-4) NZM2-XSRM-R266674
Add-on plate
For fitting to the mounting bracket when using N conductor or PE conductor terminals K25, K50, K95 or K150.LZM1(-4), LN1(-4)LZM2(-4), LN2(-4)
NZM1/2-XZB266676
1 off
Additional terminal arrangement for side wall operator with mounting bracketNZM1-XS(R)M-…, NZM2-XS(R)M-…Additional terminals K25, K50, K95, K150 a 66
Actuation:
Example: In mounting area MI, variation option 1 allows the K25 additional terminal to be mounted twice.
3 pole 4 poleFor operation on the right For operation on the left For operation on the right For operation on the left
MIMIIMI MII
MI MII
Mounting areas MI MIIVariation options V1 V2 V3 V4 V1 V2Maximum number of additional terminals
K25 2 x – – – – –K50 – 2 x – – – –K95 – – 1 x – 1 x –K150 – – – 1 x – 1 x
NZM...XS(R)M...
60Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
OrderingAccessories
For use with Part no.Article no. when ordered separately
Pricesee price list
Std. pack Notes
Rear driveFor direct rear connection of the switch to the side of the control panel or control panel door. Switch actuation on rear through side plate or control panel door.For switch with toggle lever.For enhanced protection against direct contact on the incomer side, IP2X protection against contact with a finger can be ordered a 21Degree of protection IP66, UL/CSA Type 4X
Standard, black/greyLockable on the 0 position on the handle using up to 3 padlocks.
LZM1, LN1 NZM1-XRAV107245
1 off External warning plate can be clipped on
LZM2, LN2 NZM2-XRAV107247
Red-yellow for Emergency-StopLockable on the 0 position on the handle using up to 3 padlocks.
LZM1, LN1 NZM1-XRAVR107249
1 off
LZM2, LN2 NZM2-XRAVR107261
External warning plate/designtion label
German/English LZM1(-4), LN1(-4)LZM2(-4), LN2(-4)LZM3(-4), LN3(-4)LZM4(-4), LN4(-4)
ZFS61/62-NZM7272525
1 off A bilingual external warning plate/designation label in German/English is already included in the main switch assembly kit.
German ZFS61-NZM7051089
English ZFS62-NZM7065957
French ZFS63-NZM7065958
Blank (for engraving or printing) ZFS60-NZM7065896
Further languages ZFS*-NZM7999978
Lightning symbol
Including terminal marking for main switchSmall LZM1(-4), LN1(-4)
LZM2(-4), LN2(-4)BPF-NZM7217294
10 off Included as standard in main switch assembly kit
Large LZM3(-4), LN3(-4)LZM4(-4), LN4(-4)
BPF-NZM10231363
10 off
External warning plates are available in the following languages:64 Bulgarian65 Danish66 Finnish67 Dutch68 Italian69 Greek70 Norwegian71 Polish72 Portuguese
73 Romanian74 Russian75 Swedish76 Serbo-Croatian77 Spanish78 Czech79 Turkish80 Hungarian81 Afrikaans
To obtain the order number, insert the lan-guage code number into the type reference required.Ordering exampleExternal warning plate in Finnish:ZFS66-NZM7
UVW
L1L2L3
T1T2T3
XYZ
N
PE
PEN
UVW
L1L2L3
T1T2T3
XYZ
N
PE
PEN
NZM...-XRAV..., ZFS..., BPF-...
61
http://catalog.moeller.net Moeller SK1230-1177GB
OrderingAccessories
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
For use with Part no.Article no. when ordered separately
Pricesee price list
Std. pack Notes
Add-on handle
Enables switching when the control panel door is openLZM1(-4), LN1(-4)LZM2(-4), LN2(-4)
NZM1/2-XDZ266621
1 off Push-fits on to the extension shaft100 mm free extension shaft required.Cannot be combined with NZM...-XT...-60 door coupling rotary handles as well as NZM...-XT...-0.
LZM3(-4), LN3(-4)LZM4(-4), LN4(-4)
NZM3/4-XDZ266622
1 off
Insulating surrounds
For toggle lever, rotary handle with rotary drive and remote operator.Degree of protection IP40
LZM1(-4), LN1(-4) NZM1-XBR260195
1 off For oblong cut-out on doors and enclosures with material thicknesses of 1.5 – 5 mm.External warning plate/designation label can be clipped onNZM4-XBR cannot be combined with rotary handle with rotary drive.
LZM2(-4), LN2(-4) NZM2-XBR260197
LZM3(-4), LN3(-4) NZM3-XBR284645
LZM4(-4), LN4(-4) NZM4-XBR284646
Toggle lever locking device
Off position lockable using up to 3 padlocks (hasp thickness 4 – 8 mm)LZM1(-4), LN1(-4) NZM1-XKAV
2601991 off Cannot be combined with insulating
surround.LZM2(-4), LN2(-4)LZM3(-4), LN3(-4)
NZM2/3-XKAV260201
1 off
Spacers
Enables fast and low-priced adjustment of differing frame sizes with/without rotary handle to the same front depth
LZM1(-4), LN1(-4)LZM2(-4), LN2(-4)
NZM1/2-XAB260203
1 set Grid depth 17.5 mm, M4 threadType contains 4 off spacerMaximum component capacity:LZM1: 4 units per fixing screw,LZM2: 2 units per fixing screw2 (LZM1) or 4 (LZM2) fixing screws contained per circuit-breaker
LZM3(-4), LN3(-4)LZM4(-4), LN4(-4)
NZM3-XAB260211
1 set Grid depth 17.5 mm, M5 threadOne set contains 4 spacersLZM3, LZM4: 1 off per fixing screw4 fixing screws per switch included
Clip plate
Enables snap-fit of the circuit-breaker to a DIN railLZM1(-4), LN1(-4) NZM1-XC35
2602131 off For top-hat rail 35 mm
LZM2, LN2 NZM2-XC75260215
1 off For top-hat rail 75 mmNot suitable for circuit-breakers with remote operator.
NZM...-XDZ, NZM...-XBR, NZM...-X...
62Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
OrderingMechanical interlock
For use with Part no.Article no. when ordered separately
Pricesee price list
Std. pack Notes
Mechanical interlocking of (door coupling) rotary handles
LZM1(-4), LN1(-4) NZM1-XMV281581
1 off Rotary handles on switches or door coupling rotary handles are additionally required.Cannot be combined with paralleling mechanisms, side wall operators and remote operator as well as NZM4-XBR insulating surrounds.In order to establish a mechanical interlock at least 2 interlock modules are required.Possible combinations and interlock variants a engineeringOrder Bowden cable separately
LZM2(-4), LN2(-4) NZM2-XMV281582
LZM3(-4), LN3(-4) NZM3-XMV281583
LZM4(-4), LN4(-4) NZM4-XMV281584
Bowden cablesFor mechanical interlocking of (door coupling) rotary handles
LZM1(-4), LN1(-4)LZM2(-4), LN2(-4)LZM3(-4), LN3(-4)LZM4(-4), LN4(-4)
NZM-XBZ225281585
1 off
NZM-XBZ600281586NZM-XBZ1000281587
Mechanical interlock for remote operatorFor 2 switches of the same or next frame size with each other. Mounting beside one another.
LZM2(-4), LN2(-4)+LZM2(-4), LN2(-4)
NZM2-XMVR104543
1 off Type contains parts for both switches.Remote operator also required.Maximum switching distance a engineeringCannot be combined with rotary handles, door coupling rotary handles and early-make auxiliary contacts.
LZM2(-4), LN2(-4)+LZM3(-4), LN3(-4)
NZM2/3-XMVR104544
LZM3(-4), LN3(-4)+LZM3(-4), LN3(-4)
NZM3-XMVR104545
LZM3(-4), LN3(-4)+LZM4(-4), LN4(-4)
NZM3/4-XMVR104546
LZM4(-4), LN4(-4)+LZM4(-4), LN4(-4)
NZM4-XMVR104547
For 2 switches of the same or different type with opposed operation. Extra long Bowden cable for mounting one above the other or in adjacent enclosures.
LZM2(-4), LN2(-4)+LZM2(-4), LN2(-4)
NZM2-XMVRL104548
1 off Type contains parts for both switches.Remote operator also required.Maximum switching distance a engineeringCannot be combined with rotary handles, door coupling rotary handles and early-make auxiliary contacts.
LZM2(-4), LN2(-4)+LZM3(-4), LN3(-4)
NZM2/3-XMVRL104549
LZM3(-4), LN3(-4)+LZM3(-4), LN3(-4)
NZM3-XMVRL104550
LZM3(-4), LN3(-4)+LZM4(-4), LN4(-4)
NZM3/4-XMVRL104551
LZM4(-4), LN4(-4)+LZM4(-4), LN4(-4)
NZM4-XMVRL104552
NZM...XMV(R)(L), NZM-XBZ...
63
http://catalog.moeller.net Moeller SK1230-1177GB
OrderingMulti-function device adapter
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
For use with Rated current Part no.Article no. when ordered separately
Pricesee price list
Std. pack Notes
Ie
A
Component adapter for circuit-breakers and switch-disconnectors for 60 mm busbar system
For installation on flat copper busbars 12 … 30 x 5 … 10, double T and triple T profileRated operational voltage Ue: 690 V• Halogen free• Temperature resistant to 120 °C• Self-extinguishing to UL 94• Approved for feeder branch circuits to UL508A up to 600 V• 3 pole
LZM1, LN1 160 NZM1-XAD160104554
1 off For breakers with box terminal as standard connectionConnection to system at top using the supplied connection cableIn conjunction with IP2X protection against contact with a fingerEnhancement of the protection against direct contact on the switch outgoer side possible
LZM2, LN2 250 NZM2-XAD250104555
Connection to the system possible at top or bottom via connection on rear (+)NZM2-XKR4… Mounting using clamp and screw fixing.
LZM3, LN3 550 NZM3-XAD550104556
Connection to the system possible at top via connection on rear (+)NZM3-XK13… Mounting using clamp and screw fixing.
For use with Rated current Part no. suffixArticle no. when ordered with basic unit
Pricesee price list
Part no.Article no. when ordered separately
Pricesee price list
Std. pack
Ie
A
Connection on rear for component adapters
For component adapters for LZM2, LZM3
LZM2, LN2 250 +NZM2-XKR4O281664
NZM2-XKR4281666
1 off
LZM2, LN2 250 +NZM2-XKR4U281665
NZM3-XKR13281668
LZM3, LN3 550 +NZM3-XKR13O281667
Notes Part no. and part no. suffix include parts for one switch side at top or bottom (with LZM3 top only). Required with component adapter and switch with connection on rear, see for example component adapter 104555 and 104556.O = for fitting at the topU = for fitting at the bottom
NZM...-XAD..., NZM...-XKR...
64
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Ordering OrderingAccessories
) are still possible.
ection is supplied.rators on 4 pole switches, an additional 4 pole NZM2-XAVPR or NZM3-XAVPR shroud is necessary.
ng engineering:s though the contact during make and break!act elements can be used for the NZM2(3,4)-XR… remote operators.
diness signal when the cover is closed, and not locked. A.2 A
n after the switch has tripped
ithin the first 3 seconds after switch off.
65
LZM2, LZM3, LZM4
Circ
uit-
brea
kers
, sw
itch
-dis
Rem
For ON CanLocaLock
ShroAdd
ClamCon
ProtTran
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Accessories
For use with Rated control voltage Part no.Article no. when ordered separately
Pricesee price list
Std. packNotes
Us
V
ote operator
remote switching of circuit-breakers and switch-disconnectors.and OFF switching and resetting by means of 2-wire or 3-wire control. be synchronized.l switching by hand possibleable in the 0 position of the remote operator with up to 3 padlocks (hasp thickness: 4 – 8 mm)
LZM2(-4), LN2(-4) 110 – 130 V 50/60 Hz NZM2-XR110-130AC259830
1 off
208 – 240 V 50/60 Hz NZM2-XR208-240AC259832
380 – 440 V 50/60 Hz NZM2-XR380-440AC1)
259834
24 – 30 V DC NZM2-XR24-30DC259836
110 – 130 V DC NZM2-XR110-130DC259840
220 – 250 V DC NZM2-XR220-250DC259842
LZM3(-4), LN3(-4) 110 – 130 V 50/60 Hz NZM3-XR110-130AC259848
208 – 240 V 50/60 Hz NZM3-XR208-240AC259850
380 – 440 V 50/60 Hz NZM3-XR380-440AC1)
259852
24 – 30 V DC NZM3-XR24-30DC259854
110 – 130 V DC NZM3-XR110-130DC259858
220 – 250 V DC NZM3-XR220-250DC259860
LZM4(-4), LN4(-4) 110 – 130 V 50/60 Hz NZM4-XR110-130AC266684
208 – 240 V 50/60 Hz NZM4-XR208-240AC266685
380 – 440 V 50/60 Hz NZM4-XR380-440AC1)
266686
24 – 30 V DC NZM4-XR24-30DC266691
110 – 130 V DC NZM4-XR110-130DC266693
220 – 250 V DC NZM4-XR220-250DC266694
ud for 4th poleitional shroud for mounting the NZM2-XR... and NZM3-XR... on a 4-pole switch.
LZM2-4, LN2-4 NZM2-XAVPR266677
1 off
LZM3-4, LN3-4 NZM3-XAVPR266678
1 off
p terminal springloaded clamptrol circuit terminal springloaded terminals
NZM...-XR... NZM-XRC266696
1 off
ective cover for door cutoutsparent protective shroud to increase the degree of protection to IP54
– RTR-NZM10034825
1 off Electrical remote switching and manual tripping (push to trip
A standard auxiliary contact (HIN) for the switch position detWhen installing the NZM2-XR… and NZM3-XR… remote ope3-wire control
Terminal 70/71:Please note duriFull current flowRMQ series cont
2-wire controlTerminal 75:Operational reaAC-15: 400 V; 2DC-13: 220 V; 0
Three-wire control with automatic reset to the 0 positio
Switching cycle:NZM2-XR
NZM3-XR
NZM4-XR
The time interval between OFF and ON is 3 seconds.On commands received during the time interval are ignored w
71 7270
7475
N(L1–, L2)
L1(L1+)
H10 I
71 7270
7475
N(L1–, L2)
L1(L1+)
H1S
0 I
71 7270
7475
N(L1–, L2)
L1(L1+)
H1HIA0 I
r r r60 ms t > 3 s
r 60 ms
OFF ON OFF ONON OFF
r r r80 ms t > 3 s
r 80 ms
OFF ON OFF ONON OFF
r r r100 ms t > 3 s
r 100 ms
OFF ON OFF ONON OFF
LZM2, LZM3, LZM4
66
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Ordering OrderingInsulated enclosures
hes: for 4th and 5th (if or), with 4-pole ductor)
Notes
Suitable for installation of circuit-breakers and switch-disconnectorsEnclosure for separate mounting with top and bottom cable entry.Include fixing straps for wall mounting.Short-circuit resistance at 415 V 50/60 Hz to 10 kA.
Cannot be used in combination with NZM…-XR… remote operator…,NZM…-XSV plug-in unit or NZM…-XAV withdrawable unit.Insulated additional terminal for 4th or 5th pole should be ordered separately.
CI23 enclosure with flangesCI43, CI45 and CI48 feature gland plates.
Only for switches with tunnel clamps for direct connection of cables.
150/1/BR, K240/1/BR
150/1/BR, K240/1/BR
K2X240/1/BR
150/1/BR, K240/1/BR
150/1/BR, K240/1/BR
K2X240/1/BR
67
NZM...-XCI...
Circ
uit-
brea
kers
, sw
itch
-dis
InsuWithComDegnot Stan
Red
Add
For 1-po
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Insulated enclosures
Max. rated uninterrupted current
For use with Part no.Article no. when ordered separately
Pricesee price list
Std. pack Insulated enclosure description
Retrofit terminals with 3-pole switcrequired) conductor (N, PE-conductswitches: for 5th conductor (PE con
Iu
A
lated enclosures door coupling rotary handleplete incl. all necessary functional parts
ree of protection IP65UL/CSA approveddard, black/grey
Lockable on the 0 position on the handle using up to 3 padlocks. Additionally with cover interlock.
F 63 A NZM1, LN1 NZM1-XCI23-TVD271522
1 off CI23-150 K10/1, K25/1
F 125 A NZM1(-4), LN1(-4) NZM1-XCI43-TVD271523
CI43-150 K10/1, K25/1, K50/1, K95/1N/BR
F 160 A NZM1(-4), LN1(-4) NZM1-XCI43/2-TVD104645
CI43-200 K10/1, K25/1, K50/1, K95/1N/BR
F 200 A NZM2(-4), LN2(-4) NZM2-XCI43-TVD271524
CI43-200 K10/1, K25/1, K50/1, K95/1N/BR, K
F 250 A NZM2(-4), LN2(-4) NZM2-XCI45-TVD280418
CI45-200 K10/1, K25/1, K50/1, K95/1N/BR, K
F 400 A NZM3(-4), LN3(-4) NZM3-XCI48-TVD271525
CI48-250 K95/1N/BR, K150/1/BR, K240/1/BR,
-yellow for Emergency-StopLockable on the handle and on the switch using up to 3 padlocks each. Lockable in 0 position on handle. Cover interlock as additional feature, locking facility on circuit-breaker in 0 position.
F 63 A NZM1, LN1 NZM1-XCI23-TVDVR271527
1 off CI23-150 K10/1, K25/1
F 125 A NZM1(-4), LN1(-4) NZM1-XCI43-TVDVR271528
CI43-150 K10/1, K25/1, K50/1, K95/1N/BR
F 160 A NZM1(-4), LN1(-4) NZM1-XCI43/2-TVDVR104646
CI43-200 K10/1, K25/1, K50/1, K95/1N/BR
F 200 A NZM2(-4), LN2(-4) NZM2-XCI43-TVDVR271529
CI43-200 K10/1, K25/1, K50/1, K95/1N/BR, K
F 250 A NZM2(-4), LN2(-4) NZM2-XCI45-TVDVR279356
CI45-200 K10/1, K25/1, K50/1, K95/1N/BR, K
F 400 A NZM3(-4), LN3(-4) NZM3-XCI48-TVDVR271530
CI48-250 K95/1N/BR, K150/1/BR, K240/1/BR,
Rated uninterrupted current
Terminal capacities Part no.Article no. when ordered separately
Pricesee price list
Std. pack
Iu
A mm2
itional insulated terminals
looping through the neutral and protective conductorle
32 Flexible, 1 x (1.5 – 6) K10/1093827
10 off
63 Flexible, 1 x (6 – 16), stranded, 1 x (16 – 25 ) K25/1096200
100 Flexible, 1 x (10 – 35), stranded, 1 x (16 – 50) K50/1098573
160 Stranded, 1 x (16 – 95) K95/1N/BR012336
1 off
250 Stranded, 1 x (35 – 150), 2 x (16 – 70) K150/1/BR014709
400 Stranded, 1 x (50 – 240), 2 x (25 – 120) K240/1/BR017082
630 Stranded, 1 x (240 – 300), 2 x (50 – 240) K2X240/1/BR019455
NZM...-XCI...
68Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
OrderingResidual-current release frequency response
For use with Part no.Order number for separate orders
Pricesee price list
Std. pack
Notes
Earth-fault release
Suitable for use in three- and single-phase systemsPulse current sensitive according to core-balance principle
For 3- and 4 pole LZM1(-4) circuit-breakers and LN1(-4) switch-disconnectors,dependant on mains power Ue = 200 … 415 V 50/60 Hz,
Rated fault current IDn = 0.03 A
NZM1LN1
3 pole NZM1-XFI30R104603
1 off IEC/EN 60947-2With Idn = 0.03 A: delay time tv always fixed settings at 10 ms.Alarm message > 30 % Idn via yellow LED.Trip indication max. 2 auxiliary contacts (HIAFI) can be fitted by user: N/O = M22-K01, N/C = M22-K10 are reset via the reset toggle lever.If the trip-indicating auxiliary contact in the fault current block is used, the N/C contacts operates as a N/O contact and the N/C contact operates as an N/O contact (see HIAFI marking).Not in combination with insulated enclosure or main switch assembly kit for side panel mounting with mounting bracketNZM1-XFI…U not in combination with shunt or undervoltage relase.Rated ultimate short-circuit breaking capacity is determined by the fitted LZM1, LN1.If a switch-disconnector is applied by the backup fuse to be used a Technical Data
NZM1-4LN1-4
4 pole NZM1-4-XFI30R104606
Rated fault current IDn = 0.3 A
NZM1LN1
3 pole NZM1-XFI300R104604
NZM1-4LN1-4
4 pole NZM1-4-XFI300R104607
Rated fault current IDn = 0.03 – 0.1 – 0.3 – 0.5 – 1 – 3 A, delay time tv = 10 – 60 – 150 – 300 – 450 ms.
NZM1LN1
3 pole NZM1-XFIR104605
NZM1-4LN1-4
4 pole NZM1-4-XFIR104608
Bottom mounting up to 100 ARated fault current IDn = 0.03 A
NZM1LN1
3 pole NZM1-XFI30U1)
104609NZM1-4LN1-4
4 pole NZM1-4-XFI30U104612
Rated fault current IDn = 0.3 A
NZM1LN1
3 pole NZM1-XFI300U104610
NZM1-4LN1-4
4 pole NZM1-4-XFI300U104613
Rated fault current IDn = 0.03 – 0.1 – 0.3 – 0.5 – 1 – 3 A, delay time tv = 10 – 60 – 150 – 300 – 450 ms.
NZM1LN1
3 pole NZM1-XFIU104611
NZM1-4LN1-4
4 pole NZM1-4-XFIU104614
Pulse current sensitive according to core-balance principle
For 4 pole circuit-breaker LZM2-4 and switch-disconnectors LN2-4independent of mains voltage Ue = 280 – 690 V 50/60 Hzbottom mounting up to 250 A
IEC/EN 60947-2Auxiliary contacts (1 N/O, 1N/C integrated) are reset via the reset button.Not in combination with plug-in units, insulated enclosure or main switch assembly kit for side panel mounting with mounting bracket.Rated ultimate short-circuit breaking capacity is determined by the fitted LZM2.If a switch-disconnector is applied by the backup fuse to be used a Technical Data
Rated fault current IDn = 0.03 A
NZM2-4LN2-4
4 pole NZM2-4-XFI30292343
1 off
Rated fault current IDn 0.1 - 0.3 - 1 - 3 A, delay time tv = 60 - 150 - 300 - 450 ms
NZM2-4LN2-4
4 pole NZM2-4-XFI292344
1 off
Core-balance principle with AC/DC current sensitivity (in range 0 – 100 kHz)
For 4 pole LZM2-4 circuit-breakers and switch-disconnectors LN2-4internal power supply Ue = 50 … 400 V, bottom mounting up to 250 A
IEC/EN 60947-2Observe response threshold dependence on frequency!See “Frequency response” characteristic curveAuxiliary contacts (1 N/O, 1N/C integrated) are reset via the reset button.Not in combination with plug-in units, insulated enclosure or main switch assembly kit for side panel mounting with mounting bracket.Rated ultimate short-circuit breaking capacity is determined by the fitted LZM2.If a switch-disconnector is applied by the backup fuse to be used a Technical Data
Rated fault current IDn = 0.03 A
NZM2-4LN2-4
4 pole NZM2-4-XFIA30292345
1 off
Rated fault current IDn 0.1 - 0.3 - 1 A, delay time tv = 60 - 150 - 300 - 450 ms
NZM2-4LN2-4
4 pole NZM2-4-XFIA292346
1 off
Notes 1) Suitable for use in three-phase systems
NZM...XFI...
69
http://catalog.moeller.net Moeller SK1230-1177GB
OrderingResidual-current release frequency response
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
For use with Part no.Article no. when ordered with basic unit
Pricesee price list
Std. pack Notes
Earth-fault release, 3-pole, 4-poleNot dependent on mains and control voltagesIg = 0.35 – 0.4 – 0.5 – 0.6 – 0.7 – 0.8 – 0.9 – 1.0 x Intg = 0 – 20 – 60 – 100 – 200 – 300 – 500 – 750 – 1000 ms
LZM3LN3
+NZM3-XT260756
1 off Only suitable for use in conjunction with circuit-breakers having electronic releases.LZM3-4
LN3-4+NZM3-4-XT260757
LZM4LN4
+NZM4-XT266721
LZM4-4LN4-4
+NZM4-4-XT266722
Description Part no.Article no.
Pricesee price list
Std. pack Notes
Residual current relay
Pulse-current sensitiveRated control supply voltage: Us = 230 V AC (50/60Hz)Integrated auxiliary contact (1 C/O)Ring-type transformer must also be ordered
Rated fault current IdN = 0.03 A PFR-003285555
1 off
Rated fault current IdN = 0.3 A PFR-03285556
Rated fault current IdN = 0.03 – 5 AAdjustable fault current and delay timeFault current early warning by flashing, red LED
PFR-5285557
Adjustable fault current: 0.03, 0.1, 0.3, 0.5, 1, 3, 5 AAdjustable delay time: 0.02, 0.1, 0.3, 0.5, 1, 3, 5 A
Ring-type transformer
Rated operational voltage: 690 V (50/60 Hz)Internal diameter: 20 mm PFR-W-20
2855581 off incl. fixing clip for DIN rail mounting
Internal diameter: 30 mm PFR-W-30285559
Internal diameter: 35 mm PFR-W-35285600
incl. screw fixingAlternative: fixing clip for DIN mounting railDesign note:The current transformer diameter must be selected 1.5 times larger than the envelope diameter of the passed through conductor.
Internal diameter: 70 mm PFR-W-70285601
Internal diameter: 105 mm PFR-W-105285602
Internal diameter: 140 mm PFR-W-140285603
Internal diameter: 210 mm PFR-W-210285604
Magnetic shieldingPFR-W-35 PFR-WMA-35
2860011 off Necessary for a load circuit with high
inrush currents > 4 x In, such as for example motors and
PFR-W-70 PFR-WMA-70286002
PFR-W-105 PFR-WMA-105286003
PFR-W-140 PFR-WMA-140286004
PFR-W-210 PFR-WMA-210286005
Fixing clipfor the DIN rail mounting of the PFR-W-35 current transformer and all larger
PFR-WC286006
1 off 1 set = 2 pieces
NZM3, NZM4, PFR-...
70
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Engineering Engineeringcoming circuit-breaker, outgoing circuit-breaker
LZM...4-VE...
501250 1600 800 1000 1250 1600
overload and short-circuit release set to max. value
T T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T T
T T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T T
T T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T T
T T T T T TT T 42 T T TT T 30 45 T TT T 30 45 T TT T 30 45 T TT T 25 40 T TT T 25 40 T T
71
LZM, FAZ-B(C), PKZ
Circ
uit-
brea
kers
, sw
itch
-dis
OutcircFAZ
PKZ
PKZ
PKZ
Not
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Selectivity: incoming circuit-breaker, outgoing circuit-breaker Selectivity: in
Incoming circuit-breaker
Selectivity 415 V AC between circuit-breakers enables separate shut-down of faulty system sections.
Selectivity (discrimination) exists between incoming breaker 1 and outgoing breaker 2 if, only outgoing breaker 2 trips at position 2 during a short-circuit. System sections 3 and 4 continue to operate.Incoming circuit-breaker (S1) Incoming circuit-breaker (S1) Incoming circuit-breaker (S1)LZM...1-A... LZM...2-A... LZM...3-AE... LZM...3-VE... LZM...4-AE...
Icu [kA] 18(25)(36) 25(36) 36(50) 36(50) 50In [A] 20...40 50 63 80 100 125 160 160 200 250 300 630 400 630 800 1000
going uit-breaker (S2)
In [A]
Icu(415V) [kA]
Selectivity threshold Is [kA] for selectivity between S2 and S1, overload and short-circuit release set to max. value Selectivity threshold Is [kA] for selectivity between S2 and S1,
–B(C) 0.5 15 T T T T T T T T T T T T T T T T1 15 T T T T T T T T T T T T T T T T2 15 2 T T T T T T T T T T T T T T T3 15 1.2 2 3 3 10 T T T T T T T T T T T4 15 1.2 2 3 3 8 T T T T T T T T T T T6 15 1.2 2 2.5 3 5 10 10 T T T T T T T T T10 15 1.2 1.5 2 2 4 10 10 10 10 10 10 T T T T T13 15 1 1.5 2 2 4 10 10 10 10 10 10 T T T T T16 15 1 1.2 1.5 2 3 8 8 10 10 10 10 T T T T T20 15 0.8 1.2 1.5 1.5 3 8 8 10 10 10 10 T T T T T25 15 0.7 1.2 1.5 1.5 3 7 7 10 10 10 10 T T T T T32 15 – 1.2 1 1.5 2 6 6 8 8 10 10 T T T T T40 15 – – 1 1.5 2 5 5 7 7 10 10 T T T T T50 15 – – – 1.2 1.5 4 4 6 6 10 10 T T T T T63 15 – – – – 1.5 3 3 6 6 10 10 T T T T T
M0-... 0.16 100 T T T T T T T T T T T T T T T T0.25 100 T T T T T T T T T T T T T T T T0.4 100 T T T T T T T T T T T T T T T T0.63 100 T T T T T T T T T T T T T T T T1 100 T T T T T T T T T T T T T T T T1.6 100 T T T T T T T T T T T T T T T T2.5 100 T T T T T T T T T T T T T T T T4 100 T T T T T T T T T T T T T T T T6.3 100 4 5 5 T T T T T T T T T T T T T10 100 3 4 5 6 25 T T T T T T T T T T T12 50 3 4 5 6 25 T T T T T T T T T T T16 50 1.5 1.5 2 3 5 7 T T T T T T T T T T20 50 0.8 1.5 1.5 2 3 5 T T T T T T T T T T25 50 – 1 1.5 1.5 2.5 4 T T T T T T T T T T32 50 – – 1 1 2 3.5 T T T T T T T T T T
2/ZM-... 0.6 100 T T T T T T T T T T T T T T T T1.0 100 T T T T T T T T T T T T T T T T1.6 100 T T T T T T T T T T T T T T T T2.4 100 1.2 2 2.5 10 T T T T T T T T T T T T4 100 1 1.5 2 2.5 2.5 4 10 10 10 T T T T T T T6 100 0.6 0.8 1 1.2 2 3 8 8 8 10 10 T T T T T10 100 0.5 0.7 0.8 1 1.2 2 4 4 4 5 5 T 13 T T T16 100 0.5 0.6 0.7 0.8 1.2 1.5 3 3 3 4 4 T 7 T T T25 30 – 0.6 0.7 0.7 1.2 1.5 2 2 2 3 3 20 5 20 T T32 30 – – 0.6 0.7 1.2 1.5 2 2 2 3 3 15 3.5 15 T T40 30 – – 0.6 0.7 1 1.5 2 2 2 2 2 15 3.5 15 T T
M4 16 100 0.5 0.8 0.8 0.8 2 5 5 5 5 5 5 45 16 45 T T25 100 – 0.7 0.8 0.8 1.5 5 5 5 5 5 5 25 10 25 42 T32 50 – – 0.8 0.8 1.5 4 4 4 4 4 4 18 8 18 30 4540 50 – – – 0.8 1.5 3 3 3 3 3 3 18 8 18 30 4550 50 – – – – 1 2.5 2.5 2.5 2.5 2.5 2.5 18 8 18 30 4558 50 – – – – – 2.5 2.5 2.5 2.5 2.5 2.5 15 6.5 15 25 4063 50 – – – – – 2 2 2 2 2 2 15 6.5 15 25 40
es T: full selectivity
2
1
3 4
LZM, FAZ-B(C), PKZ
72
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Engineering Engineeringcoming circuit-breaker, outgoing circuit-breaker
LZM...4-VE...
501250 1600 800 1000 1250 1600
ort-circuit release of the incoming
T T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T TT T T T T T
T T T T T TT T T T T TT T T T T T
T T T T T TT T T T T T
T T T T T TT T T T T T
20 20 – – 20 2020 20 – – 20 20– 20 – – – 20– – – – – –
20 20 – – 20 2020 20 – – 20 20– 20 – – – 20– – – – – –
73
LZM
Circ
uit-
brea
kers
, sw
itch
-dis
OutbreaLZM
LZM
LZM
LZM
LZM
LZM
Not
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Selectivity: incoming circuit-breaker, outgoing circuit-breaker Selectivity: in
Incoming circuit-breaker
Outgoing circuit-breaker
Selectivity 415 V AC between circuit-breakers enables separate shut-down of faulty system sections. Selectivity (discrimination) exists between incoming breaker 1 and outgoing breaker 2 if, only outgoing breaker 2 trips at position 2 during a short-circuit. System sections 3 and 4 continue to be operational.
Incoming circuit-breaker (S1) Incoming circuit-breaker (S1)LZM...1-A... LZM...2-A... LZM...3-AE... LZM...3-VE... LZM...4-AE...
Icu[kA] 18(25)(36) 25(36) 36(50) 36(50) 50In[A] 20...40 50 63 80 100 125 160 160 200 250 300 630 400 630 800 1000
going circuit-ker (S2)
In[A]
Icu(415V) [kA]
Prospective short-circuit current (kA). Set the overload and short-circuit release of the incoming circuit-breaker to the max. value.
Prospective short-circuit current (kA). Set the overload and shcircuit-breaker to the max. value.
...1-A... 20...40 25...100 – – 0.5 0.7 0.8 1.5 1.5 1.5 2 3 3 20 25 25 T T50 25...100 – – – 0.6 0.8 1.5 1.5 1.5 2 3 3 20 25 25 T T63 25...100 – – – – 0.8 1.5 1.5 1.5 2 3 3 15 20 20 T T80 25...100 – – – – – 1.5 1.5 1.5 2 3 3 15 20 20 T T100 25...100 – – – – – – 1.5 1.5 2 3 3 15 20 20 T T125 25...100 – – – – – – – – 2 3 3 15 20 20 T T160 25...100 – – – – – – – – 2 3 3 15 20 20 T T
...2-A... 160 25...150 – – – – – – – – – 2 2 10 15 15 T T200 25...150 – – – – – – – – – – – 10 15 15 T T250 25...150 – – – – – – – – – – – 10 15 15 T T
...3-AE... 400 50...150 – – – – – – – – – – – 7.5 – 12 T T630 50...150 – – – – – – – – – – – – – – T T
...3-VE... 400 50...150 – – – – – – – – – – – 4 – 12 T T630 50...150 – – – – – – – – – – – – – – T T
...4-AE... 800 50...100 – – – – – – – – – – – – – – – –1000 50...100 – – – – – – – – – – – – – – – –1250 50...100 – – – – – – – – – – – – – – – –1600 50...100 – – – – – – – – – – – – – – – –
...4-VE... 800 50...100 – – – – – – – – – – – – – – – –1000 50...100 – – – – – – – – – – – – – – – –1250 50...100 – – – – – – – – – – – – – – – –1600 50...100 – – – – – – – – – – – – – – – –
es T: total selectivity
2
1
3 4
LZM
74Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
EngineeringMCB, back-up protection
Protection of PVC insulated cables against thermal overload with short-circuitsAccording to VDE 0100 part 430 cables and conductors must be protected against short-circuit and overload. The overload protection is obtained by using LZM circuit-breakers with settable, current-dependent, delayed overload release.
Short-circuit protection is provided by adjustable instantaneous releases, which open the main contacts in less than 25 ms. The short-circuit total opening time restricts the temperature rise of the cable to a minimum.
The tables indicate the minimum conductor cross-section reliably protected by circuit-breakers during a short-circuit. (Operating voltage UN = 415 V)
Min. protected cross-section mm2 copperLZM...1(-4)-...20 6LZM...1(-4)-...25 … 160 10LZM...2(-4)-...20 … 300 10LZM...3(-4)-...250 … 630 16LZM...4(-4)-...630 … 1600 95
Back-up protection
between LZM(N)(S) incoming circuit-breaker and LZM(E)(B)(C)(N) outgoing circuit-breakerIncoming circuit-breaker aLZM1 LZM2 LZM3
In up to 160 A up to 300 A up to 630 AIcu(415 V) 25 kA 36 kA 25 kA 36 kA 50 kA
Outgoing circuit-breaker bIcu(415 V) In
LZME1 16 kA up to 160 A 25 36 25 36 50LZMB1 25 kA up to 160 A 25 36 25 36 50LZMC1 36 kA up to 160 A – 36 36 50LZMB2 25 kA up to 300 A 25 36 25 36 50LZMC2 36 kA up to 300 A – 36 – 36 50LZMC3 36 kA up to 630 A – – – – 50LZMN3 50 kA up to 630 A – – – – 50
a
b
Where the prospective fault current at the point of installation of circuit-breakers is very high, it is conventional to use LZMN current-limiting circuit-breakers. An attractively priced alternative is to fit a LZMN current-limiting circuit-breaker upstream of LZMB(C) standard circuit-breakers, if the fault level is too high for LZMB(C) switches.
The table shows which current-limiting circuit-breaker LZMN in combination with LZMB(C) are to be used to provide protection at the network locations with high short-circuit capacities.
The selectivity limit is determined by the response current of the non-delayed short-circuit release in the upstream incoming circuit-breaker. In many applications this is sufficient.
between LZM...1-A... incoming circuit-breaker and FAZ-B(C)/PLSM-B(C)... outgoing circuit-breakerOutgoing circuit-breaker
Outgoing circuit-breakerLZM(B)(C)2-A... LZMC(N)1-A...
FAZ-B(C)...0,5 – 16 25 kA 30 kA20 – 40 20 kA 20 kA50, 63 15 kA 15 kA
PLSM-B(C)...(/...)0,5 – 16 25 kA 30 kA20 – 40 20 kA 20 kA50, 63 15 kA 15 kA
between LZM...2-A... incoming circuit-breaker and FAZ-B(C)/PLSM-B(C)... outgoing circuit-breakerOutgoing circuit-breaker
Incoming circuit-breakerLZMB(C)2-A... LZMN2-A...
FAZ-B(C)...0,5 – 10 25 kA 50 kA13 – 32 25 kA 30 kA40 – 63 20 kA 20 kA
PLSM-B(C)...(/...)0,5 – 10 25 kA 50 kA13 – 32 25 kA 30 kA40 – 63 20 kA 20 kA
LZM...
PLSM
Icc
LZM...
PLSM
Icc
LZM1, LZM2, LZM3
75
http://catalog.moeller.net Moeller SK1230-1177GB
EngineeringDirection of blow-out, minimum clearances, tube cable lugs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Direction of blow-out
Minimum clearancesbetween two adjacently mounted switchesMinimum clearance a in mm
between switch and other partsMinimum clearances in mm
DimensionsFor pressing the cable lugs a press tool K22, HK60/22 or EK22from the company Klauke is necessary with the following press inserts:R22/95 for 95 mm2
R22/120 for 120 mm2
R22/150 for 150 mm2
R22/185 for 185 mm2
R22/240 for 240 mm2
Top, front Bottom, rear
LZM1 X –LZM21) X XLZM3 X XLZM4 X –
1) LZM2E(B)(C) – A … as LZM1
b ba
cd
LZM1 LZM2 LZM3 LZM4LZM1 0 5 5 15LZM2 5 5 5 15LZM3 5 5 5 15LZM4 15 15 15 15
b c dF 690 V 1000 V F 690 V 1000 V F 690 V 1000 V
LZM1 0 – 60 – 0 –LZM21) 5 5 35 35 35 35LZM3 5 5 60 60 60 60LZM4 15 15 100 200 0 0
1) LZM2B(C) – A … C= 60 mm, d = 0 mm
g
ed
a
ifb
hc
Cable lug For use with Rated cross section
Terminal bolt Dimensions in mm
mm2 o a b c d e f g h iKS95-NZM7 LZM2 95 M8 53+2 23g0.5 18g0.2 10g1 19 8,5 25 13,5 4,4KS120-NZM7 LZM2 120 M8 56+2 23g0.5 19.5g0.2 10g1 19 8,5 26 15 4,4KS150-NZM7 LZM2 150 M8 61+2 23g0.5 21g0.2 10g1 19 8,5 30 16,5 4,4NZM2-XKS185 LZM2 185 M8 65g1.5 22g1 24g0.3 9+1
–0,5 19+2,5–0,5 8.5+0,05
–0,1 30g2 19g0.4 7NZM3-XKS185 LZM3, LZM4 185 M10 65 24,5 24 11,5 18 10,5 30 19 7.0g0.8
NZM3-XKS240 LZM3, LZM4 240 M10 72 31 26 11,5 19 10,5 35 21 5.0g0.8
LZM1, LZM2, LZM3, LZM4
76Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
EngineeringAuxiliary switches, trip-indicating auxiliary contacts
Front cut-outCut-out atoggle lever
Cut-out brotary handle, remote operator
Distance from mounting plate and door cutout
Cut-out a Cut-out b
cmm
dmm
emm
fmm
emm
fmm
LZM1 68 73 40 23 46 91LZM2 103 108 79 36 96 101LZM3 120.5 125.5 79 36 96 136LZM4 138 146 101 105 118 204
f
e
Y
X
f
e
Y
X X
c
d
b
a
Standard auxiliary contact (HIN)
Early-make auxiliary contact (HIV) Trip-indicating auxiliary contact (HIA)
0 l I Switching on Q Contact closedq Contact open
0 m I Switching off
+ m I Trip
L1L2L3
HIN
L1L2L3
HIN
L1L2L3
HIN
I
I
+ I
+
+
+
L1L2L3
HIV
I
I
++
+
+
I
L1L2L3
HIV
L1L2L3
HIV
LZM 1, 2, 3I
I
++
+
+
I
L1L2L3
HIV
L1L2L3
HIV
L1L2L3
HIV
LZM 4L1L2L3
HIA
L1L2L3
HIA
L1L2L3
HIA
+
+
+I
I
+I
Notes If early-make contacts are required in combination with shunt or undervoltage releases, please select the combination type in the “Release” section.
LZM1, LZM2, LZM3, LZM4
77
http://catalog.moeller.net Moeller SK1230-1177GB
EngineeringMechanical interlock for (door-coupling) rotary handles
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Interlocking variants and combination optionsA B
OFF OFFON/TRIP
ON/TRIP
A B C
OFF OFF OFFON/TRIP
ON/TRIP ON/TRIP
A B C
OFF OFF OFFON/TRIP
ON/TRIP
ON/TRIP
A B C D
OFF OFF OFF OFFON/TRIP ON/TRIP
ON/TRIP ON/TRIP
= Switch clearance 3 pole = Switch clearance 4 pole
A B ON
ON
A B C ON ON
ON
A B CON ON
ON ON
ON ON
A B DCON ON
ON ON
x3P
x4P
x3P
x4P
NZM-XBZ225 right switchmax. switch clearance LZM1 LZM2 LZM3 LZM4
X3P X4P X3P X4P X3P X4P X3P X4P
left switch mm mm mm mm mm mm mm mmLZM1 3/4 pole 135 105 120 85 135 90 125 80LZM2 3/4 pole 135 105 120 85 135 90 125 80LZM3 3/4 pole 90 75 75 35 85 40 80 45LZM4 3/4 pole 50 35 40 15 25 – 15 –
NZM-XBZ600 right switchmax. switch clearance LZM1 LZM2 LZM3 LZM4
X3P X4P X3P X4P X3P X4P X3P X4P
left switch mm mm mm mm mm mm mm mmLZM1 3/4 pole 510 480 495 460 510 465 475 405LZM2 3/4 pole 510 480 495 460 510 465 475 405LZM3 3/4 pole 460 430 450 410 460 415 460 390LZM4 3/4 pole 400 370 380 340 400 375 390 320
NZM-XBZ1000 right switchmax. switch clearance LZM1 LZM2 LZM3 LZM4
X3P X4P X3P X4P X3P X4P X3P X4P
left switch mm mm mm mm mm mm mm mmLZM1 3/4 pole 910 880 895 860 910 865 865 795LZM2 3/4 pole 910 880 895 860 910 865 865 795LZM3 3/4 pole 820 790 850 810 860 815 860 790LZM4 3/4 pole 750 720 730 700 800 775 790 720
LZM, NZM…-XBZ-…
78Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
EngineeringMechanical interlock for remote operator, residual-current relay
XMVR mechanical interlock(Mounting adjacent)NZM...-XMVRMax. switch clearance right switch
LZM2 LZM3 LZM4X3p X4p X3p X4p X3p X4p
left switch mm mm mm mm mm mmLZM2 3/4 pole 130 95 95 50 – –LZM3 3/4 pole – – 135 90 155 85LZM4 3/4 pole – – – – 120 50
X3p = max. switch clearance 3 poleX4p = max. switch clearance 4 pole
XMVRL mechanical interlockMounting in adjacent enclosuresNZM...-XMVRLMax. switch clearance right switch
LZM2 LZM3 LZM4X3p X4p X3p X4p X3p X4p
left switch mm mm mm mm mm mmLZM2 3/4 pole 350 315 420 385 – –LZM3 3/4 pole – – 400 365 460 390LZM4 3/4 pole – – – – 420 350
XMVRL mechanical interlock(Mounting one above the other)NZM…-XMVRLMax. switch clearance Switch top
LZM2 LZM3 LZM43/4 pole 3/4 pole 3/4 pole
Y Y YSwitch bottom mm mm mmLZM2 3/4 pole 220 225 –LZM3 3/4 pole – 220 230LZM4 3/4 pole – – 230
Y = max. switch clearance
Ring-type transformer
3P
x4P
Maximum rated current [A] DiameterPower distribution
Motor/capacitor Transformer part no.PFR-W-…d1
Max. conductor circumference (mm)d2
50 50 20 13150 100 30 20150 100 35 23400 200 70 47600 250 105 70
1200 630 140 931800 800 210 140
d2
d1 f 1.5 x d2
NZM…-XMVR(L)
79
http://catalog.moeller.net Moeller SK1230-1177GB
EngineeringSizes 1, 2: tripping characteristics
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
System and line protection with LZM1
System and line protection with LZM2 Systems, cable, selectivity and generator protection with LZM2
Trip
ping
tim
e [s
]
Setting range
Toler
ance
t r [s]
LZM1(-4)-A...
2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100
x Ir
10.001
0.002
0.0040.0060.008
0.01
0.02
0.040.060.08
0.1
0.2
0.40.60.8
1
2
468
10
20
40 60
600
80100
60002.5 h
200
400
8001000
2000
4000
8000
(10 min)
(1 min)
10x InIi = 6
2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100
x Ir
10.001
0.002
0.0040.0060.008
0.01
0.02
0.040.060.08
0.1
0.2
0.40.60.8
1
2
468
10
20
40 60
600
80100
60002.5 h
200
400
8001000
2000
4000
8000
(10 min)
(1 min)
10x InIi = 6
LZM2(-4)-A...
Trip
ping
tim
e [s
]
Setting range
Toler
ance
t r [s]
Characteristics for Ir = 1,0 x In
Trip
ping
tim
e [s
]
LZM2(-4)-VE...
1000750500
300200
10060
202 3 4 5 6 7 8 9 10
0
Ii = 12 x In
Isd = x Ir
tsd [ms]
20tr [s]
171410
68
4
2
2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100
x Ir
10.001
0.002
0.0040.0060.008
0.01
0.02
0.040.060.08
0.1
0.2
0.40.60.8
1
2
468
10
20
40 60
600
80100
60002.5 h
200
400
8001000
2000
4000
8000
(10 min)
(1 min)
LZM1, LZM2
80Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
EngineeringSize 3: tripping characteristics
System and line protection with LZM3 Systems, cable, selectivity and generator protection with LZM3
Systems, cable, selectivity and generator protection with LZM3
Trip
ping
tim
e [s
] Characteristics for Ir = 1,0 x In
LZM3(-4)-AE...
63.52.5 32 854 7 630 AIi = x In
2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100
x Ir
10.001
0.002
0.0040.0060.008
0.01
0.02
0.040.060.08
0.1
0.2
0.40.60.8
1
2
468
10
20
40 60
600
80100
60002.5 h
200
400
8001000
2000
4000
8000
(10 min)
(1 min)
Trip
ping
tim
e [s
] Characteristics for Ir = 1,0 x In
without “I2t = constant” function
LZM3(-4)-VE...
400 A
400 A
1000750500300200
10060
20
2 3 4 5 6 7
7
8 9 10
6
0
5432 7 8 9 11x InIi =
Isd =
6543.52.5 32 7 8 630 AIi = x In
x Ir
tsd [ms]
62 3 3.52.51.5 4 5 630 AIsd = x Ir
20tr [s]
171410
68
4
2
2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100
x Ir
10.001
0.002
0.0040.0060.008
0.01
0.02
0.040.060.08
0.1
0.2
0.40.60.8
1
2
468
10
20
40 60
600
80100
60002.5 h
200
400
8001000
2000
4000
8000
(10 min)
(1 min)
Characteristics for Ir = 1,0 x In
I2t = constant
Trip
ping
tim
e [s
]
LZM3(-4)-VE...
400 A
400 A
2 3 4 5 6 8 910 x Ir
21.5 2.5 3.53 4 5 6 7
7
Isd =
Isd =
x Ir
20tr [s]
171410
68
4
2
630 A
2 3 4 5 6 7 8 9 11Ii = x In
2 2.5 3.53 4 5 6 8Ii = x In7 630 A
1 2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100
x Ir
tsd [m
s] = 2
0........
1000
0.001
0.002
0.0040.0060.008
0.01
0.02
0.040.060.08
0.1
0.2
0.40.60.8
1
2
468
10
20
40 60
600
80100
60002.5 h
200
400
8001000
2000
4000
8000
(10 min)
(1 min)
LZM3
81
http://catalog.moeller.net Moeller SK1230-1177GB
EngineeringSize 4: tripping characteristics
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Systems, cable, selectivity and generator protection with LZM4 System and line protection with LZM4
Systems, cable, selectivity and generator protection with LZM4
Trip
ping
tim
e [s
] Characteristics for Ir = 1,0 x In
I2t = constant
LZM4(-4)-VE...
6542 3 7 8 9 10
2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100
Isd =
t sd [m
s] =
20..........
..1000
6542 3 7 8 10 12 x In
x Ir
Ii =
20tr [s]
171410
68
4
2
x Ir
10.001
0.002
0.0040.0060.008
0.01
0.02
0.040.060.08
0.1
0.2
0.40.60.8
1
2
468
10
20
40 60
600
80100
60002.5 h
200
400
8001000
2000
4000
8000
(10 min)
(1 min)
Trip
ping
tim
e [s
] Characteristics for Ir = 1,0 x In
LZM4(-4)-AE...
10.001
0.002
0.0040.0060.008
0.01
0.02
0.040.060.08
0.1
0.2
0.40.60.8
1
2
468
10
20
40 60
600
80100
60002.5 h
200
400
8001000
2000
4000
8000
(10 min)
(1 min)
65432 7 8 10 12x InIi =
2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100
x Ir
Trip
ping
tim
e [s
] Characteristics for Ir = 1,0 x In
without “I2t = constant” function
LZM4(-4)-VE...
10007505003002001006020
6542 3 7 8 9 10
0
x IrIsd =
6542 3 7 8 10 12 x InIi =
tsd [ms]
20tr [s]
171410
68
4
2
2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100
x Ir
10.001
0.002
0.0040.0060.008
0.01
0.02
0.040.060.08
0.1
0.2
0.40.60.8
1
2
468
10
20
40 60
600
80100
60002.5 h
200
400
8001000
2000
4000
8000
(10 min)
(1 min)
LZM4
82Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
EngineeringSize 1, 2, 3: let-through characteristics
Let-through current xD
3
6
4
20
108
100
60
200
40
80
1 6 5 108 15 20 41 32 5040 8060 100 15030
2 x I cc
415 V+440 V
[kA]DÎ
[kA]Icc rms
LZMB1(-4)-A(S)15...160
3
6
4
20
108
100
60
200
40
80
1 6 5 108 15 20 41 32 5040 8060 100 15030
2 x I cc
415 V
[kA]DÎ
690 V
440 V
525 V
[kA]Icc rms
LZMC1-A20...160
3
6
4
20
108
100
60
200
40
80
1 6 5 108 15 20 41 32 5040 8060 100 15030
2 x I cc
[kA]DÎ
[kA]Icc rms
LZMB2(-4)-A(S)1,6...300
3
6
4
20
108
100
60
200
40
80
1 6 5 108 15 20 41 32 5040 8060 100 15030
2 x I cc
[kA]DÎ
[kA]Icc rms
LZMC2-A160...300
3
6
4
20
108
100
60
200
40
80
1 6 5 108 15 20 41 32 100 15030
2 x I cc
[kA]DÎ
5040 8060[kA]Icc rms
LZMN2(-4)-A(S,VE)1,6...250
3
6
4
20
108
100
60
200
40
80
1 6 5 108 15 20 41 32 100 15030
2 x I cc
[kA]DÎ
5040 8060
LZMC3/N3(-4)-AE(VE)400...630
[kA]Icc rms
LZM1, LZM2, LZM3
83
http://catalog.moeller.net Moeller SK1230-1177GB
EngineeringSizes 1, 2, 3: let-through characteristics
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Let-through energy J
a 1 half-cycle
415 V
a
2
6
4
4
2
8
68
6
4
2
8
105
106
107
104
6 5 108 15 20 41 32 100 15030
[A2 s]yZ
5040 8060[kA]Icc rms
LZMB1(-4)-A(S)15...160
a
2
6
4
4
2
8
68
6
4
2
8
105
106
107
104
6 5 108 15 20 41 32 100 15030
[A2 s]yZ
5040 8060
415 V
[kA]Icc rms
LZMC1-A20...160
a
2
6
4
4
2
8
68
6
4
2
8
105
106
107
104
6 5 108 15 20 41 32 100 15030
[A2 s]yZ
5040 8060[kA]Icc rms
LZMB2(-4)-A(S)160...250
a
2
6
4
4
2
8
68
6
4
2
8
105
106
107
104
6 5 108 15 20 41 32 100 15030
[A2 s]yZ
5040 8060[kA]Icc rms
LZMC2-A160...250
a
2
6
4
4
2
8
68
6
4
2
8
105
106
107
104
6 5 108 15 20 41 32 100 15030
[A2 s]yZ
5040 8060
[kA]Icc rms
LZMN3(-4)-AE(VE)400...630
LZM1, LZM2, LZM3
84Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
EngineeringSize 2: residual-current release frequency response
Frequency response NZM2-4-XFIA30 NZM2-4-XFIA30 mA 100 mA
NZM2-4-XFIA300 mA 1000 mA
1 10 100 1000
1000
10000
100
1010000 100000
[mA]IDn
[Hz]f
1 10 100 1000
1000
10000
100
1010000 100000
[mA]IDn
[Hz]f
1 10 100 1000
1000
10000
100
1010000 100000
[mA]IDn
[Hz]f
1 10 100 1000
10000
100000
1000
10010000 100000
[mA]IDn
[Hz]f
NZM2-4-XFIA
85
http://catalog.moeller.net Moeller SK1230-1177GB
Notes
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
86
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Technical data Technical dataCircuit-breakers
d uninterrupted current 630 A
Rated uninterrupted current max. 1600 A
C3 LZMN3 LZMN4
n)dle: IP66
8000 80006000 6000415 415III/3 III/31000 1000
withdrawable unit, , LN3: vertical, 90° left, remote control, , LN3: vertical and 90° to all directions
With withdrawable unit, LZM4, LN4: vertical with remote control, LZM4, LN4: vertical and 90° to all directions
87
LZM…1-I, LZM…2-I, LZM…3-I, LZM…4-I
Circ
uit-
brea
kers
, sw
itch
-dis
GenStanProt
Clim
AmbSO
MecSafe
Bb
Mou
DireDeg
DE
T
CircRate
MA
RateOveRate
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Circuit-breakers
Rated uninterrupted current max. 160 A
Rated uninterrupted current max. 300 A
Ratemax.
LZME1 LZMB1 LZMC1 LZMB2 LZMC2 LZM
eraldards IEC/EN 60947 IEC/EN 60947ection against direct contact Finger and back of hand proof to VDE 0106 Part 100 Finger and back of hand proof to VDE 0106 Part 100
atic proofing Damp heat, constant, according to IEC 60068-2-78Damp heat, cyclical to IEC 60068-2-30
Damp heat, constant, according to IEC 60068-2-78Damp heat, cyclical to IEC 60068-2-30
ient temperaturetorage °C –25…+70 –25…+70peration °C –25…+70 –25…+70
hanical shock resistance (IEC/EN 60068-2-27) 20 (half-sinusoidal shock 20 ms) 20 (half-sinusoidal shock 20 ms) isolation to VDE 0106 Part 101 and Part 101/A1etween auxiliary contacts and main contacts V AC 500 500etween the auxiliary contacts V AC 300 300nting position
ction of incoming supply As required As requiredree of protection
evice In the operating controls area: IP20 (basic degree of protection) In the operating controls area: IP20 (basic degree of protectionclosures With insulating surround: IP40, with door coupling rotary handle: IP66 With insulating surround: IP40, with door coupling rotary han
erminals Tunnel terminal: IP10Phase isolator and strip terminal: IP00
Tunnel terminal: IP10Phase isolator and strip terminal: IP00
uit-breakersd impulse withstand voltage Uimp
ain contacts V 6000 6000 6000 8000 8000 8000uxiliary contacts V 6000 6000 6000 6000 6000 6000
d operational voltage Ue V AC 415 415 415 415 415 415rvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3 III/3d insulation voltage Ui V 690 690 690 690 690 690
LZM1, LN1: Vertical and 90° With residual-current release, LZM1, LN1: Vertical and 90° in all directions
LZM2, LN2: Vertical and 90° in all directionsWith plug-in adapter LZM2, LN2: vertical and 90° right/left with residual current release, LZM2: vertical and 90° to all directions
WithLZM3with LZM3
LZM…1-I, LZM…2-I, LZM…3-I, LZM…4-I
88
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Technical data Technical dataCircuit-breakers
d uninterrupted current max. 630 A Rated uninterrupted current max. 1600 AC3 LZMN3 LZMN4
Sw
187 105105 105
85 5050 5042.5 2525 25
3-…250, 400: 4003-…500, 630: 630
A B
3.3 19.23.3 19.2
630 16007500 500030 30
2500 150040 97< 10 < 25
89
LZM…1-I, LZM…2-I, LZM…3-I, LZM…4-I
Circ
uit-
brea
kers
, sw
itch
-dis Rate
24
RateI
O
I
O
M
UtiliRate
tt
RateR
LifesMaxLifes
CurrTota
Not
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Circuit-breakers
Rated uninterrupted current max. 160 A Rated uninterrupted current max. 300 A RateLZME1 LZMB1 LZMC1 LZMB2 LZMC2 LZM
itching capacityd short-circuit making capacity40 V Icm kA 50 63 121 63 121 12100/415 V Icm kA 36 53 76 53 76 76d short-circuit breaking capacity Icn
cu to IEC/EN 60947 operating sequence -t-CO
240 V 50/60 Hz Icu kA 25 30 55 30 55 55400/415 V 50/60 Hz Icu kA 18 25 36 25 36 36
cs to IEC/EN 60947 operating sequence -t-CO-t-CO
240 V 50/60 Hz Icu kA 12.5 15 27.5 15 27.5 27.5400/415 V 50/60 Hz Icu kA 9 12.5 18 12.5 18 18
aximum low-voltage h.b.c. fuse1) A gG/gL LZM.1-…20…100: 200LZM.1-…125, 160: 315
355 355 LZM.LZM.
zation category to IEC/EN 60947-2 A A A A A Ad short-time withstand current = 0.3 s Icw kA – – – – 1.9 3.3 = 1 s Icw kA – – – – 1.9 3.3d making and breaking capacityated operational current AC-1 400/415 V 50/60 Hz Ie A 160 160 160 300 300 630pan, mechanical Operations 10000 10000 10000 10000 10000 7500imum operating frequency Ops/h 30 30 30 30 30 30pan, electrical
AC-1 400/415 V 50/60 Hz Operations 5000 5000 5000 5000 5000 2500ent heat loss per pole at Iu2) W 16.7 16.7 16.7 19 19 40l opening delay at short-circuit ms < 10 < 10 < 10 < 10 < 10 < 10
es 1) Maximum back-up fuse, if the expected short-circuit currents at the installation location exceed the switching capacity of the circuit-breaker.2) For current heat loss per pole the specification refers to the maximum nominal current of the frame size.
LZM…1-I, LZM…2-I, LZM…3-I, LZM…4-I
90Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
Technical dataSwitch-disconnectors
LN1(-4)max. 160 A
LN2(-4)max. 250 A
LN3(-4)max. 630 A
LN4(-4)max. 1600 A
Switch-disconnectorsRated impulse withstand voltage Uimp
Main contacts V 6000 8000 8000 8000Auxiliary contacts V 6000 6000 6000 6000
Rated operational voltage Ue V AC 690 690 690 690Rated uninterrupted current max.
IEC/EN 60947-2 annex L Iu A 160 250 630 1600Technical data, divergent from the products for the IEC market UL489, CSA 22.2 No. 5.1
Iu A 125 160 550 1200
Overvoltage category/pollution degree III/3 III/3 III/3 III/3Rated insulation voltage Ui V AC 690 690 1000 1000For use in IT electrical power networks V 690 690 690 525
Switching capacityRated short-circuit making capacity Icm kA 2.8 5.5 25 53Rated short-time withstand current
t = 0.3 s Icw kA 2 3.51) 12 25t = 1 s Icw kA 2 3.51) 12 25
Rated conditional short-circuit currentWith back-up fuse A gG/gL PN1(N1)63…125: 125
PN1(N1)-160: 160PN2(N2)-160…250: 250
PN3(N3)-400…630:630
N4-630…1600: 2 x 800
400 … 415 V kA 100 100 100 100With downstream fuse A gG/gL LN1-63…125: 125
LN1-160: 160LN2-160…250: 250
LN3-400…630: 630
LN4-630…1600: 2 x 800
400 … 415 V kA 100 100 100 100Rated making and breaking capacity
Rated operational current, AC-22/23A415 V Ie A 160 250 630 1600
Lifespan, mechanical Operations
10000 10000 7500 5000
Maximum operating frequency Ops./h 120 120 60 60Lifespan, electrical to IEC/EN 60947-4-1 section B
AC-1400/415 V Opera
tions5000 5000 2500 1500
AC-3400/415 V Opera
tions3000 3000 1000 750
Current heat loss per pole at Iu2) W 12.7 16 40 97
Notes 1) The rated short time withstand current for PN2/N2 in conjunction with residual-current release NZM2-4-XFI... Icw = 1.5 kA2) The current heat loss per pole ratings refer to the maximum current rating of the frame size.
LN…
91
http://catalog.moeller.net Moeller SK1230-1177GB
Technical dataTemperature influence
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Response values of the overload release at temperatures deviating from the reference temperatures
Device Type Release type
Temperature compensation coefficient
20 °C 30 °C 40 °C 50 °C 60 °C 65 °C 70 °C
Thermomagnetic release (TM)System protection Protection of systems (reference temperature 40 °C)
LZM...1(-4)-A15…80 TM 1.14 1.07 1 0.93 0.86 0.83 0.79LZM...1(-4)-A90…125 TM 1.14 1.07 1 0.93 0.86 0.83 0.79LZM...1(-4)-A160 TM 1.08 1.04 1 0.96 0.92 0.90 0.88LZM...2(-4)-A125…200 TM 1.04 1.02 1 0.98 0.96 0.95 0.94LZM...2(-4)-A250/300 TM 1.04 1.02 1 0.98 0.96 0.95 0.94LZM...2(-4)-A125…200 + XSV TM with XSV 1.04 1.02 1 0.98 0.96 0.95 0.94LZM...2(-4)-A250/300 + XSV TM with XSV 1.04 1.02 1 0.98 0.96 0.95 0.94
Notes With temperatures which deviate from the reference temperature, a slight change of the overload protection properties occurs. In order to determine the release time using the tripping characteristics the temperature compensation coefficient in accordance with the table must be considered.Example: An LZM1-A100 is calibrated for a reference temperature of 40 °C.
What happens when it is operated at an ambient temperature of 60 °C? At 60 °C, the temperature compensation coefficient of 0.86 results in a reduced operating current of Ir = 100 A x 0.86 = 86 A. In other words at an ambient temperature of 60 °C the LZM1-A100 trips as if it were set to 86 A.
Reduction of the rated operational current (derating) under particular ambient conditions (according to IEC 947)
Device Type Release type
Derating coefficient
20 °C 30 °C 40 °C 50 °C 60 °C 65 °C 70 °CThermomagnetic release (TM)
System protection Protection of systems (reference temperature 40 °C)LZM...1(-4)-A15…80 TM 1 1 1 1 1 1 1LZM...1(-4)-A90…125 TM 1 1 1 1 0.86 0.83 0.8LZM...1(-4)-A160 TM 1 1 1 0.95 0.9 0.85 0.8LZM...2(-4)-A15…200 TM 1 1 1 1 1 1 1LZM...2(-4)-A250 TM 1 1 1 1 0.9 0.85 0.8LZM...2(-4)-A20…200 + XSV TM with XSV 1 1 1 1 1 1 1LZM...2(-4)-A250 + XSV TM with XSV 1 0.97 0.92 0.87 0.81 – –
Notes The derating coefficient must be considered in accordance with the following table in order to determine the maximum permissible current loading at different ambient temperatures.Example: An LZM2-A250 should be operated at an ambient temperature of 65 °C.
How high is the permissible rated operational current Ie? At 65 °C the derating coefficient is 0.85, this means Ie = 250 A x 0.85 = 212.5 A. The LZM2-A250 may be operated at an ambient temperature of 65 °C with a maximum Ie = 212.5 A.
Part no. Weightkg
Part no. Weightkg
Circuit-breaker Plug-in adapter elementsLZM...1-... 1.046 +NZM2-XSV 4.7LZM...1-4-... 1.325 +NZM2-4-XSV 5.9LZM...2-... 2.345 Withdrawable unitLZM...2-4-... 3.5 +NZM3-XAV 21LZM...3-... 6.34 +NZM3-4-XAV 27LZM...3-4-... 8.4 +NZM4-XAV 52LZM...4-... 21 +NZM4-4-XAV 65LZM...4-4-... 27
92Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
Technical dataTemperature influence
Reduction of the rated operational current (derating) under particular ambient conditions (according to IEC 947)
Device Type Release type
Derating coefficient
20 °C 30 °C 40 °C 50 °C 60 °C 65 °C 70 °C
Electronic release (E)System protection
LZM...3(-4)-AE630 E 1 1 1 1 0.9 0.85 0.8LZM...3(-4)-AE630 + XAV E with XAV 0.96 0.92 0.87 0.83 0.78 0.75 0.73LZM...4(-4)-AE800...1250 E 1 1 1 1 1 1 1LZM...4(-4)-AE1600 E 1 1 1 1 0.87 0.85 0.82LZM...4(-4)-AE800...1250 + XAV E with XAV 1 1 1 1 1 1 1LZM...4(-4)-AE1600 + XAV E with XAV 1 0.98 0.93 0.89 0.85 0.83 0.8
Systems protection, cable protection, selectivity and generator protectionLZM...3(-4)-VE400 E 1 1 1 1 1 1 1LZM...3(-4)-VE630 E 1 1 1 1 0.9 0.85 0.8LZM...3(-4)-VE400 + XAV E with XAV 1 1 1 1 1 1 1LZM...3(-4)-VE630 + XAV E with XAV 0.96 0.92 0.87 0.83 0.78 0.75 0.73LZM...4(-4)-VE800...1250 E 1 1 1 1 1 1 1LZM...4(-4)-VE1600 E 1 1 1 1 0.87 0.85 0.82LZM...4(-4)-VE800...1250 + XAV E with XAV 1 1 1 1 1 1 1LZM...4(-4)-VE1600 + XAV E with XAV 1 0.98 0.93 0.89 0.85 0.83 0.8
Notes The derating coefficient must be considered in accordance with the following table in order to determine the maximum permissible current loading at different ambient temperatures.Example: An LZM3-VE630 should be operated at an ambient temperature of 65 °C.
How high is the permissible rated operational current Ie? At 65 °C the derating coefficient is 0.85, this means Ie = 630 A x 0.85 = 535.5 A. The LZM3-VE630 may be operated at an ambient temperature of 65 °C with a maximum Ie = 535.5 A.
93
http://catalog.moeller.net Moeller SK1230-1177GB
Technical dataEffective power loss
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
LZM up to 250 A with thermomagnetic release (3- and 4-pole)Fixed mounting Fixed mountingLZM1- LZM2-A... A...
In [A] P R P R[W] [μOhm] [W] [μOhm]
20 9.8 8180 5.1 425025 8.8 4680 8 425026 – – – –30 – – – –32 9.1 3030 10 314033 – – – –35 – – – –40 11 2220 13 280045 – – – –50 13.5 1760 18 227060 – – – –63 14 1190 20 170070 – – – –80 15.5 850 22 107090 – – – –100 24 730 28 855110 – – – –125 38 570 29 589150 – – – –160 50 460 40 427175 – – – –200 – – 48 332225 – – – –250 – – 57 310
Note: The values stated in the table apply for 3- and 4-pole fixed mounted devices with an equal load distribution.On 4-pole devices the current in the N-conductor is equal to zero. The total resistive load is the measured value for a 3-pole or a 4-pole switch.The total heat dissipation is the value measured at In, 50/60Hz for a 3-pole or 4-pole switch.The heat dissipation can be calculated with the formula: P = 3 x R x I²
LZM up to 1600 A with electronic release (3- and 4-pole)Fixed mounting Supplementary
Plug-in unitsFixed mounting Supplementary
Withdrawable unitsFixed mounting Supplemementary
Withdrawable unitsLZM2- LZM3 LZM4R R R R R R[μOhm] [μOhm] [μOhm] [μOhm] [μOhm] [μOhm]
275 100 100 70 37 10
Note: The values stated in the table apply for 3- and 4-pole devices with an equal load distribution.On 4-pole devices the current in the N-conductor is equal to zero. The total resistive load is the measured value for a 3-pole or a 4-pole switch (independent of In and the type of release).The total resistive load for a plug-in or withdrawable switch results from: the resistive value for fixed mounted + resistive value for plug-in or withdrawable.The heat dissipation can be calculated with the formula: P = 3 x R x I²
LZM1, LZM2
94
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Technical data Technical dataTerminal capacities
In1)
A
ar
–
1400
) 1250
1000
1400
16004 x 240
–––
1400
–
–
pleaes inquirepleaes inquire–pleaes inquire
––
1100 1.0 1.0 1250
(2 x ) 10 x 40 x 1.0
1.0 1600 1.0
1.0 16002 x (10 x 50 x 1.0)
16002000
12502 x (40 x 10)150016002 x (50 x 10)
95
LZM…
Circ
uit-
brea
kers
, sw
itch
-dis Term
StanAcce
RateB
T
B
Al coT
B
Cu sB
F
M
B
CopB
Not
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Terminal capacities
LZM1160 A
In1)
ALZM2300 A
In1)
ALZM3630 A
In1)
ALZM41600 A
inal capacitiesdard equipment Box terminal Screw terminal Screw terminal Screw terminalssories Screw connection
Tunnel terminalConnection on rear
Box terminalTunnel terminalConnection on rear
Box terminalTunnel terminalConnection on rear
Tunnel terminalConnection on reStrip terminal
d power of coilox terminal Solid mm2 1 x (10 – 16)
2 x (6 – 16)160 1 x (4 – 16)
2 x (4 – 16)250 2 x 16 500
Stranded mm2 1 x (25 – 70)2 x 25
1 x (25 – 185)2 x (25 – 70)
250 1 x (35 – 240)2 x (25 – 120)
unnel terminal SolidStranded
mm2 1 x 16 160 1 x 16 250Single hole mm2 1 x (25 – 95) 1 x (25 – 185) 1 x (25 – 185) 350Double hole fitting mm2 – – – – 1 x (50 – 240)
2 x (50 – 240)6302 x 185
–
4-hole mm2 – – – – – – 4 x (50 – 240)olt terminal and rear-side connection
Direct on the switch Solid mm2 1 x (10 – 16)2 x (6 – 16)
160 1 x (4 – 16)2 x (4 – 16)
250 1 x 162 x 16
6302 x 185
Stranded mm2 1 x (25 – 70)3)
2 x 251 x (25 – 185)2 x (25 – 70)
1 x (25 – 240)2 x (25 – 240)
1 x (120 … 1854 x (50 … 185)
Module plate Single hole min. mm2 – – – – – – 1 x (120 – 300)max. mm2 – – – – – – 2 x (95 – 300)
Module plate Double hole min. mm2 – – – – – – 2 x (95 – 185)max. mm2 – – – – – – 4 x (35 – 185)
Connection width extension mm2 2 x 300 6302 x 185
4 x 3006 x (95 – 240)
nductors, Al cableunnel terminal Solid
Strandedmm2 1 x 16 160 1 x 16 250 1 x 16 350 –
Single hole mm2 1 x (25 – 95) 1 x (25 – 185)2) 1 x (25 – 185)2) –Double hole fitting mm2 – – – – 1 x (50 – 240)
2 x (50 – 240)630 –
4-hole mm2 – – – – – – 4 x (50 – 240)olt terminal and rear-side connection
Direct on the switch Solid mm2 1 x (10 – 16)2 x (10 – 16)
160 1 x (10 – 16)2 x (10 – 16)
250 1 x 162 x (10 – 16)
400 –
Stranded mm2 1 x (25 – 35)2 x (25 – 35)
1 x (25 – 50)2 x (25 – 50)
1 x (25 – 120)2 x (25 – 120)
–
Module plate Single hole min. mm2 – – – – – – 1 x (185 – 240)Single hole max. mm2 – – – – – – 2 x (70 – 185)
Module plate Double hole mm2 – – – – – – 4 x 50Connection width extension mm2 2 x 240
6 x (70 – 240)trip (number of segments x width x segment thickness)ox terminal min. mm 2 x 9 x 0.8 160 2 x 9 x 0.8 250 6 x 16 x 0.8 630 –
max. mm 9 x 9 x 0.8 10 x 16 x 0.8 10 x 24 x 1.0+ 5 x 24 x 1.0(2 x) 8 x 24 x 1.0
–
lat conductor terminal min. mm 6 x 16 x 0.8max. mm (2 x) 10 x 32 x
odule plate Single hole mm – – – – – – (2 x) 10 x 50 x
olt terminal and rear-side connectionFlat copper strip, with holes min. mm 2 x 16 x 0.8 250 6 x 16 x 0.8 630 (2 x) 10 x 50 xFlat copper strip, with holes max. mm 10 x 16 x 0.8 10 x 32 x 1.0 + 5
x 32 x 1.0 (2 x) 10 x 50 x
Connection width extension mm2 – – – – (2 x) 10 x 50 x 1.0 (2 x) 10 x 80 x
per busbar (width x thickness)olt terminal and rear-side connection
Screw connection M6 M8 M10 M10Direct on the switch min. mm 12 x 5 160 16 x 5 250 20 x 5 630 25 x 5
max. mm 16 x 5 20 x 5 30 x 10+30 x 5
2 x (50 x 10)2 x (80x 10)
Module plate Single hole min. mm – – – – – – 25 x 5max. mm – – – – – – 2 x (50 x 10)
Module plate Double hole mm – – – – – – 2 x (50 x 10)Connection width extension min. mm – – – – – 630
10 x 4060 x 10
max. mm – – – – 2 x (10 x 50) 2 x (80 x 10)
es 1) The rated currents In have been determined conform to IEC/EN 60947 (switchgear standard) and generally relate to the max. defined cross-sections and are intended for the purpose of orientation. The engineering standards which apply in each case must be observed.
2) depending on the cable manufacturer up to 240 mm2 can be connected.3) depending on the cable manufacturer up to 95 mm2 can be connected.
LZM…
96Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
Technical dataAuxiliary contacts
at AC = 50/60 Hz M22-K… NZM-XHIV NZM-XHI
Auxiliary contactsRated operational voltage
AC Ue V AC 500 500 500DC Ue V DC 220 220 220
Conventional thermal current Ith = Ie A 4 4 4Rated operational current
AC–15 115 V Ie A 4 4 4230 V Ie A 4 4 4400 V Ie A 2 2 2500 V Ie A 1 1 1
DC-13 24 V Ie A 3 3 342 V Ie A 1.7 1.5 –60 V Ie A 1.2 0.8 1.2110 V Ie A 0.8 0.5 0.5220 V Ie A 0.3 0.2 0.2
Short-circuit protection max. fuse A gG/gL 10 10 10Max. miniature circuit-breaker A PKZM0-10/FAZ-B6 FAZ-B6 FAZ-B6
Early-make time compared to the main contacts during switch on and off (switching times with manual operation)
ms LZM1, LN1: approx. 20LZM2, LN2: approx. 20LZM3, LN3: approx. 20LZM4, LN4: approx. 90With LZM4/N4 the HIV does not feature early break.
Terminal capacitiesSolid or flexible conductor with ferrule mm2 1 x (0.75 – 2.5)
2 x (0.75 – 2.5)1 x (0.75 – 2.5)2 x (0.75 – 2.5)
1 x (0.75 – 2.5)2 x (0.75 – 2.5)
AWG 1 x (18 – 14)2 x (18 – 14)
1 x (18 – 14)2 x (18 – 14)
1 x (18 – 14)2 x (18 – 14)
M22-K…, XHI(V)
97
http://catalog.moeller.net Moeller SK1230-1177GB
Technical dataEquipping with auxiliary contacts, time differences
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Maximum equipment and position of the internal accessoriesc b a
-XHIV(2S)or -XAor -XU
HIA HIN Contacts per slot with HIA and HIN
LZM1, LN1 1 1 1 1 N/OLZM2, LN2 1 1 2 1 N/CLZM3, LN3 1 1 3 2 N/OLZM4, LN4 1 2 3 2 N/C
N/O = normally open contactN/C = normally closed contact
a
b
c
Time differences ON-OFF
Main contact
Auxiliary contact, early make
Auxiliary contact, normal (HIN)
Time difference a (ms) Time difference b (ms)Manual operation Motor operators Manual operation Motor operatorsHIV HIN HIV HIN HIV HIN HIV HIN
K10 K01 K10 K01 K10 K01 K10 K01
LZM1 202) 0 2.5 – – – 202) 0 2.5 – – –
LZM2 202) 3.5 6.5 Not permissible
2.5 4.5 202) 3 4.5 Not permissible
3 4
LZM3 202) 4 8 Not permissible
2 4 202) 3.5 8 Not permissible
3 6.5
LZM4 902) 7 11 Not permissible
on request on request 01)2) 12 15 Not permissible
on request on request
Notes 1) With LZM4/N4 the HIV does not feature early break.2) Minimum value, as it is dependent on the switching speed
a b
a b
LZM…
98Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
Technical dataUndervoltage releases, shunt releases
NZM1(2/3)-XU... NZM4-XU…
Undervoltage releaseRated control voltage
Alternating voltage at 50/60 Hz Us V AC 24…600 24…600DC Us V DC 12…250 12…250
Operating rangeDrop-out voltage x Us 0.35 – 0.7 0.35 – 0.7Pick-up voltage x Us 0.85 – 1.1 0.85 – 1.1
Power consumptionAC
Pick-up AC VA 1.5 3.6Sealing AC VA 1.5 3.6
DCPick-up DC W 0.8 2.5Sealing DC W 0.8 2.5
Max. opening delay (response time until the main circuits open)
ms 19 23
Minimum command time ms 10 – 15 10 … 15Terminal capacities
Solid or flexible conductor with ferrule mm2 1 x (0.75 … 2.5)2 x (0.75 … 2.5)
1 x (0.75 … 2.5)2 x (0.75 … 2.5)
AWG 1 x (18 … 14)2 x (18 … 14)
1 x (18 … 14)2 x (18 … 14)
UVU-NZM
Undervoltage releases, off-delayedRated operational voltage
Alternating voltage at 50/60 Hz Ue V AC 24, 220 – 550DC Ue V DC 24
Inrush current (peak value) Ie mA < 500Power consumption VA 50Delay time tsd ms 70 – 4000With additional external capacitor, 90.000 μF f 35 V s To 16
With additional external capacitor, 30.000 μF f 35 V s To 8
Terminal capacitiesSolid or flexible conductor with ferrule mm2 1 x (0.5 – 2.5)
2 x (0.5 – 1.5)
NZM1(2/3)-XA... NZM4-XA... NZM2/3-XA...-MNS NZM4-XA…-MNS
Shunt releaseRated control voltage
AC Us V AC 12…440 12…440 230 230DC Us V DC 12…440 12…440
Frequency range Hz 0 – 400 0 – 400 50/60 50/60Operating range
AC x Us 0.7…1.1 0.7…1.1 0.1…1.1 0.1…1.1DC x Us 0.7…1.1 0.7…1.1
Power consumptionPick-up AC/DC VA/W 2.5 2.5 – –Sealing AC/DC VA/W 2.5 2.5 – –
Maximum current consumption at 110% Us (230 V 50 Hz) A – – 0.5 1Max. opening delay (response time until the main circuits open)
ms 20 22 20 22
Duty factor ms L L 1000 ms 1000 msMinimum command time ms 10 … 15 10 … 15 10 … 15 10 … 15Terminal capacities
Solid or flexible conductor with ferrule mm2 1 x (0.75 … 2.5)2 x (0.75 … 2.5)
1 x (0.75 … 2.5)2 x (0.75 … 2.5)
1 x (0.75 … 2.5)2 x (0.75 … 2.5)
1 x (0.75 … 2.5)2 x (0.75 … 2.5)
AWG 1 x (18 … 14)2 x (18 … 14)
1 x (18 … 14)2 x (18 … 14)
1 x (18 … 14)2 x (18 … 14)
1 x (18 … 14)2 x (18 … 14)
NZM…-XU, NZM…-XA…
99
http://catalog.moeller.net Moeller SK1230-1177GB
Technical dataRemote operator, capacitor units
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
NZM-XCM
Capacitor unit for shunt releaseRated operational voltage Ue V AC 230Rated operational current Ie mA < 10Inrush current (peak value) Ie A 3Terminal capacities
Solid or flexible conductor with ferrule mm2 1 x (0.5 – 2.5)2 x (0.5 – 1.5)
AWG 1 x (20 – 14)2 x (20 – 16)
NZM2-XR... NZM3-XR... NZM4-XR…
Remote operatorRated control voltage
AC Us V AC 110…440 110…440 110…440DC Us V DC 24…250 24…250 24…250
Operating rangeAC Us 0.85…1.1 0.85…1.1 0.85…1.1DC Us 0.85…1.1 0.85…1.1 0.85…1.1
Motor ratingAC 110 … 130 V AC VA 350 350 350
208 … 240 V AC VA 350 350 350380 … 440 V AC VA 350 350 350
DC 24 … 30 V DC W 250 250 250110 … 130 V DC W 250 250 250220 … 250 V DC W 250 250 250
Rated power of coilAC 110 … 130 V AC VA 270 270 270
208 … 240 V AC VA 270 270 270380 V … 440 V AC VA 270 270 270
DC 24 … 30 V DC W 210 210 210100 … 130 V DC W 210 210 210220 … 250 V DC W 210 210 210
Total make time ms 60 80 100Total opening delay ms 300 1000 3000Minimum signal duration
with switch on ms 30 30 30with switch off ms 150 250 500
Lifespan, mechanical Operations 20000 15000 10000Maximum operating frequency Ops./h 120 60 20Terminal capacities
Solid or flexible conductor with ferrule mm2 0.75 … 2.5 0.75 … 2.5 0.75 … 2.5AWG 18 … 14 18 … 14 18 … 14
NZM-XCM, NZM…-XR…
100Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
Technical dataResidual-current relay
PFR-003 PFR-03 PFR-5
ElectricalStandards IEC/EN 60947-2, IEC 755, IEC 1008, IEC 1009Sensitivity Pulse current sensitive, type ARated control voltage Us V AC 230 g20 % (50/60 Hz)Motor rating Pe W 3 3 3Rated fault currents IDn mA 0.03 0.3 0.03, 0.1, 0.3, 0.5, 1, 3, 5Delay time tv s 0.02 (non-delayed) 0.02 (non-delayed) 0.02, 0.1, 0.3, 0.5, 1, 3, 5Relay contacts 1 integrated changeover
contact1 integrated changeover contact
1 integrated changeover contact
Rated voltage of the relay contact V AC/DC 250/100 250/100 250/100Rated current of the relay contact A 6 6 6Fault current warning Hz – – 0.5 = 25% – 50% IDn
1 = 50% – 75% IDn 2 = 75% – 100% IDn
MechanicalStandard front dimension mm 45 45 45Device height mm 85 85 85Device width mm 45 45 45Mounting Snap fixing, top-hat rail DIN 46277, IEC/EN 60715Terminals top and bottom Box terminalsTerminal protection Finger/back-of-hand proof to BGV A2, VDE 106 part 100
Terminal capacities mm2 2 x 0.75 – 2.5 solid, 2 x 0.75 – 1.5 flexible/with ferrulesSealability – yes
PFR-…
101
http://catalog.moeller.net Moeller SK1230-1177GB
Notes
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
102
B
conn
ecto
rs
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Technical Data Technical DataResidual-current releases
2-4-XFI30 +NZM2-4-XFI +NZM2-4-XFIA30 +NZM2-4-XFIA
60947-2 IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2current sensitive ing to core-e principle
Pulse current sensitive according to core-balance principle
Sensitive to AC/DC (type B)
Sensitive to AC/DC (type B)
ndent of mains e
independent of mains voltage
0 V independent of mains voltage
0 V independent of mains voltage
50 V (dependent on mains power)
50 V (dependent on mains voltage)
e- and single-phase systems690 280…690 50…400 (3~) 50…400 (3~)
50/60 50/60 50/604 4-pole 4-pole
50 15…250 15…250 15…250
0.1…0.3…1…3 0.03 0.1…0.3…1
Hz 50/60 Hz with AC voltage: 0 – 100 kHzwith pulsed DC voltage: 50 Hz
with AC voltage: 0 – 100 kHzwith pulsed DC voltage: 50 Hz
= ICU = ICU = ICU
– – –
0 f 2000 f 2000 f 2000
96 96 96Bottom Bottom Bottom
uired As required Bottom Bottom
+70 –25…+70 –25…+70 –25…+70yes, setting buttons yes, setting buttons
ZM2 standard connection
ZM2 standard connection
103
NZM…-XFI…
Circ
uit-
brea
kers
, sw
itch
-dis Elec
StanSens
Min
SuitRate
RateNumRate
Rate
Dete
RatecapabreaFaul
MecLifescurr
MecStanMouMouSuppDegAmbSeal
Term
Moeller SK1230-1177GB Moeller SK1230-1177Ghttp://catalog.moeller.net http://catalog.moeller.net
Residual-current releases
NZM1(-4)-XFI30R NZM1(-4)-XFI300R NZM1(-4)-XFIR NZM1(-4)-XFI30U NZM1(-4)-XFI300U NZM1(-4)-XFIU +NZM
tricaldards IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2 IEC/ENitivity Pulse current sensitive according to core-balance principle Pulse current sensitive according to core-balance
principlePulse accordbalanc
. operating voltageor detection of fault currents type A/AC
80 V (dependent on mains voltage)
80 V (dependent on mains voltage)
80 V (dependent on mains voltage)
80 V (dependent on mains voltage)
80 V (dependent on mains voltage)
80 V (dependent on mains voltage)
indepevoltag
or detection of fault currents type B
ability for the application In three- and single-phase systems In single-phase In single-phase In thred operational voltage Ue V AC 200…415 (3~) 200…415 (3~) 200…415 (3~) 200…415 (3~) 200…415 (3~) 200…415 (3~) 280…
d frequency f Hz 50/60 50/60 50/60 50/60 50/60 50/60 50/60ber of poles 3/4 3/4 3/4 3/4 3/4 3/4 4d current range In A 15…125 15…125 15…125 15…100 15…100 15…100 15…2
d fault currents IDn A 0.03 0.3 0.03…0.1…0.3…0.5…1…3
0.03 0.3 0.03…0.1…0.3…0.5…1…3
0.03
ction range of the fault current 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60
d ultimate short-circuit making city and -rated ultimate short-circuit king capacity
IDm A = ICU = ICU = ICU = ICU = ICU = ICU = ICU
t current warning f 0.3 x IDn f 0.3 x IDn f 0.3 x IDn f 0.3 x IDn f 0.3 x IDn f 0.3 x IDn –
hanical shock resistance (IEC 60068-2-27) 20 (half-sinusoidal shock 20 ms) 20 (half-sinusoidal shock 20 ms)pan, mechanical (50 % with fault
ent)Operations 20000 20000 20000 20000 20000 20000 f 200
hanicaldard front dimension mm 45 45 45 45 45 45 96nting on the right side sidewise on the right Bottom Bottom Bottom Bottom Bottomnting position Vertical and 90° in all directions Vertical and 90° in all directionsly LZM1 from above LZM1 from above LZM1 from above LZM1 from above LZM1 from above LZM1 from above As req
ree of protection IP20 in the operating component area IP20 in the operating component areaient temperature °C –5…+40 –5…+40 –5…+40 –5…+40 –5…+40 –5…+40 –25…ability yes, setting buttons yes, setting buttons
inal capacityFlexible without ferrule mm2 such as LZM1 standard terminal such as LZM1 standard terminal with L
flexible with ferrules mm2 such as LZM1 standard terminal such as LZM1 standard terminal with L
NZM…-XFI…
104Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
DimensionsSize 1: basic units
Circuit-breaker3 poleLZME1LZMB1LZMC1LN1
a Blow out area, minimum clearance to other parts f 60 mm
Circuit-breaker4 poleLZME1-4LZMB1-4LZMC1-4LN1-4
a Blow out area, minimum clearance to other parts f 60 mm
CoversNZM1(-4)-XKSAScrew connectionNZM1(-4)-XKSIP2X protection against contact with a finger for shroudNZM1(-4)-XIPAScrew connection
a 3 poleb 4 pole
30
16
9.5 10
.2
112
126
f 6
0
145
6364 41
.545
21
5
R 10
4
68
NZM...1-...-(C)NA
84.5
30
90
44.6SW4 M4 x 50/10
a
162
57
F 90°
60 21
5
R104
68
84.5
44.630
120
112
126
9.5
145
1641
.545
SW4 M4 x 50
a
6364
89
f 6
0
N
SW 4
4
21
M6 x 14
59
34 2664
158
80
IP2X
16
90a
120b
296
LZM1, LN1
105
http://catalog.moeller.net Moeller SK1230-1177GB
DimensionsSize 1: accessories
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Tunnel terminalNZM1(-4)-XKA
a 3 poleb 4 pole
Connection on rearNZM1(4)-XKR
Control circuit terminal IP2X protection against contact with a fingerNZM1-XIPK, NZM-XSTK NZM1(-4)-XIPK
a 3 poleb 4 pole
90
20 20
3264
48 M6 x 14SW 4
a
120b
SW 5
128
126
63o 22
M430
30 30 30
30 15
128
63
126
15
30
o 22
M415
120
90
6418
1010 50
102
6
SW 4
o 6.6
M6 x 14
2 – 5
M6 x 20
90
108
89
a
120 b
90
64
13
46 10
76
91
a
120b
NZM1…-XK…, NZM1…XIPK, NZM-XSTK
106Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
DimensionsSize 1: accessories
Rotary driveRotary handle on circuit-breaker
a Up to 3 padlocks
Door coupling rotary handleNZM1-XTVD(V)(R)
a Up to 3 padlocks
45
45
54
80.3
90
120
F 4
3
36
a
NZM1-XDV NZM1-XDTVNZM1-XDVR
d bd = 4 – 8b f 34
2385
85
35
a
ZFS...-NZM7
R46
o 8
71
8
27.5
71
o 40
73.5
2 – 5
d b
d = 4 – 8b f 34
NZM1-XDV…, NZM1-XTVD…
107
http://catalog.moeller.net Moeller SK1230-1177GB
DimensionsSize 1: accessories
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Door coupling rotary handle with extension shaftNZM1-XTVD(V)(R)NZM1/2-XV4(6)
NZM1-XTVD(V)(R)-60 NZM1-XTVD(V)(R)-0
a Special tip
Minimum door coupling rotary handle clearance from door pivot point
8
27
73
210 – 400(400 – 600)
55
2 – 5
36NZM1/2-XV4(NZM1/2-XV6) 23g0.5
o 4
58
23g0.5
NZM1/2-XV...
167 – 210
16 – 60
23g0.5
a
128 – 167
41 – 75
NZM...1-... f 130
NZM1-XTVD…
108Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
DimensionsSize 1: accessories
Main switch assembly kit for side panel mountingNZM1-XS(R)-L NZM1-XS(R)-R
Main switch assembly kit for side panel mounting with mounting bracketNZM1-XS(R)M-L NZM1-XS(R)M-R
Undervoltage releaseShunt releaseEarly-make auxiliary contacts
a NZM1-XA(HIV)NZM1-XU(HIV)(20)NZM1-XHIVb NZM1-XA(HIV)(L)NZM1-XU(V)(HIV)(L)(20)NZM1-XHIV(L)c NZM1-XHIVR
Spacers Clip plateNZM1/2-XAB NZM1-XC35
9095-31073.5
122-5 129
90 95-310 73.5
12 2-5 129 15
41
51.5
12
73.5
2-5
57.2
163
195.5
131.4
NZM1/2-XZB
176
145
178.5
12
73.5
2-5
57.2
163
145
195.5
131.4
176
178.5
NZM1/2-XZB
23.2
38.6
39.3
39.3
2020
a c
b
17.5
103
35
30
90
126
9.5
145
157
1.5
8.4
NZM1-XS, NZM1…HIV
109
http://catalog.moeller.net Moeller SK1230-1177GB
DimensionsSize 1: accessories
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Insulating surroundsNZM1-XBR a Mounting aperture
Rotary handle on switch with door interlockNZM1-XDTV(R) a Mounting aperture
Rear drive Toggle lever locking deviceNZM1-XRAV(R) NZM-XKAVNZM1-4-XRAV(R)
a NZM1-XRAV(R)b NZM1-4-XRAV(R)
a Up to 3 padlocks
ZFS...-NZM7
64
117
1.5 – 5
9.5
148.5
132
11.5
19
23
82 53
1.5 – 5
9.5
32
11.5
19
9
14.4
13253
11
40
o 4
145
115117
148
a
b
32
a
45
46.3
1
F 80
d b
d = 4 – 8b f 34
NZM…-X…
110Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
DimensionsSize 1: accessories
Mechanical interlockNZM1-XMV + NZM1-XDV(R)
NZM1-XMV + NZM1-XTVD(V)(R)
NZM1-XMV + NZM1-XTVD(V)(R)-60 NZM1-XMV + NZM1-XTVD(V)(R)-0
a Special tip
90
120
45
40
40143
5
7
29.280
.3
45
22.5
51
3127
NZM1/2-XV4 (NZM1/2-XV6)
245 – 400 (400 – 600)
Part no. xNZM1/2-XV4 245 – 400NZM1/2-XV6 400 – 600
202 – 245
NZM1/2-XV...
163 – 202
a
NZM1-XMV, NZM1-XTV…
111
http://catalog.moeller.net Moeller SK1230-1177GB
DimensionsSize 1: accessories
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Insulated enclosuresNZM1-XCIK5-T... NZM1-XCI23-T...
NZM1-XCI43-T... NZM1-XCI43/2-T...
Component adapterNZM1-XAD160
200 160
231
280
8
187.5
250
175
246
8
250
80
375
495
8
60
60
175
246
60
225
296
250
80
375
495
8
60
200
65.590
NZM1-XCI…, NZM1-XAD
112Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
DimensionsSize 1: accessories
Residual-current relayPFR-003PFR-03PFR-5
Current transformerPFR-W-20…30 PFR-W-35...210
Fixing clipPFR-WC PFR-WMA
Residual-current releaseNZM1(-4)-XFI...R
NZM1(-4)-XFI...U
5 6 7 8
1 2 3 4
68
4436
7345 67 85 a
G
H
J I
F
B
33
46
C D
A
E
F
6.5
Part no. A B C D E FPFR-W-35 100 79 26 48.5 35 35PFR-W-70 130 110 32 66 70 52PFR-W-105 170 146 38 94 105 72PFR-W-140 220 196 48.5 123 140 97PFR-W-210 299 284 69 161 210 141
F G H I JPFR-W-20 32 60 24 46 21PFR-W-30 32 70 30 59 30
51.7
32.7
6.0
12.5
o B
o C
A1 A2
A
Part no. A ØB ØC A1 A2PFR-WMA-35 91 28 40 35 28PFR-WMA-70 105 62 75 35 35PFR-WMA-105 153 98 110 35 60PFR-WMA-140 153 133 145 35 60PFR-WMA-210 153 203 215 35 60
135 105
68
4542
.5
80.1
22014
5
220
145
120
145
90.15
145
23.1
4542
.5
6880.1
NZM1…-XFI…, PFR-…
113
http://catalog.moeller.net Moeller SK1230-1177GB
DimensionsSize 2: Basic units
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Circuit-breaker3 poleLZMB2LZMC2LN2
a Blow out area, minimum distance to other parts f 35 mmb Minimum distance to adjacent parts f 5 mm
Circuit-breaker4 poleLZMB2-4LZMC2-4LN2-4
a Blow out area, minimum distance to other parts f 35 mmb Minimum distance to adjacent parts f 5 mm
35 5
R 12
4
103
NZM...2-...(C)NA
149
25
24.5 3
95
105
35 78.7
135
19.5
145
8072
.5
184
11SW5
a
a b
b
f 3
5
f 3
5f 5f 5
M4 x 85/20
M8 x 22
100
NZM...2-...-(C)NA(> 480 V)NS2-...-NA
64
217
70 25 5
R 12
4
22xM8
85/20xM4
103
149
24.5 3
95
35 78.7
135
19.5
145
8072
.5
184
SW5
a
140
a
100
b
b
f 3
5f
35
f 5f 5
N
LZM2, LN2
114Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
DimensionsSize 2: accessories
Box terminal Tunnel terminal(+)NZM2(-4)-...-XKC(O)(U) NZM2(-4)-XKAIP2X protection against contact with a fingerNZM2(-4)-XIPK
a 3 poleb 4 pole
Covers Control circuit terminalNZM2(-4)-XKSA NZM2-XSTSCable lug NZM-XSTKNZM2-XKS185IP2X protection against contact with a finger for shroudNZM2(-4)-XIPA
a 3 poleb 4 pole
140
105 a
b
65
25
22.1F
20
111
80
M10
19
SW 5
30
80
SW 8
SW 5 M8 x 22
105
140
a
b
3755
25
87
80
81
175
337
SW 5 M8 x 22
105
140
a
b
140
105 a
b
100
105
NZM2…-XK…, NZM2…-XIP…, NZM2…-XST…
115
http://catalog.moeller.net Moeller SK1230-1177GB
DimensionsSize 2: accessories
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Connection on rear(+)NZM2(-4)-XKR(O)(U)
Rotary driveRotary handle on circuit-breaker
a Up to 3 padlocks
17.5
70
35 35 35
8018
6
o 2
0
10 48 10
M8 x 30
100
105
140
SW 4
M43 – 5
o 22
18
35
35 35
M4
o 30
72
145
80
160
72
145
80
160
o 8.6
140
52
104
95
R46
100
75 67F 59
a
NZM2-XDV NZM2-XDTVNZM2-XDVR NZM2-XDTV2 d b
d = 4 – 8b f 34
NZM2…-XKR…, NZM2-XDV…, NZM2-XDTV…
116Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
DimensionsSize 2: accessories
Door coupling rotary handleNZM2-XTVD(V)(R)...
a Up to 3 padlocks
Door coupling rotary handle with extension shaftNZM2-XTVD(V)(R)NZM1/2-XV4(6)
2385
85
35
a
ZFS...-NZM7
R46
o 8
71
8
27.5
71
o 40
73.5
2 – 5
d b
d = 4 – 8b f 34
8
27
73
55
2 – 5
36NZM1/2-XV4(NZM1/2-XV6)
o 4
5
17
23g0.5
245 – 400(400 – 600)
NZM2…-XTV…, NZM1/2-XV4(6)
117
http://catalog.moeller.net Moeller SK1230-1177GB
DimensionsSize 2: accessories
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Door coupling rotary handle with extension shaftNZM2-XTVD(V)(R)-60 NZM2-XTVD(V)(R)-0 Minimum door coupling rotary handle clearance from door
pivot point
a Special tip
Main switch assembly kit for side panel mountingNZM2-XS(R)-L
NZM2-XS(R)-R
23g0.5
NZM1/2-XV...
205 – 249
16 – 60
23g0.5
a
172 – 205
41 – 75
NZM...2-... f 130
10595-31073.5
0.52-5
170.5
105 95-310 73.5
0.5 2-5
170.5
15
41
51.5
NZM2-XTVD…, NZM2-XS…
118Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
DimensionsSize 2: accessories
Main switch assembly kit for side panel mounting with mounting bracketNZM2-XS(R)M-L
NZM2-XS(R)M-R
Rear driveNZM2-XRAV
a NZM2-XRAV(R)b NZM2-4-XRAV(R)
168
73.5
0.52-5 172.1
47.2
200.5
216
218.5
185
NZM1/2-XZB
168
73.5
0.5 2-5 172.1
47.2
200.5
216
218.5
185
NZM1/2-XZB
184
145133
168b
a
NZM2…-XS…, NZM2…-XRAV…
119
http://catalog.moeller.net Moeller SK1230-1177GB
DimensionsSize 2: accessories
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Spacers Clip plateNZM1/2-XAB NZM2-XC75
Insulating surroundsNZM2-XBR
a Mounting aperture
Rotary handle on switch with door interlockNZM2-XDTV(R)
a Mounting aperture
17.5
120.5
NZM1/2-XAB
35
130
169
10517
2
ZFS...-NZM7
127
132
1.5 – 5
9.5
10
17.523158.5
142
103
64
a
1.5 – 5
9.5
32
63
9
103
9
o 4
10.4
14210
17.5
NZM2-XDTV(R)a
NZM…-XAB, NZM2-XBR, NZM2-XDTV…
120Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
DimensionsSize 2: accessories
Toggle lever locking deviceNZM2/3-XKAV
a Up to 3 padlocks
F 88
a
92.5
50
1.3
a
d b
d = 4 – 8b f 34
Part no. aLZM2, LN2 52.5LZM3, LN3 70
NZM2…-XKAV
121
http://catalog.moeller.net Moeller SK1230-1177GB
DimensionsSize 2: accessories
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Mechanical interlockNZM2-XMV + NZM2-XD
NZM2-XMV + NZM2-XTVD(V)(R)
Mechanical interlockNZM2-XMV + NZM2-XTVD(V)(R)-60 NZM2-XMV + NZM2-XT(V)D(V)(R)-0
a Special tip
36
47.5
95
75
140
50
52.5
105 41
46180
6
9.6
73
5050
X
NZM1/2-XV4(6)
NZM1/2-XV...
240 – 284
a
207 – 240
NZM2-XMV, NZM2-XTVD…, NZM2-XD
122Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
DimensionsSize 2: accessories
Remote operatorNZM2-XR...
a Up to 3 padlocksb Remote operator hinged
35NZM2-XAVPR
7.2
21.5
105
250
105
140
52.5
105
135
F 13.7
235.5
322.8
a
b
d b
d = 4 – 8b f 34
NZM2-XR…
123
http://catalog.moeller.net Moeller SK1230-1177GB
DimensionsSize 2: accessories
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Insulated enclosuresNZM2-XCI43-T... NZM2-XCI45-T...
Component adapterNZM2-XAD250
Plug-in units+NZM2(-4)-XSV
250
80
375
187.
517
495
60
60
225
296
190
250
500
660
80
17
375 225
296
60
145
20
145
20
190
35
35 35
106
63
15.7
205
67.1
57.5
184
241
25
87.5 148.3
92.3
190.5
M4 x 93
M4 x 85
M8 x 22
NZM2(-4)-XSVS
NZM2(-4)-XSVE
SW5
35 78.7
35
237
396
109.
7
105
140
NZM2-XCI…, NZM2-XAD, NZM2…-XSV
124Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
DimensionsSize 2: accessories
Residual-current releaseNZM2(-4)-XFI...
Undervoltage releases, off-delayedUVU-NZMCapacitor unitNZM-XCM
70
35
29.5
140
6 103
108
149
252
265
291
22
29.5
22
22
29.5
22
87.7
85100
78 50 60M4 X 16
115
M5 X 16
NZM2(-4)-XFI, NZM-XDMI…, UVU-NZM
125
http://catalog.moeller.net Moeller SK1230-1177GB
DimensionsSize 3: Basic units
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Circuit-breaker3 poleLZMC3LZMN3LN3
a Blow-out space, minimum distance to other parts f 60 mmb Minimum distance to adjacent parts f 5 mm
Circuit-breaker4 poleLZMC3-4LZMN3-4LN3-4
a Blow-out space, minimum distance to other parts f 60 mmb Minimum distance to adjacent parts f 5 mm
31
M10 x 30
5
120.5NZM...3-...-4(C)NA
166
45
135
29.5
2895
69.745SW5
140
216
234
20.5
275
123.
511
7
11
a
a
f 6
0f
60
f 5f 5
b
b
M5 x 75
R 20
5
315.5
31 5
R 20
5
120.5
16629
.528
95
69.7
123.
411
7
90
135
216
234
20.5
275
M5 x 75SW5
M10 x 30
45
185
a
a b
b
f 6
0f
60
f 5f 5
N
LZM3, LN3
126Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
DimensionsSize 3: accessories
Box terminal Tunnel terminal(+)NZM3(-4)-XKC(O)(U) NZM3(-4)-XKA1(2)IP2X protection against contact with a fingerNZM3(-4)-XIPK
Covers Control circuit terminalNZM3(-4)-XKSA NZM3/4-XSTSCable lug NZM-XSTKNZM3-XKS185IP2X protection against contact with a finger NZM3(-4)-XIPA
a 3 poleb 4 pole
140
26.5
185
31
M12
75
F 18.7
12417
2
25
SW 5
2580
35
32 27
54
25
140
185
124
M10 x 30
SW 8
SW 8 SW 8
459
96
124
103140
185
253
SW 8 M10 x 30
140
185
148
149
a
b
NZM3…-XK, NZM3…-XIP…, NZM3-XST…
127
http://catalog.moeller.net Moeller SK1230-1177GB
DimensionsSize 3: accessories
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Connection width extensionNZM3(-4)-XKV70TerminalsNZM3(-4)-XK22X21NZM3(-4)-XK300
a NZM3(-4)-XK22X21b NZM3(-4)-XK300
Connection on rear(+)NZM3(-4)-XKR(O)(U)
o 1343
200
433
401
401
295
45 45
140
188
255
24 36.561
6
433
295
123.
5
49
5.75
11.528
70
33
70
45 26.5
20 1850 50 6
M10 x 30
a
b
6
37 24
70 70 70
45 45 45
185
258
325
o 13
o 6.4
123.
522
10
o 2
8
571111
112
3 – 5
M10 x 35
o 11140
185
M522
45
45 45
o 30
117
234
247
124
M590
45 45 45
o 30SW 8
117
234
247
124
NZM3…XK…
128Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
DimensionsSize 3: accessories
Phase isolatorsNZM3-4-XKP
Spacers Insulating surroundsNZM3-XAB NZM3-XBR a Mounting aperture
100
161.
6
45
90
210
255
3.5
200
599
616
138
17.5
NZM3-XAB
ZFS...-NZM7
162
132
1.5 – 5
9.5
10
17.5
23193.5
17711
0
64
a
NZM3…-XKP, NZM3-XAB, NZM3-XBR
129
http://catalog.moeller.net Moeller SK1230-1177GB
DimensionsSize 3: accessories
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Rotary driveRotary handle on circuit-breaker
a Up to 3 padlocks
Door coupling rotary handleNZM3-XTVD(V)(R)...
a Up to 3 padlocks
F82
.6
95
R87
105
124
140
185
a
NZM3-XDVNZM3-XDVR d b
d = 4 – 8b f 34
35
o 8
71
8
27.5
71
o 40
95
2 – 5
a
2385
85
ZFS...-NZM7
R87
d b
d = 4 – 8b f 34
NZM3-XDV…, NZM3-XTVD…
130Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
DimensionsSize 3: accessories
Door coupling rotary handle with extension shaftNZM3-XTVD(V)(R)NZM3/4-XV4(6)
NZM3-XTVD(V)(R)-60 NZM3-XTVD(V)(R)-0
a Special tip
Minimum door coupling rotary handle clearance from door pivot point
2 – 5
8
27
95
X
59
36 23g0.5NZM3/4-XV4(6)
32.5 o
60
29
Part no. xNZM3/4-XV4 270 – 400NZM3/4-XV6 400 – 600
23g0.5
NZM3/4-XV...
18 – 60
235 – 27723g0.5
a
199.5 – 235
42 – 77.5
NZM...3-... f 180
NZM3-XTVD…
131
http://catalog.moeller.net Moeller SK1230-1177GB
DimensionsSize 3: accessories
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Main switch assembly kit for side panel mountingNZM3-XS(R)-L
NZM3-XS(R)-R
95
2 – 5
2 – 5
195
105
86 – 433
86 – 433 2 – 5
2 – 5
195
39.110
524.1
95
NZM3-XS…
132Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
DimensionsSize 3: accessories
Mechanical interlockNZM3-XMV + NZM3-XDV(R)
NZM3-XMV + NZM3-XTVD(V)(R)
NZM3-XMV + NZM3-XTVD(V)(R)-60 NZM3-XMV + NZM3-XTVD(V)(R)-0
a Special tip
47.5
95
105
99
140
185
96.5
40
69196
5
20
34.5
73.2
5050
305 – 400(400 – 600)
NZM3/4-XV4(NZM3/4-XV6)
NZM3/4-XV...
270 – 312
a
235 – 270
NZM3-XMV, NZM3-XTVD…, NZM3-XDV
133
http://catalog.moeller.net Moeller SK1230-1177GB
DimensionsSize 3: accessories
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Insulated enclosures Component adapterNZM3-XCI48-TD NZM3-XAD550
190
29 60
275
369375
375
750
910
32.5
80
270
38
229
45 45
140 63
NZM3-XCI…, NZM3-XAD…
134Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
DimensionsSize 3: accessories
Remote operatorNZM3-XR...
a Up to 3 padlocks
Withdrawable unit+NZM3(-4)-XAV
a 3-pole d withdrawnb 4-pole e test
f connectedc Up to 3 padlocks
60.5
NZM3-XAVPR
143.5
10
260.5
358
F 13
5.5
140
9528
291.
5
140 70
140
185
a
b
17
d b
d = 4 – 8b f 34
45
96
200 a
227 a
250 b
272 b
200
2525 15
1.8
SW 8
c
170.
817
5.8
R 130
341.
6
313.
5
171
309d
299e
271f
225.5 5
91
130
31 M10 x 30
400
520
d b
d = 4 – 8b f 34
NZM3-X…
135
http://catalog.moeller.net Moeller SK1230-1177GB
DimensionsSize 4: Basic units
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Circuit-breaker3 poleLZMN4LN4
a Blow out area, minimum distance to other parts f 100 mmb Minimum distance to adjacent parts f 15 mm
M5 x 110
70
210
70
204
207
138
33 8
4421 11
711
9
F
100 100
171.
587
.5
401
313
180
108
a
1515
2545
f 1
00
f 15f 15
b
b
o 10.5
LZM4, LN4
136Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
DimensionsSize 4: accessories
Circuit-breaker4 poleLZMN4-4LN4
a Blow out area, minimum distance to other parts f 100 mmb Minimum distance to adjacent parts f 15 mm
Covers Tunnel terminalNZM4(-4)-XKSA NZM4-4-XKA
a 3 poleb 4 polec Clearance from conductive parts f 100 mm
M5 x 110
70
280
140
207
138
33 8
4421 117
119
10017
1.5
87.540
1
31318
010
8a
25100
1515
45
f 1
00
f 15f 15
b
b
N
o 10.5
c
210 a
280 b
531
f 1
00
108.
5
128
210
280
53
25
f 1
00
a
b
c
30.5
171.
573
.5
32
60
M10 x 604 x SW8
2 x SW16
LZM4, LN4, LZM4…-XK
137
http://catalog.moeller.net Moeller SK1230-1177GB
DimensionsSize 4: accessories
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Screw connectionModule plate Flat cable terminalSingle hole NZM4(-4)-XKBNZM4(-4)-XKM12-holeNZM4(-4)-XKM2
a 3 poleb 4 polec Clearance from conductive parts f 100 mm
Module plate2 holes, verticalNZM4(-4)-XKM2S...
Part no. a bNZM4(-4)-XKM1 36 47NZM4(-4)-XKM2 32 40NZM4(-4)-XKB – 47
M10 × 50
210
280
504043
25
o 11
a
a
b
43
171.
5b
SW5NZM4-XKM2
NZM4-XKM1
SW16
NZM4(-4)-XKB NZM4(-4)-XKB
M 10 x 50
SW16
50
280
50
210
171.
5
x70
32
16
70 7070 70
33
o 13
o 13
486
518
32
1648
6
518
Part no. xNZM4(-4)-XKM2S-1250 12NZM4(-4)-XKM2S-1600 20
NZM4…-XKM
138Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
DimensionsSize 4: accessories
Connection width extensionNZM4-XKV95 NZM4-XKV110
NZM4-4-XKV95 NZM4-4-XKV120
95 95
50 77 18
210 28.5
543
573
48
15
171.
5
15 15
107.5 107.5
50 77 30.5
210
267 292
4154
3
573
30 30
M10 x 50
o 11 o 11
SW16
95 47.547.5 95
5050
42 42
15
427730
18 1818
30 18
80
122 122 122
543
573
446362
280 8341
595
625
15
48
15
M10 x 50
171.
5
30
o 11o 11
NZM4-XKV…
139
http://catalog.moeller.net Moeller SK1230-1177GB
DimensionsSize 4: accessories
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Connection on rearNZM4(-4)-XKR Fitting on mounting plate
Rear connection possible also with rotation by 90°.a 3 poleb 4 pole
Phase isolatorsNZM4-4-XKP
172
15
30
16
3-5
9.5
M10 x 30
208
104
M5
35
70
180
411
87.5
7220
5.5
45 25
o 11
210
280
SW16
a
b
278
139
M5
70
140
180
88
206
72
411
114
190
70
140
3.5
NZM4(-4)-XKP, NZM4(-4)-XKR
140Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
DimensionsSize 4: accessories
Rotary handle on circuit-breakerNZM4-XDV(R)
a Up to 3 padlocks
Door coupling rotary handleNZM4-XTVD(V)(R)...
a Up to 3 padlocks
210
280
a
58.5
162
R 137
204
117
73.5
60.5
221.
5
57 69
5
33
f 8
9.5
d b
d = 4 – 8b f 34
2385
85
ZFS...-NZM7
R137
a
70
18
o 8
71
71
o 40
d b
d = 4 – 8b f 34
NZM4-XDV…, NZM4-XTVD…
141
http://catalog.moeller.net Moeller SK1230-1177GB
DimensionsSize 4: accessories
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Door coupling rotary handle with extension shaftNZM4-XTVD(V)(R)NZM3/4-XV4(6)
NZM4-XTVD(V)(R)-60 NZM4-XTVD(V)(R)-0
a Special tipMinimum door coupling rotary handle clearance from door pivot point
Main switch mounting kits for side-wall mountingNZM4-XS(R)-LNZM4-XS(R)-R
57
5
21
o 6
0
2 – 5
8
27
95
300 – 400(400 – 600)
59
36 23g0.5
NZM3/4-XV4(NZM3/4-XV6)
23g0.5
NZM3/4-XV...
18 – 60
270 – 312 23g0.5
42 – 77.5
234.5– 270
a
NZM...4-... f 180
86 – 433
229
221.
5
100
24.1
34.1
2 – 5
NZM4-XTVD…, NZM4…-XV, NZM4-XS…
142Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
DimensionsSize 4: accessories
Insulating surroundsNZM4-XBR
a Mounting aperture
Mechanical interlockNZM4-XMV + NZM4-XDV(R)
NZM4-XMV + NZM4-XTVD(V)(R) NZM4-XMV + NZM4-XTVD(V)(R)-60
ZFS...-NZM7
231
154
23
262.5
246
125
64
1.5 – 5
9.5
10
17.5
a
47.5
95
221.
5
34.5
162
210
280
40
69230
5
20
73.2
5050
335 – 400(400 – 600)
NZM3/4-XV4(NZM3/4-XV6)NZM3/4-XV...
305 – 347
NZM4-XBR, NZM4-XMV, NZM4-X…
143
http://catalog.moeller.net Moeller SK1230-1177GB
DimensionsSize 4: accessories
Circ
uit-
brea
kers
, sw
itch
-dis
conn
ecto
rs
Mechanical interlockNZM4-XMV + NZM4-XTVD(V)(R)-0
a Special tip
Remote operatorNZM4-XR…
a Up to 3 padlocksRemote operator folded
a
270 – 305
204
b
84.4
a
189.5
208
210
55.6
189.5
208
210 280
435.2
313.4
175.4
12.5
F 13.4
45.5
19.4
117
189
306.
4
454.
4
d b
d = 4 – 8b f 34
NZM4-XMV, NZM4-X…
144Ci
rcui
t-br
eake
rs, s
wit
ch-d
isco
nnec
tors
Moeller SK1230-1177GB http://catalog.moeller.net
DimensionsSize 4: accessories
Withdrawable unit+NZM4-4-XAV
a 3-poleb 4-pole
d Disconnectede Testf Connected
c Up to 3 padlocks
70 131
275
297
350
367
560
33
680
353.5 d
341 e
313 f
243 8
509
451
217
274.
5
R 130
2525
2525
300
a
b
c
M6 x 12
d b
d = 4 – 8b f 34
NZM4…-XAV