short instructions bus connection actuator controls

16
Certificate Registration No. 12 100/104 4269 Actuator controls Short instructions bus connection AUMATIC AC 01.1 ACExC 01.1 Profibus DP

Upload: others

Post on 29-Oct-2021

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Short instructions bus connection Actuator controls

Certificate Registration No.12 100/104 4269

Actuator controls

Short instructions bus connection

AUMATICAC 01.1

ACExC 01.1Profibus DP

Page 2: Short instructions bus connection Actuator controls

2

Actuator controls AUMATIC AC 01.1 / ACExC 01.1Profibus DP Short instructions

Scope of these instructions: These instructions are valid for multi-turn actuators of the type rangesSA(R) 07.1 – SA(R) 16.1 and SA(R)ExC 07.1 – SA(R)ExC 16.1as well as for part-turn actuators of the type rangesSG 05.1 – SG 12.1 and SGExC 05.1 – SGExC 12.1with the controls AUMATIC AC 01.1 or ACExC 01.1with Profibus DP interface.

Table of contents Page

1. Safety instructions 31.1 Range of application 31.2 Commissioning (electrical connection) 31.3 Maintenance 31.4 Warnings and notes 3

2. Short description 3

3. Electrical connection 43.1 Power supply (standard) 43.2 Remote position transmitter 43.3 AUMATIC on wall bracket 43.4 Fitting of the connection housing 53.5 Test run 53.5.1 Bus connection (standard) 53.5.2 Mains and bus connection for explosion-proof version 73.5.3 Bus cables 93.6 Setting the Profibus DP address via local controls 10

4. Redundant bus connection with component redundancy (option) 124.1 Settings for the redundant Profibus interface 2 (component redundancy) 12

5. Description Profibus DP interface 135.1 Status indications in the display 135.2 Assignment of the customer inputs of the Profibus DP interface (option) 145.3 Assignment of the Profibus DP connection 14

6. Appendix A Connection of the screen for AUMATIC ACExC 01.1 15

Addresses of AUMA offices and representatives 16

Page 3: Short instructions bus connection Actuator controls

1. Safety instructions1.1 Range of application AUMA actuators are designed for the operation of industrial valves, e.g.

globe valves, gate valves, butterfly valves and ball valves. For other applica-tions, please consult us. The manufacturer is not liable for any possibledamage resulting from use in other than the designated applications. Suchrisk lies entirely with the user.Observance of these operation instructions is considered as part of thecontrols’/ actuator’s designated use.

1.2 Commissioning(electrical connection)

During electrical operation certain parts inevitably carry lethal voltages.Work on the electrical system or equipment must only be carried out by askilled electrician himself or by specially instructed personnel under thecontrol and supervision of such an electrician and in accordance with theapplicable electrical engineering rules.

1.3 Maintenance The maintenance instructions must be strictly observed, otherwise a safeoperation of the multi-turn actuator/ controls is no longer guaranteed.

1.4 Warnings and notes Non-observance of the warnings and notes may lead to serious injuries ordamage. Qualified personnel must be thoroughly familiar with all warningsand notes in these operation instructions.Correct transport, proper storage, mounting and installation, as well ascareful commissioning are essential to ensure a trouble-free and safeoperation.The following references draw special attention to safety-relevant proce-dures in these operation instructions. Each is marked by the appropriatepictograph.

This pictograph means: Note!“Note” marks activities or procedures which have major influence on thecorrect operation. Non-observance of these notes may lead to consequen-tial damage.

This pictograph means: Electrostatically endangered parts!The printed circuit boards are equipped with parts which may be damagedor destroyed by electrostatic discharges. If the boards need to be touchedduring setting, measurement or for exchange, it must be assured that imme-diately before a discharge through contact with an earthed metallic surface(e.g. the housing) has taken place.

This pictograph means: Warning!“Warning” marks activities or procedures which, if not carried out correctly,can affect the safety of persons or material.

2. Short description AUMA actuators have a modular design. Motor and gearing are mounted ina common housing.The actuators are driven by an electric motor and controlled with the elec-tronic controls AUMATIC. The electronic controls are included in the scopeof delivery.

3

Actuator controls AUMATIC AC 01.1 / ACExC 01.1Short instructions Profibus DP

Page 4: Short instructions bus connection Actuator controls

3. Electrical connection .Work on the electrical system or equipment must only becarried out by a skilled electrician himself or by speciallyinstructed personnel under the control and supervision ofsuch an electrician and in accordance with the applicableelectrical engineering rules.. Installation regulations for Profibus DP must be observedfor the wiring.

3.1 Power supply (standard) For explosion-proof version (type designation: ACExC) see page 7..Check whether type of current, supply voltage and frequency correspondto motor data (refer to name plate at motor)..Loosen bolts (50.01) (figure B-1) and remove connection housing..Loosen screws (51.01) and remove socket carrier (51.0) from connectionhousing (50.0).. Insert cable glands suitable for connecting cables.(The enclosure protection stated on the name plate is only ensured if suit-able cable glands are used)..Seal cable entries which are not used with suitable plugs..Connect cables according to order-related wiring diagram.The wiring diagram applicable to the actuator is attached to the handwheelin a weather-proof bag, together with the operation instructions. In casethe wiring diagram is not available, it can be obtained from AUMA (statecommission no. refer to name plate) or downloaded directly from theInternet (www.auma.com).

3.2 Remote position transmitter For the connection of remote position transmitters (potentiometer, RWG)screened cables must be used.

3.3 AUMATIC on wall bracket The AUMATIC can also be mounted separately from the actuator on a wallbracket..For the connection of actuator and AUMATIC on wall bracket, use suitable

flexible and screened connecting cables.(Preconfectioned cables can be obtained from AUMA on request).The permissible cable length between actuator and AUMATIC amounts tomax. 100 m..Versions with potentiometer in the actuator are not suitable. Instead of thepotentiometer, a RWG has to be used in the actuator..Connect the wires in correct phase sequence.Check direction of rotation before switching on.

Actuator controls AUMATIC AC 01.1 / ACExC 01.1Profibus DP Short instructions

4

Figure B-1: Mains connection

50.0

50.01

51.0

51.01

Mainscable

Technical data Motor power connections1) Protective earth Control pinsNo. of contacts max. 6 (3 are used) 1 (leading contact) 50 pins / socketsMarking U1, V1, W1, U2, V2, W2 according to VDE 1 to 50Voltage max. 750 V – 250 VCurrent max. 25 A – 16 AType of customer connection Screws Screw for ring lug ScrewsCross section max. 6 mm2 6 mm2 2.5 mm2

Material: Pin / socket carrier Polyamide Polyamide PolyamideContacts Brass (Ms) Brass (Ms) Brass, tin plated or gold plated (option)

1) Suitable for copper wires. For aluminium wires contact AUMA.

Table 1: Technical data AUMA plug/ socket connector for bus connection

Figure B-2: AUMATIC on wall bracket

Connecting cable to the actuator

Page 5: Short instructions bus connection Actuator controls

3.4 Fitting of the connectionhousing

After mains connection:. Insert the socket carrier (51.0) into the plug cover (50.0) and fasten it withscrews (51.01)..Clean sealing faces at the connection housing and the actuator housing..Check whether O-ring is in good condition..Apply a thin film of non-acidic grease (e.g. Vaseline) to the sealing faces..Replace connection housing (50.0) and fasten bolts (50.01) evenly crosswise..Fasten cable glands with the specified torque to ensure the required enclo-sure protection.

3.5 Test run Perform test run. Refer to the operation instructions for the actuator(multi-turn actuator SA(R) … / part-turn actuator SG ...).

Check limit and torque switching:Check limit and torque switching, electronic position transmitter RWG orpotentiometer (option) and, where necessary, re-set.The settings are described in the operation instructions to the actuator(multi-turn actuator SA(R) … part-turn actuator SG … ).

For actuators with feedback signal (RWG, potentiometer), a reference oper-ation has to be performed after the setting has been changed.

Perform reference operation:.Run actuator electrically (via the push-buttons OPEN and CLOSE) of thelocal controls once to the end position OPEN and once to the end positionCLOSED.. If no reference operation is performed after changing the limit switching,the feedback signal via the bus is not correct. The bus signals the missingreference operation as warning.

3.5.1 Bus connection (standard) For explosion-proof version (type designation: ACExC) see page 7.For version with FO (fibre optics) refer to separate operation instructions“AUMATIC AC 01.1 FO connection”.

Disconnect power before removing the plug cover.

.Loosen and remove plug cover (figure B-3). The connection board (figuresC-1, C-2 and C5) is located behind the plug cover.. Insert cable glands suitable for bus cables.(The enclosure protection stated on the name plate is only ensured if suit-able cable glands are used)..Seal cable entries which are not used with suitable plugs..Connect bus cable. Refer to figures C-1 to C-6.

The termination resistors for channel 1 and channel 2 are switched in viaswitches (S1) and (S2). Both switches are supplied in position ‘OFF’. Onlyconnect the termination resistors (position ’ON’) if the actuator is the finalstation in the Profibus segment.

As soon as the termination resistors are switched on, theconnection to the next Profibus DP device is automaticallyinterrupted to avoid multiple terminations.

Actuator controls AUMATIC AC 01.1 / ACExC 01.1Short instructions Profibus DP

5

Figure B-3: AUMATIC busconnection

Plug cover Entries for buscables

S1ON Bus termination channel 1 ONOFF Bus termination channel 1 OFF

S2ON Bus termination channel 2 ON (option)OFF Bus termination channel 2 OFF (option)

S31SPC one Profibus board2SPC two Profibus boards (component redundancy, option)

Table 2: Switch positions from S1 – S3

Page 6: Short instructions bus connection Actuator controls

1) The connection board for overvoltage is not suitable forcomponent redundancy (page 12).

Actuator controls AUMATIC AC 01.1 / ACExC 01.1Profibus DP Short instructions

6

Figure C-2: Connection board (for overvoltage protection)1)

S1Bus termination

Channel 1

S2Bus terminationChannel 2

Figure C-1: Connection board (standard)S1

Bus terminationChannel 1

X1

1 2 3 4

Figure C-4: Connection for overvoltage protection1)

from previous / to nextProfibus DP device

Channel 1

X1 X2

Figure C-3: Connection (standard)

from previous / to nextProfibus DP device

Channel 1

Figure C-5: Connection board (for component redundancy)

S2Bus terminationChannel 2

S3S1Bus termination

Channel 1

Profibuscable

AUMAlabelling atconnection

SUB-D 9 connector(for other

Profibus devices)Colour

A N/A 8 greenB P/B 3 red

Table 3: Assignment of the Profibus cable

X1 X2 X3 X4

Figure C-6: Connection for component redundancy (option)

from previous / to nextProfibus DP device

Channel 1

from previous / to nextProfibus DP device

Channel 2

Page 7: Short instructions bus connection Actuator controls

3.5.2 Mains and bus connection for explosion-proof version

For version with FO (fibre optics) refer to separate operation instructions“AUMATIC ACExC 01.1 FO connection”.

When working in potentially explosive areas, observe theEuropean Standards EN 60079-14 “Electrical Installations inHazardous Areas” and EN 60079-17 “Inspection and Mainte-nance of Electrical Installations in Hazardous Areas”.Work on the electrical system or equipment must only becarried out by a skilled electrician himself or by speciallyinstructed personnel under the control and supervision ofsuch an electrician and in accordance with the applicableelectrical engineering rules.

For the Ex-plug/socket connector (figure D-1), the electrical mains connec-tion is made after removing the plug cover (50.0) at the EEx e terminals ofthe terminal board (51.0). The flameproof compartment (type of protectionEEx d) remains hereby closed..Check whether type of current, supply voltage and frequency correspond

to motor data (refer to name plate at motor)..Loosen bolts (50.01) (figure D-1) and remove plug cover.. Insert cable glands with “EEx e” approval and of size suit-able for connecting cables. For the recommended cableglands refer to appendix A, page 15.(The enclosure protection stated on the name plate is onlyensured if suitable cable glands are used)..Seal cable entries which are not used with suitable plugs..No more than max. 2 wires with the same cross sectionmay be connected to one terminal.

.Remove cable sheathing in a length of 120 – 140 mm.Strip wires: Controls max. 8 mm, motor max. 12 mm.For stranded wires use end-sleeves according to DIN 46228..Connect bus cable. Refer to figures (D-4 or D-5).The termination resistor for channel 1 is connected through linking theterminals 31 – 33 and 32 – 34 (standard).The termination resistor for channel 2 is connected through linking theterminals 35 – 37 and 36 – 38 (component redundancy only)..Only connect the termination resistors if the actuator is the final station inthe Profibus segment..Connect screen extensively to the cable glands. For the recommendedcable glands refer to appendix A, page 15.

If the actuator must be taken from the valve, e.g. for service purposes, it canbe separated from the mains without having to remove the wiring (figureD-2). For that the screws (51.02) are removed and the plug/ socketconnector is pulled off. Plug cover (50.0) and terminal board (51.0) remaintogether.

Flameproof enclosure! Before opening, ensure that there isno explosive gas and no voltage.

A special parking frame (figure D-3) for protection against touching the barecontacts and against environmental influences is available.

Actuator controls AUMATIC AC 01.1 / ACExC 01.1Short instructions Profibus DP

7

Figure D-1: Connection

50.0

50.01

51.0

Figure D-2: Disconnection fromthe mains

50.0

51.0

51.02

Figure D-3: Parking frameaccessory)

Parking frame

Page 8: Short instructions bus connection Actuator controls

Actuator controls AUMATIC AC 01.1 / ACExC 01.1Profibus DP Short instructions

8

35

35 38

36

36 37

B

B

A

A

B

A

Figure D-5: Bus connection for channel 2(component redundancy only)

from the previousProfibus DP devicechannel 2

to the nextProfibus DP devicechannel 2

Another bus station follows the actuator

Actuator is the final bus station

31

31 34

32

32 33

B

B

A

A

B

A

Figure D-4: Bus connection for channel 1(Standard)

Another bus station follows the actuator

Actuator is the final bus station

from the previousProfibus DP devicechannel 1

To the nextProfibus DP devicechannel 1

Technical data Motor power connections1) Protective earth Control pinsNo. of contacts max. 3 1 (leading contact) 38 pins / socketsMarking U1, V1, W1 according to VDE 1 to 24, 31 to 50Voltage max. 550 V – 250 VCurrent max. 25 A – 10 AType of customer connection Screws Screws ScrewsCross section max. 6 mm2 6 mm2 1.5 mm2

Material: Pin / socket carrier Araldite / Polyamide Araldite / Polyamide Araldite / PolyamideContacts Brass (Ms) Brass (Ms) Brass (Ms) tin-plated1) Suitable for copper wires. For aluminium wires contact AUMA.

Table 4: Technical data Ex-plug/ socket connector with terminal board for explosion-proof actuators

Page 9: Short instructions bus connection Actuator controls

3.5.3 Bus cables Only cables according to standard DIN 19245 or EN 50170-2, cable type A,may be used for Profibus DP wiring.

A maximum of up to 32 Profibus devices may be connected in one segment.If more devices are to be connected to one Profibus network, severalsegments must be connected with repeaters.The bus cable must be laid at a distance of at least 20 cm from other cables.It should be laid in a separate, conductive and earthed cable trunking.It must be ensured that there are no potential differences between the indi-vidual devices on the Profibus (Perform a potential compensation).

Cable specification cable type A for Profibus DP

Impedance: 135 to 165 Ohm, at a frequencyof 3 to 20 MHz.

Cable capacity: < 30 pF per metreCable diameter > 0.64mmCross section: > 0.34 mm², corresponds to AWG 22Loop resistance: 110 Ohm per kmScreening: CU shielding braid or shielding braid and

shielding foil

Actuator controls AUMATIC AC 01.1 / ACExC 01.1Short instructions Profibus DP

9

Transmission speedin kBit/s ≤ 93,75 187.5 500 1500

Maximum segment lengthin m 1200 1000 400 200

Table 5

2-wire cable

Controls (master)

Figure E: Example: Profibus with one segment

Bus terminationswitched on

Bus terminationswitched on

Connectionboard

Profibus DP board

AUMATICProfibus DP

Page 10: Short instructions bus connection Actuator controls

3.6 Setting the Profibus DP address via local controlsThis clause only describes the setting of the actuator address (slaveaddress). For further detailed instructions on the indication, operation andsetting of the AUMATIC refer to the operation instructions of the actuator(multi-turn actuator SA(R) … / part-turn actuator SG …with AUMATIC AC ...).

Factory setting:

Slave address: 2.Set selector switch at the AUMATIC to position OFF (0), figure F-1..Switch on supply voltage..Select menu indication M0:.Press push-button in one of the status indications(S0, S1, S2, S3 or S4) longer than 2 seconds:

> 2 Sec..Select SETTINGS with push-button :

.Confirm the selection SETTINGS with :

.Select PROFIBUS DP1 by pushing several times:

.Confirm the selection PROFIBUS DP1 with .

.Select EDIT with push-button :

Confirm the selection EDIT with :

Actuator controls AUMATIC AC 01.1 / ACExC 01.1Profibus DP Short instructions

10

C

FigureF-1 M0MAIN MENU

LANGUAGE /CONTRAST

SETTINGS

OPERATIONAL DATA

FigureF-2 M1MAIN MENU

LANGUAGE / CONTRAST

SETTINGS

OPERATIONAL DATA

FigureF-3 M10SETTINGS

SET LIMIT SWITCHES

SEATING MODE

TORQUE

FigureF-4 M1BSETTINGS

POSITIONER

SPEED SETTING

PROFIBUS DP1

FigureF-5 M1B0PROFIBUS DP1

VIEW

EDIT

FigureF-6 M1B1PROFIBUS Dp1

VIEW

EDIT

Page 11: Short instructions bus connection Actuator controls

.With the push-buttons and the value of the selected position can bechanged..To accept the input and move to the next digit, press push-button ,proceed until all password digits are entered. When accepting the lastdigit, the entered password is checked (default password: 0000), if it isvalid, the following indication appears:

.Confirm SLAVE ADDRESS with push-button .

.Change to the edit mode with :

Now you can use the push-buttons and to set the slave address from0 to 125..Pressing the push-button accepts the input..To return to the previous indication without accepting the entered value

press the push-button .

Remarks:The other parameters CABLE REDUNDANCY and CHANNEL CHECK TIMEare reserved for special applications and the factory settings should not bechanged. (CABLE REDUNDANCY = OFF;CHANNEL CHECK TIME = 5.0 S)

For redundant applications an AUMATIC with component redundancy (2ndProfibus DP interface in the AUMATIC, see page 12) is to be used.

Actuator controls AUMATIC AC 01.1 / ACExC 01.1Short instructions Profibus DP

11

M1B10EDITSLAVEADDRESS

CABLE REDUNDANCY

CHANNEL CHECK TIME

FigureF-8

M1B10EDITSLAVE ADDRESS

2

:EDIT C:ESC

FigureF-9

M1B10EDITSLAVE ADDRESS

2

:EDIT :OK C:ESC

FigureF-10

C

ENTER PASSWORD0 * * *

:EDIT :OK C:ESC

FigureF-7

Page 12: Short instructions bus connection Actuator controls

4. Redundant bus connection with component redundancy (option)

The AUMATIC can be equipped with a second (redundant) Profibus inter-face. In this version, communication to the actuator can be establishedsimultaneously through both Profibus interfaces. If one of the Profibuscomponents fails, e. g. through cable break, those operation commands,which are sent via the other Profibus component, are executed.If there is a communication to the master available via both Profibus inter-faces, the operation commands of the interface which first established acommunication to the master will be executed.For the bus connection refer to page 5 ff.

Both Profibus DP sub-assemblies have to be programmed inthe same way by the master(identical setting in the GSD file).

4.1 Settings for the redundant Profibus interface 2 (component redundancy)

The redundant Profibus DP component 2 is set in the same way as thesetting for the Profibus component 1 (see page 10 ff and via the followingmenus:

Menu structureMAIN MENU (M)

SETTINGS (M1)PROFIBUS DP2 (M1E)

SLAVE ADDRESS (M1EX0)

In case of component redundancy, the parameter CABLEREDUNDANCY of both Profibus components must be set toOFF (this corresponds to the factory setting).

Actuator controls AUMATIC AC 01.1 / ACExC 01.1Profibus DP Short instructions

12

Page 13: Short instructions bus connection Actuator controls

5. Description Profibus DP interface

LED ’SYSTEM OK’(V1)(green)

This LED shows the correct voltage supply to the Profibus DP board.

Is continuously illuminated: Voltage connected to Profibus DP interface.Is blinking: Microcontroller defective.Is not illuminated: No voltage at the DP interface.

LED ’DATA EX’ (V2)(green)

When LED is illuminated, the Profibus DP interface has entered ‘DataExchange’ state. Only in this state can the actuator be controlled by theProfibus DP master and the state of actuator be read.

LED ‘CAN STATE’ (V3)(red)

Is illuminated or blinking: Communication to logic is faultyIs not illuminated: Communication with logic is o.k.

LED ’STATE’ (V4)(green)

Is illuminated or not illuminated: Profibus DP interface is not readyis blinking: Program on the Profibus DP interface is

being executed.

Regular blinking of the LED during operation indicates correct operation ofthe Profibus DP interface.

5.1 Status indications in thedisplay

The status indications (Group S) in the display show the current operationmode as well as faults and warnings. For detailed notes regarding theindication and operation see the appropriate operation instructions of theactuator.

Actuator controls AUMATIC AC 01.1 / ACExC 01.1Short instructions Profibus DP

13

C

Figure P: Profibus DP interface

X2

X4

V16V19V22V25

S1

SYSTEM OK (V1)DATA EX (V2)

CAN STATE (V3)STATE (V4)

S1-1

Only one Profibus DP interfaceavailable

OFF

Two Profibus DP interfaces avail-able

1st Profibus DP interface: OFF

2nd Profibus DP interface: ONS1-2 Spare OFF

Table 6: DIP switch S1: Configuration of the Profibus DP board

Page 14: Short instructions bus connection Actuator controls

5.2 Assignment of the customer inputs of the Profibus DP interface (option)

X4 This plug provides pins for 4 digital customer inputs and 2 analoguecustomer inputs.

These signals are freely available inputs, which the microcontroller transmitsinto the process representation input (OPTIONS part 1, bits 4-7). The inputsare galvanically isolated and internally connected to 0 V via pull-down resis-tors. In an unconnected state a logical zero is transmitted. To set an input tological one, + 24 V DC must be applied.

Via these inputs external 0/4 – 20mA sensors for transmitting the measuredvalues through the Profibus can be connected..Proposed wiring diagrams (appendix C of the operation

instructions) for these signals must be observed..The bounce time of the connected switches should not bemore than 1 ms..The inputs AN1 and AN2 do not have galvanic isolation viaopto-isolator.

The measuring range of the analogue inputs can be set (see Operationinstructions Profibus DP, CONFIGURATION).

5.3 Assignment of the Profibus DP connection

X2 On this plug the bus signals and the galvanically isolated voltage supply forthe bus termination, as well as the bus termination resistors on the ProfibusDP board, are connected.

Actuator controls AUMATIC AC 01.1 / ACExC 01.1Profibus DP Short instructions

14

Pin Description LED3 R1: digital input 1 V 164 R2: digital input 2 V 195 R3: digital input 3 V 226 R4: digital input 4 V 257 0 V

Table 7: Digital inputs (galvanically isolated)

Pin Description2 AN1: Analogue signal (0 – 20 mA)

13 GND (Systemground)25 AN2: Analogue signal (0 – 20 mA)28 GND (Systemground)

Table 8: Analogue inputs

Pin Description1 Channel 1: B-cable bus termination2 Channel 1: A-cable bus termination3 Channel 1: B-cable Profibus4 Channel 1: A-cable Profibus8 Channel 2: A-cable Profibus (redundant channel)7 Channel 2: B-cable Profibus (redundant channel)9 Channel 2: B-cable bus termination (redundant channel)

10 Channel 2: A-cable bus termination (redundant channel)

Table 9: Pin assignment X2

Page 15: Short instructions bus connection Actuator controls

6. Appendix A Connection of the screen for AUMATIC ACExC 01.1

The screen of the fieldbus cable should be extensively connected with therespective threads.

Recommended threads, e.g. WAZU-EMV/EX by Hugro(see www.hugro-gmbh.de).

Actuator controls AUMATIC AC 01.1 / ACExC 01.1Short instructions Profibus DP

15

Page 16: Short instructions bus connection Actuator controls

Certificate Registration No.12 100/104 4269

www.auma.com

AUMA Riester GmbH & Co. KGP.O. Box 136279373 Müllheim, [email protected]

+49 7631 - 809-0+49 7631 - 809 1250

+49 711 - 34803 0+49 711 - 34803 34

AUMA Riester GmbH & Co. KGP. O. Box 1151D - 73747 [email protected]

For detailed information on AUMA products refer to the Internet:Y001.311/003/en/1.08

EuropeAUMA Riester GmbH & Co. KGFactory MüllheimDE-79373 MüllheimTel +49 7631 809 - 0Fax +49 7631 809 - [email protected] Ostfildern-NellingenDE-73747 OstfildernTel +49 711 34803 - 3000Fax +49 711 34803 - [email protected] Centre CologneDE-50858 KölnTel +49 2234 20379 - 00Fax +49 2234 20379 - [email protected] Centre MagdeburgDE-39167 NiederndodelebenTel +49 39204 759 - 0Fax +49 39204 759 - [email protected] Centre BavariaDE-85386 EchingTel +49 81 65 9017-0Fax +49 81 65 [email protected] Office, Ship building sectorDE-21079 HamburgTel +49 40 791 40285Fax +49 40 791 [email protected] Office, IndustryDE-29664 WalsrodeTel +49 5167 504Fax +49 5167 [email protected] OfficeDE-39167 NiederndodelebenTel +49 39204 75980Fax +49 39204 [email protected] OfficeDE-45549 SprockhövelTel +49 2339 9212 - 0Fax +49 2339 9212 - [email protected]ürttemberg OfficeDE-73747 OstfildernTel +49 711 34803 80Fax +49 711 34803 [email protected] OfficeDE-74937 SpechbachTel +49 6226 786141Fax +49 6226 [email protected] OfficeDE-76764 RheinzabernTel +49 7272 76 07 - 23Fax +49 7272 76 07 - [email protected] plant sectorDE-79373 MüllheimTel +49 7631 809 192Fax +49 7631 809 [email protected]üro BavariaDE-93356 Teugn/NiederbayernTel +49 9405 9410 24Fax +49 9405 9410 [email protected] Armaturenantriebe GmbHAT-2512 TribuswinkelTel +43 2252 82540Fax +43 2252 [email protected]

AUMA (Schweiz) AGCH-8965 BerikonTel +41 566 400945Fax +41 566 [email protected] Servopohony spol. s.r.o.CZ-10200 Praha 10Tel +420 272 700056Fax +420 272 [email protected] AUMATOR ABFI-02270 EspooTel +35 895 84022Fax +35 895 [email protected] FranceFR-95157 Taverny CédexTel +33 1 39327272Fax +33 1 [email protected] ACTUATORS Ltd.GB- Clevedon North Somerset BS21 6QHTel +44 1275 871141Fax +44 1275 [email protected] ITALIANA S.R.L.IT-20023 Cerro Maggiore MilanoTel +39 0331-51351Fax +39 [email protected] BENELUX B.V.NL-2314 XT LeidenTel +31 71 581 40 40Fax +31 71 581 40 [email protected] Polska Sp. zo. o.PL-41-310 Dabrowa GórniczaTel +48 32 26156 68Fax +48 32 26148 [email protected] Priwody OOORU-141400 Moscow regionTel +7 495 221 64 28Fax +7 495 221 64 [email protected] ARMATUR ABSE-20039 MalmöTel +46 40 311550Fax +46 40 [email protected]ØNBECH & SØNNER A/SDK-2450 København SVTel +45 33 26 63 00Fax +45 33 26 63 [email protected] S.A.ES-28027 MadridTel +34 91 3717130Fax +34 91 [email protected]. G. Bellos & Co. O.E.GR-13671 Acharnai AthensTel +30 210 2409485Fax +30 210 [email protected] SØRUM A. S.NO-1301 SandvikaTel +47 67572600Fax +47 [email protected] Sintra

Tel +351 2 1910 95 00Fax +351 2 1910 95 [email protected] Endüstri Kontrol Sistemieri Tic. Ltd.Sti.TR-06460 Övecler AnkaraTel +90 312 472 62 70Fax +90 312 472 62 [email protected] Control Limited Liability CompanyUA-02099 KiyivTel +38 044 566-9971, -8427Fax +38 044 [email protected]

AfricaAUMA South Africa (Pty) Ltd.ZA-1560 SpringsTel +27 11 3632880Fax +27 11 [email protected] CairoTel +20 2 3599680 - 3590861Fax +20 2 [email protected]

AmericaAUMA ACTUATORS INC.US-PA 15317 CanonsburgTel +1 724-743-AUMA (2862)Fax +1 [email protected] Chile Respresentative OfficeCL- La Reina BuinTel +56 2 821 4108Fax +56 2 281 [email protected] S. A.AR-C1140ABP Buenos AiresTel +54 11 4307 2141Fax +54 11 4307 [email protected] Termoindustrial Ltda.BR-13190-000 Monte Mor/ SP.Tel +55 19 3879 8735Fax +55 19 3879 [email protected] Inc.CA-L4N 5E9 Barrie OntarioTel +1 705 721-8246Fax +1 705 [email protected] Ferrostaal de Colombia Ltda.CO- Bogotá D.C.Tel +57 1 4 011 300Fax +57 1 4 131 806dorian.hernandez@manferrostaal.comwww.manferrostaal.comPROCONTIC Procesos y Control AutomáticoEC- QuitoTel +593 2 292 0431Fax +593 2 292 [email protected] DE MEXICO S. A. de C. V.MX-C.P. 02900 Mexico D.F.Tel +52 55 55 561 701Fax +52 55 53 563 [email protected] S.A.C.PE- Miralflores - LimaTel 00511444-1200 / 0044 / 2321Fax [email protected] Inc.PR-00936-4153 San JuanTel +18 09 78 77 20 87 85Fax +18 09 78 77 31 72 [email protected]

SuplibarcaVE- Maracaibo Estado, ZuliaTel +58 261 7 555 667Fax +58 261 7 532 [email protected]

AsiaAUMA (INDIA) PRIVATE LIMITEDIN-560 058 BangaloreTel +91 80 2839 4655Fax +91 80 2839 [email protected] JAPAN Co., Ltd.JP-210-0848 Kawasaki-ku,Kawasaki-shi KanagawaTel +81 44 329 1061Fax +81 44 366 [email protected] ACTUATORS (Singapore) Pte Ltd.SG-569551 SingaporeTel +65 6 4818750Fax +65 6 [email protected] Middle East Rep. OfficeAE- DubaiTel +971 4 3682720Fax +971 4 [email protected] CONTROLS Ltd.HK- Tsuen Wan, KowloonTel +852 2493 7726Fax +852 2416 [email protected] Controls Co., Ltd.KR-153-803 Seoul KoreaTel +82 2 2113 1100Fax +82 2 2113 1088/[email protected] Eng. Company W. L. L.KW-22004 SalmiyahTel +965 4817448Fax +965 [email protected] Trading EnterprisesQA- DohaTel +974 4433 236Fax +974 4433 [email protected] Valves and Intertrade Corp. Ltd.TH-10120 Yannawa BangkokTel +66 2 2400656Fax +66 2 [email protected] Advance Enterprises Ltd.TW- Jhonghe City Taipei Hsien (235)Tel +886 2 2225 1718Fax +886 2 8228 [email protected] Beijing Representative OfficeCN-100029 BeijingTel +86 10 8225 3933Fax +86 10 8225 [email protected]

AustraliaBARRON GJM Pty. Ltd.AU-NSW 1570 ArtarmonTel +61 294361088Fax +61 [email protected]

2006-01-30