short-circuits in es

57
- 1 - Short-circuits in ES Short-circuit: cross fault, quick emergency change in ES the most often fault in ES transient events occur during short-circuits Short-circuit formation: fault connection between phases or between phase(s) and the ground in the system with the grounded neutral point Main causes: insulation defect caused by overvoltage direct lightning strike insulation aging direct damage of overhead lines or cables

Upload: others

Post on 05-Apr-2022

1 views

Category:

Documents


0 download

TRANSCRIPT

- 1 -

Short-circuits in ES

Short-circuit: • cross fault, quick emergency change in ES • the most often fault in ES • transient events occur during short-circuits

Short-circuit formation: • fault connection between phases or between phase(s) and the ground

in the system with the grounded neutral point

Main causes: • insulation defect caused by overvoltage • direct lightning strike • insulation aging • direct damage of overhead lines or cables

- 2 -

Short-circuit impacts: • total impedance of the network affected part decreases • currents are increasing => so called short-circuit currents Ik • the voltage decreases near the short-circuit • Ik impacts causes device heating and power strain • problems with Ik disconnecting, electrical arc and overvoltage

occurred during the short-circuit • synchronism disruption of ES working in parallel • communication line disturbing => induced voltages

Note: In short-circuit places transient resistances arise.

• transient resistance is a sum of electrical arc resistance and resistance of other Ik way parts (determination of exact resistances is difficult)

• current and electrical arc length is changing during short-circuit => resistance of electrical arc is also changing

- 3 -

• transient resistances are neglected for Ik calculation (dimensioning of electrical devices) → perfect short-circuits

Short-circuits types

Symmetrical short-circuits: • Three-phase short-circuit => all 3 phases are affected by short-circuit

little occurrence in the case of overhead lines the most occurrences in the case of cable lines => other kinds of

faults change to 3ph short-circuit due to electrical-arc impact

Unbalanced (asymmetrical) short-circuits: • phase-to-phase short-circuit • double-phase-to-ground short-circuit • single-phase-to-ground short-circuit:

in MV a different kind of fault => so called ground fault in case of ground fault in MV (insulated or indirectly grounded

neutral point) => no change in LV (grounded neutral point)

- 4 -

Short-circuit type

Diagram

Occurrence probability (%)

MV 110 kV

220 kV

3ph 5 0,6 0,9

2ph 10 4,8 0,6

2ph to ground 20 3,8 5,4

1ph * 91 93,1

- 5 -

Short-circuit current time behaviour

2L Li

21W =

∞<=dt

dWP L → transient event

Time behaviour: open-circuit, resistances neglected → reactance, current of inductive character, higher Ik values

Impact of R on Ik attributes:

• finite R values decrease short-circuit impacts • R neglecting results in time constants prolongation τ = L/R

- 6 -

U = Umax in the short-circuit moment → Ik starts from zero (min. value)

Short-circuit components (f = 50 Hz): • sub-transient – exponential envelope, kT ′′ (damping winding) • transient – exponential envelope, kT′ (field winding) • steady-state – constant magnitude

It is caused by synchronous machine behaviour during short-circuit → more significant during short-circuits near the machine.

- 7 -

U = 0 in the short-circuit moment → Ik starts from max. value

- 8 -

Values • symmetrical short-circuit current ksI - steady-state, transient and

sub-transient component sum, RMS value • sub-transient short-circuit current kI ′′ - ksI RMS value in the period

of sub-transient component ( )kT30t ′′÷= • initial sub-transient short-circuit current 0kI ′′ - kI ′′ value in the

moment of short-circuit origin t = 0 • DC component kaI - disappears exponentially, kaT • peak short-circuit current kmI - the first half-period magnitude

during the maximal DC component

- 9 -

Short-circuits in 3ph system

Conversion between phase values and symmetrical components

( ) ( )( )120

0

2

1

2

2

C

B

A

ABC UTUUU

1aa1aa111

UUU

U =

=

=

( ) ( )( )ABC1

C

B

A2

2

0

2

1

120 UTUUU

111aa1aa1

31

UUU

U −=

=

=

Impedance matrix in symmetrical components (for series sym. segment)

( )

′+′−

′−=

=Z2Z00

0ZZ000ZZ

Z000Z000Z

Z

0

2

1

120

- 10 -

3ph system during short-circuit – internal generator voltage E (or Ui)

( ) ( )( ) ( )ABCABCABCABC UIZE +=

Symmetrical system (independent systems 1, 2, 0)

( ) ( )( ) ( )120120120120 UIZE += 0000

2222

1111

UIZE

UIZE

UIZE

+=

+=

+=

- 11 -

Generator symmetrical voltage → only positive sequence component Reference phase A:

( ) ( )( )

=

=

== −

00E

00

E

EaEa

E

111aa1aa1

31ETE

A

A

A2

A2

2

ABC1

120

+

=

=

0

2

1

0

2

1

0

2

1

0

2

1

UUU

III

Z000Z000Z

00E

EEE

Negative and zero sequence are caused by voltage unbalance in the faulted place.

- 12 -

In the fault point 6 quantities (U120, I120) → 3 equations necessary to be added by other 3 equations according to the short-circuit type (local unbalance description).

- 13 -

Three-phase (to-ground) short-circuit

3 char. equations

0UUU CBA ===

- 14 -

Components

( ) ( )( )

=

== −

000

000

111aa1aa1

31UTU 2

2

ABC1

120

0UUU 021 ===

0I;0I;ZEI 02

11 ===

Phases ( ) ( )( )120ABC ITI =

1C

1

2B

1A Z

EaI;ZEaI;

ZEI ===

Only the positive-sequence component included.

- 15 -

Single-phase-to-ground short-circuit

3 char. equations

0II;0U CBA ===

- 16 -

Components

( ) ( )( )

=

== −

A

A

AA2

2

ABC1

120

III

31

00I

111aa1aa1

31ITI

021

021 ZZZEIII

++===

( )

100

122

1201

IZU

IZU

IZZU

−=

−=

+=

All three components are in series.

- 17 -

Phases

( ) ( )( )

=

==

00I3

III

1aa1aa111

ITI1

1

1

1

2

2120ABC

0I;0I;ZZZ

E3I CB021

A ==++

=

( ) ( )( )( )

( ) ( )( ) ( )

1

022

02

22

10

12

120

2

2120ABC I

Z1aZaaZ1aZaa

0

IZIZ

IZZ

1aa1aa111

UTU

−+−−+−=

−−

+

==

- 18 -

Phase-to-phase short-circuit

3 char. equations

0I;II;UU ACBCB =−==

- 19 -

Components

( )

−=

=0

I3jI3j

31

II0

111aa1aa1

31I B

B

B

B2

2

120

0I;II;ZZ

EI 01221

1 =−=+

=

0U

IZZZEZUU

0

1221

221

=

⋅=+⋅==

Positive and negative components in parallel.

- 20 -

Phases

( ) ( )( )

−=

==

1

11

1

2

2120ABC

I3jI3j

0

0I

I

1aa1aa111

ITI

21C

21BA ZZ

E3jI;ZZE3jI;0I

+=

+−==

( ) ( )( )

⋅−⋅−⋅

=

−−=

==

12

12

12

1

1

1

1

1

2

2120ABC

IZIZIZ2

UUU2

0UU

1aa1aa111

UTU

- 21 -

Double-phase-to-ground short-circuit

3 char. equations

0I;0UU ACB ===

- 22 -

Components

( )

=

=

A

A

AA2

2

120

UUU

31

00

U

111aa1aa1

31U

120

201

20

02

20

201

1

IZZ

ZI;IZZ

ZI

ZZZZZ

EI

+−=

+−=

++

=

20

201

20

20

021

ZZZZZ

ZZZZE

UUU

++

+===

- 23 -

All three components are in parallel.

Phases ( ) ( )( )120ABC ITI =

( )201021

22

20

B ZZZZZZ)1a(Z)aa(ZEI

++−+−=

( )201021

22

0C ZZZZZZ

)1a(Z)aa(ZEI++

−+−=

( ) ( )( )

=

==

00U3

UUU

1aa1aa111

UTU1

1

1

1

2

2120ABC

- 24 -

Components during short-circuit: 3ph positive 2ph positive, negative 2ph ground positive, negative, zero

1ph positive, negative, zero

- 25 -

Short-circuits calculation by means of relative values

Relative values – related to a defined base.

base power (3ph) Sv (VA) base voltage (phase-to-phase) Uv (V) base current Iv (A) base impedance Zv (Ω)

vvv IU3S =

v

vfv I

UZ =

Relative impedance

2v

v2vf

v

vf

vf

vf

v

v

vfv USZ

U3SZ

U3U3

UIZ

IUZ

ZZz =====

- 26 -

Initial sub-transient short-circuit current (3ph short-circuit)

1

fA0k

Z

UII ==′′

v

2v

11 SUzZ =

v

1v

v

1

v

2v

1

v

0k Iz1

U3S

z1

SUz

3U

I ===′′

Initial sub-transient short-circuit power

v11

vv0kv0k S

z1

zIU3IU3S ==′′=′′

- 27 -

Similarly for 1ph short-circuit

v021

)1(0k I

zzz3I

++=′′

2ph short-circuit

v21

)2(0k I

zz3I

+=′′

Note: Sometimes it is respected generator loading, more precisely higher internal generator voltage than nominal one.

v1

0k Iz1kI =′′

k > 1

- 28 -

( ) )3(k

)1(k I5,10I ′′÷=′′

)3(k

)2(k I

23I ′′=′′

)3(k

)z2(k I3

23I ′′

÷=′′

- 29 -

Short-circuit currents impacts

Mechanical impacts Influence mainly at tightly placed stiff conductors, supporting insulators, disconnectors, construction elements,… Forces frequency 2f at AC → dynamic strain.

Force on the conductor in magnetic field )N(sinlIBF α⋅⋅⋅= )T(HB ⋅μ= )m/H(104 7

0−⋅π=μ

α – angle between mag. induction vector and the conductor axis (current direction)

Magnetic field intensity in the distance a from the conductor

)m/A(a2

IHπ

=

- 30 -

2 parallel conductors → force perpendicular to the conductor axis (sin α = 1) → it is the biggest

)N(laI102lI

a2I104F

277 −− ⋅=⋅

π⋅π=

The highest force corresponds to the highest immediate current value → peak short-circuit current Ikm (1st magnitude after s.-c. origin)

( ) )A(I2e1I2I 0kT/01,0

0kkmk ′′κ=+′′= −

κ – peak coefficient according to grid type (κLV = 1,8; κHV = 1,7) theoretical range κ = 1 ÷ 2 Tk – time constant of equivalent short-circuit loop (Le/Re) i.e. for DC component of short-circuit current 0kI ′′ - initial sub-transient short-circuit current

Real value differs according to the short-circuit origin moment. AC component decreasing slower than for DC therefore neglected.

- 31 -

Max. instantaneous force on the conductor length unit

)m/N(a

I10kk2f2

km721

−⋅⋅⋅= k1 – conductor shape coefficient

k2 – conductors configuration and currents phase shift coefficient

a – conductors distance

- 32 -

Heat impacts Key for dimensioning mainly at freely placed conductors. They are given by heat accumulation influenced by time-changing current during short-circuit time tk (adiabatic phenomenon).

Heat produced in conductors

)J(dt)t(i)(RQkt

0

2k ⋅ϑ=

Thermal equivalent current – current RMS value which has the same heating effect in the short-circuit duration time as the real short-circuit current

=kt

0

2kk

2ke dt)t(itI

)A(dt)t(it1I

kt

0

2k

kke =

Calculation according to ke coefficient as kI ′′ multiple keke IkI ′′=

- 33 -

Ground fault in three-phase systems

MV grids without a directly grounded neutral point (distribution systems) → single-phase ground fault has a different character than short-circuits (small capacitive current).

Fault current proportional to the system extent. A5Ip > → arc formation → conductors, towers, insulators burning →

→ 2ph, 3ph short-circuits (mainly at cables)

GF compensation → uninterrupted system operation (until the failure clearance, short supply break), arc self-extinguishing

Ground fault • resistive (100x Ω), metal and arc (x Ω)

- 34 -

Conditions in a system with insulated neutral point

Assumptions: considered only capacities to the ground, symmetrical source voltage, open-circuit system Insulated neutral point – systems of a small extent, A10Ip <

Before the fault

c

b

a

Ua^ Ub

^ Uc^

ka0 kb0 kc0

Ia^ Ib

^ Ic^

Ufc^

Ufb^

Ufa^

vvn/vn

U0^

- 35 -

0UUU c,b,fa0c,b,a =−− c,b,a0c,b,ac,b,a UkjI ω=

System with insulated neutral point 0III cba =++

Symmetrical source fafcfa

2fb UaU,UaU ==

Neutral point voltage

fa0c0b0a

0c0b2

0a0 U

kkkkakakU

++++−=

Unbalanced capacities 0U0 ≠ Symmetrical capacities 0Ukkkk 000c0b0a ====

- 36 -

Ex.: 2 tower terminals 22 kV, l = 50 km “Talon” Horizontal

%)8,3(km/nF00,4kkm/nF16,4kk

0b

0c0a

=Δ===

%)9,12(km/nF90,3kkm/nF48,4kk

0b

0c0a

=Δ===

V12867UV12620UU

%)3,1(V165U

b

ca

0

===

=

V13275UV12425UU%)5,4(V573U

b

ca

0

===

=

V12702Ufn =

- 37 -

Perfect (metal) durable ground fault

Symmetrical system c

b

a

Ua^ Ub

^ Uc^

k0 k0 k0

Ia^

Ib^

Ic^Ufc

^

Ufb^

Ufa^

U0^

Ic^Ib

^

Ip^

Fault current composed of 2 capacitive currents in the disaffected phases.

0Ua =

cbap IIII +==

b0b UkjI ω= c0c UkjI ω=

fa0fa0a UU0UUU −==−− !

- 38 -

( ) fa30j

fa2

fb0bfb0b Ue3Ua1UUU0UUU

−=+−=+==−− ! ( ) fa

30jfafc0cfc0c Ue3Ua1UUU0UUU

−−=+−=+==−− !

→ affected phase voltage – zero neutral point voltage – phase-to-ground value disaffected phases voltage – phase-to-phase value

Ground fault current ( )cb0cbp UUkjIII +ω=+= ( ) ( )[ ] fa

20 Ua1a1kj +−++−ω= ( ) fa

20 U11aa2kj −+++−ω=

( )V,F,s;AUkj3Ukj3I 100fa0p

−ω=ω−=

- 39 -

Voltage and current conditions

U0^ Ub

^Uc^

Ufa^

Ufb^Ufc

^

c b

aIp^

Ic^

Ib^

IL^

- 40 -

Fault current depends on the total system extent and almost doesn’t depend on the fault point distance from the transformer.

( )V,km,km/F,s;AlUk3I 1f01p

−ω=

Ip^

Ip^

- 41 -

Note: overhead 22 kV – current c. 0,06 A/km cables 22 kV – current c. 4 A/km Note: MV system can be operated also with GF, on LV level again 3-phase supplying due to transformers MV/LV D/yn (Y/zn)

Talon Horizontal

A49,2I

A44,2II

pb

pcpa

=

== A68,2I

A51,2II

pb

pcpa

=

==

- 42 -

Resistive ground fault

c

b

a

Ua^ Ub

^ Uc^

k0 k0 k0

Ip-Ia^

Ib^

Ic^Ufc

^

Ufb^

Ufa^

U0^

Ic^Ib

^Ip^ Ia

^

^

Rp

Affected phase voltage non-zero

cbapap IIIR/UI ++=−= Neutral point voltage

( )( ) fa1

p0c0b0a

1p0c0b

20a

0 URkkkj

RkakakjU −

+++ω+++ω

−=

0R p = fa0 UU −= ∞=pR 0U0 = (for symmetrical capacities)

- 43 -

Neutral point voltage (talon blue, horizontal yellow)

Phase voltages (A - blue, B - yellow, C - green) - talon

- 44 -

Fault current – talon, phase A

- 45 -

Ground fault current compensation

Compensation in systems where A5Ip > - suitable A10Ip > - necessary Method: continuously controlled arc-suppression coil (Petersen coil) between the transformer neutral point and the ground (in case of transformers with D winding by means of grounding transformer with Zn, Yn – artificial neutral point)

c

b

a

U0^

k0 k0 k0Ip^

L

IL^

IL^

Ib^ Ic

^

Ib^

Ic^

Ia^

- 46 -

Faultless state 0U0 = - symmetrical capacities f0 U01,0xU ⋅≈ - usual unbalance

Perfect ground fault fa0 UU −=

Arc-suppression coil current

LUjI 0

L ω−=

Total compensation

pL II −=

000 Ukj3L

Uj ω−=ω

- 47 -

Hence

)F,s;H(k3

1L 1

02

ω=

Coil power (reactive inductive) L

20

*000

*L0 QUkjUUkj3IUS =ω=ω==

Ideal compensation: 0Ip = in the fault point Real situation: residual current (small active)

• inaccurate inductance setting (error or intention) • uncompensatable active component (power line conductance, coil

R) • higher harmonics

000L

p UL

1k3jG3R1I

ω−ω++=

- 48 -

U0^ Ub

^Uc^

Ufa^

Ufb^Ufc

^

c b

a

Ip^

Ib+Ic^^ IL

^

ILL^

ILR^

- 49 -

Arc-suppression coil tuning

L dimensioning by calculation, setting in the faultless state (for given system configuration). Tuning is done by magnetic circuit change by means of motor (air gap).

Coil voltage ( )

( ) fa0c0b0a

20c0b

20a

2

L U1kkkL

kakakLU−++ω

++ω−=

- 50 -

Resonance dependence

( )LfUU

fa

L = ( )0c0b0a2REZ kkk

1L++ω

=

L (H)LREZ

CABLE

OHL

ΔL

UL

Ufa

∼ΔU

0

- 51 -

Overhead power lines • higher capacitive unbalance • maximum limited by resistances • LREZ compensates GF totally → resonance coil • setting by UL measurement • with small R the transformer neutral point is strained too much in

resonance → intended (small) detuning → dissonance coil

Cable power lines • small capacitive unbalance → flat curve → difficult tuning

- 52 -

- 53 -

Neutral point voltage (talon blue, horizontal violet)

talon H45,16LREZ = horizontal H76,15LREZ =

- 54 -

Fault current for coil detuning (talon blue, horizontal violet)

phase A phase B

- 55 -

Cable systems grounded with the resistance

c

b

a

UR^

k0 k0 k0Ip^

R

IR^

IR^

Ib^ Ic

^

Ic^

Ib^

Ia^

R1

R1

R1

X1

X1

X1

During the fault

• neutral point voltage almost phase-to-ground value • Ip uncompensated • Ip depends on the system extent x decreases with the distance from

the transformer (short-circuit character) • R value choice can influence Ip size and character

( ) f0P Uk3jR/1I ω+−=

- 56 -

U0^ Ub

^Uc^

Ufa^

Ufb^Ufc

^

c b

a

Ip^

Ib^

Ic^Ib+Ic

^

IR^

^

- 57 -

Neutral point voltage in a faultless state ( ( ) km50km/nF450kk;k1k 0c0a0c0b ⋅⋅==Δ−= )

Ω= 20R uz