HH-PF-01 External Masonry Cavity Wall, Partial-Fill - Suspended Beam And Block Floor, Insulation Above Slab
HH-PF-02 External Masonry Cavity Wall, Partial-Fill - Suspended In-Situ Concrete Floor, Insulation Below Slab
HH-PF-04 External Masonry Cavity Wall, Partial-Fill - Independent Lintel
HH-PF-03 External Masonry Cavity Wall, Partial-Fill - Concrete Ground Bearing Floor, Insulation Below Slab
HH-PF-05 External Masonry Cavity Wall, Partial-Fill - Steel Lintel, Perforated Base Plate, (Insulated Soffit)
HH-PF-06 External Masonry Cavity Wall, Partial-Fill - Sill
HH-PF-07 External Masonry Cavity Wall, Partial-Fill - Jamb
HH-PF-08 External Masonry Cavity Wall, Partial-Fill - Intermediate Timber Floor Within A Dwelling
HH-PF-09 External Masonry Cavity Wall, Partial-Fill - Precast Concrete Separating Floor Between Dwellings
HH-PF-10 External Masonry Cavity Wall, Partial-Fill - Pitched Roof, Gable, Insulation At Ceiling Level, Ventilated Loft
HH-PF-11 External Masonry Cavity Wall, Partial-Fill - Pitched Roof, Gable, Insulation At Rafter Level, Unventilated Rafter Void
HH-PF-12 External Masonry Cavity Wall, Partial-Fill - Pitched Roof, Eaves, Insulation At Ceiling Level, Ventilated Loft
HH-PF-13 External Masonry Cavity Wall, Partial-Fill - Pitched Roof, Eaves, Insulation At Rafter Level, Unventilated Rafter Void
HH-PF-14 External Masonry Cavity Wall, Partial-Fill - Normal Corner
HH-PF-15 External Masonry Cavity Wall, Partial-Fill - Inverted Corner
HH-PF-16 External Masonry Cavity Wall, Partial-Fill - Party Wall Between Dwellings
HH-PW-17 Party Wall Masonry, Full Fill - Suspended Beam And Block Floor, Insulation Above Slab
HH-PW-18 Party Wall Masonry, Full Fill - Suspended Concrete Floor, Insulation Below Slab
HH-PW-19 Party Wall Masonry, Full Fill - In-Situ Concrete Ground Bearing Floor, Insulation Below Slab
HH-PW-20 Party Wall Masonry, Full Fill - Roof, Insulation At Ceiling Level, Ventilated Loft
HH-PW-21 Party Wall Masonry, Full Fill - Roof, Insulation At Rafter Level, Unventilated Rafter Void
Detail Ref. Detail Title
HH-PF-23 External Masonry Cavity Wall, Partial-Fill - Pitched Roof, Eaves - Insulation At Rafter Level, Unventilated Rafter Void
HH-PF-22 External Masonry Cavity Wall, Partial-Fill - Steel Lintel, Open Back (no continuous base plate)
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
Standard Junction Details(partial Fill)
INDEX
AHRSJB
Nov 2012 AN.T.S.
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
A 11/2014 SJBHH-PF-22 & HH-PF-23 ADDED
ventilated void
wall cavity insulation tocontinue at least 215mm
from top of beam
partial-fill cavitywall insulation
floor insulation to tightly abutwall blockworkdpc
clear cavity
perimeter insulation toprovide minimum resistanceof 0.8m²K/W
Celcon blocks to inner leaf,above and below dpc
dpm
precast beam and block floorwith Celcon Standard infill blocks
Celcon infill blocks built into wallsto have the same compressivestrength as wall blocks
base course incorporatingdpm and dpc
max. 75mm screed thickness
Celcon foundation blocks
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,
Partial Fill - Suspended Beam And Block
Floor, Insulation Above Slab
HH-PF-01
AHRSJB
Nov 2012 1:100 @ A4
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
B
A 11/2013 SJBMAX. SCREED THICKNESS NOTEADDED.
For Ψ values applicable to this detail,see Constructive Details CD0001orLABC Registered ConstructionDetails E5MCPF16 - 21.
B 11/2014 SJBLABC REFERENCE ADDED
dpmdpcwall cavity insulation to
continue at least 215mmbelow underside of slab
partial-fill cavitywall insulation
clear cavity
floor insulation to tightly abutwall blockwork
Celcon blocks to inner leaf,above and below dpc
base course incorporatinglapped dpm and dpc
Celcon foundation blocks
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,
Partial Fill - Suspended In-Situ Concrete
Floor, Insulation Below Slab
HH-PF-02
AHRSJB
Nov 2012 1:100 @ A4
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
B
A 11/2013 SJBMAX. FLOOR THICKNESS NOTEADDED
B 11/2014 SJB
For Ψ values applicable to this detail,see Constructive Details CD0002orLABC Registered ConstructionDetails E5MCPF28 - 33.
MAX. FLOOR THICKNESS NOTEREMOVED. LABC REFERENCEADDED.
dpm
dpc
Celcon blocks to inner leaf,above and below dpc
partial-fill cavitywall insulation
clear cavity
base course incorporatinglapped dpm and dpcwall insulation to continue
at least 215mm belowunderside of slab perimeter insulation to provide
minimum resistance of 0.8m²K/W
floor insulation to tightly abutwall blockwork
Celcon foundation blocks
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,
Partial Fill - Concrete Ground Bearing
Floor, Insulation Below Slab
HH-PF-03
AHRSJB
Nov 2012 1:100 @ A4
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
B
A 11/2013 SJBMAX. FLOOR THICKNESS NOTEADDED
B 11/2014 SJB
For Ψ values applicable to this detail,see Constructive Details CD0003orLABC Registered ConstructionDetails E5MCPF22 - 27.
MAX. FLOOR THICKNESS NOTEREMOVED. LABC REFERENCEADDED.
minimum frameoverlap 30mm
PVC-U cavity closerfully insulated
internal lintel
Celcon blocks to inner leaf
partial-fill cavitywall insulation
external lintel
clear cavity
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,Partial Fill - Independent Lintel
HH-PF-04
AHRSJB
Nov 2012 A1:100 @ A4
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
A 11/2014 SJBLABC NOTE ADDED
For Ψ values applicable to this detail,see Constructive Details CD0004orLABC Registered ConstructionDetails E2MCPF4 - 6.
minimum frameoverlap 30mm
soffit insulation with min.resistance of 0.6m²K/W
insulated steel lintel with perforatedbase plate (equivalent conductivity30W/mK or less)
Celcon blocks to inner leaf
partial-fill cavitywall insulation
clear cavity
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
HH-PF-05
AHRSJB
Nov 2012 A1:100 @ A4
External Masonry Cavity Wall,
Partial Fill - Steel Lintel, Perforated
Base Plate, (Insulated Soffit)
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
A
For Ψ values applicable to this detail,see Constructive Details CD0005orLABC Registered ConstructionDetails E1MCPF4 - 6.
11/2014 SJBMAX. LINTEL HEIGHT NOTEREMOVED. LINTEL BASEPLATEADDED. LABC REFERENCE ADDED
minimum frameoverlap 30mm
partial-fill cavitywall insulation
clear cavityAircrete blocks to inner leaf
insulated steel lintel, no continuousbase plate. max. steel thickness 3.0mm
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
HH-PF-22
AHRSJB
Nov 2014 01:100 @ A4
External Masonry Cavity Wall,
Partial Fill - Steel Lintel, Open back
(no continuous base plate)
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
For Ψ values applicable to this detail,see LABC Registered ConstructionDetails E2MCPF7 - 9.
minimum frameoverlap 30mm
clear cavity
PVC-U cavity closer,fully insulated
Celcon blocks to inner leaf
partial-fill cavitywall insulation
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,
Partial Fill - Sill
HH-PF-06
AHRSJB
Nov 2012 A1:100 @ A4
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
For Ψ values applicable to this detail,see Constructive Details CD0006orLABC Registered ConstructionDetails E3MCPF4 - 6.
A 11/2014 SJBLABC NOTE ADDED
minimum frameoverlap 30mm
clear cavity
partial-fill cavitywall insulation Celcon blocks to inner leaf
PVC-U cavity closer,fully insulated
300mm max.
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,Partial Fill - Jamb
HH-PF-07
AHRSJB
Nov 2012 A1:100 @ A4
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
For Ψ values applicable to this detail,see Constructive Details CD0007orLABC Registered ConstructionDetails E4MCPF4 - 6.
A 11/2014 SJBLABC NOTE ADDED
timber floor joists may be built intoinner block leaf or supported onjoist hangers
Celcon blocks to inner leaf
clear cavity partial-fill cavitywall insulation
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,
Partial Fill - Intermediate Timber FloorWithin A Dwelling
HH-PF-08
AHRSJB
Nov 2012 A1:100 @ A4
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
For Ψ values applicable to this detail,see Constructive Details CD0008orLABC Registered ConstructionDetails E6MCPF4 - 6.
A 11/2014 SJBLABC NOTE ADDED
clear cavity
proprietary fire stop precast concreteplank floor
ceiling void
Celcon blocks to inner leaf
concrete screed
resilient layer to RobustDetails specification
partial-fill cavitywall insulation
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,
Partial Fill - Precast Concrete Separating
Floor Between Dwellings
HH-PF-09
AHRSJB
Nov 2012 A1:100 @ A4
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
For Ψ values applicable to this detail,see Constructive Details CD0009orLABC Registered ConstructionDetails E7MCPF4 - 6.
A 11/2014 SJBPROPRIETARY FIRE STOP NOTEREVISED. LABC NOTE ADDED.
clear cavity
minimum 200mmwall insulation above
ceiling insulation
ceiling insulation
pack compressible insulationbetween last truss and wall
Celcon blocks to inner leaf
partial-fill cavitywall insulation
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,
Partial Fill - Pitched Roof, Gable -
Insulation At Ceiling Level, Ventilated Loft
HH-PF-10
AHRSJB
Nov 2012 A1:100 @ A4
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
For Ψ values applicable to this detail,see Constructive Details CD0010orLABC Registered ConstructionDetails E12MCPF4 - 6.
A 11/2014 SJBLABC NOTE ADDED
partial-fill cavitywall insulation
fill this void with insulationhaving a maximum conductivity
of 0.040W/mK
clear cavity
100mm minimum
breathable roofmembrane
pack compressible insulationbetween last rafter and wall
insulation under rafters(optional)
min. 150mm rafters void fullyfilled with insulation withmax. λ = 0.040W/mK
Celcon blocks to inner leaf
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
HH-PF-11
AHRSJB
Nov 2012 1:100 @ A4
External Masonry Cavity Wall,Partial Fill - Pitched Roof, Gable - Insulation
At Rafter Level, Unventilated Rafter Void
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
B
A 11/2013 SJBRAFTERS INSULATION THICKNESSNOTE ADDED
For Ψ values applicable to this detail,see Constructive Details CD0011orLABC Registered ConstructionDetails E13MCPF4 - 6.
B 11/2014 SJBLABC NOTE ADDED
ceiling insulationbetween and overroof trusses
ventilated loft
partial-fill cavitywall insulation
clear cavity
Celcon blocks to inner leaf
proprietary ventilatorbetween rafters
min. 50mm insulationbetween wall plate
and vent
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
HH-PF-12
AHRSJB
Nov 2012 1:100 @ A4
External Masonry Cavity Wall,Partial Fill - Pitched Roof, Eaves - Insulation
At Ceiling Level, Ventilated Loft
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
B
A 11/2013 SJBWALL PLATE INSULATION COVERNOTE MOVED
For Ψ values applicable to this detail,see Constructive Details CD0012orLABC Registered ConstructionDetails E10MCPF4 - 6.
B 11/2014 SJBLABC NOTE ADDED
insulation to entirely filleaves gap betweenwall insulation and
ceiling insulation
clear cavity
partial-fill cavitywall insulation
Celcon blocks to inner leaf
150mm min. rafters with insulationof max. λ = 0.040W/mk between,to sloping ceiling section
breathable roofmembrane
insulation underrafters (optional)
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
HH-PF-13
AHRSJB
Nov 2012 1:100 @ A4
External Masonry Cavity Wall,Partial Fill - Pitched Roof, Eaves - Insulation
At Rafter Level, Unventilated Rafter Void
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
A
A 11/2013 SJBRAFTERS INSULATION NOWSHOWN AS 150mm.
For Ψ values applicable to this detail,see Constructive Details CD0013.
150mm rafters with insulationof λ = 0.044W/mk between,to sloping ceiling section
proprietary fire stop (if required),max λ ≤ 0.044W/mK
clear cavity
breathable roofmembrane
50mm insulation under
rafters, max λ = 0.022W/mK
Aircrete blocks to inner leaf
partial-fill cavitywall insulation
insulation to entirely filleaves gap betweenwall insulation and
ceiling insulation
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
HH-PF-23
AHRSJB
Nov 2014 1:100 @ A4
External Masonry Cavity Wall,Partial Fill - Pitched Roof, Eaves - Insulation
At Rafter Level, Unventilated Rafter Void
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
0
For Ψ values applicable to this detail,see LABC Registered ConstructionDetails E11MCPF4 - 6.
clear cavity
Celcon blocksto inner leaf
Partial-fillwall insulation
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
HH-PF-14
AHRSJB
Nov 2012 A1:100 @ A4
External Masonry Cavity Wall,Partial Fill - Normal Corner
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
For Ψ values applicable to this detail,see Constructive Details CD0014orLABC Registered ConstructionDetails E16MCPF4 - 6.
A 11/2014 SJBLABC NOTE ADDED
partial-fillcavity insulation
clear cavity
Celcon blocksto inner leaf
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
HH-PF-15
AHRSJB
Nov 2012 A1:100 @ A4
External Masonry Cavity Wall,Partial Fill - Inverted Corner
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
For Ψ values applicable to this detail,see Constructive Details CD0015orLABC Registered ConstructionDetails E17MCPF4 - 6.
A 11/2014 SJBLABC NOTE ADDED
partial-fill cavitywall insulation
clear cavity
Celcon blocks toinner leaf
8mm parge coat may be omitted(subject to Robust Detail requirements)
2 x 100mm leaves to separatingwalls above dpc:Celcon Standard (3.6N/mm²)Celcon High Strength (7.3N/mm³)Celcon Super Strength (8.7N/mm²)
cavity width min. 75mmup to 100mm max.
(subject tp Robust Detailrequirements)
full fill mineral wool cavity wallinsulation, density up to 40kg/m³
proprietary insulated fire stopif required
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,Partial Fill - Party Wall Between Dwellings
HH-PF-16
AHRSJB
Nov 2012 A1:100 @ A4
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
For Ψ values applicable to this detail,see Constructive Details CD0016orLABC Registered ConstructionDetails E18MCPF7 - 10.
A 11/2014 SJBPROPRIETARY FIRE STOP NOTEREVISED. LABC NOTE ADDED.
ventilated void
floor insulation to tightly abutwall blockwork
insulation to continueat least 215mm below
top of beams
full fill mineral wool cavity wall
insulation, density up to 40kg/m³
precast beam and blockfloor with Celcon Standardinfill blocks
Celcon infill block built into wallsto have the same compressivestrength as wall blocks
dpmdpm
2 x 100mm leaves to separatingwall above and below dpc:Celcon Standard (3.6N/mm²)Celcon High Strength (7.3N/mm²)Celcon Super Strength (8.7N/mm²)
cavity width min. 75mmup to 100mm max.
(subject to Robust Detailrequirements)
8mm parge coat may beomitted (subject to Robust
Detail requirements)
minimum 225mm
max. 75mm screed thickness
perimeter insulation toprovide minimum resistanceof 0.8m²K/W
Celcon foundation blocks
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
Party Wall Masonry, Full Fill -
Suspended Beam And Block Floor,
Insulation Above Slab
HH-PW-17
AHRSJB
Nov 2012 1:100 @ A4
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
B
A 11/2013 SJBMAX. SCREED THICKNESS NOTEADDED
For Ψ values applicable to this detail,see Constructive Details CD0017orLABC Registered ConstructionDetails P1PCFF1 - 2.
B 11/2014 SJBLABC NOTE ADDED.
dpmfloor insulation to tightly abutwall blockwork
insulation to continueat least 215mm belowunderside of slab
cavity width min. 75mmup to 100mm max.
(subject to Robust Detailrequirements)
8mm parge coat may beomitted (subject to Robust
Detail requirements)
2 x 100mm leaves to separatingwall above and below dpc:Celcon Standard (3.6N/mm²)Celcon High Strength (7.3N/mm²)Celcon Super Strength (8.7N/mm²)
base course incorporatinglapped dpm and dpc
full fill mineral wool cavity wallinsulation, density up to 40kg/m³
dpm
Celcon foundation blocks
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
Party Wall Masonry, Full Fill -
Suspended Concrete Floor,
Insulation Below Slab
HH-PW-18
AHRSJB
Nov 2012 1:100 @ A4
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
B
A 11/2013 SJBMAX. SCREED THICKNESS NOTEADDED
For Ψ values applicable to this detail,see Constructive Details CD0018orLABC Registered ConstructionDetails P1PCFF3 - 4.
B 11/2014 SJBMAX. FLOOR THICKNESS NOTEREMOVED. LABC REFERENCEADDED.
dpm
floor insulation to tightly abutwall blockworkdpm
wall insulation to continueat least 215mm below
underside of slab
base course incorporatinglapped dpm and dpc
perimeter insulation to provideminimum resistance of 0.8m²K/W
cavity width min. 75mmup to 100mm max.
(subject to Robust Detailrequirements)
2 x 100mm leaves to separatingwall above and below dpc:Celcon Standard (3.6N/mm²)Celcon High Strength (7.3N/mm²)Celcon Super Strength (8.7N/mm²)
full fill mineral wool cavity wall
insulation, density up to 40kg/m³
8mm parge coat may beomitted (subject to Robust
Detail requirements)
Celcon foundation blocks
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
Party Wall Masonry, Full Fill -
In-situ Concrete Ground Bearing Floor,
Insulation Below Slab
HH-PW-19
AHRSJB
Nov 2012 1:100 @ A4
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
B
A 11/2013 SJBMAX. FLOOR THICKNESS NOTEADDED
For Ψ values applicable to this detail,see Constructive Details CD0019orLABC Registered ConstructionDetails P1PCFF5 - 6.
B 11/2014 SJBMAX. FLOOR THICKNESS NOTEREMOVED. LABC REFERENCEADDED.
minimum 200mmwall insulation above
ceiling insulation
8mm parge coat may beomitted (subject to Robust
Detail requirements)
ceiling insulation
pack compressible insulationbetween last rafter and wall
full fill mineral woolcavity wall insulation,density up to40kg/m³
cavity width min. 75mmup to 100mm max.
(subject to Robust Detailrequirements)
2 x 100mm leaves to separatingwall above dpc:Celcon Standard (3.6N/mm²)Celcon High Strength (7.3N/mm²)Celcon Super Strength (8.7N/mm²)
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
Party Wall Masonry, Full Fill -
Roof, Insulated At Ceiling Level,
Ventilated Loft
HH-PW-20
AHRSJB
Nov 2012 A1:100 @ A4
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
For Ψ values applicable to this detail,see Constructive Details CD0020orLABC Registered ConstructionDetails P4PCFF1 - 2.
A 11/2014 SJBLABC NOTE ADDED
breathable roofmembrane
minimum 100mminsulation
full fill mineral wool cavity wallinsulation, density up to 40kg/m³
2 x 100mm leaves to separating wall:Celcon Standard (3.6N/mm²)
Celcon High Strength (7.3N/mm²)Celcon Super Strength (8.7N/mm²)
cavity width min. 75mm up to 100mm max.(subject to Robust Detail requirements)
pack compressible insulationbetween last rafter and wall
insulation under rafters(optional)
min. 150mm rafters void fullyfilled with insulation
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
Party Wall Masonry, Full Fill -
Roof, Insulated At Rafter Level,
Unventilated Rafter Void
HH-PW-21
AHRSJB
Nov 2012 1:100 @ A4
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
B
A 11/2013 SJBRAFTERS INSULATION THICKNESSNOTE ADDED
For Ψ values applicable to this detail,see Constructive Details CD0021orLABC Registered ConstructionDetails P5PCFF1 - 2.
B 11/2014 SJBLABC NOTE ADDED