s onrol irin an prorammin i e pars gie p/n c001 rev 11 phone () … control quick setup... ·...
TRANSCRIPT
1 of 22
Opus Control Wiring and Programming Quick Setup Parts Guide
P/N C-00139 Rev 4-1-16
Nabco Entrances Inc. S82 W18717 Gemini Drive Muskego, Wisconsin 53150Phone: (877) 622-2694 Fax: (888) 679-3319 www.nabcoentrances.com
This document is meant to serve as a Quick Set-Up Guide only. Installation manuals referenced below should be downloaded and reviewed for complete installation instructions.
• Turn OFF all power to the Automatic Door if a Safety System is not working.
• Instruct the Owner to keep all power turned OFF until corrective action can be achieved by a NABCO trained technician. Failure to follow these practices may result in serious consequences.
• NEVER leave a Door operating without all Safety detection systems operational.
WARNING
Associated Manuals Part Numbers: Opus Control Wiring and Programming Manual; P/N 15-14973
DN 133614
1312
1110
98
76
54
32
1
2 of 22
Opus Control Wiring and Programming Quick Setup Parts Guide www.NabcoEntrances.com
P/N C-00139 Rev 4-1-16
Table of Contents
SECTION 1: TO THE INSTALLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SECTION 2: 120 VAC GENERAL WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SECTION 3: THE OPUS CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SECTION 4: PROGRAMMING THE OPUS CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
SECTION 5: FOLD DOOR WIRING DIAGRAM (ACCESSORIES) . . . . . . . . . . . . . . . . . . . . . . . . . . 10
SECTION 6: SWING DOOR WIRING DIAGRAMS (ACCESSORIES) . . . . . . . . . . . . . . . . . . . . . . . 11
SECTION 7: TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
SERVICE PARTS: OPUS SIDE LOAD UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
SERVICE PARTS: OPUS BOTTOM LOAD UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3 of 22
www.NabcoEntrances.com� Opus�Control�Wiring�and�Programming�Instruction�Quick�Setup�Parts�Guide
Rev 4-1-16 P/N C-00139
SECTION 1: TO THE INSTALLERThe purpose of this manual is to familiarize the installer with the proper installation and operation of this system. It is essential that this equipment be properly installed and operational before the door is used by the public. It is the installer’s responsibility to inspect the operation of the entrance system to be sure it complies with any applicable standards. In the United States, ANSI Standard 156.10 (Used to cover Full Energy doors) and ANSI Standard 156.19 (Used to cover Low Energy doors) apply. Other local standards or codes may apply. Use them in addition to the ANSI standards. The owner should determine the door is operating properly and should immediately call for service if there is any malfunction. All installation changes and adjustments must be made by qualified, NABCO trained technicians.The Opus Control can be installed within the Header of new or existing; Swing Door systems, Fold Door Systems and Slide Door Systems. The Opus Control can be sold as a Retrofit Kit to replace Magnum Controls, Analog Controls, and U-01 to U-19 Controls.Retrofit kits can be purchased by contacting Customer Service at 1-888-679-3319.
SECTION 2: 120 VAC GENERAL WIRINGShut the installation site, branch Circuit Breaker OFF. Failure to do so may result in serious personal or fatal injury. When uncertain whether power supply is disconnected, always verify using a voltmeter.
All high voltage electrical connections must be made by licensed electricians according to National and Local electrical codes/regulations.
Permanent wiring shall be employed as required by local codes.
Keep all Incoming 120 VAC wiring separate from low voltage wiring within Header. 120 VAC Power wires must be routed (separate from other wiring) located near the top of inside Header.
Ensure that the Grounding of the Electric Power Supply is installed/connected in a proper way (especially the PE Cable from the Building Side).
Attention: Note: It is recommended for the Installer to house all Incoming 120 VAC wires within an Electrical Conduit.
DN 1335
SINGLE
120 VAC
SIMULTANEOUS PAIR
120 VAC
WHITE
BLACK
NEUTRAL
HOT
GROUND
OPUS CONTROL
BLACK
BLACK
1413
1211
109
8
76
54
32
1
Ground Screw
ON/OFF Rocker Switch
WHITE
BLACK
NEUTRAL
HOT
GROUND
OPUS CONTROL
BLACK
BLACK
OPUS CONTROL
BLACK
WHITE
GREENGREEN
1413
1211
109
8
76
54
32
1
1413
1211
109
8
76
54
32
1
Ground Screw
ON/OFF Rocker Switch
Motor
21
MotorBLACK
21
Motor
21
WARNING
WARNING
CAUTION
CAUTION
CAUTION
4 of 22
Opus Control Wiring and Programming Quick Setup Parts Guide www.NabcoEntrances.com
P/N C-00139 Rev 4-1-16
SECTION 3: THE OPUS CONTROLThe Opus Control is used to power and control operating characteristics of the door. This is done through the use of Harnesses connected to Terminals located on the Control Board, plus wiring that is connected to other components within the Header.
Note: When the LCD Screen is ON and displays settings, the Hold Close feature is disabled. When the LCD screen is OFF, and does not display settings, the Hold Close feature is enabled.
Figure 1 Opus ControlDN 1328
1413
1211
109
8
76
54
32
1
①
②
③
④ ⑤ ⑥
⑦
⑧
1 CN3 I/O Terminal Strip 5 - LCD Screen2 CN5 Output Terminal Strip 6 CN2 Motor Connector3 CN4 CANBus Communication 7 CN1 Power Connector4 - Rotary Dial 8 - Fuse, MC
3 .1 The Rotary DialThe Rotary Dial is located at the bottom, left side of the LCD Display and is utilized to scroll through LCD screens by:
XX Turning the Rotary Dial:•XClockwise: To scroll forward through screens and programming options. •XCounterclockwise: To scroll backward through screens and programming options.
XX Pressing down on the Rotary Dial: •XGains access to a different screen on another Level.•XUnlock/locks screen Titles and selected Options.•XSelects current option.
1. Scroll through screens by turning the Rotary Dial or pressing down on the Rotary Dial.2. To go back to the beginning, press and hold down for (2) seconds on the Rotary Dial. Release the Rotary Dial once the Level
One screen is displayed.
DN 1242
Type: GT710 SwingStatus: Slow ClosingError: -----Ac� va� on: IN EXTSwitch: LCHK BCHKOther: BA 6B SLS
Keep Pushing Switch=> Se� ng Mode
Rotary Dial
UNIT SPECIFICATIONS11
20
10
1
LCD Screen
Figure 2 The Rotary Dial
3 .2 LCD Screen Transition(4) LCD Screens are categorized within the following Hierarchy Levels:
XX Level One: Specification XX Level Two: Access XX Level Three: Category XX Level Four: Parameter
5 of 22
www.NabcoEntrances.com� Opus�Control�Wiring�and�Programming�Instruction�Quick�Setup�Parts�Guide
Rev 4-1-16 P/N C-00139
UNIT SPEC ERROR ANSI TERMINAL
Level 1
Hold pushing Switch
ACCESS• Password se�ng• Stroke Se�ng• Se�ng screen
Push
SETTING CATEGORY
Operator Type / Low Energy or Full / Door Hand / Encoder?
Open Speed / Back Check Speed / Back Check Range / Close Speed / Latch Check Speed / Latch Check Range / Open �mer / Reac�on Power / Open Recycle sens / Close Recycle sens / A�er Open Recycle
Hold Close Force / Power Close Range / ManualOpen Func�on / ManualOpen Sens / Manual Open �mer / BCHK Lockout Angle / LCHK Lockout Angle / Stop Force adjustmnt / SimPair se�ng
Output1 se�ng / Output2 se�ng / RelayOutput3 se�ng / Open Delay Timer / Lock Condi�on
Input 62 se�ng / Input 62 open �mer / Input H se�ng / Input H open �mer / Input 62 Circuit / Input 6B Circuit / Input SWL Circuit / Input BA Circuit62 Safety Check / 6B Safety Check / SWL Safety Check
Base Se�ng
Movement Se�ng
Op�onal Se�ng
Output Se�ng
Input Se�ng
Push
Hold pushingSwitch
Hold pushingSwitch
Push and hold Rotary switch for (2) seconds
Push and hold Rotary switch for (2) seconds
Push and hold Rotary switch for (2) seconds
History Se�ng Opera�on Cnt / Open Recycle Cnt / Close Recycle Cnt / Latest Recycle Posi�on
DN 1334
Figure 3 LCD Screen Transition
3 .3 Level One: Specification Screens
Type: GT710 SwingStatus: Slow ClosingError: -----Ac� va� on: IN EXTSwitch: LCHK BCHKOther: BA 6B SLS
Keep Pushing Switch=> Se� ng Mode
DN 1241
UNIT SPECIFICATIONS11
20
10
1
ANSI specs (reference)
Opening Time to 80 deg
Closing Time to LCHK
LCHK to FullClosed
ANSI SPECIFICATIONS11
20
10
1
11
20
10
1
8 BA 1 12VDC9 SQ 2 GND10 Mul� 3 6111 M0 4 6212 M1 5 6B13 Out3 6 SWL14 GND 7 Out2
TerminalTERMINAL SPECIFICATIONS
Figure 4 Level One Screens
When Power is turned ON for the first time, the Door does not move. Instead, an LCD screen will illuminate to display a Level One: Unit Specification screen (Default screen). There are (3) Level One screens:
XX Unit Specifications: Displays the type of door and current status of the unit. The type of door (swing, slide or folding) can be changed within the Base Settings Category (Level 3 and Level 4). Please refer to Subsection 6.1 The screen above shows the Opus control installed on a GT710.
XX ANSI Specifications: Displays the actual time of opening and closing of the door to help determine ANSI compliance.(Applies to swing doors only).
XX Terminal Specifications: Displays the current status of all of the Input/Output lines of the terminal strip.Level One screens are used to inform the User all specifications that have already been programmed into the Opus Control. If a specification needs to be changed, the User must reprogam the Opus Control within the Level Three screen, or Level Four screen.
3 .4 Level Two: Access Screen
DN 1244
Password Password
Stroke Learning Yes No
ACCESS SCREEN11
20
10
1
Figure 5 Level Two Screen
6 of 22
Opus Control Wiring and Programming Quick Setup Parts Guide www.NabcoEntrances.com
P/N C-00139 Rev 4-1-16
3 .4 .1 PasswordThe Default password is (0045) and has been programmed into all Opus Controls. To prevent tampering of the Opus Control, the password cannot be changed.
1. Briefly press down on the Rotary Dial. Turn the Rotary dial until the first number (0) is displayed. Repeat until the Default password (0045) has been entered. a. Level Three screen will display.
3 .4 .2 Stroke LearningXX Activates the Door to teach the Opus Control the Full Open and Full Closed positions. XX Measures from Full Closed to Full Open points to determine where Check Points should happen.XX Determines if an existing Operator Type is correct.XX Determines if Handing is correct.
1. Briefly press down on the Rotary Dial to select: XX Yes
• Opus will start the Stroke Learning Cycle• The door will Close slowly → Open Slowly → Close Again
XX No• If the Operator and Door Handing settings are correct, Opus will not have to Learn Stroke. Opusautomatically
determines the Stroke during a normal door cycle.• If the Operator Type or Door Hand are the wrong setting, the following messages after the Stroke Learning Cycle will
display: “Wrong Motor! Restroke”; or “Wrong Hand! Restroke”. If this event occurs, enter the proper settings within the Base Setting Category screens.
3 .5 Level Three: Category Screen
3 .5 .1 Within Password Level Three Setting Category displays Parameter options for Level Four.
Low Energy or Full Low Full
Se� ng Category Base Se� ng Movement Se� ng Op� onal Se� ng Output Se� ng Input Se� ng History Data
DN 1246
11
20
10
1
LEVEL THREE SCREEN11
20
10
1
LEVEL FOUR SCREENPARAMETER OPTION FOR BASE SETTING
Figure 6 Level Three screen linked to Password
3 .5 .2 Within Stroke (only if Yes was selected)Level Three Setting Category will display Error messages if the Door has been programmed incorrectly.
.
Wrong Motor! Restroke
DN 1249
11
20
10
1
OPERATOR TYPE
Wrong Hand! Restroke
11
20
10
1
HANDING
Figure 7 Stroke Learning: Level Four
3 .6 Level Four: Parameter Setting ScreensParameter Options are utilized to select appropriate Parameter Settings. Parameter Options are available after entering a Password.
7 of 22
www.NabcoEntrances.com� Opus�Control�Wiring�and�Programming�Instruction�Quick�Setup�Parts�Guide
Rev 4-1-16 P/N C-00139
SECTION 4: PROGRAMMING THE OPUS CONTROL
4 .1 Base Settings
Base SettingsParameter Range Default Action
Operator Type XX GT-300/400/500 SwingXX GT-1175 SlideXX GT-710 Swing
GT-710Swing
XX Select Operator TypeXX Select GT300/400/500 Swing, if installing a GT-1400 Fold Foor
Low Energy or Full XX Low EnergyXX Full Energy
Low Select type of operator application
Swing Door Handing XX LeftXX Right
Right From the Exterior Side of Building, determine which Handing to enter: Right or Left
RIGHT HANDING
DN 1308
LEFT HANDING
Pivot S� le on Swing Door
Swing Door
EXTERIOR SIDE OF BUILDING
Fold Door Handing XX LeftXX Right
Right From the Exterior Side of Building, determine which Handing to enter: Right or Left
DN 0833
EXTERIOR BREAKOUT SIDE
LEFT HAND RIGHT HAND
Slide Door Handing XX LeftXX Right
Right From the Exterior Side of Building, determine which Handing to enter: Right or Left
RIGHT HANDING
DN 1326
LEFT HANDING
EXTERIOR SIDE OF BUILDING
Encoder XX YesXX No
XX Yes XX Select YES if Encoder is installed with Motor.XX Select NO if Encoder is not installed with Motor.
4 .2 Movement Settings
Movement SettingsParameter Range Default Description
Open Speed 0 - 7 3 The higher the number the faster the Door opensBack Check Speed 0 - 7 3 Sets door speed during Back CheckBack Check Range 0 - 7 3 XX Swing Door: 2-1/2° to 35° of Fully Open
XX Slide Door: 1" to 13-3/4" of Fully OpenClose Speed 0 - 7 3 The higher the number the faster the Door closesLatch Check Speed 0 - 7 3 Sets door speed during latch checkLatch Check Range 0 - 7 3 XX Swing Door: 10° to 45° of Fully Closed
XX Slide Door: 1" to 13-3/4" of Fully ClosedOpen Timer 0-10, 12, 15, 20, 25, 30 2 Amount of Hold Open time after deactivation in secondsReaction Power 0 - 7 3 Determines how fast the door reacts to a reactivation when closingOpen Recycle Sens 0 - 7 3 Determines how hard the door will push against an obstruction
during opening
8 of 22
Opus Control Wiring and Programming Quick Setup Parts Guide www.NabcoEntrances.com
P/N C-00139 Rev 4-1-16
Movement SettingsParameter Range Default Description
Close Recycle Sens 0 - 7 3 Determines how hard the door will push against an obstruction during closing
After Open Recycle Slow Open Stop Slow Open Determines what happens after a recycle during Opening cycle.Close RecycleReopen
Yes Yes Determines what happens after a recycle while closing cycle.No
4 .3 Optional SettingsOptional Settings
Parameter Range Default DescriptionHold Close Force 0 - 3 0 0 OFF
3 Strongest Hold Close forcePower Close Range XX No Power Close
XX Whole Close CycleXX Latch Check OnlyXX Latch and Back
No Power Close
Closing assisted by Motor to fight wind or stack pressure
Manual Open Function XX No ActionXX Push and GoXX Stop and CloseXX Try to close
No Action Does nothingP & G Enables push and goS & C Door pauses at open angle then closesDoor will creep to Close
Manual Open Sensitivity 0 - 3 1 Angle/force to activate Push and GoManual Open Timer XX 0-10, 12, 15, 20, 25, 30
XX Same as Open TImer4 Hold Open time for Manual Opening
BCHK Lockout Angle 0 - 9 0 XX Sensor lockout angle at Back CheckXX Range is from 0° to 30° from Fully OpenXX Used for Swing or Fold Door Units only
A
0 Narrow A Wide
LCHK Lockout Angle 0 - 9 0 XX Sensor lockout angle at Latch CheckXX Range is from 0° to 30° from Fully CloseXX Used for Swing or Fold Door Units only
A
0 Narrow A Wide
DN 1309
Latch Check (LCHK)Lockout Angle
Back Check (BCHK)Lockout Angle Available Angle
Con� nuous Safety
Available Anglefor Low EnergyDoor MountApproach Side Sensor
Available Angle Safety with lockout
Available Angle Safety with Lockout
SAFETY WITH LOCKOUT AREASLOCKOUT PARAMETERS
Stop Force Adjustment 0 - 7 3 Determines how the door reacts to a continuous safety signal: Slow Open, Stop, or Slow Close
SimPair Setting Single Door Single Door
Select type of Door Normal Sim Pair
Overlap Sim Pair Overlap Sim Pair is for an Astragal Application
9 of 22
www.NabcoEntrances.com� Opus�Control�Wiring�and�Programming�Instruction�Quick�Setup�Parts�Guide
Rev 4-1-16 P/N C-00139
4 .4 Output SettingsAttention: The following Output Settings Table is for RETRO FIT KITS ONLY . Output Settings for all other Units
are preset at the NABCO Factory .
Output SettingsParameter Terminal Range Default DescriptionOutput1 Terminal 7 XX — —
XX Fully Closed PositionXX Closing StatusXX Opening StatusXX Full Opened PositionXX Error State OutputXX Recycle happenedXX Electric Strike LockXX Electric Magnetic LockXX AirlockXX Breakout Pass throughXX Door SequencingXX Sensor Monitoring (N.O) XX Sensor Monitoring (N.C.XX BEA Bodyguard Output
Full Open XX Relay doesn’t change stateXX Relay changes when fully closedXX Relay changes when door is closingXX Relay changes when door is openingXX Relay changes when fully openXX Relay changes when error detectedXX Relay changes when recycle occursXX Set for electric strike functionalityXX Set for Mag lock functionalityXX Set for Airlock functionalityXX Relay changes when breakout occursXX Provision for door sequencingXX Normally open contacts for MonitoringXX Normally closed contacts for MonitoringXX For BEA Bodyguard
Output 2 Terminal 13 Full Closed
Output 3 Electric Lock Terminals
— —
Open Delay Timer N/A XX 0.1 - 0.9 secXX After Unlock Input
0.3 XX Delay time after activation to allow lock to unlock before the door starts moving.
XX Only functional if Electric Lock is selectedLock Condition N/A XX Every Fully Closed
XX Oneway/Night OnlyEvery FullyClosed
Determines when the electric lock engages
4 .5 Input SettingsInput Settings
Parameter Terminal Range DefaultInput 62 Terminal
4XX — — XX All Activation ModeXX Interior ActivationXX Exterior ActivationXX Beam SensorXX LE Approach SensorXX Unlock InputXX Spring Close OnlyXX Sequential InputXX Open SlowXX Safety with LockoutXX Continuous SafetyXX Reduced OpeningXX Emergency CloseXX Hold Open Mode
Exterior Activation
XX No inputXX Activates in all modes but OFFXX Activation on interior for One Way modeXX Activation on exteriorXX Beam inputXX LE door mounted sensorXX Receives unlocked signal from elec LockXX Turns off power close and hold closeXX Takes on activation to open then another to close the door
XX Causes slow opening of the doorXX Swingside header mounted sensor inputXX Swing side door mounted sensor inputXX Causes unit to change to reduced openXX Forces the door to slowly close and lockXX Causes the door to hold open forever
Input 62Open Timer
N/A XX 0-10, 12, 15, 20, 25,XX Same as Open Timer
Same as Open Timer
Hold open time for Input 62
Input H Open Timer
N/A XX 0-10, 12, 15, 20, 25,XX Same as Open Timer
Same asOpen Timer
Hold open time for Input H
Input 61 Circuit N/A XX Normally OpenXX Normally Close
NormallyOpen
Circuit logic for Input 61
Input 62 Circuit N/A XX Normally OpenXX Normally Close
NormallyOpen
Circuit logic for Input 62
10 of 22
Opus Control Wiring and Programming Quick Setup Parts Guide www.NabcoEntrances.com
P/N C-00139 Rev 4-1-16
Input SettingsParameter Terminal Range DefaultInput H Setting Terminal
10XX — — XX All Activation ModeXX Interior ActivationXX Exterior ActivationXX Beam SensorXX LE Approach SensorXX Unlock InputXX Spring Close OnlyXX Sequential InputXX Open SlowXX Safety with LockoutXX Continuous SafetyXX Reduced OpeningXX Emergency CloseXX Hold Open Mode
— — XX No inputXX Activates in all modes but OFFXX Activation on interior for One Way modeXX Activation on exteriorXX Beam inputXX LE door mounted sensorXX Receives unlocked signal from elec LockXX Turns off power close and hold closeXX Takes on activation to open then another to close the door
XX Causes slow opening of the doorXX Swingside header mounted sensor inputXX Swing side door mounted sensor inputXX Causes unit to change to reduced openXX Forces the door to slowly close and lockXX Causes the door to hold open forever
Input 6B Circuit N/A XX Normally OpenXX Normally Close
NormallyOpen
Circuit logic for Input 6B
Input SWL Circuit N/A XX Normally OpenXX Normally Close
NormallyOpen
Circuit logic for Input SWL
Input BA Circuit N/A XX Normally OpenXX Normally Close
NormallyOpen
Circuit logic for Input BA
6B Stop Closing N/A XX Yes No Determines door movement stop or close, when 6B is ON at latch check while closing cycle.XX No
After 6B Open? N/A XX Yes Yes Determines door movement open or close, after 6B.XX No
61 Monitoring N/A XX ActiveXX Not Active
Not Active Sensor monitoring function *
62 Monitoring N/A XX ActiveXX Not Active
Not Active Sensor monitoring function *
6B Monitoring N/A XX ActiveXX Not Active
Not Active Sensor monitoring function *
SWL Monitoring N/A XX ActiveXX Not Active
Not Active Sensor monitoring function *
* If Safety Check is enabled for any input then the sensor MUST be connected to Output 1 or 2.Output 1 or 2 must then be programmed to “Sensor Health Check”. If an error occurs, the door will
hold open until the error clears or the power is cycled.
4 .6 History Settings
History SettingsParameter Description
Operation Cnt XX Indicates number of Door open cycles.XX Updated every 100 door cycles.
Open Recycle Cnt Indicates number of times the Door reversed direction during Opening cycle after sensing:XX An object was struck.XX The amount of friction that surpassed the recycle sensitivity setting.
Close Recycle Cnt Indicates number of times the Door reversed direction during Closing cycle after sensing:XX An object was struck.XX The amount of friction that surpassed the Recycle Sensitivity Setting.
Latest Recycle Position XX Indicates the last recycle position during opening and closing.XX For swing doors it displays the approximate angle from closed at recycle. For slide doors it displays the position in inches from closed.
11 of 22
www.NabcoEntrances.com� Opus�Control�Wiring�and�Programming�Instruction�Quick�Setup�Parts�Guide
Rev 4-1-16 P/N C-00139
SECTION 5: FOLD DOOR WIRING DIAGRAM (ACCESSORIES)
DN 1
341
112
VDC
+12V
DC2
GND
Com
mon
for 1
2V a
nd S
igna
ls3
61In
terio
r Ac�
va�
on
462
Exte
rior A
c� v
a� o
n/Pr
ogra
mm
able
Inpu
t5
6BSw
ing
Door
Con�
nuo
us S
afet
y (d
oor m
ount
ed, s
win
g sid
e Sa
fety
Sen
sor)
Slid
e Do
orHo
ldin
g Be
am6
SWL
Swin
g Do
orSa
fety
with
Loc
kout
(ove
rhea
d, sw
ing
side
safe
ty se
nsor
)Sl
ide
Door
Side
lite
Sens
or7
Out
1Pr
ogra
mm
able
Out
put
AC
UV
ISIO
N
AC
US
EN
SO
R
FOLD
SID
E
AP
RO
AC
H S
IDE
FOLD
SID
E
RE
DW
HIT
E
BLA
CK
GR
EE
N
RE
D
BLU
E
BR
OW
N
WH
ITE
14-1
0823
-01
AC
US
EN
SO
R H
AR
NE
SS
22-9
184
AC
UV
ISIO
N H
AR
NE
SS
22-1
1023
14-8
902
AC
US
EN
SO
R14
-890
2
AC
US
EN
SO
R H
AR
NE
SS
22-9
184
RE
DW
HIT
E
BLA
CK
GR
EE
N
1 2 2 3 1 2 2 4 1 2 2 6
To P
in #
on
Opu
s C
ontro
l
7654321
RO
CK
ER
SW
ITC
H
EX
IT
AUTO
ON
OFF
HO
LD O
PE
N
21-9
823
141312111098
N.O
. BR
EA
K-O
UT
SW
ITC
HE
S
RE
D
to
pin
14
WH
ITE
to
pin
12B
LUE
to
pin
11
BLA
CK
to
pin
8 on
Opu
s
12345
8
BA
B
reak
-out
, Use
d m
ainl
y fo
r slid
ing
door
s, c
an b
e us
ed fo
r ON
/OFF
with
sw
ing
door
s.
9
SQ
Seq
uent
ial a
ctiv
atio
n. S
igna
l to
open
, Sig
nal t
o cl
ose.
10
H
Pro
gram
mab
le in
put
11
M0
Mod
e 0,
Whe
n gr
ound
ed, p
uts
door
into
"One
-Way
" Mod
e, ("
Hol
d-O
pen"
whe
n gr
ound
ed w
ith M
1)12
M
1
M
ode
1, W
hen
grou
nded
, put
s do
or in
to "N
ight
" Mod
e, ("
Hol
d-O
pen"
whe
n gr
ound
ed w
ith M
0)13
O
ut2
Au
x. O
utpu
t 2,
Pro
gram
mab
le o
utpu
t, cl
oses
to G
ND
14
GN
D
Gro
und
(com
mon
) for
all
abov
e si
gnal
s
12 of 22
Opus Control Wiring and Programming Quick Setup Parts Guide www.NabcoEntrances.com
P/N C-00139 Rev 4-1-16
SECTION 6: SWING DOOR WIRING DIAGRAMS (ACCESSORIES)6 .1 Activation
DN 1329
1413
1211
109
8
76
54
32
1
1413
1211
109
8
76
54
32
1
Exterior Push-PlateInterior Push-Plate
COM N.O.
32
4
COM N.O.
All Devices Must BeN.O. Dry Contact
Powered Activation Devices(sensor, card reader, radio receiver, etc.)
Powered Activation Devices
Non-Powered Activation Devices
WARNING!Total Power Consumption Of All Sensors And Powered Activation
Devices Must Not Exceed 750 mA
76
54
32
1
32
4
All Device Outputs Must BeN.O. Dry Contact
76
54
32
1
COMN .O.PWR+ PWR-
1
COMN .O.PWR+ PWR-
Exterior ActivationInterior Activation
RADIORECEIVER
1 12VDC +12VDC2 GND Common for 12V and Signals3 61 Interior Ac� va� on4 62 Exterior Ac� va� on/Programmable Input5 6B Swing Door Con� nuous Safety (door mounted, swing side Safety Sensor)
Slide Door Holding Beam6 SWL Swing Door Safety with Lockout (overhead, swing side safety sensor)
Slide Door Sidelite Sensor7 Out1 Programmable Output
13 of 22
www.NabcoEntrances.com� Opus�Control�Wiring�and�Programming�Instruction�Quick�Setup�Parts�Guide
Rev 4-1-16 P/N C-00139
6 .2 Activation using Old ON/OFF/Hold-Open Switch
DN 1330
1 12VDC +12VDC2 GND Common for 12V and Signals3 61 Interior Ac� va� on4 62 Exterior Ac� va� on/Programmable Input5 6B Swing Door Con� nuous Safety (door mounted, swing side Safety Sensor)
Slide Door Holding Beam6 SWL Swing Door Safety with Lockout (overhead, swing side safety sensor)
Slide Door Sidelite Sensor7 Out1 Programmable Output
1413
1211
109
8
76
54
32
1
1413
1211
109
8
76
54
32
1
Exterior Push-PlateInterior Push-Plate
COM N.O. COM N.O.
All Devices Must BeN.O. Dry Contact
Powered Activation Devices(sensor, card reader, radio receiver, etc.)
Powered Activation Devices
Non-Powered Activation Devices
WARNING!Total Power Consumption Of All Sensors And Powered Activation
Devices Must Not Exceed 750 mA
All Device Outputs Must BeN.O. Dry Contact
COM N.O.PWR+ PWR- COM N.O.PWR+ PWR-
Exterior ActivationInterior Activation
RADIORECEIVER
76
54
32
1
32
4
RED BLUE
BLACK14
1312
1110
98
8
WHITE
Off
Hold Open
On
Off
76
54
32
1
32
4
1
RED BLUE
BLACK
1413
1211
109
8
8
WHITE
Off
Hold Open
On
Off
14 of 22
Opus Control Wiring and Programming Quick Setup Parts Guide www.NabcoEntrances.com
P/N C-00139 Rev 4-1-16
6 .3 Safety
DN 1
331
112
VDC
+12V
DC2
GND
Com
mon
for 1
2V a
nd S
igna
ls3
61In
terio
r Ac�
va�
on
462
Exte
rior A
c� v
a� o
n/Pr
ogra
mm
able
Inpu
t5
6BSw
ing
Door
Con�
nuo
us S
afet
y (d
oor m
ount
ed, s
win
g sid
e Sa
fety
Sen
sor)
Slid
e Do
orHo
ldin
g Be
am6
SWL
Swin
g Do
orSa
fety
with
Loc
kout
(ove
rhea
d, sw
ing
side
safe
ty se
nsor
)Sl
ide
Door
Side
lite
Sens
or7
Out
1Pr
ogra
mm
able
Out
put
141312111098
76543217654321
2 4
CO
MN
.O.
PW
R+
PW
R-
1
Doo
r Mou
nted
App
roac
h S
ide
Sen
sor
Doo
r Mou
nted
Sw
ing
Sid
e S
enso
r
CO
MN
.O.
PW
R+
PW
R-
5 6
CO
M
N.O
.
PW
R+
PW
R-
Ove
rhea
dS
win
g S
ide
Sen
sor
7654321
1413121110987654321
SAFE
TY S
ENSO
RS W
ITH
MO
NIT
ORI
NG
FU
NCT
ION
BODY
GU
ARD
(and
oth
er se
nsor
s usin
g Bo
dyGu
ard
type
sign
al)
MO
NIT
OR
For s
afet
y se
nsor
s equ
ippe
d w
ith a
mon
itorin
g fu
nc� o
n,Te
rmin
al 7
shou
ld b
e co
nnec
ted
to th
e m
onito
r inp
ut o
f the
sens
or.
Out
1 (t
erm
inal
7) m
ust b
e se
t to
"Sen
sor H
ealth
Che
ck".
Se
e pr
ogra
mm
ing
inst
ruc�
ons
for d
etai
ls.
DAT
A+
DAT
A�Fo
r saf
ety
sens
ors e
quip
ped
with
Bod
yGua
rd ty
pe lo
ck-o
ut si
gnal
,co
nnec
t Dat
a+ to
term
inal
1 (1
2vdv
), an
d Da
ta- t
o Te
rmin
al 1
3 (o
ut 2
).
Out
2 (t
erm
inal
13)
mus
t be
set t
o "B
odyG
uard
Out
put"
. Se
e pr
ogra
mm
ing
inst
ruc�
ons
for d
etai
ls.
!!!W
ARN
ING
!!!
Tota
l Pow
er C
onsu
mp�
on
of a
ll Se
nsor
s and
Pow
ered
Ac�
va�
on
Devi
ces M
ust N
ot E
xcee
d 75
0 m
A
15 of 22
www.NabcoEntrances.com� Opus�Control�Wiring�and�Programming�Instruction�Quick�Setup�Parts�Guide
Rev 4-1-16 P/N C-00139
6 .4 Lock
DN 1
332
141312111098
7654321
* Fai
l-Sec
ure
Ele
ctric
Stri
ke
* Fai
l-Sec
ure
Lock
Sho
wn,
Fail-
Saf
e an
d M
ag-L
ocks
will
use
N
.C. i
nste
ad o
f N.O
.
Pow
er S
uppl
y Fo
rE
lect
ric S
trike
N.O
.
CO
MN
.C.
Varis
tor
(MO
V, T
VS
)!!
! WAR
NIN
G!!
! L
OCK
S RE
QU
IRE
SEPA
RATE
PO
WER
SU
PPLY
Lock
s sho
uld
not b
e po
wer
ed b
y th
e O
pus C
ontr
ol
Aux.
Out
put 3
Not
e: M
ust a
djus
t Se�
ngs
for A
uxill
iary
Out
put #
3 fo
r Typ
e of
Ele
ctric
Loc
k
16 of 22
Opus Control Wiring and Programming Quick Setup Parts Guide www.NabcoEntrances.com
P/N C-00139 Rev 4-1-16
6 .5 Standard Wiring for Single Full Automatic
DN 1
519
!!! W
ARN
ING
!!!
TOTA
L PO
WER
CO
NSU
MPT
ION
OR
ALL
SEN
SORS
MU
ST N
OT
EXCE
ED 7
50 m
A
ON
/OFF
/Hol
d-O
pen
Switc
hP/
N A
-008
05
CO
M
N.O
.
PW
R+
PW
R-
CO
M
N.O
.
PW
R+
PW
R-
CO
MN
.O.
PW
R+
PW
R-
CO
MN
.O.
PW
R+
PW
R-
Ac� v
a� o
nSe
nsor
Ove
rhea
dSw
ing
Side
Sen
sor
(if u
sed) Do
or M
ount
edAp
proa
ch S
ide
Sens
or
Door
Mou
nted
Swin
g Si
de S
enso
r
17 of 22
www.NabcoEntrances.com� Opus�Control�Wiring�and�Programming�Instruction�Quick�Setup�Parts�Guide
Rev 4-1-16 P/N C-00139
6 .6 Standard Wiring for Simultaneous Pair Full Automatic
DN 1520
!!! WARNING!!!TOTAL POWER CONSUMPTION OF ALL SENSORS CONNECTED
TO EACH CONTROL MUST NOT EXCEED 750 mA
ON/OFF/Hold-Open SwitchP/N A-00805
Ac� va� onSensor
OverheadSwing Side Sensor
(if used)
Door MountedApproach Side Sensor
Door MountedSwing Side Sensor
76
54
32
1
32
COM
N.O.
PWR+PWR-
1
RED
BLUE
BLACK
1413
1211
109
8
8
WHITE
1413
1211
109
8
76
54
32
1
6
45
COMN.O. PWR+PWR-
COM N.O.PWR+PWR-
COMN.O. PWR+PWR-
COM N.O.PWR+PWR-
1413
1211
109
8
76
54
32
1
76
54
32
1
21
45
COM
N.O.
PWR+
PWR-
Off
Hold Open
On
Off
Door MountedApproach Side Sensor
Door MountedSwing Side Sensor
OPUS Sim-Pair HarnessP/N M-01680
18 of 22
Opus Control Wiring and Programming Quick Setup Parts Guide www.NabcoEntrances.com
P/N C-00139 Rev 4-1-16
6 .7 Connecting a Break-Out Switch
DN 1521
BREAK�OUT WITH ON/OFF/HOLD�OPEN SWITCH
ON/OFF/Hold-Open SwitchP/N A-00805
Break-out Switch wired in series withBlue Wire from ON/OFF/Hold-Open Switch
Panic Latch Kit P/N A-00430 (Clear)
A-70430 (Dark Bronze)
RED
RED
BLUE
BLACK
1413
1211
109
8
8
WHITE
Off
Hold Open
On
Off
RED
1413
1211
109
8
8
14
BA (break-out input) must be set to N.C. on the Opus Control (is by default).Panic Latch must be mounted so that the:• Switch is open when the Door is broken out.• Closed when not broken-out
BREAK�OUT WITHOUT ON/OFF/HOLD�OPEN SWITCH
BA (break-out input) must be set to N.C. on the Opus Control (is by default).Panic Latch must be mounted so that the:• Switch is open when the Door is broken out.• Closed when not broken-out
19 of 22
www.NabcoEntrances.com� Opus�Control�Wiring�and�Programming�Instruction�Quick�Setup�Parts�Guide
Rev 4-1-16 P/N C-00139
6 .8 Other
DN 1333
1413
1211
109
8
76
54
32
1
1413
1211
109
8
8 BA Break-out, Used mainly for sliding doors, can be used for ON/OFF with swing doors. 9 SQ Sequential activation. Signal to open, Signal to close.10 H Programmable input 11 M0 Mode 0, When grounded, puts door into "One-Way" Mode, ("Hold-Open" when grounded with M1)12 M1 Mode 1, When grounded, puts door into "Night" Mode, ("Hold-Open" when grounded with M0)13 Out2 Aux. Output 2, Programmable output, closes to GND14 GND Ground (common) for all above signals
For connecting to a second Opus for
Sim-Pair, Astragal, Sequencing
1413
1211
109
8
10
14
Example of a switch being used to turn on/off Power-Close and Hold Closed.Programmable input "H" (terminal 10)
would be set "Spring Close Only".
To see other options for the programmable input, see programming
and input settings.
PROGRAMMABLE INPUT
6 .9 Motor Wiring
6 .9 .1 GT300/400/500/600/1400
DN 1315
ENCODER MOTOR WIRING NON�ENCODER WIRING
Handing Harness (Right Hand Units)
To Opus Control To MotorTo MotorNon-Encoder
Adapter Harness
To Opus ControlMotor
Harness
To Door Posi� onSwitches
Brake Module
20 of 22
Opus Control Wiring and Programming Quick Setup Parts Guide www.NabcoEntrances.com
P/N C-00139 Rev 4-1-16
6 .9 .2 GT710/8710
DN 1327
ENCODER MOTOR WIRING
To Opus ControlMotor Harness
Motor Fuse
To Motor
NON�ENCODER MOTOR WIRINGNon-Encoder Adapter Motor Harness
To Door Posi� on Switches
To Motor
Motor Fuse
Motor HarnessTo Opus Control
SECTION 7: TROUBLESHOOTINGIf the Opus detects an error, the LCD backlight will start flashing and display an Error message within the Error Screen or before the Level Two Screen.
Table 1: Error Message
Error Msg Description ResolutionRecycle Warning Recycle was detected more than (5) times while
opening or closing cycle continuously.XX Check Door resistance and Door Path for resistance to movement.•XIt may be necessary to adjust the Recycle
Sensitivity.MPU Error Microprocessor detects errors within the Internal or
External Circuits.XX This could be just a fluke.•XIf the Error occurs repeatedly, please replace
the Opus Control.Drive Circuit Error If the Drive Circuit detects an unusual state, the
Opus will stop door movement. Possible causes are:XX Over current at motorXX Abnormal voltage at Motor CircuitXX Abnormal value from Motor Current detection.
XX Check the Motor connection. •XOpus Control may not be connected to the
motor. •XMotor wire may be shorted.
XX If Motor connection is normal; the cause could be electrical noise.
XX If this error doesn’t occur repeatedly then it’s most likely not an issue.
Communication Error XX CAN-bus Communication ErrorXX Can happen in Simultaneous Pair applications.
Check the CAN-bus Cable between the two Opus Controls.
61 Sensor Error XX The Sensor must support active monitoring.XX This error could occur when the sensors are setup for Health Check through:•XOutput 1,2 or 3•XInput 61, 62, 6B
XX SWL is set for Safety Check and the sensor doesn’t respond to the safety check signal.
Turn the power off and then on to see if the error clears. If not then check the wiring from the sensor to the Output terminal. Possibly replace the sensor.
62 Sensor Error6B Sensor ErrorSWL Sensor Error
Notice: If after troubleshooting a problem, and a satisfactory solution cannot be achieved, please call Nabco Entrances at 1-877-622-2694 between 8 am – 4:30pm Central time for additional assistance .
DO NOT leave any problem unresolved . If the door cannot be repaired immediately, turn off the door and leave it inoperable until repairs can be made . Advise the owner NOT to operate the door in the automatic mode until repairs are effected . NEVER leave a door operating without all safety detection systems operational .
21 of 22
www.NabcoEntrances.com� Opus�Control�Wiring�and�Programming�Instruction�Quick�Setup�Parts�Guide
Rev 4-1-16 P/N C-00139
DN 1321
1413
1211
109
8
76
54
32
1
21
12
211
2
3 2 1
2 11 2
1 2
3
4
56
8 9 10 1112
7
SERVICE PARTS: OPUS SIDE LOAD UNITS
13
Side LoadItem Part Finish/Sizes/Notes Description
1 M-01546 “CONTROLLER,OPUS”2 A-01003 Not used on GT710 “BRAKE MODULE,OPUS”3 A-01000 “HARNESS,MOTOR,OPUS CONTROL4 M-01072 Single HARNESS,POWER,MAGNUM BOARD5 A-01001 “HARNESS,HANDING,NGT-10”6 A-01002 Not used on GT710 “HARNESS,ADAPTER,NON-ENCOD,OPUS CONTROL7 T-00335 SHCS:10-24x0.313L.8 T-00365 WASHER:5/32IDx3/4ODx.020THK:POLYETHYLE9 V-00552 FUSE;5A;GMA;5X20mm
10 V-00098 SADDLE, WIRE11 V-00283 GT710 Only SPACER,CIRCUIT BOARD,STANDOFF12 T-00364 GT710 Only SHCS:10-24x1.000L.:ZINC13 M-01680 Simultaneous Pair “HARNESS,OPUS CONTROL,SIM PAIR”
123456789
10111213
22 of 22
Opus Control Wiring and Programming Quick Setup Parts Guide www.NabcoEntrances.com
P/N C-00139 Rev 4-1-16
DN 1320
1413
1211
109
8
76
54
32
1 21
12
211
2
3 2 1
2 11 2
1 2 3 456
7
8 9 10 11 12 13
SERVICE PARTS: OPUS BOTTOM LOAD UNITS
14
Bottom LoadItem Part Finish/Sizes/Notes Description
1 M-01546 “CONTROLLER,OPUS”2 M-01066 CHASSIS, CONTROL3 M-01040 CONTROL BOX MOUNT4 A-01003 “BRAKE MODULE,OPUS”5 A-01001 “HARNESS,HANDING,NGT-10”6 A-01002 “HARNESS,ADAPTER,NON-ENCOD,OPUS CONTROL7 A-01000 “HARNESS,MOTOR,OPUS CONTROL8 M-01072 Single HARNESS,POWER,MAGNUM BOARD9 T-00367 NUT:HEX:10-24:ZN
10 V-00283 SPACER,CIRCUIT BOARD,STANDOFF11 T-00369 PHMS:10-24x0.500L.:PHIL:ZINC12 V-00552 FUSE;5A;GMA;5X20mm13 V-00098 SADDLE, WIRE14 M-01680 Simultaneous Pair “HARNESS,OPUS CONTROL,SIM PAIR”
123456789
1011121314