Presents Course Sponsor : Nova Polymers, Inc Eight Evans St Fairfield, NJ 07004 Phone: (973) 882-7890 Fax: (973) 882-5614 E-mail: [email protected] Web: www.novapolymers.com Course Number : 08RMID Course Title : ADA Requirements for Room Identification Signs An AIA Continuing Education Program Credit for this course is 1 AIA/CES Learning Units

Upload: zen-marketing-llc

Post on 23-Mar-2016

220 views

Category:

Documents


1 download

DESCRIPTION

Program #: 08RMID Credits: 1AIA CES LU Program: ADA Requirements for Room Identification Signs HSW: Yes Description: This course will educate the attendee about current ADA requirements as it relates to room identification signs, and will also provide education about the most commonly used material (photopolymer) for ADA compliant signage

TRANSCRIPT

Page 1: Room Identification Signage

Presents

Course Sponsor: Nova Polymers, Inc Eight Evans St Fairfield, NJ 07004 Phone: (973) 882-7890 Fax: (973) 882-5614

E-mail: [email protected] Web: www.novapolymers.com

Course Number: 08RMID

Course Title: ADA Requirements for Room Identification Signs

An AIA Continuing Education Program Credit for this course is 1 AIA/CES Learning Units

Page 2: Room Identification Signage

Nova Polymers, Inc. is a Registered Provider with The American Institute of

Architects Continuing Education Systems.

Credit earned on completion of the program will be reported to CES Records

for AIA members.

Page 3: Room Identification Signage

This program is registered with the AIA/CES for continuing professional education. As such, it does not include content

that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in

any material or product.

Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation .

Page 4: Room Identification Signage

Copyright Materials

This presentation is protected by US and International copyright laws. Reproduction,

distribution, display and use of the presentation without written permission of the speaker is

prohibited.

Page 5: Room Identification Signage

•  What Is ADA? •  Regulations Relating To ADA Compliance •  States and the ADA including Title 24 •  Understand General Terminology •  Signage Design Restrictions •  What Areas Require ADA Compliant Signage? •  How To Make A Photopolymer Sign. •  Understanding Photopolymer And Its Applications

5

Course Objectives

Page 6: Room Identification Signage

• The Americans with Disabilities Act was signed into law in July 1990 by former President George H.W. Bush.

•  In July 1991 the ADA legislation and supporting guidelines were published in the Department of Justice Federal Register.

•  The ADA protects the civil rights of people with disabilities in employment and access to good and services.

What is ADA?

Page 7: Room Identification Signage

• The ADA is broken into sections (Title II, Title III) and enforced by the Department of Justice (DOJ) and the Department of Transportation (DOT).

• Title III of the ADA applies to places of public accommodation and commercial facility open to public access and is enforced by the DOJ. Title III includes, but is not limited to, restaurants, schools, museums, public office buildings, retail and social service establishment.

• The most prevalent area of signage affected by the ADA under Title III is room identification and wayfinding.

What is ADA?

Page 8: Room Identification Signage

• Under the ADA any person may file a federal lawsuit, either for individual discrimination or as a class action.

• Under the ADA any person may request the DOJ to investigate and act upon an ADA discrimination claim.

• The attorney General may also file a civil action suit in cases of general public importance.

What is ADA?

Page 9: Room Identification Signage

Legal Remedies

• Although the ADA covers all public facilities, the court can order any facility ADA accessible.

• The court can also award monetary damages of up to $55,000 for the first ADA violation and up to $110,000 for each subsequent violation, emphasizing the importance of understanding how to comply with ADA laws.

What is ADA?

Page 10: Room Identification Signage

• Without proper signs a blind person cannot find their way around a building.

• By not being able to find doorways and other amenities; they face functional barriers.

• These barriers are every bit as daunting as structural barriers are to those who require a ramp to access a building but it is not there.

Why ADA Signs Are Important

Page 11: Room Identification Signage

There are two primary groups of people the ADA focuses on relating to signage; the blind and the visually impaired.

Two Groups and Their Wayfinding Needs

Page 12: Room Identification Signage

The functionally blind make up 2-3% of the population and cannot see signs, interior changes, color, or type.

The Blind

Page 13: Room Identification Signage

When walking, they expect information to be where their hands fall and where their feet and cane follow.

The functionally blind make up 2-3% of the population, and only a very small percentage of this group are able to read Braille or raised letters.

The Blind

Page 14: Room Identification Signage

The visually impaired can distinguish type and color, but with an increased level of difficulty thus requiring different means of accessibility.

The Visually Impaired

Page 15: Room Identification Signage

People with visual disabilities make up at least 25% of the population and among people older than 65, this figure can be as high as 75%.

Ironically, although this population is so large, they are often the most neglected, both in design practice and in code enforcement.

The Visually Impaired

Page 16: Room Identification Signage

ADA Regulations… The Process

Page 17: Room Identification Signage

The American Nation Standard Institute ICC/ANSI A117.1

The ICC/ANSI A117.1 primarily provides the basis of the accessibility sections of the International Building Code (IBC) and is the basis for the federal ADAAG published by the Access Board.

The A117.1 Committee consists of several trade organization, design associations, disability advocacy organizations, and other experts.

American Nation Standard Institute

Page 18: Room Identification Signage

The American Nation Standard Institute ICC/ANSI A117.1

The A117.1 Standard is available for adoption by jurisdictions internationally and is intended to be used as a reference in accordance to establishing the jurisdictions law as in the case of the ADAAG.

The ANSI A117.1 - 2003 Standard was approved on November 26, 2003 and was used to develop the 2004 ADAAG from the US Access Board.

The committee recently concluding the 2008 cycle which will undoubtedly be seen in a future version the ADAAG.

American Nation Standard Institute

Page 19: Room Identification Signage

United States Access Board

The ADA Accessibility Guidelines (ADAAG)

The Unites States Access Board develops the ADAAG. These guidelines serve as the baseline for standards used to enforce the ADA by the DOJ and DOT. The ADAAG derives from an earlier Federal standard called the Uniform Federal Accessibility Standards (UFAS).

Source: American with Disabilities Act and Architectural Barriers Act Accessibility Guidelines

Page 20: Room Identification Signage

Source: American with Disabilities Act and Architectural Barriers Act Accessibility Guidelines

The ADA Accessibility Guidelines (ADAAG)

The Board’s guidelines serve as the baseline for standards used to enforce the ADA.

It is these standards, not the Board’s guidelines, which the public must follow.

United States Access Board

Page 21: Room Identification Signage

“Guidelines” … “Standards” … what’s the difference?

Guidelines versus standards … Guidelines are issued by the Board, standards by designated agencies such as DOJ and DOT.

Standards are what the public must follow to comply with the laws; the guidelines are what these agencies must follow in setting or updating their standards.

Source: American with Disabilities Act and Architectural Barriers Act Accessibility Guidelines

United States Access Board

Page 22: Room Identification Signage

United States Access Board

The original ADAAG issued by the DOJ in 1991 is still being enforced on the Federal level. However, on July 23, 2010 the DOJ signed final regulations revising the ADA to include the 2004 ADAAG. This was published in the Federal Register September 15, 2010 and will take effect March 15, 2011.

*Compliance with the 2010 Standards for Accessible Design is permitted as of September 15, 2010, but not required until March 15, 2012.

Page 23: Room Identification Signage

States and The ADA

Page 24: Room Identification Signage

States and The ADA

The DOJ is currently enforcing the original ADAAG and has not yet adopted the 2004 ADAAG.

While all projects are subject to the Federal ADA many states have adopted the newer 2004 ADAAG or, in the case of California, have their own state regulations.

A state can modify their building codes as long as they get approval from the DOJ.

Page 25: Room Identification Signage

States and The ADA

Enforcement of state codes is done by local state officials who interpret the codes and guidelines.

If there is any discrepancies or confusions as to what the code means, then consulting with your local official to get his or her interpretation is highly recommend.

In truth, there are only a few key differences in the codes that have an effect on signage. However, these difference are important to know when designing, fabricating and/or installing signage.

Page 26: Room Identification Signage

States and The ADA

1991  ADA 2004  ADAAG Own  Accessibility  Code

Alabama Alaska  –  no  enforcement California  –  Title  24

Arizona Connec7cut Kentucky

Arkansas Idaho Maryland

Colorado Indiana  –  pending  DOJ  Cert. MassachuseEs

Delaware Maine  –  pending  DOJ  Cert. Minnesota

District  of  Colombia Michigan North  Carolina

Florida Montana Tennessee

Georgia Nevada Texas  –  substan7ally  follows  1991ADAAG  with  small  changes

Hawaii New  Hampshire

Illinois New  Jersey

Iowa New  Mexico

Kansas New  York

Louisiana North  Dakota

Mississippi Oklahoma

Missouri Oregon

Ohio Pennsylvania

Vermont Rhode  Island

West  Virginia South  Carolina

Wyoming South  Dakota

Utah  –  pending  DOJ  Cert.

Virginia

Washington  –  pending  DOJ  Cert

Wisconsin

Page 27: Room Identification Signage

California Codes - Title 24

Title 24 of the California Code of Regulations, known as the California Building Standard Code or simply “Title 24” contains the regulations that govern the construction of buildings in California. As noted, states can modify their respective building codes.

Title 24 has a few important differences related to signage. While there are others, we're going to focus on three key areas relating to permanent room identification signage.

Page 28: Room Identification Signage

California Codes - Title 24

The first deals with Grade II Braille.

Grade II Braille incorporates the use of 189 contractions and short-form words, and is now the standard Braille used in most applications across the states.

Title 24, which uses Grade II Braille, requires in section 1117B.5.6 that the spacing of the individual Braille cells be further apart than what is required under the original ADA.

Page 29: Room Identification Signage

California Codes - Title 24

Page 30: Room Identification Signage

California Codes - Title 24

The second difference in Title 24 relating to Braille is the placement of Braille on the sign.

All codes require Braille to be a minimum of 3/8" from tactile characters and raised boards.

Title 24 in section 1117B.5.5 however places a maximum distance of 1/2" from the raised characters.

Page 31: Room Identification Signage

California Codes - Title 24

The third point of interest is the requirement for all accessible toilet and bathing facilities to have the “International Symbol of Accessibility” mounted on the door leading into the facility.

Page 32: Room Identification Signage

California Codes - Title 24

The men’s sanitary facilities are required to be identified by an equilateral Triangle ¼” inch thick with edges 12” inches long and a vertex pointing upward (see figure 2.1).

figure2.1

Page 33: Room Identification Signage

California Codes - Title 24

The women’s sanitary facilities are required to be identified by a Circle, ¼” inch thick and 12” inches in diameter (see figure 2.2).

figure2.2

Page 34: Room Identification Signage

California Codes - Title 24

Unisex sanitary facilities is required to be identified by a Circle ¼” thick, 12” inches in diameter with a ¼” thick Triangle superimposed on the circle and within the 12” inch diameter (see figure 2.3)

figure2.3

Page 35: Room Identification Signage

Signs Covered by the ADA:

Page 36: Room Identification Signage

Signs Covered by the ADA:

Identification of permanent rooms & spaces - Wall Mounted

Directional & Informational Signs – Wall mounted

Directional & Informational Signs - Ceiling or Projecting Wall Mount

Page 37: Room Identification Signage

Exempt from ADA Requirements:

•  Building Directories •  Personnel Signs •  Menu-boards •  Hours of Operation, etc.

These are considered “Temporary” and are not required to comply with ADA guidelines.

Page 38: Room Identification Signage

What constitutes a permanent room or space? Where tactile signs required? •  Restrooms •  Exits •  Room Numbers •  Other room designations not likely to change.

Permanent Room ID - Wall Mounted

Page 39: Room Identification Signage

Permanent Room ID - Wall Mounted

Current Guidelines:

Required to be Tactile with 1/32” minimum raised copy, accompanied by Grade II Braille.

Tactile character height minimum is 5/8”, maximum 2”

Page 40: Room Identification Signage

New provision for Separate Tactile and Visual Messages. This is becoming highly recommended as part of the new ADA code.

Permanent Room ID - Wall Mounted New ADAAG Guidelines:

Example

The attributes that make type legible to the visual reader are different than for the tactile reader.

Page 41: Room Identification Signage

New provision for Separate Tactile and Visual Messages, are to detach the needs of the blind and the needs of the disabled.

A. Tactile characters shall be: 1. 1/2 inch minimum height. 2. 3/4" maximum height. 3. Not required to contrast with

the background.

Permanent Room ID - Wall Mounted New ADAAG Guidelines:

Page 42: Room Identification Signage

B. Visual characters shall be: 1. Uppercase and/or lowercase. 2. Style shall be conventional in form. Simple serifs are allowed. 3. Stroke thickness shall be 10 percent minimum and 30 percent

maximum of the letter height. 4. Spacing between characters shall be 10 percent minimum and

35 percent maximum of the character height. 5. Minimum character height is 5/8", providing height above floor is

below 70 inches and minimum viewing distance is 6 feet or less.

If minimum viewing distance is greater than 6 feet, increase letter height by 1/8 inch for each foot.

Permanent Room ID - Wall Mounted New ADAAG Guidelines:

Page 43: Room Identification Signage

VISUAL: Serifs, Upper & Lower Case, Variable Stroke Width, Color, etc…

TACTILE: Requires tracing finger along a thin character bead with very wide letter spacing.

Braille Placement - Directly below corresponding text.

Page 44: Room Identification Signage

Guidelines: • Wide Kerning - No less than 1/8” between the 2 closest points of adjacent

characters.

Permanent Room ID - Wall Mounted New ADAAG Guidelines:

Page 45: Room Identification Signage

Permanent Room ID - Wall Mounted New ADAAG Guidelines:

703.3.2 Position. Braille shall be positioned below the corresponding text. If text is multi-lined, Braille shall be placed below the entire text.

Braille shall be separated 3/8 inch (9.5 mm) minimum from any other tactile characters and 3/8 inch (9.5 mm) minimum from raised borders and decorative elements.

Page 46: Room Identification Signage

Permanent Room ID - Wall Mounted New ADAAG Guidelines:

Page 47: Room Identification Signage

Permanent Room ID - Wall Mounted New ADAAG Guidelines:

EXCEPTION:

Braille provided on elevator car controls shall be separated 3/16 inch (4.8 mm) minimum and shall be located either directly below or adjacent to the corresponding raised characters or symbols.

Page 48: Room Identification Signage

Permanent Room ID - Wall Mounted New ADAAG Guidelines:

Braille Placement - Directly below corresponding text.

Correct

Not Allowed

Not Allowed

Page 49: Room Identification Signage

Permanent Room ID - Wall Mounted Location

The law requires that signs be configured and displayed as follows:

Permanent room I.D. signs must be mounted on the latch side of the door, 48" minimum and 60” maximum from the finished floor to the bottom baseline of text.

Page 50: Room Identification Signage

Permanent Room ID - Wall Mounted Location

What if there is no wall space on the latch side of the door? Double Doors?

Page 51: Room Identification Signage

Permanent Room ID - Wall Mounted Location

703.4.2 Location. Where a tactile sign is provided at a door, the sign shall be located alongside the door at the latch side. Where a tactile sign is provided at double doors with one active leaf, the sign shall be located on the inactive leaf. Where a tactile sign is provided at double doors with two active leafs, the sign shall be located to the right of the right hand door.

Page 52: Room Identification Signage

Permanent Room ID - Wall Mounted Location

703.4.2 Location. Where there is no wall space at the latch side of a single door or at the right side of double doors, signs shall be located on the nearest adjacent wall. Signs containing tactile characters shall be located so that a clear floor space of 18 inches (455 mm) minimum by 18 inches (455 mm) minimum, centered on the tactile characters, is provided beyond the arc of any door swing between the closed position and 45 degree open position.

EXCEPTION: Signs with tactile characters shall be permitted on the push side of doors with closers and without hold-open devices.

Page 53: Room Identification Signage

Permanent Room ID - Wall Mounted

FINISH & CONTRAST:

• Characters must be eggshell, matte or non-glare finish. • Characters must contrast with background… (light on dark) or (dark on light)

Page 54: Room Identification Signage

Permanent Room ID - Wall Mounted

Pictograms:

703.6.1 Pictogram Field. Pictograms shall have a field height of 6 inches (150 mm) minimum.

• Characters and Braille shall not be located in the pictogram field.

Page 55: Room Identification Signage

Directional & Information Signs – Ceiling or Projecting Wall Mount

New ADAAG Guidelines: FINISH & CONTRAST:

• Characters & background must be eggshell, matte or non-glare finish. • Characters must contrast with background… (light on dark) or (dark on light)

Page 56: Room Identification Signage

Directional & Information Signs – Ceiling or Projecting Wall Mount

New ADAAG Guidelines: SYMBOLS:

• The size of symbols used for directional signs is not regulated.

Page 57: Room Identification Signage

Directional & Information Signs – Ceiling or Projecting Wall Mount

New ADAAG Guidelines: TACTILE? / MINIMUMS:

• Obviously not required to be tactile. •  Minimum to be 2” height, providing sign is no higher than 10’ above floor. Minimum character heights established based on viewing distance. •  Mount high enough so that 80” clear head space is maintained.

Note: Old ADDAG required minimum height to be 3”

Page 58: Room Identification Signage

Directional & Information Signs – Ceiling or Projecting Wall Mount

New ADAAG Guidelines:

MINIMUMS: • 

Letters Minimum to be 2” height, providing sign is no higher than 10’ above floor. Minimum character heights established based on viewing distance.

Page 59: Room Identification Signage

Understanding Photopolymer & It’s Applications

Page 60: Room Identification Signage

Understanding Photopolymer And Its Applications

What is Photopolymer?

Photopolymer is a photo-sensitive synthetic compound that hardens when exposed to an ultraviolet light source. Photopolymer is available in both liquid and sheet form and has a number of applications that span a multitude of industries – ranging from flexographic printing, architectural modeling, rubber stamps and Architectural and way-finding signage.

Page 61: Room Identification Signage

Understanding Photopolymer And Its Applications

What is Photopolymer?

• A 1/32” clear, high resolution photopolymer layer of material is extruded to a variety of base substrates. The extrusion process combined with the cross linking of the photopolymer molecules creates a chemical weld between the two surfaces; creating an integral bond.

• Compared to the tedious routing and engraving methods, photopolymer signs are easily produced and cost-efficient and allow the creation of an integral sign, which is almost always what is specified in educational facilities due to vandalism concerns.

Page 62: Room Identification Signage

Understanding Photopolymer And Its Applications

Photopolymer is the predominant material used for manufacturing ADA-compliant signage.

The ADA compliant sign material is manufactured by extruding a 1/32” photopolymer layer to a variety of base substrates.

This process ensures a consistent an compliant height of all tactile areas.

Page 63: Room Identification Signage

Understanding Photopolymer And Its Applications

This material combines the moisture resistant durability of photopolymer (.001 moisture absorption ratio) with a hard acrylic-like PETG plastic base.

The unique combination of PETG with a moisture resistant photopolymer layer makes the most versatile sign material on the market today.

The PETG base of signs have the density of acrylic and the added benefit of heat forming capabilities without fragile handling characteristics.

Page 64: Room Identification Signage

Understanding Photopolymer And Its Applications

•  The signs are shatterproof and can be thermo or cold formed creating shapes and bends not possible with other materials. The PETG base is odorless and user friendly. It can be sheared, drilled, sawed or routed without chipping or breakage.

•  Polymer layer will not decay in most environments and can be easily machined without cracking or chipping.

•  All photopolymer sign material is not created equal. Make sure the material you are specifying or fabricating has a low moisture absorption ratio.

Page 65: Room Identification Signage

Clear Base Photopolymer

Solutions (PETG)

Page 66: Room Identification Signage

What is PETG?

• PETG, glycol-modified polyethylene terephthalate, is a co polyester that is a clear amorphous thermoplastic.

• PETG exhibits has high stiffness, hardness, and good impact strength.

Page 67: Room Identification Signage

What is PETG?

PETG exhibits good resistance to dilute aqueous solutions of mineral acids, bases, salts, and soaps. PETG also has good resistance to aliphatic hydrocarbons, alcohols, and a variety of oils.

Page 68: Room Identification Signage

Clear Base Photopolymer Solutions (PETG)

Photopolymer layer is a moisture resistant, with a Durometer hardness rating of 80 Shore D.

Page 69: Room Identification Signage

Clear Base Photopolymer Solutions (PETG)

All sheets come with a high-tack back liner to prevent scratching.

The clear PETG base of all sheets contains a co-extruded UV inhibitor to block unwanted light contamination.

Page 70: Room Identification Signage

Clear Base Photopolymer Solutions (PETG)

Recyclable and Biodegradable

• PETG waste (such as small off cuts) can be sent to a recycling facility after the photopolymer has been removed.

• The photopolymer effluent is 100% biodegradable and can be disposed of into any public sewer system.

Page 71: Room Identification Signage

Code Requirements - Flammability

Signs made from photopolymer or PETG thermoplastic will meet all flammability requirements for light transmitting plastics specified by

–  BOCA Building Officials and Code Administrators

–  SBCCI Southern Building Code Congress International

–  ICBO International Conference of Building Officials

Page 72: Room Identification Signage

Code Requirements – Rate of Burn

Signs made from photopolymer on PETG thermoplastic when tested according to ASTM D 635 will burn less than one inch. It therefore meets the requirements for classification CC1 at a nominal thickness of 1/16".

Page 73: Room Identification Signage

Code Requirements – Vertical Burn

Products made from photopolymer on PETG thermoplastic is classified by UL as 94V-2 in a thickness of 1/8" or greater. A sheet thickness less than 1/8" is classified as 94 HB.

Page 74: Room Identification Signage

Other Ratings

Self Ignition Temperature (ASTM D 1929))

According to tests by an independent laboratory, signs made from photopolymer on PETG thermoplastic have a self ignition temperature of 800 degrees Fahrenheit (425 C).

This test result exceeds the BOCA requirement of 650 degrees Fahrenheit (345 C) when tested by ASTM D 1929.

ASTM D1929 - 96(2001)e1 Standard Test Method for Determining Ignition Temperature of Plastics

Page 75: Room Identification Signage

How to manufacture

photopolymer signage

Page 76: Room Identification Signage

How To Make A Photopolymer Sign?

Photopolymer is an efficient, environmentally conscious and innovative material for way finding and ADA-compliant signage.

Unlike other processes where the tactile area and Braille and applied with glue; photopolymer creates an integral sign as the photo reactive layer becomes one with a variety of base substrates.

As the photopolymer cross-links when exposed to ultraviolet light, it hardens and etches into the base of the material.

Page 77: Room Identification Signage

Step 1 - Contact with film negative

Step 2 - Exposure with UV Light

Step 3 - Wash in Plain Tap Water

Step 4 - Drying

Step 5 - Post exposure

The 5 step process in making photopolymer signage:

Processing Photopolymer

Page 78: Room Identification Signage

Setting Up Photopolymer Panel For Exposure

Page 79: Room Identification Signage

Negative On Photopolymer Panel Under Vacuum

Page 80: Room Identification Signage

Photopolymer Panel After Washout

Page 81: Room Identification Signage

Photopolymer Panel In Dryer

Page 82: Room Identification Signage

Processed Photopolymer Panel

Page 83: Room Identification Signage

Efficiency, Cycle Time and Cost Control Based on the processing times of photopolymer, the fabricator can yield 11 production cycles through the equipment each hour.

Based on an average sign panel size of 8” x 8”, the fabricator is capable of producing over 400 ADA compliant signs each work day.

Using materials that have patterns or colors extruded into the material will also reduce the amount of time required to decorate the panel.

Since signs are typically the last component to be manufactured, using a material that has a short cycle time will help in eliminating delays, while complimenting the design of your project.

Page 84: Room Identification Signage

Presents End of AIA CES Program

Course number 08RMID

ADA Requirements for Room Identification Signs