Infrared Imaging Solutions Inc 1-877-526-IRIS

ROOF INSPECTION USING INFRARED THERMOGRAPHY

Kenaidan Contracting Ltd

Barrie, ON

Brian Jastrow Level III Thermographer

5/11/2011

Report prepared by: Haley Ryan

Page 2: ROOF INSPECTION USING INFRARED THERMOGRAPHY · 2014. 4. 7. · Infrared Imaging Solutions Inc 1-877-526-IRIS ROOF INSPECTION USING INFRARED THERMOGRAPHY Kenaidan Contracting Ltd Barrie,

Infrared Imaging Solutions Inc 1-877-526-IRIS

Roof Inspection using Infrared Thermography

P a g e | 1

REFERENCE #1

PRIORITY LOCATION EQUIPMENT

Reference Garage Roof

6.7

13.1 °C

7

8

9

10

11

12

13

PARAMETERS ANALYSIS

Date 11/05/2011

Filename IR_6089.jpg

Max Temperature 14.5 °C

Min Temperature 4.5 °C

Thermal variance detected on roof and parapet possibly

caused by moisture infiltration within the membrane.

Verified with moisture meter and marked with orange

spray paint.

Page 3: ROOF INSPECTION USING INFRARED THERMOGRAPHY · 2014. 4. 7. · Infrared Imaging Solutions Inc 1-877-526-IRIS ROOF INSPECTION USING INFRARED THERMOGRAPHY Kenaidan Contracting Ltd Barrie,

Infrared Imaging Solutions Inc 1-877-526-IRIS

Roof Inspection using Infrared Thermography

P a g e | 2

REFERENCE #2

PRIORITY LOCATION EQUIPMENT

NOTE Overall

PARAMETERS ANALYSIS

Date 11/05/2011

Filename IR_6080.jpg

Max Temperature 27.0 °C

Min Temperature -12.1 °C

Large amounts of debris on the roof.

IE: Nails, brackets, razor blades, could cause premature

roof damage.

Page 4: ROOF INSPECTION USING INFRARED THERMOGRAPHY · 2014. 4. 7. · Infrared Imaging Solutions Inc 1-877-526-IRIS ROOF INSPECTION USING INFRARED THERMOGRAPHY Kenaidan Contracting Ltd Barrie,

Infrared Imaging Solutions Inc 1-877-526-IRIS

Roof Inspection using Infrared Thermography

P a g e | 3

REFERENCE #3

PRIORITY LOCATION EQUIPMENT

Reference: Garage Roof

3.5

24.8 °C

5

10

15

20

PARAMETERS ANALYSIS

Date 11/05/2011

Filename IR_6085.jpg

Max Temperature 30.5 °C

Min Temperature -14.6 °C

No Thermal variances due to moisture infiltration detected

across the garage roof around the skylights.

Page 5: ROOF INSPECTION USING INFRARED THERMOGRAPHY · 2014. 4. 7. · Infrared Imaging Solutions Inc 1-877-526-IRIS ROOF INSPECTION USING INFRARED THERMOGRAPHY Kenaidan Contracting Ltd Barrie,

Infrared Imaging Solutions Inc 1-877-526-IRIS

Roof Inspection using Infrared Thermography

P a g e | 4

REFERENCE #4

PRIORITY LOCATION EQUIPMENT

Reference: Garage Roof

0.8

19.3 °C

2

4

6

8

10

12

14

16

18

PARAMETERS ANALYSIS

Date 11/05/2011

Filename IR_6083.jpg

Max Temperature 19.0 °C

Min Temperature -21.3 °C

No thermal variance detected around skylights.

Page 6: ROOF INSPECTION USING INFRARED THERMOGRAPHY · 2014. 4. 7. · Infrared Imaging Solutions Inc 1-877-526-IRIS ROOF INSPECTION USING INFRARED THERMOGRAPHY Kenaidan Contracting Ltd Barrie,

Infrared Imaging Solutions Inc 1-877-526-IRIS

Roof Inspection using Infrared Thermography

P a g e | 5

REFERENCE #5

PRIORITY LOCATION EQUIPMENT

Reference: Garage ROof

5.1

21.0 °C

6

8

10

12

14

16

18

20

PARAMETERS ANALYSIS

Date 11/05/2011

Filename IR_6090.jpg

Max Temperature 21.8 °C

Min Temperature -11.2 °C

No thermal variances due to moisture infiltration around

skylights.

Page 7: ROOF INSPECTION USING INFRARED THERMOGRAPHY · 2014. 4. 7. · Infrared Imaging Solutions Inc 1-877-526-IRIS ROOF INSPECTION USING INFRARED THERMOGRAPHY Kenaidan Contracting Ltd Barrie,

Infrared Imaging Solutions Inc 1-877-526-IRIS

Roof Inspection using Infrared Thermography

P a g e | 6

REFERENCE #6

PRIORITY LOCATION EQUIPMENT

Note Generator Roof

PARAMETERS ANALYSIS

Date 16/05/2011

Filename

Max Temperature 70.0 °C

Min Temperature 3.9 °C

Debris on roof surface will cause premature failure.

Page 8: ROOF INSPECTION USING INFRARED THERMOGRAPHY · 2014. 4. 7. · Infrared Imaging Solutions Inc 1-877-526-IRIS ROOF INSPECTION USING INFRARED THERMOGRAPHY Kenaidan Contracting Ltd Barrie,

Infrared Imaging Solutions Inc 1-877-526-IRIS

Roof Inspection using Infrared Thermography

P a g e | 7

REFERENCE #7

PRIORITY LOCATION EQUIPMENT

Reference: Generator Roof

11.3

20.2 °C

12

14

16

18

20

PARAMETERS ANALYSIS

Date 11/05/2011

Filename IR_6079.jpg

Max Temperature 22.4 °C

Min Temperature -7.2 °C

Thermal variance detected across generator roof (south

section) on 5’ x 6’ section – possibly caused by moisture

infiltration within the membrane. Verified with moisture

meter and marked with orange paint.

Page 9: ROOF INSPECTION USING INFRARED THERMOGRAPHY · 2014. 4. 7. · Infrared Imaging Solutions Inc 1-877-526-IRIS ROOF INSPECTION USING INFRARED THERMOGRAPHY Kenaidan Contracting Ltd Barrie,

Infrared Imaging Solutions Inc 1-877-526-IRIS

Roof Inspection using Infrared Thermography

P a g e | 8

REFERENCE #8

PRIORITY LOCATION EQUIPMENT

Reference:

9.9

22.0 °C

12

14

16

18

20

PARAMETERS ANALYSIS

Date 11/05/2011

Filename IR_6082.jpg

Max Temperature 25.8 °C

Min Temperature 2.8 °C

10.4

22.3 °C

20

Generator Roof West Secton: Thermal variances found

across roof and parapet. Moisture meter verified IR

findings and area marked off with orange paint.

Page 10: ROOF INSPECTION USING INFRARED THERMOGRAPHY · 2014. 4. 7. · Infrared Imaging Solutions Inc 1-877-526-IRIS ROOF INSPECTION USING INFRARED THERMOGRAPHY Kenaidan Contracting Ltd Barrie,

Infrared Imaging Solutions Inc 1-877-526-IRIS

Roof Inspection using Infrared Thermography

P a g e | 9

REFERENCE #9

PRIORITY LOCATION EQUIPMENT

Reference Tank Roof

12.4

21.9 °C

14

16

18

20

PARAMETERS ANALYSIS

Date 11/05/2011

Filename IR_6080.jpg

Max Temperature 27.0 °C

Min Temperature -12.1 °C

Thermal variance detected across 4 x 4 section of roof

possibly caused by moisture infiltration. Verified by

moisture meter and marked off with orange paint.

Page 11: ROOF INSPECTION USING INFRARED THERMOGRAPHY · 2014. 4. 7. · Infrared Imaging Solutions Inc 1-877-526-IRIS ROOF INSPECTION USING INFRARED THERMOGRAPHY Kenaidan Contracting Ltd Barrie,

Infrared Imaging Solutions Inc 1-877-526-IRIS

Roof Inspection using Infrared Thermography

P a g e | 10

REFERENCE #10

PRIORITY LOCATION EQUIPMENT

Reference: Garage Roof

5.5

17.0 °C

6

8

10

12

14

16

PARAMETERS ANALYSIS

Date 11/05/2011

Filename IR_6091.jpg

Max Temperature 16.7 °C

Min Temperature -20.8 °C

No thermal variance detected around skylights.