Role of Electrolyzers in Grid Services Rob Hovsapian Manager – Power and Energy Systems Idaho National Laboratory Hydrogen Technical Advisory Committee Washington D.C. May 4, 2017

Upload: others

Post on 05-Aug-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

1 | Program Name or Ancillary Text eere.energy.gov

Role of Electrolyzers in Grid ServicesRob Hovsapian

Manager – Power and Energy SystemsIdaho National Laboratory

Hydrogen Technical Advisory Committee

Washington D.C.May 4, 2017

Page 2: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

2

• Current activities - role of hydrogen refueling stations in the electricity grid and renewable energy assimilation

• H2@Scale has a longer term vision with potential benefits of hydrogen to the energy nexus

H2@Scale Relevance

2

Page 3: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

3

Relevance & Objective

• Relevance: Electrolyzer model validation and simulation in adistributed real time environment that is used for electrolyzer basedfueling station business case analysis (California focus)

• Objective: Validate the benefits of hydrogen electrolyzers throughgrid services and hydrogen sale to fuel cell vehicles for full-scaledeployment.

– Characterization of the potential and highest economic value based on the needs ofmultiple stakeholders for specific grid regions.

– Demonstration of the reliable, fast-reacting performance of hydrogen-producingelectrolyzers for at-scale energy storage devices.

– Verification of the communications and controls needed for successful participation inelectricity markets and DR programs and ancillary services, leading to additional revenueand reduced hydrogen production cost.

Page 4: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

4

Electrolyzers, Renewables, and Power Grid

• Grid modeling: Utility distribution network identification and modeling in Real Time Simulator for present case

• Electrolyzer operation: Interface development between electrolyzer and Real Time Simulator to perform Power-Hardware-In-the-Loop (PHIL) model validation

• Utility/Aggregator involvement to provide real world test conditions• Economic analysis: Operations optimization to calculate maximum

revenue– Compare revenue to costs to determine competitiveness– Based on

• 2015 Utility rate and/or CAISO nodal price (region, connection, operation strategy)

• 2015 California renewable profiles (PV or wind)• Hydrogen production capacity factor (80, 90, or 95%)

Page 5: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

5

• Response time to a change in power set-point (electrolyzer demonstrated to be milliseconds)

• Settling time after a set-point change (electrolyzer demonstrated to be milliseconds)

• Duration possible for a change in power consumption (electrolyzer demonstrated to be unlimited)

• Turndown level (electrolyzer demonstrated to have a 10:1 turndown capability)

• Startup and shutdown time (electrolyzer demonstrated to start and stop in less than 30 seconds)

Electrolyzers and Response Metrics for Grid Services

Time response and level of variation in power consumption of 120 kW stack electrolyzer at NREL

Page 6: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

6

INLTRANSMISSION NETWORK

NRELDISTRIBUTION NETWORK

Experimental Setup

Real Time Digital Simulator (RTDS) enables communication, control, and experimental operation between grid modeling, Front End Controller (FEC), electrolyzer system, and economic benefit evaluator.

Page 7: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

7

Hardware Testbed Configuration

INLRTDS

Electrolyzernode voltage

phasorinformation

Current drawn by electrolyzerfrom interfaced

node

UDP/IP communication

Analog voltage

control signal

Grid emulator

Measurementfeedback

DCpower

Electrolyzer

PG&E grid and

EMS

+ -

Controllable rectifier

Power adjustment signal from EMS

Reference DC current command

Front endcontroller

DC current feedback

NREL

Low Level Controller

Firing pulse

Page 8: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

8

Demand Response Simulations

Remote electrolyzer operation over 200 hour test period shows electrolyzer’s ability to participate in grid support market

Four distinct profiles were used to characterize the electrolyzer response to remote commands1. Ramp Up, Ramp Down → variations in increasing or decreasing load steps2. Load Steps → variations in the size of change3. Utility Demand Response → expected performance of electrolyzer in grid application4. Random Variations → variations in the speed of change

Sample utility Demand Response time series data (PG&E E-20 profile) used to remotely control the electrolyzer over ~7 hour window 8 March 2016.

|steady state error| < 1%

Page 9: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

9

Electrolyzer Characterization Testing

0.0

50.0

100.0

150.0

200.0

250.0

31-Jan 10-Feb 20-Feb 1-Mar 11-Mar 21-Mar 31-Mar

Test

Hou

rs

Ramp Up, Ramp DownLoad StepsUtility Demand Response

Random Variations

Types of tests run to achieve 200 hours

Page 10: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

10

Summary of ElectrolyzerCharacterization Testing

PerformanceMetric

Ramp Load DR Random

Response Time < 1seconds < 1seconds < 1seconds < 1seconds

Settling Time < 1seconds < 1seconds < 1seconds < 1seconds

Slew Rate +1 kW/second-1 kW/second

(Other rates were 0.5 and 2

kW/second)

Predetermined load values at variable times

10 kW, 20 kW, 30 kW, 40 kW, 50 kW, 118

kW, & E-20 DR (PG&E) at 2, 5, and 10 minutes interval

Random set-points between 13 & 118

kW per second

Operational Limits

13 kW to 118 kW 13 kW to 118 kW 13 kW to 118 kW 13 kW to 118 kW

Startup and Shutdown Time

30 seconds and < 1 second

30 seconds and < 1 second

30 seconds and < 1 second

30 seconds and < 1 second

Fast response time & quick slew rate

Page 11: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

11

Electrolyzer Modeling

Electrolyzer model developed in RSCAD and validated against 120 kW stack using RTDS simulations

Collect empirical data on 50-cell PEM stack

Develop balance of plant model in RSCAD using theoretical equations

Match empirical and theoretical results using curve fitting to derive parameters

Compare time-series results from PEM stack and model using INL RTDS test protocol

Time-series results showing actual and model performance

Polarization curves showing model and actual results at varying temperature and pressure

Theoretical parameters used to model stack voltage

Page 12: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

12

Front End Controller & Electrolyzers

GRID (DISTRIBUTION

NETWORK)AC/DC RECTIFIER

FRONT END CONTROLLER

ELECTROLYZER+

H2 STORAGE

Communication lineAC Power lineDC Power line

AGGREGATOR/DMS/EMS

Schematics

The project combines modeling, simulation, and hardware for the validation of system performance and to quantify economic benefit based on different operation scenarios relevant to utilities.

Page 13: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

13

Front End Controller

FEC consists of three modules:

1. Communication modulerealizes data exchange between FEC, utility, and electrolyzer’s low level controller

2. Optimization modulecomputes set point for electrolyzer operation that optimizes the revenue of the hydrogen refueling station

3. Interpretation modulegenerates the reference control signal in order to ensure that the low level controller properly integrates with the FEC

Advanced controllability of electrolyzers by Front End Controller to support the grid signals

Page 14: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

14

FEC Inputs/Outputs

FAST LOOP (VOLTAGE AND FREQUENCY

STABILITY)

SLOW LOOP (ECONOMICS AND USER

DEMANDS OPTIMIZATION)

Vrms

freq

Pressure

Temperature

Storage Pressure (SOC)

Energy Pricing(Programmable or Time of the day forecast)

Hydrogen Demand(Programmable or forecast)

Power set point (Optimal or Programmable)

Idc – Rectifier(Power control pilot)

MaximumPower

ActualPower

DR override (Utility Control)

Programmable Hydrogen Price

User override (Programmable fields orProgrammable Power output)

Front End Controller adds greater ‘awareness’ and hence ‘better response’

Page 15: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

15

• Several current and future locations of the hydrogen refueling stations are generated from earlier NREL studies

• Network synthesis and modeling in real-time simulator at INL, represents the PG&E infrastructure

• It spans major distribution and coupling transmission lines (from 69 kV to 138 kV) associated with the hydrogen refueling infrastructure

• Serves as a testbed for testing grid services and stability of connecting electrolyzers in utility systems

• Centralized and distributed electrolysis is assessed under different grid and market conditions

Grid Modeling, Real-Time PG&E Network

Real-time grid model of Pacific Gas & Electric that covers hydrogen refueling station interconnections

Page 16: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

16

Impacts of Electrolyzer on Power System Transient Stability

Resistive Capabilities and Impacts on the Grid

Demonstration of reduction in transients created from faults with electrolyzers in the grid

Page 17: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

17

Frequency Support by Multiple Electrolyzers with FEC

Multiple electrolyzers controlled by FEC can enhance overall grid stability by limiting frequency excursions

59.992

59.979

Fault location: Node 39Fault type: Three phase balanceFault duration: 0.1 seconds

59.992

59.992

59.979

59.979

59.996

59.996

59.997

59.992

59.992

59.992

Loca

l Fre

quen

cy (H

z)

NODE 39

NODE 40

NODE 32

Page 18: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

18

Voltage Support by Multiple Electrolyzers with FEC

Multiple electrolyzers controlled by FEC can enhance overall grid stability by limiting voltage excursions

0.989

NODE 39

Fault location: Node 39Fault type: Three phase balanceFault duration: 0.1 seconds

0.962

0.989

1

1

1

1.003

1.003

1.002

0.999

0.999

1

Loca

l Vol

tage

(P.U

.)

NODE 40

NODE 32

Page 19: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

19

Frequency Support by Centralized Electrolysis

Electrolyzer Response Without FEC

Electrolyzers controlled by FEC can enhance enhance grid stability by limiting frequency excursions

59.986

59.9714

59.981

59.98659.985

59.984

Electrolyzer Response With FEC

Page 20: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

20

Voltage Support by Centralized Electrolysis

Electrolyzers controlled by FEC can enhance enhance grid stability by limiting voltage excursions

0.985

0.9980.9960.995

0.973

0.9950.996

1.003

Electrolyzer response without FEC

Electrolyzer response with FEC

Page 21: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

21

Grid Simulator Based Control of Electrolyzer Stack

First use of grid simulator capability at ESIF to control the electrolyzer power supplies• Demonstration of a major power hardware-in-the-loop capability for NREL• Control via remote command from INL RTDS and safety limits verified

Command outside of limitation

Zoom from below Zoom from below

First use of grid simulator capability at ESIF to control the electrolyzer power supplies

Page 22: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

22

Variability of Renewable Energy Sources

• Renewable Energy sources such as wind and solar demonstrate high degree of time dependent variability i.e., seconds to minutes to days…

• Electrolyzers have an innate capability to respond in seconds to follow control set points

• How can electrolyzers offset the variability observed by the power?– Grids expected predictable and non-varying generation sources – Hydrogen demands per day for different years are used as a constraint

Page 23: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

23

2018 Case with 7,200 FCEVs

• Objective: Offset time-dependent, aggregated variability of solar and wind power using electrolysis

• Total of 13 MW electrolyzer plant is used for this example

• 2018 test case projections from ARB on vehicle fuel use to generate 1,800 kg/day of hydrogen for 7,200 FCEVs

• Approximate fuel dispensed in Santa Clara, Sacramento, San Francisco, Marin, Contra Cost and Alameda county

• Total energy consumed to generate this hydrogen demand 90.28 MWh/day

0

2

4

6

8

10

12

14

0 5 10 15 20

Rea

l Pow

er in

MW

Time of the day

Total Wind and Solar Generation

Page 24: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

24

Wind, Solar, and Electrolysis

• Advanced control of a 13 MW electrolysis plant to offset variability of wind and solar power

• A fixed and predictable power injected into the grid from solar and wind plant due to coordinated operation with electrolyzers

0

2

4

6

8

10

12

0 5 10 15 20

Rea

l Pow

er in

MW

Time of the day

Electrolyzer performance to produce 1800 kg/day

0

0.5

1

1.5

2

2.5

3

0 5 10 15 20

Rea

l Pow

er in

MW

Time of the day

Aggregate Feed into the Grid (2018)

Page 25: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

25

2022 Case with 43,600 FCEVs

• Objective: Offset time-dependent, aggregated variability of solar and wind power using electrolysis

• Total of 45 MW electrolyzer plant is used for this example

• Typical efficiency of PV ~20-30%• 2022 test case is used as reference to

generate 7,575 kg/day of hydrogen for 43,600 FCEVs

• Approximate fuel dispensed in Santa Clara, Sacramento, San Francisco, Marin, Contra Cost and Alameda county

• Total energy consumed to generate 330 MWh/day

0

10

20

30

40

50

60

0 5 10 15 20

Pow

er in

MW

Time of the day

Total wind and solar generation

Page 26: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

26

Wind, Solar, and Electrolysis

• Advanced control of a 45 MW electrolysis plant to offset variability of wind and solar power

• A fixed power injected into the grid from solar and wind plant due to coordinated operation with electrolyzers

0

1

2

3

4

5

6

7

8

9

0 5 10 15 20

Pow

er in

MW

Time of the day

Total feed in the grid (2022)

0

5

10

15

20

25

30

35

40

45

50

0 5 10 15 20 25 30

Pow

er in

MW

Time of the day

Electrolyzer performance to generate 7,575 kg/day of hydrogen (2022)

Page 27: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

27

Future Work

• Hardware implementation and integration of FEC with the electrolyzer stack at NREL

• Successful verification and validation of the FEC functionalities of providing grid services as requested

• Renewable energy integration and smoothing based on the controllability aspects of electrolyzer and the FEC

• Quantification of the value of hydrogen refueling stations in renewable integration

• Role of hydrogen refueling stations in grid stability, flexibility, and participating in various demand response scenarios

Page 28: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

28

Summary

• Verifying and validating the participation of electrolyzers (hydrogen refueling station) in providing grid services

• First of a kind, distributed real-time simulation with PHIL (electrolyzer) between INL and NREL – FEC and electrolyzer responding to grid signals and providing required services– Extensive 200 hours (FY 2016) and 300 hours (FY 2017) of testing completed

• Electrolyzer stack efficiency and hydrogen quality is ensured to be acceptable during the whole project

• Improved transient stability observed under grid fault conditions verified with PHIL

• Hardware realization of FEC and its integration with the electrolyzer stack is under progress

• Contributes directly to the DOE Milestone 3.9 related to Systems Analysis & Technology Validation

– [From MYRDD 3.9] Validate large-scale system for grid energy storage that integrates renewable hydrogen generation and storage with fuel cell power generation by operating for more than 10,000 hours with a round-trip efficiency of 40%. (4Q, 2020)

Page 29: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

29

Thank you

Page 30: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

30

Backup Slides

30

Page 31: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

31

• Peak capacity management– deploying fleets of electrolyzers to consistently and reliably reduce critical peak

loads within a defined region or location on the grid

• Energy market price response– fleets of electrolyzers consume energy when prices are low and defer consumption

(set energy free) when prices are high

• Regulation– operating point adjustment counteracts short-term changes in electricity use that

might affect the stability of the power system

• Spinning Reserve– by reducing its power consumption fleets of electrolyzers can support the event

when loss of generation unit in the grid occurs

Identified Grid Services 1

Page 32: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

32

• Ramping– analogue to generator, fleets of electrolyzers start and stop on command, while the

“ramp rate” is the rate at which they can increase or decrease consumption

• Artificial inertia– fleets of electrolyzers regulate active power consumption in response

rate of change of frequency

• Distribution voltage management– upon detecting the voltage deviations (self-sensing and/or receipt of external

measurement signals) fleets of electrolyzers adjust the net load in the form of their reactive and/or real power components

• Autonomous grid service responses– additional (high-level) controller enables grid services in “stand-alone” mode

Identified Grid Services 2

Page 33: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

33

• Purely resistive load, supplied from a DC source (power converter)

• Very high rate of change and flexibility in setting power operating points

• Capable of sensing deviations in power systems, capable of adjusting their operating points to support the grid (fleets of electrolyzers)

• Frequency and voltage support by reducing/increasing power consumption

Key Capabilities of Electrolyzers

Page 34: Role of Electrolyzers in Grid Services - Energy · 2020. 11. 21. · Power Grid • Grid modeling: Utility distribution network identification and modeling in Real Time Simulator

34

• High-level controller (Front-end controller)– applies EMS requirements and supports power quality by varying the

electrolyzer’s operating point– communicates to other FECs to coordinate remedy actions

Controller Requirements