rirs 400 - biv ventilatoren - seitenkanalverdichter · 2009-08-19 · rirs page:47 the company...
TRANSCRIPT
RIRS
Page:46
The company reserves the right to make changes of technical data without prior notice
ver. 090617
RIRS 400
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
* RIRS 400VW have been measured without water heater in system.
400VE 400VW 400HE 400HW
Heater
water
- power [kW] -
AVS 160
-
AVS 160- water temp. Tin/Tout [Co] - -
- water flow rate [l/s] - -
- water pressure drop [kPa] - -
electric- phase/voltage [50 Hz/VAC] ~1, 230 - ~1, 230 -
- power consumption [kW] 1,2 - 1,2 -
Fans
- phase/voltage [50 Hz/VAC] ~1, 230 ~1, 230 ~1, 230 ~1, 230
exhaust- power/current [W/A] 190 / 0,84 190 / 0,84 190 / 0,84 190 / 0,84
- speed [min-1] 1850 1850 1850 1850
supply- power/current [W/A] 190 / 0,84 190 / 0,84 190 / 0,84 190 / 0,84
- speed [min-1] 1850 1850 1850 1850
- protection class IP-44 IP-44 IP-44 IP-44
Total power consumption - power/current [kW/A] 1,58 / 6,9 0,38 / 6,9 1,58 / 6,9 0,38 / 6,9
Integrated automatic control system + + + +
Thermal efficiency 75% 75% 75% 75%
Filter classexhaust EU5 EU5 EU5 EU5
supply EU5 EU5 EU5 EU5
Insulation [mm] 50 50 50 50
Weight [kg] 79,0 78,0 70,0 69,0
RIRS 400VERIRS 400VW*supplyexhaust
RIRS 400HERIRS 400HW*supplyexhaust
RIRS
Page:47
The company reserves the right to make changes of technical data without prior notice
ver. 090617
Pict. code Art.-no Type
AHU GRERIRS4002 RIRS 400VEK
AHU GRERIRS4003 RIRS 400VEDPict. code Art.-no Type
P PRG037 Remote controller UNI
P PRG039 Programmable controller PRO
AF GFIRIRS4002 Set of spare filters for RIRS 400V
SD ZJG009 Pressure switch PS600B
SK GSKSKG003 Closing damper SKG 160
SKP PVRPS042 Actuator for damper 227S-230-05
RIRS 400VE accessories
AHU
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
SUPPLY
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
EXTRACT
RIRS
Page:48
The company reserves the right to make changes of technical data without prior notice
ver. 090617
RIRS 400VW accessories
Pict. code Art.-no Type
AHU GRERIRS4005 RIRS 400VWK
AHU GRERIRS4006 RIRS 400VWD
Pict. code Art.-no Type
P PRG037 Remote controller UNI
P PRG039 Programmable controller PRO
AF GFIRIRS4002 Set of spare filters for RIRS 400V
SD ZJG009 Pressure switch PS600B
VS GSIAVS003 Water heater AVS 160
AM PREG002 Mixing point RMG3-1,0
VV PRGT056 Water valve VXP45.10-1,0
VP PRGT052 Actuator for water valve SSB81
SK GSKSKG003 Closing damper SKG 160
SKP PVRPS049 Actuator for damper 228-230-05
T1 PJGT006 Thermostat CO4C
T2 PJU020 Temperature sensor TE704
AHU
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
SUPPLY
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
EXTRACT
RIRS
Page:49
The company reserves the right to make changes of technical data without prior notice
ver. 090617
RIRS 400HE accessories
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
Pict. code Art.-no Type
AHU GRERIRS4001 RIRS 400HEPict. code Art.-no Type
P PRG037 Remote controller UNI
P PRG039 Programmable controller PRO
AF GFIRIRS4001 Set of spare filters for RIRS 400H
SD ZJG009 Pressure switch PS600B
SK GSKSKG003 Closing damper SKG 160
SKP PVRPS042 Actuator for damper 227S-230-05
AHU
SUPPLY EXTRACT
RIRS
Page:50
The company reserves the right to make changes of technical data without prior notice
ver. 090617
RIRS 400HW accessories
Pict. code Art.-no Type
AHU GRERIRS4005 RIRS 400HEPict. code Art.-no Type
P PRG037 Remote controller UNI
P PRG039 Programmable controller PRO
AF GFIRIRS4001 Set of spare filters for RIRS 400H
SD ZJG009 Pressure switch PS600B
VS GSIAVS003 Water heater AVS 160
AM PREG002 Mixing point RMG3-1,0
VV PRGT056 Water valve VXP45.10-1,0
VP PRGT052 Actuator for water valve SSB81
SK GSKSKG003 Closing damper SKG 160
SKP PVRPS049 Actuator for damper 228-230-05
T1 PJGT006 Thermostat CO4C
T2 PJU020 Temperature sensor TE704
AHUTo
tal p
ress
ure
[Pa]
Air flow [m3/h]
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
SUPPLY EXTRACT
RIRS
Page:51
The company reserves the right to make changes of technical data without prior notice
ver. 090617
RIRS 700
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
* RIRS 700VW and RIRS 700HW have been measured without water heater in system.
700VE 700VW 700HE 700HW
Heater
water
- power [kW] -
AVS 250
-
AVS 250- water temp. Tin/Tout [Co] - -
- water flow rate [l/s] - -
- water pressure drop [kPa] - -
electric- phase/voltage [50 Hz/VAC] ~1, 230 - ~1, 230 -
- power consumption [kW] 2,0 - 2,0 -
Fans
- phase/voltage [50 Hz/VAC] ~1, 230 ~1, 230 ~1, 230 ~1, 230
exhaust- power/current [W/A] 300 / 1,31 300 / 1,31 300 / 1,31 300 / 1,31
- speed [min-1] 2050 2050 2050 2050
supply- power/current [W/A] 300 / 1,31 300 / 1,31 300 / 1,31 300 / 1,31
- speed [min-1] 2050 2050 2050 2050
- protection class IP-44 IP-44 IP-44 IP-44
Total power consumption - power/current [kW/A] 2,6 / 11,32 0,6 / 2,63 2,6 / 11,32 0,6 / 2,63
Integrated automatic control system + + + +
Thermal efficiency 74% 74% 74% 74%
Filter classexhaust EU5 EU5 EU5 EU5
supply EU5 EU5 EU5 EU5
Insulation [mm] 50 50 50 50
Weight [kg] 104,0 103,0 96,0 95,0
RIRS 700VERIRS 700VW*supplyexhaust
RIRS 700HERIRS 700HW*supplyexhaust
RIRS
Page:52
The company reserves the right to make changes of technical data without prior notice
ver. 090617
Pict. code Art.-no Type
AHU GRERIRS7002 RIRS 700VEK
AHU GRERIRS7003 RIRS 700VEDPict. code Art.-no Type
P PRG037 Remote controller UNI
P PRG039 Programmable controller PRO
AF GFIRIRS7002 Set of spare filters for RIRS 700V
SD ZJG009 Pressure switch PS600B
SK GSKSKG005 Closing damper SKG 250
SKP PVRPS042 Actuator for damper 227S-230-05
RIRS 700VE accessories
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
SUPPLY
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
EXTRACT
AHU
RIRS
Page:53
The company reserves the right to make changes of technical data without prior notice
ver. 090617
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
SUPPLY
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
EXTRACT
RIRS 700VW accessories
Pict. code Art.-no Type
AHU GRERIRS7005 RIRS 700VWK
AHU GRERIRS7006 RIRS 700VWKPict. code Art.-no Type
P PRG037 Remote controller UNI
P PRG039 Programmable controller PRO
AF GFIRIRS7002 Set of spare filters for RIRS 700V
SD ZJG009 Pressure switch PS600B
VS GSIAVS005 Water heater AVS 250
AM PREG002 Mixing point RMG3-1,0
VV PRGT056 Water valve VXP45.10-1,0
VP PRGT052 Actuator for water valve SSB81
SK GSKSKG005 Closing damper SKG 250
SKP PVRPS049 Actuator for damper 228-230-05
T1 PJGT006 Thermostat CO4C
T2 PJU020 Temperature sensor TE704
AHU
RIRS
Page:54
The company reserves the right to make changes of technical data without prior notice
ver. 090617
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
SUPPLY
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
EXTRACT
RIRS 700HE accessories
Pict. code Art.-no Type
AHU GRERIRS7001 RIRS 700HEPict. code Art.-no Type
P PRG037 Remote controller UNI
P PRG039 Programmable controller PRO
AF GFIRIRS7001 Set of spare filters for RIRS 700H
SD ZJG009 Pressure switch PS600B
SK GSKSKG005 Closing damper SKG 250
SKP PVRPS042 Actuator for damper 227S-230-05
AHU
RIRS
Page:55
The company reserves the right to make changes of technical data without prior notice
ver. 090617
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
SUPPLY
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
EXTRACT
RIRS 700HW accessories
Pict. code Art.-no Type
AHU GRERIRS7004 RIRS 700HWPict. code Art.-no Type
P PRG037 Remote controller UNI
P PRG039 Programmable controller PRO
AF GFIRIRS7001 Set of spare filters for RIRS 700V
SD ZJG009 Pressure switch PS600B
VS GSIAVS005 Water heater AVS 250
AM PREG002 Mixing point RMG3-1,0
VV PRGT056 Water valve VXP45.10-1,0
VP PRGT052 Actuator for water valve SSB81
SK GSKSKG005 Closing damper SKG 250
SKP PVRPS049 Actuator for damper 228-230-05
T1 PJGT006 Thermostat CO4C
T2 PJU020 Temperature sensor TE704
AHU
RIRS
Page:56
The company reserves the right to make changes of technical data without prior notice
ver. 090617
RIRS 1500
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
* RIRS 1500VW have been measured without water heater in system.
1500VE 1500VW 1500HE 1500HW
Heater
water
- power [kW] -
AVS 315
- 5,45
- water temp. Tin/Tout [Co] - - 80 / 60
- water flow rate [l/s] - - 0,07
- water pressure drop [kPa] - - 2,5
electric- phase/voltage [50 Hz/VAC] ~3, 400 - ~3, 400 -
- power consumption [kW] 4,5 - 4,5 -
Fans
- phase/voltage [50 Hz/VAC] ~1, 230 ~1, 230 ~1, 230 ~1, 230
exhaust- power/current [W/A] 390 / 1,71 390 / 1,71 390 / 1,71 390 / 1,71
- speed [min-1] 2750 2750 2750 2750
supply- power/current [W/A] 390 / 1,71 390 / 1,71 390 / 1,71 390 / 1,71
- speed [min-1] 2750 2750 2750 2750
- protection class IP-44 IP-44 IP-44 IP-44
Total power consumption - power/current [kW/A] 5,3 / 10,07 0,80 / 3,58 5,3 / 10,07 0,80 / 3,58
Integrated automatic control system + + + +
Thermal efficiency 74% 74% 74% 74%
Filter classexhaust EU5 EU5 EU5 EU5
supply EU5 EU5 EU5 EU5
Insulation [mm] 50 50 50 50
Weight [kg] 170,0 168,0 159,0 165,0
RIRS 1500VERIRS 1500VW*supplyexhaust
RIRS 1500HEsupplyexhaust
RIRS 1500HWsupplyexhaust
RIRS
Page:57
The company reserves the right to make changes of technical data without prior notice
ver. 090617
RIRS 1500VE accessories
Pict. code Art.-no Type
AHU GRERIRS1502 RIRS 1500VEK
AHU GRERIRS1503 RIRS 1500VEDPict. code Art.-no Type
P PRG037 Remote controller UNI
P PRG039 Programmable controller PRO
AF GFIRIRS1502 Set of spare filters for RIRS 1500V
SD ZJG009 Pressure switch PS600B
SK GSKSKG006 Closing damper SKG 315
SKP PVRPS042 Actuator for damper 227S-230-05
AHU
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
SUPPLY
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
EXTRACT
RIRS
Page:58
The company reserves the right to make changes of technical data without prior notice
ver. 090617
RIRS 1500VW accessories
Pict. code Art.-no Type
AHU GRERIRS1505 RIRS 1500VWK
AHU GRERIRS1506 RIRS 1500VWKPict. code Art.-no Type
P PRG037 Remote controller UNI
P PRG039 Programmable controller PRO
AF GFIRIRS1502 Set of spare filters for RIRS 1500V
SD ZJG009 Pressure switch PS600B
VS GSIAVS006 Water heater AVS 315
AM PREG003 Mixing point RMG3-1,6
VV PRGT049 Water valve VXP45.10-1,6
VP PRGT052 Actuator for water valve SSB81
SK GSKSKG006 Closing damper SKG 315
SKP PVRPS049 Actuator for damper 228-230-05
T1 PJGT006 Thermostat CO4C
T2 PJU020 Temperature sensor TE704
AHU
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
SUPPLY
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
EXTRACT
RIRS
Page:59
The company reserves the right to make changes of technical data without prior notice
ver. 090617
RIRS 1500HE accessories
Pict. code Art.-no Type
AHU GRERIRS1501 RIRS 1500HEPict. code Art.-no Type
P PRG037 Remote controller UNI
P PRG039 Programmable controller PRO
AF GFIRIRS1501 Set of spare filters for RIRS 1500H
SD ZJG009 Pressure switch PS600B
SK GSKSKG006 Closing damper SKG 315
SKP PVRPS042 Actuator for damper 227S-230-05
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
SUPPLY
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
EXTRACT
AHU
RIRS
Page:60
The company reserves the right to make changes of technical data without prior notice
ver. 090617
RIRS 1500HW accessories
Pict. code Art.-no Type
AHU GRERIRS1504 RIRS 1500HWPict. code Art.-no Type
P PRG037 Remote controller UNI
P PRG039 Programmable controller PRO
AF GFIRIRS1501 Set of spare filters for RIRS 1500H
SD ZJG009 Pressure switch PS600B
AM PREG003 Mixing point RMG3-1,6
VV PRGT049 Water valve VXP45.10-1,6
VP PRGT052 Actuator for water valve SSB81
SK GSKSKG006 Closing damper SKG 315
SKP PVRPS049 Actuator for damper 228-230-05
AHU
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
SUPPLY
Tota
l pre
ssur
e [P
a]
Air flow [m3/h]
EXTRACT