Reviewed For Code Compliance 2014 National Electrical Code is the code in effect at time of application submission. ART 7.15.2016 7 net not 15. Need to revise. ART 7.15.2016 Show a furniture layout consistent with 7 net or calculate at 5 net per table 1004.1.1. ART 7.15.2016 Revise to provide accessible parking per table [B]1106.1. The site plan shows one accessible space per 25 consistent with table [B]1106.1. ART 7.15.2016

Upload: vucong

Post on 23-Jul-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

Reviewed For Code Compliance

2014 NationalElectrical Code is thecode in effect at timeof applicationsubmission. ART7.15.2016

7 net not 15. Need torevise. ART 7.15.2016

Show a furniture layoutconsistent with 7 net orcalculate at 5 net pertable 1004.1.1. ART 7.15.2016

Revise to provideaccessible parking pertable [B]1106.1. Thesite plan shows oneaccessible space per25 consistent withtable [B]1106.1.ART 7.15.2016

 Planworx Architecture, P.A.                                Permit Review Response Letter 

5711 Six Forks Road, Suite 100, Raleigh North Carolina, 27609                   (919)846‐8100 / fax 846‐2661 

 Date:    06‐27‐16 Project:   Hawthorne at Leland  To:     Evolve Construction LLC and A. Thompson at the Brunswick permit office      RE:    Building Department Plan Review Comments   This letter is being provided to address the plan review comments to the above referenced project from the Brunswick County plan review office.   Project tracking #408723, 409136, 409130, 409144, 409473, 409474 Apartment Building Type 1: Department‐Plan Review 1. Sheet A0.10 code summary type I + 1E. The 2014 National Electrical Code in the code in effect. Plans state 2011 NEC. 

Planworx Response: This was a typo. The code summary has been corrected to reflect the correct code. 2. Sheet A1.62. The handrail detail at top of stairs needs to terminate into wall or back into self per figure 505.10.2 ICC A117.1‐2009. 

Planworx Response: A note has been added to the stair sections, stair plans and enlarged details on sheets  A1.60‐63, A2.04  3. Sheet M5.01. The 4" inch dyer exhaust duct needs to be wrapped with approved 1HR fire wrap from penetration of rated floor/ceiling assembly to the termination at the exterior wall cap/ceiling grille per M504.2. Crenshaw Response:  Detail has been revised to require 1‐hr fire wrap on all dryer vents.  

4. Sheet E1.04. Need an emergency light in the sprinkler riser / fire alarm room for first responders per [B]1006.3. 

Crenshaw Response:  This fixture has been added.  Project tracking #408837, 409135 Apartment Building Type 1E: Department‐Plan Review 1. Sheet A0.10 code summary type 1+1E. Need to revise all applicable electrical and appendix B to address code change from 2011 NEC to 2014 NEC. The 2014 NEC is the code in effect at time of application.  

Planworx Response: This was a typo. The code summary has been corrected to reflect the correct code.  

2. Sheet A0.10 code summary type 1+1E. Need to complete the ADA parking summary. The statement "see civil" on the plans. Need to provide parking space count for ADA per section 1106 of the NC building code.  

Planworx Response: See civil sheets for site parking summary information and/or necessary sheet revisions. Planworx does not have the final civil plans so cannot provide the number on the Appendix B of our plans.  

Reviewed For Code Compliance

 Planworx Architecture, P.A.                                Permit Review Response Letter 

5711 Six Forks Road, Suite 100, Raleigh North Carolina, 27609                   (919)846‐8100 / fax 846‐2661 

3. Sheet A0.10 code summary type 1+1E. Need table for plumbing fixture requirements completed based on per unit count per table P403.1.  

Planworx Response: The plumbing fixture chart has been corrected reflect NCBC Table 2902.1 

 

4. Sheet A0.10 code summary type 1+1E. Need electrical and mechanical code summaries or comcheck report. Information not located within plans.  

Crenshaw Response:  The electrical Energy Code summary for Bldg 1 is on Sheet E1.03 and Bldg 1E is on sheet E1.09.  The Energy Code summary is on sheet M6.01.   

5. Sheet A1.61 and A1.62. Revise to address handrail at the top of the stairs to terminate into wall or back into self per figure 505.10.2 of ICC A117.1‐2009.  

Planworx Response: A note has been added to the stair sections, stair plans and enlarged details on sheets  A1.60‐63, A2.04  

6. Need to mark locations of area of refuge for each floor and provide code specifications per [B]1007.6.1 through 1007.10.  

Planworx Response: An accessible elevator is not required per NCBC 1007.2.1. due to the building being three stories. Per NCBC 1007.3, exception 7, areas of refuge are not required in stairways for R‐2 occupancies. Per NCBC 1007.8, two way communication is shown on sheets E107‐112. 

7. Sheet E1.07. Revise emergency light location to provide an emergency light in the sprinkler riser room per [B]1006.3.  

Crenshaw Response:  This fixture has been added. 8. Per sealed plans truss roof system sheet 8.15. Need truss layout from the truss company showing all imposed loads exceeding 5,000lbs.  Planworx Response: General contractor to provide permitting office with truss package.  9. The 88 page set of building and trades plans were PDF protected and was unable to stamp or provide markups.  Need to provide unlocked PDF and cloud all revisions as listed above herein. Planworx Response: GC to provide permit office with useable files.  Project tracking #408839, 409134, 409152, 409471, 409472  Apartment Building Type 2: 1. Sheet A0.10 code summary type 2+2E. Need to revise all applicable electrical and appendix B to address code change from 2011 NEC to 2014 NEC. The 2014 NEC is the code in effect at time of application.  

Planworx Response: This was a typo. The code summary has been corrected to reflect the correct code. 2. Sheet A0.10 code summary type 2+2E. Need to complete the ADA parking summary. The statement "see civil" on the plans. Need to provide parking space count for ADA per section 1106 of the NC building code.  

Planworx Response: See civil sheets for site parking summary information and/or necessary sheet revisions. Planworx does not have the final civil plans so cannot provide the number on the Appendix B of our plans.   Reviewed For Code Compliance

 Planworx Architecture, P.A.                                Permit Review Response Letter 

5711 Six Forks Road, Suite 100, Raleigh North Carolina, 27609                   (919)846‐8100 / fax 846‐2661 

3. Sheet A0.10 code summary type 2+2E. Need table for plumbing fixture requirements completed based on per unit count per table P403.1.  Planworx Response: The plumbing fixture chart has been corrected reflect NCBC Table 2902.1 

 4. Sheet A0.10 code summary type 2+2E. Need electrical and mechanical code summaries or comcheck report. Information not located within plans.  Crenshaw Response:  The Electrical Energy Code summary for Bldg 2 is on Sheet E1.06.  The Mechanical Energy Code summary is on sheet M6.01.    5. Sheet A2.04. Revise to address handrail at the top of the stairs to terminate into wall or back into self per figure 505.10.2 of ICC A117.1‐2009.  Planworx Response: A note has been added to the stair sections, stair plans and enlarged details on sheets  A1.60‐63, A2.04  6. Need to mark locations of area of refuge for each floor and provide code specifications per [B]1007.6.1 through 1007.10.  Planworx Response: An accessible elevator is not required per NCBC 1007.2.1. due to the building being three stories. Per NCBC 1007.3, exception 7, R‐2 occupancies are not required in stairways. Per NCBC 1007.8, we have revised the drawings to show two‐way communication. 

7. Sheet E1.10. Revise emergency light location to provide an emergency light in the sprinkler riser room per [B]1006.3. Crenshaw Response:  This fixture has been added.  8. Per sealed plans truss roof system sheet AS8.15. Need truss layout from the truss company showing all imposed loads exceeding 5,000lbs.  Planworx Response: General contractor to provide permitting office with truss package.  9. The 77 page set of building and trades plans were PDF protected and was unable to stamp or provide markups. Need to provide unlocked PDF and cloud all revisions as listed above herein.  Planworx Response: GC to provide the permit office with useable files.  Project tracking #408842, 409150  Apartment Building Type 2E: Department‐Plan Review 1. Sheet A0.12 code summary type 2+2E. Need to revise all applicable electrical and appendix B to address code change from 2011 NEC to 2014 NEC. The 2014 NEC is the code in effect at time of application.  

Planworx Response: This was a typo. The code summary has been corrected to reflect the correct code. 2. Sheet A0.12 code summary type 2+2E. Need to complete the ADA parking summary. The statement "see civil" on the plans. Need to provide parking space count for ADA per section 1106 of the NC building code.  

Planworx Response: See civil sheets for site parking summary information and/or necessary sheet revisions. Planworx does not have the final civil plans so cannot provide the number on the Appendix B of our plans. 3. Sheet A0.12 code summary type 2+2E. Need table for plumbing fixture requirements completed based on per unit count per table P403.1.  

Planworx Response: The plumbing fixture chart has been corrected reflect NCBC Table 2902.1 Reviewed For Code Compliance

 Planworx Architecture, P.A.                                Permit Review Response Letter 

5711 Six Forks Road, Suite 100, Raleigh North Carolina, 27609                   (919)846‐8100 / fax 846‐2661 

4. Sheet A0.12 code summary type 2+2E. Need electrical and mechanical code summaries or comcheck report. Information not located within plans.  

Crenshaw Response:  The Electrical Energy Code summary for Bldg 2 is on Sheet E1.06.  The Mechanical Energy Code summary is on sheet M6.01.   

6. Sheet A2.04. Revise to address handrail at the top of the stairs to terminate into wall or back into self per figure 505.10.2 of ICC A117.1‐2009.  

Planworx Response: A note has been added to the stair sections, stair plans and enlarged details on sheets  A1.60‐63, A2.04  

7. Need to mark locations of area of refuge for each floor and provide code specifications per [B]1007.6.1 through 1007.10.  

Planworx Response: An accessible elevator is not required per NCBC 1007.2.1. due to the building being three stories. Per NCBC 1007.3, exception 7, R‐2 occupancies are not required in stairways. Per NCBC 1007.8, we have revised the drawings to show two‐way communication. 

8. Sheet E1.10. Revise emergency light location to provide an emergency light in the sprinkler riser room per [B]1006.3.  

Crenshaw Response:  This fixture has been added.  9. Sheet E1.10. Revise emergency light location to provide an emergency light in the electrical / elevation control room per 110.34(D) 2014 NEC. Crenshaw Response:  This fixture has been added. 

10. Per sealed plans truss roof system sheet AS8.15. Need truss layout from the truss company showing all imposed loads exceeding 5,000lbs.  

Planworx Response: General contractor to provide permitting office with truss package. 

11. The site plan is marked “Progress drawings do not use for construction”. Need for construction site plan to review showing ADA parking, signs, and accessibility requirements per chapter 11 NC building code.  

Planworx Response: GC to provide permit office with final, sealed plans.  12. The 77 page set of building and trades plans were PDF protected and was unable to stamp or provide markups. Need to provide unlocked PDF and cloud all revisions as listed above herein. Planworx Response: GC to provide the permit office with useable files.   Project tracking #408829 Clubhouse: Department‐Plan Review 1. Sheet A0.14 Clubhouse code summary. The 2014 National electrical code  is the code  in effect. The 2011 NEC code is listed on the Appendix B. Planworx Response: This was a typo. The code summary has been corrected to reflect the correct code. 

   Reviewed For Code Compliance

 Planworx Architecture, P.A.                                Permit Review Response Letter 

5711 Six Forks Road, Suite 100, Raleigh North Carolina, 27609                   (919)846‐8100 / fax 846‐2661 

2.  Sheet  A0.14  Clubhouse  code  summary.  Revise  the  occupant  load  and  exit  width  requirements  per  Table 1004.1.1. The multipurpose room and lounge occupant loads need to be designed at 7 net per Table 1004.1.1. The billiard  room needs  to be designed at 11 gross per Table 1004.1.1. The  change will  reflect Table 1004.1.1 and increase the total occupant load to approximately 253. On the appendix B these areas were based on 15 net which it for tables and chairs. I spoke with Fire Marshal Garner and he concurs with the occupant load revision to reflect Table 1004.1.1 per comments herein. Planworx Response: Based on a conversation with Andrew Thompson on 6‐15, a furniture plan has been added to the floor plan to accurately depict the use of those spaces and clarify what occupant loading was intended. The lounge room will be used as a typical leasing lounge area with couches, tables and chairs. We also discussed the billiards room occupant load factor. Our office views the gaming floor occupant load of 11 gross for a gambling type of space with craps, keno and slot machines as described in the building code table description. There will only be one billiard table with other tables and chairs in the room and therefore feel the occupant load should be 15 net for tables and chairs. The required space of a billiard table also requires more space than a traditional gaming floor.  In regards to the multi‐purpose room, we agree with your assessment of 7 net. The life safety plan and Appendix B was updated accordingly. 

 3.  Sheet  A0.14  Clubhouse  code  summary.  Revise  plumbing  and  fixture  tables  per  revised  occupant  load  per comments in items #2. Planworx Response: The Appendix B was updated accordingly based on the above comment of providing 7 net in the mulit‐purpose room occupant loading. 

 4. Sheet M4.01. Duct detectors need audible and visible signals notification devices per 606.4.1 #2. Add revisions on plans and in notes. Crenshaw Response:  A/V devices have been added to the Reception area of the Clubhouse.   5. Sheet E4.02. Need emergency light in the yoga room per [B]1006.1. Crenshaw Response:  This fixture has been added.   6. Site plan.  ADA accessibility plan per section 1101.2 (Accessible entrance, accessible route, signage 1110, and accessible parking). Planworx Response: See civil sheets for site parking summary information and/or necessary sheet revisions. Planworx does not have the final civil plans so cannot provide the number on the Appendix B of our plans.  Project tracking #409475  Poolhouse: Department‐Plan Review 1. Sheet A0.15 Pool house Code summary. Need to revise appendix B to address code change from 2011 NEC to 2014 NEC. The 2014 NEC is the code in effect at time of application.  

Planworx Response: This was a typo. The code summary has been corrected to reflect the correct code. 

2. Sheet A0.15 Pool house Code summary. Complete the accessible parking summary per section [B]1106 of the North Carolina Building code.  

Planworx Response: See civil sheets for site parking summary information and/or necessary sheet revisions. Planworx does not have the final civil plans so cannot provide the number on the Appendix B of our plans.  Reviewed For Code Compliance

 Planworx Architecture, P.A.                                Permit Review Response Letter 

5711 Six Forks Road, Suite 100, Raleigh North Carolina, 27609                   (919)846‐8100 / fax 846‐2661 

3. Sheet A4.01.  Need UL fire rating detail for U305, U356, and P522. Per design comments for the fire separation for the pool equipment room.   

Planworx Response: The UL details can be found on sheets A0.20‐A0.22. 

4. Per sealed plans truss roof system sheet A4.11. Need truss layout from the truss company showing all imposed loads exceeding 5,000lbs. 

Planworx Response: General contractor to provide permitting office with truss package. 

5. Sheet E5.01. Need emergency light in the electrical room and equipment room per NEC 110.34(D).  Crenshaw Response: This fixture has been added.  6. Sheet AS4.10 and A4.11. Need revised plans designed and sealed for the 130 wind zone and chapter 16 of the North  Carolina building code. General notes states 100 mph wind zone. Planworx Response: This was a typo. The structural notes have been revised.  Project tracking #409130, 409144, 409471, 409472, 409473, 409474 Garage Types 1 and 2: Department‐Plan Review 1. Sheet A0.16 Garage building summary. Need to revise 2009 North Carolina State Building Codes. The 2012 North Carolina Building Code (2009 IBC with NC amendments) is the code in effect at time of application.  Planworx Response: This was a typo. The code summary has been corrected to reflect the correct code.  2. Sheet A0.16 Garage building summary. Need to revise appendix B to address code change from 2011 NEC to 2014 NEC. The 2014 NEC is the code in effect at time of application.  Planworx Response: This was a typo. The code summary has been corrected to reflect the correct code.  3. Per sealed plans truss roof system sheet AS6.10. Need truss layout from the truss company showing all imposed loads exceeding 5,000lbs.  Planworx Response: General contractor to provide permitting office with truss package.  4. Sheet A0.16 Garage building summary. Need UL fire rating detail for U305 (interior non‐bearing walls) and P522 (roof / ceiling assembly) per design comments on the plans.  Planworx Response: The UL details can be found on sheets A0.20‐A0.22. 

5. Sheet A0.16 Garage building summary. The life safety summary has fire alarm and smoke detection marked but on plans have been provided.  Planworx Response:   Project tracking #409476 Maint building: Department‐Plan Review 1. The site plan is marked “Progress drawings do not use for construction”. Need for construction site plan to review showing ADA parking, signs, and accessibility requirements per chapter 11 NC building code.  Planworx Response: GC to provide permit office with final, sealed plans.  2. Revise sheet A0.17. The 2012 North Carolina building code is the code in effect (2009 IBC with NC amendments known as “2012 code”).  Planworx Response: This was a typo. The code summary has been corrected to reflect the correct code.  Reviewed For Code Compliance

 Planworx Architecture, P.A.                                Permit Review Response Letter 

5711 Six Forks Road, Suite 100, Raleigh North Carolina, 27609                   (919)846‐8100 / fax 846‐2661 

3. Revise sheet A0.17. 2014 NEC is the electrical code in effect.  Planworx Response: This was a typo. The code summary has been corrected to reflect the correct code. 

4. Revise sheet A0.17. Complete accessible parking table per Table 1106.1 NC building code.  Planworx Response: See civil sheets for site parking summary information and/or necessary sheet revisions. Planworx does not have the final civil plans so cannot provide the number on the Appendix B of our plans. 5. Revise sheet A0.17. Fire alarm and smoke detection system marked on the life safety requirement with no detail sheets provided.  Planworx Response: See revised PME drawings.  6. Revise sheet A.017. Mark emergency lighting under the life safety section.  Planworx Response: The code summary has been revised.  7. Revise sheet A.017. Energy summary for commercial buildings of Type VB construction R38 in ceiling per Table 502.2(1) of NC energy code.  Planworx Response: The code summary has been revised accordingly. A note has been added to detail 5/A7.02 to clarify there is insulation in the attic space.  8. Revise sheet A.017. Energy summary for commercial buildings of Type VB construction R19 in walls per Table 502.2(1) of NC energy code.  Planworx Response: The code summary has been revised accordingly to reflect the information in the detail 5/A7.02 which is R‐13 with rigid insulation ILO the other option of R‐19.   9. Provide truss layout showing all imposed loads exceeding 5,000lbs. Per sheet A7.02 calls for a truss roof system by others.  Planworx Response: General contractor to provide permitting office with truss package.  10. Revise sheet E6.01. 1. Need an emergency light in the bathroom per [B]1006.3. 2. Need an emergency light above the electrical panel (panelboard) per NEC 110.34(D).  Crenshaw Response: The fixtures have been added.  Department‐Fire 1. Exit sign required, must be lit or an approved self‐luminous; Emergency Light required in the maintenance bay;  Emergency Light required on the exterior by the personnel door; Fire extinguisher required. Planworx Response: A fire extinguisher was noted on the floor plan.  Project tracking #409478 Pavilion: Department‐Plan Review 1. Sheet A0.18 Pavilion Building Code Summary. The design professional has classified the pavilion as Group‐U. Per [B]302.1 Occupant classification the proposed use is an area is intended for the gathering of persons for purposes of social and possible food or drink consumption. The occupant classification based on the intent of the code section [B]303.1 “Assembly” exception #3 less than 750 square feet would be a business occupancy (i.e. small assembly). Revising the occupant classification to Group B would meet the intent of section [B]302.1 and would align with the proposed use as opposed to a Group U classification.  Planworx Response: We have revised the code summary to reflect a B occupancy instead of the permitted U.    Reviewed For Code Compliance

 Planworx Architecture, P.A.                                Permit Review Response Letter 

5711 Six Forks Road, Suite 100, Raleigh North Carolina, 27609                   (919)846‐8100 / fax 846‐2661 

2. Sheet A0.18 Pavilion Building Code Summary. Assembly occupant load per table 1004.1.1 for standing space is 5 net. Revise the occupant load count for 5 net. 567 SF / 5 NET = 113 Occupants. The calculation provided by the design professional is for table and chairs and not standing space which is not consistent with code requirements based on use of the space per table 1004.1.1.  Planworx Response: We have revised the occupant load calculations on the code summary and floor plan.  3. Sheet A0.18 Pavilion Building Code Summary. Revise the life safety section to address panic hardware per [B]1008.1.10.  Planworx Response: The pavilion is open on all sides and there are no doors for this structure.  4. Sheet A0.18 Pavilion Building Code Summary. Revise the life safety section to address exit signs per [B]1011.1. A minimum of two marked exits are required per table [B]1021.1.  Planworx Response: Per NCBC 1011.1, exit signs are only required “where the exit or the path of travel is not immediately visible to the occupants.” We feel that sine the pavilion is open on all four sides, the exit is immediately visible and therefore exit signs are not required. Per exception #2 of section 1011.1, we are asking for an exception to not provide them.  5. Sheet A0.18 Pavilion Building Code Summary. Revise the life safety section to address emergency lights per [B]1006.3.  Planworx Response: Per section 1006.3, the pavilion does not have the 5 areas listed that are required to have emergency power. The pavilion is open on all four sides.  6. Sheet A0.18 Pavilion Building Code Summary. Revise the exit requirement section / table to address two required exits per table [B]1021.1.  Planworx Response: The code summary has been revised.  7. Sheet A0.18 Pavilion Building Code Summary. Revise the plumbing fixture requirements section per [P]table 403.1.  Planworx Response: Per NCBC section 2902.3, facilities shall not be in excess of 500’ from the provided space. All apartment buildings are within 500’ from the pavilion with the exception of apartment site buildings 900 and 1000 which are 672’ and 508’. With a majority of residents living within the 500’ radius, it is reasonable to expect them to return to their apartment to use the bathroom.  8. Sheet AS7.01 Pavilion Structure framing plans. Revise design for the 130 wind zone and per Chapter 16 of NC building code. The plan design comments are for 90 mph wind zone.  Planworx Response: This was a typo. The code summary has been corrected to reflect the correct wind speed.  9. Sheet M4.03. Need to provide gas piping plan and manufactures installation instructions for the proposed fireplace.  Crenshaw Response:  Gas piping plan and riser have been added to plan.  10. Sheet E6.02. Need to revise note #2 on top right of the plans for the 2014 National Electrical code.  Crenshaw Response: Code reference in note has been updated.    No further comments noted. End of response letter. 

Reviewed For Code Compliance

Reviewed For Code Compliance