Page 1: Reverse Polarity Signaling Module · Bosch Security Systems, Inc. is not responsible ... 1 FPD-7024 FACP 11 Negative (-) connection from power supply to D185 2 D185 module 12 EOL

Reverse Polarity Signaling ModuleD185

en Installation Instructions

Page 2: Reverse Polarity Signaling Module · Bosch Security Systems, Inc. is not responsible ... 1 FPD-7024 FACP 11 Negative (-) connection from power supply to D185 2 D185 module 12 EOL
Page 3: Reverse Polarity Signaling Module · Bosch Security Systems, Inc. is not responsible ... 1 FPD-7024 FACP 11 Negative (-) connection from power supply to D185 2 D185 module 12 EOL

NoticesThese instructions cover the installation of the D185 Reverse Polarity Signaling Module in afire system supervised by a fire alarm control panel (FACP) or a combination Burglary/Firecontrol panel.Before installing the module, become familiar with the Installation and Operation Guide for thecontrol panel you are using.Install, test and maintain the module according to these instructions, NFPA 72, local codes,and the authority having jurisdiction (AHJ). Failure to follow these instructions can result infailure of a detector to initiate an alarm event. Bosch Security Systems, Inc. is not responsiblefor improperly installed, tested or maintained devices.

!Warning!

Follow these instructions to avoid personal injury and damage to equipment.

NFPA 72 requires that you perform a complete system wide functional test following anymodifications, repair, upgrades or adjustments made to the system’s components, hardware,wiring, programming and software/firmware.

DescriptionThe D185 Reverse Polarity Signaling Module connects a control panel with either a single setor a pair of leased telephone company (telco) lines in NFPA 72 remote station applications.The module’s three input terminals accept alarm, trouble, or supervisory input from thecontrol panel, and the module transmits this information to a monitoring station after a built-in20±5 sec) delay. This module operates with either a 12 VDC or 24 VDC supply. All circuits arepower limited.The module can be used with the Bosch Security Systems, Inc. control panels indicated in thefollowing table. You can also use the module with non-Bosch, UL Listed control panels whereit is referenced as compatible in the control panel's installation instructions.

Control panels Compatible relays See section:

Active:

FPD-7024 panel D275, PAM-4 Wiring to an FPD-7024 FACP,page 7

G Series (GV2 and higher)panels1

D275, PAM-4 Wiring to a G Series controlpanel, page 8

Legacy:

D7024 panel See control panel documentation on the Bosch website(http://www.boschsecurity.com)

G Series (prior to GV2)panels2

D9412, D7412, and D7212**panels

DS9400 panel*

1

2

Reverse Polarity Signaling Module Notices | en 3

Bosch Security Systems, Inc. Installation Instructions 2013.05 | 03 | F.01U.034.781

Page 4: Reverse Polarity Signaling Module · Bosch Security Systems, Inc. is not responsible ... 1 FPD-7024 FACP 11 Negative (-) connection from power supply to D185 2 D185 module 12 EOL

Control panels Compatible relays See section:

1 G Series (GV2 or higher) = GV4 (D9412GV4, D7412GV4, and D7212GV4**), GV3(D9412GV3, D7412GV3, and D7212GV3**), and GV2 (D9412GV2, D7412GV2, andD7212GV2**) panels

2 G Series (prior to GV2) = D9412G, D7412G, and D7212G** panels

* Legacy products were investigated to comply only to UL864 8th edition

** indicates products which are not UL listed for commercial fire applications

Figure 2.1: D185 reverse polarity signaling module

1 Input terminals 10 Connects to telco line for sendingsupervisory signals

2 Earth Ground 11 Connects to telco line for sendingalarm\trouble signals

3 Common 12 Connects to telco line for sendingalarm\trouble signals

4 Connects to control panel Aux orexternal power supply (12 VDC or24 VDC)

13 Not used

5 Connects to Trouble Relay on controlpanel

14 Connects to end-of-line (EOL)supervisory relay (such as, D275,PAM‑4)

6 Connects to Supervisory Relay oncontrol panel

15 Alarm signal adjuster

7 Connects to Alarm Relay on the controlpanel

16 Supevisory signal adjuster

8 Output terminals 17 Alarm Test LED

9 Connects to telco line for sendingsupervisory signals

18 Alarm Test switch

4 en | Notices Reverse Polarity Signaling Module

2013.05 | 03 | F.01U.034.781 Installation Instructions Bosch Security Systems, Inc.

Page 5: Reverse Polarity Signaling Module · Bosch Security Systems, Inc. is not responsible ... 1 FPD-7024 FACP 11 Negative (-) connection from power supply to D185 2 D185 module 12 EOL

OperationUnder normal conditions, the module sends a steady 10 mA of current to the alarm telcooutputs and 14 mA of current to the supervisory output which connects to a monitoringstation. In an alarm or supervisory condition, the module reverses the output current polarityand signals a trouble condition by interrupting the output voltage and current.

Input Output

Alarm Supevisory Trouble Alarm Supervisory

No Current No Current No Current Normal Normal

No Current No Current Active High No Current Normal

No Current Active High No Current No Current Reversed Polarity

No Current Active High Active High No Current Reversed Polarity

Active High No Current No Current Reversed Polarity Normal

Active High Active High No Current Reversed Polarity Reversed Polarity

Active High Active High Active High Reversed Polarity Reversed Polarity

Table 3.1: Input and output states

Alarm and trouble responses (alarm output telco lines)The module responds to an alarm input from the control panel by reversing the alarm telcooutput polarity. The module responds to a trouble input from the control panel by interruptingthe current to the alarm telco outputsIf the control panel sends an alarm during a trouble signal, the module overrides the troubletelco output and responds with an alarm telco output (reversed polarity).

Supervisory response (supervisory output telco lines)The module responds to a supervisory signal input by reversing the polarity of the supervisorytelco outputs. A second set of telco lines must be connected.

Alarm testThe Alarm Test Switch (Item 18 in Figure 1 on page 2) disables module output during testingthat triggers a trouble output from the module during testing. Generally, this switch is off butduring an Alarm Test, you must move the switch to the ON position. Turning on the Alarm TestSwitch lights the Alarm Test LED (Item 17 in Figure 1).

InstallationNotice!

Install the module within 20 ft (6 m) of the control panel with a minimum of 22 AWG

(0.34 mm2) wire. Ensure all wiring is in conduit.

Install the D185 in a system by:

3

3.1

3.2

3.3

4

Reverse Polarity Signaling Module Notices | en 5

Bosch Security Systems, Inc. Installation Instructions 2013.05 | 03 | F.01U.034.781

Page 6: Reverse Polarity Signaling Module · Bosch Security Systems, Inc. is not responsible ... 1 FPD-7024 FACP 11 Negative (-) connection from power supply to D185 2 D185 module 12 EOL

Danger!

Inform the operator and the local AHJ before installing this module in an existing system.

Disconnect all power to the control panel before installing this module.

1. Removing power from the control panelBefore making or removing any connections to the FACP, remove the standby batterypower.Remove AC power from the system at the dedicated 120 VAC breaker.

2. Mounting the moduleThe module mounts on a snap-track and installs with a supplied screw in the controlpanel enclosure.

3. Connecting the moduleThe module has twelve screw terminal connection points, six on the left side for inputsand six on the right side for outputs (see the D185 reverse polarity signaling modulefigure in Description, page 3 and the Wiring, page 6 section).

!

Caution!

Connect input power only to the PWR Terminals.

4. Restoring power to the control panelRestore AC power to the system at the dedicated 120 VAC breaker.Reconnect the standby battery power.

5. Adjusting the amount of output currentTo adjust the amount of output current required on the telco output, use a screwdriver torotate the alarm signal adjuster.

WiringAn external 12 VDC or 24 VDC power supply listed for fire signaling units or commercial orresidential burglary units can be used.The external power supply must be UL1481 or UL864 Listed, regulated, and power‑limited.Install the control panel and external power supply in the same room no more than 20 ft (6 m)apart. The interconnecting wires between the control panel and external power supply mustbe in conduit.The power source for both the auxiliary power supply and the control panel must be from thesame dedicated AC branch circuit.

5

6 en | Notices Reverse Polarity Signaling Module

2013.05 | 03 | F.01U.034.781 Installation Instructions Bosch Security Systems, Inc.

Page 7: Reverse Polarity Signaling Module · Bosch Security Systems, Inc. is not responsible ... 1 FPD-7024 FACP 11 Negative (-) connection from power supply to D185 2 D185 module 12 EOL

Wiring to an FPD-7024 FACP

Wiring for power supplied by the FACP

Figure 5.1: Wiring an FPD-7024 FACP to supply 12 VDC power to the D185

1 FPD-7024 FACP 11 Negative (-) connection from powersupply to D185

2 D185 module 12 EOL supervision relay

3 Positive (+) power to Relay 3 (NC3) 13 Relay leads

4 Relay 3 (COM3) to trouble trigger 14 2.2 kΩ EOL resistor

5 Positive (+) power to Relay 2 (NO2) 15 D275 +12 VDC input (red wire)

6 Relay 2 (COM2) to supervisory trigger 16 Positive (+24 VDC) power connectionfrom FACP to EOL supervision relay

7 Earth Ground 17 D185 supervisory zone connection toEOL supervision relay

8 Positive (+) power to Relay 1 (NC1) 18 Telco connection for supervisory signal

9 Relay 1 (COM1) to alarm trigger 19 Telco connection for alarm\troublesignals

10 Positive (+) power connection fromFACP to D185 and EOL supervisionrelay

5.1

5.1.1

Reverse Polarity Signaling Module Notices | en 7

Bosch Security Systems, Inc. Installation Instructions 2013.05 | 03 | F.01U.034.781

Page 8: Reverse Polarity Signaling Module · Bosch Security Systems, Inc. is not responsible ... 1 FPD-7024 FACP 11 Negative (-) connection from power supply to D185 2 D185 module 12 EOL

Wiring for power supplied by an external power supply

Figure 5.2: Wiring an FPD-7024 FACP to a D185 with power supplied by an external power supply

1 FPD-7024 FACP 10 External power supply

2 D185 module 11 Positive (+) connection from powersupply to FACP relays, EOLsupervision relay, and D185

3 Positive (+) power to Relay 3 (NC3) 12 Negative (-) connection from powersupply to D185

4 Relay 3 (COM3) to trouble trigger 13 EOL supervision relay

5 Positive (+) power to Relay 2 (NO2) 14 Relay leads

6 Relay 2 (COM2) to supervisory trigger 15 2.2 kΩ EOL resistor

7 Positive (+) power to Relay 1 (NC1) 16 D185 supervisory zone connection toEOL supervision relay

8 Relay 1 (COM1) to alarm trigger 17 Telco connection for supervisory signal

9 Earth Ground 18 Telco connection for alarm\troublesignals

Wiring to a G Series control panel

5.1.2

5.2

8 en | Notices Reverse Polarity Signaling Module

2013.05 | 03 | F.01U.034.781 Installation Instructions Bosch Security Systems, Inc.

Page 9: Reverse Polarity Signaling Module · Bosch Security Systems, Inc. is not responsible ... 1 FPD-7024 FACP 11 Negative (-) connection from power supply to D185 2 D185 module 12 EOL

Wiring for power supplied by the control panel

Figure 5.3: Wiring G Series panels to supply power to a D185

1 D185 module 10 D185 SUPV TRIG connection to D130

2 G Series panel 11 G Series Relay A connection to D185ALRM TRIG

3 EOL supervision relay 12 D185 SUPV ZONE connection to theEOL supervision relay

4 D130 relay 13 G Series Relay C connection to EOLsupervision relay

5 If using 24 VDC, cut the wire 14 Connection to one relay lead of theEOL supervision relay to an on‑boardpoint on the control panel

6 Earth Ground 15 Connection to the other relay lead ofthe EOL supervision relay to anon‑board point on the control panel

7 Common connection between controlpanel, D130 relay, and D185 module

16 1 kΩ EOL resistor as specified for thecontrol panel

8 +12 VDC aux power from control panel 17 Telco connection for supervisory signal

9 G Series Relay B connection to D185TRBL TRIG

18 Telco connection for alarm\troublesignals

5.2.1

Reverse Polarity Signaling Module Notices | en 9

Bosch Security Systems, Inc. Installation Instructions 2013.05 | 03 | F.01U.034.781

Page 10: Reverse Polarity Signaling Module · Bosch Security Systems, Inc. is not responsible ... 1 FPD-7024 FACP 11 Negative (-) connection from power supply to D185 2 D185 module 12 EOL

Wiring for power supplied by an external power supply

Figure 5.4: Wiring G Series panels to a D185 with power supplied by an external power supply

1 D185 module 11 D185 supervisory trigger connection toD130 relay

2 G Series panel 12 G Series Relay A connection to D185ALRM TRIG

3 External power supply 13 D185 supervisory zone connection tothe EOL supervision relay

4 EOL supervision relay 14 G-series Relay C connection to theD130 relay

5 D130 relay 15 Connection to one relay lead of theEOL supervision relay to an on‑boardpoint on the control panel

6 If using 24 VDC, cut the wire 16 Connection to the other relay lead ofthe EOL supervision relay to anon‑board point on the control panel

7 Earth Ground 17 1 kΩ EOL resistor as specified for thecontrol panel

8 Common connection for externalpower supply, control panel, EOLsupervision relay, and D185 module

18 Telco connection for alarm\troublesignals

9 Positive (+) connection from powersupply to EOL supervision relay+12 VDC or +24 VDC input and D185PWR + terminal

19 Telco connection for supervisory signal

5.2.2

10 en | Notices Reverse Polarity Signaling Module

2013.05 | 03 | F.01U.034.781 Installation Instructions Bosch Security Systems, Inc.

Page 11: Reverse Polarity Signaling Module · Bosch Security Systems, Inc. is not responsible ... 1 FPD-7024 FACP 11 Negative (-) connection from power supply to D185 2 D185 module 12 EOL

10 G Series Relay B connection to D185TRBL TRIG

Programming

Programming an FPD-7024 FACPRelay 1 steady activation on alarm, Relay 2 steady activation on supervisory, and Relay 3steady activation on trouble.For programming details, see the control panel’s Installation and Operation Guide (IOG).

Programming a G Series control panelRelay A steady activation on alarm, Relay B steady activation on trouble, and Relay C steadyactivation on supervisory.For programming details, see the control panel’s Program Entry Guide (PEG).

SpecificationsElectrical

12 V 24 V

Power Inputs (forstandby batterycalculations)

Start up voltage 11 VDC

Minimum voltage 10.2 VDC

Maximum voltage 30 VDC

Idle current draw 245 mA 120 mA

Alarm current draw 300 mA 143 mA

Inputs Minimum Maximum

– Alarm* Voltage 10.2 VDC 30 VDC

Current 2.25 mA 8.1 mA

– Supervisory Voltage 10.2 VDC 30 VDC

Current 2.25 mA 8.1 mA

– Trouble Voltage 10.2 VDC 30 VDC

Current 2.25 mA 8.1 mA

Supervisory Zone (current sink) Minimum Maximum

0 mA 35 mA

Telco Output CurrentAdjustment Range

Minimum Maximum

Current 2.5 mA 15 mA

Nominal 10 mA

* The alarm activation delay is 20±5 sec

6

6.1

6.2

7

Reverse Polarity Signaling Module Notices | en 11

Bosch Security Systems, Inc. Installation Instructions 2013.05 | 03 | F.01U.034.781

Page 12: Reverse Polarity Signaling Module · Bosch Security Systems, Inc. is not responsible ... 1 FPD-7024 FACP 11 Negative (-) connection from power supply to D185 2 D185 module 12 EOL

Environmental

Environment Indoor, dry

Relative Humidity <93%, non‑condensing

Temperature +32°F to +120°F (0°C to +49°C)

12 en | Notices Reverse Polarity Signaling Module

2013.05 | 03 | F.01U.034.781 Installation Instructions Bosch Security Systems, Inc.