  • Residential Plumbing Inspector (CAP)

    Lesson 2

    Utilities

    Base on 2014 OPSC

    1 Updated: June 2015

  • of 100

    Sewers

    305.0 Every building in which plumbing fixtures are

    installed shall have a connection to a public or

    private sewer.

    308.0 Except as otherwise provided in this code, no

    plumbing system, drainage system, building sewer,

    private sewage disposal system, or parts thereof shall

    be located in any lot other than the lot that is the site

    of the building, structure, or premises served by such

    facilities.

    2

  • of 100

    713.2 When no public sewer intended to serve any lot or

    premises is available in any thoroughfare or right of way

    abutting such lot or premises, drainage piping from any

    building or works shall be connected to an approved

    private sewage disposal system.

    713.4 The public sewer shall be permitted to be

    considered as not being available when such public

    sewer or any building or any exterior drainage facility

    connected thereto is located more than two-hundred

    (200) feet from any proposed building or exterior

    drainage facility on any lot or premises that abuts and is

    served by such public sewer.

    3

  • of 100

    713.3 Within the limits prescribed by Section 713.4 hereof,

    the rearrangement or subdivision into smaller parcels of a lot

    that abuts and is served by a public sewer shall not be

    deemed cause to permit the construction of a private sewage

    disposal system, and plumbing or drainage systems on any

    such smaller parcel or parcels shall connect to the public

    sewer.

    713.4 The public sewer shall be permitted to be considered

    as not being available when such public sewer or any

    building or any exterior drainage facility connected thereto

    is located more than two-hundred (200) feet from any

    proposed building or exterior drainage facility on any lot or

    premises that abuts and is served by such public sewer.

    4

  • of 100 5

  • of 100

    Sewers

    312.0 The drainage system of each new building and of new work installed in any existing building shall be separate and independent from that of any other building, and, when available, every building shall have an independent connection with a public or private sewer.

    Exception: where one building stands in the rear of another building on an interior lot, and no private sewer is available or can be constructed to the rear building through an adjoining court, yard, or driveway, the building drain from the front building shall be permitted to be extended to the rear building.

    6

  • of 100 7

  • of 100 8

  • of 100

    TABLE 7-1

    Materials for Drain, Waste, Vent Pipe and Fittings

    Material Underground Drain, Waste,

    Vent Pipe and Fittings

    Above ground Drain,

    Waste, Vent Pipe and

    Fittings

    Building Sewer Pipe and

    Fittings

    Referenced Standard(s)

    Pipe Referenced Standard(s) Fittings

    ABS (Schedule40) X X X

    ASTM D1527, ASTM

    D2661, ASTM D26801 ,

    ASTM F628

    ASTM D2661, ASTM D26801

    Asbestos-Cement X

    ASTM C4281 , ASTM C141

    Brass

    X

    ASTM B43

    Cast-Iron X X X ASTM A74, ASTM A888,

    CISPI 301

    ASME B16.12, ASTM A74, ASTM A888, CISPI 301

    Co-Extruded ABS

    (Schedule40) X X X ASTM F1488 ASTM, D2661, ASTM D26801

    Co-Extruded PVC

    (Schedule40) X X X ASTM F1488, ASTM F891

    ASTM D2665, ASTM F7941 , ASTM F1866

    Copper

    (Type DWV) X X X

    ASTM B75, ASTM B251,

    ASTM B302, ASTM B306 ASME B16.23, ASME B16.29

    Galvanized Malleable Iron

    X

    ASME B16.3

    Galvanized Steel

    X

    ASTM A53

    PVC

    (Schedule 40) X X X

    ASTM D1785, ASTM

    D2665, ASTM F7941 ASTM D2665, ASTM F7941 , ASTM F1866

    Stainless Steel 304 X

    ASME A112.3.1 ASME A112.3.1

    Stainless Steel 316L X X X ASME A112.3.1 ASME A112.3.1

    Vitrified Clay (Extra

    strength)

    X ASTM C700 ASTM C700

    1 For Building Sewer applications.

    9

  • of 100

    Clay Pipe

    10

  • of 100

    PVC DWV Pipe

    11

  • of 100

    ABS Pipe

    12

  • of 100

    SDR Pipe

    ASTM-D-3034

    This product is listed per chapter 14

    13

  • of 100

    Concrete

    14

  • of 100

    Cast Iron Sewer Pipe

    15

  • of 100

    718.3 No building sewer or other drainage piping or part thereof, which is constructed of materials other than those approved for use under or within a building, shall be installed under or within five (5) feet of any building or structure, or part thereof, nor less than one (1) foot below the surface of the ground. The provisions of this subsection include structures such as porches and steps, whether covered or uncovered; breezeways; roofed porte cocheres; (po rt-k-sher) roofed patios; carports; covered walks; covered driveways; and similar structures or appurtenances.

    16

  • of 100

    Trenching

    315.0 Trenches deeper than the footing of any

    building or structure and paralleling the same

    shall be not less than 45 degrees

    17

  • of 100

    Backfill

    315.3 Excavations shall be completely backfilled as

    soon after inspection as practicable. to such piping.

    Trenches shall be backfilled in thin layers to twelve

    (12) inches above the top of the piping with clean

    earth, which shall not contain stones, boulders,

    cinder fill, frozen earth, construction debris, or other

    materials that would damage or break the piping or

    cause corrosive action.

    18

  • of 100 19

  • of 100

    Water & Sewer

    720.1 Building sewers or drainage piping of

    clay or materials that are not approved for use

    within a building shall not be run or laid in the

    same trench as the water pipes unless both of

    the following requirements are met:

    (1) The bottom of the water pipe, at points,

    shall be not less than twelve (12) inches above

    the top of the sewer or drain line.

    20

  • of 100

    (2) The water pipe shall be placed on a solid shelf

    excavated at one (1) side of the common trench with

    a clear horizontal distance of not less than twelve

    (12) inches from the sewer or drain line. Water

    pipes crossing sewer or drainage piping constructed

    of clay or materials that are not approved for use

    within a building shall be laid not less than twelve

    (12) inches above the sewer or drain pipe.

    Note: For the purpose of this section, within the

    building shall mean within the fixed limits of the

    building foundation.

    21

  • of 100 22

  • of 100

    718.1 Building sewers shall be run in practical alignment and at a uniform slope of not less than one-fourth (1/4) of an inch per foot toward the point of disposal.

    Exception: When approved by the building official and where it is impractical, due to the depth of the street sewer or to the structural features or to the arrangement of any building or structure, to obtain a Slope of one-fourth (1/4) of an inch per foot, any such pipe or piping four (4) inches through six (6) inches shall be permitted to have a slope of not less than one-eighth (1/8) inch per foot and any such piping eight (8) inches and larger shall be permitted to have a slope of not less than one-sixteenth (1/16) of an inch per foot.

    Take a look at table 7-5 FN 5

    Slope

    23

  • of 100 24

  • of 100

    718.3 No building sewer or other drainage piping or

    part thereof, which is constructed of materials other

    than those approved for use under or within a

    building, shall be installed under or within five (5)

    feet of any building or structure, nor less than one (1)

    foot below the surface of the ground.

    Depth

    25

  • of 100

    Size of Sewer

    717.1 The minimum size of any building sewer shall

    be determined on the basis of the total number of

    fixture units drained by such sewer, in accordance

    with Table 7-8. No building sewer shall be smaller

    than the building drain.

    Rule of thumb;

    3-bath house minimum 3 sewer

    4-bath house minimum 4 sewer 26

  • of 100 27

  • of 100

    Table 7-5

    Maximum Unit Loading and Maximum Length of Drainage and Vent Piping

    Size of Pipe, inches

    (mm)

    1-1/4

    (32)

    1-1/2

    (40)

    2

    (50)

    2-1/2

    (65)

    3

    (80)

    4

    (100)

    5

    (125)

    6

    (150)

    8

    (200)

    10

    (250)

    12

    (300)

    Maximum Units

    Drainage Piping1

    Vertical 1 22 16

    3 32

    3 48

    4 256 600

    1,38

    0 3,600 5,600 8,400

    Horizontal 1 22

    83 14

    3 35

    4,5 216

    5 428

    5 720

    5 2,640

    5 4,6805

    8,2005

    Maximum Length

    Drainage Piping

    Vertical, feet 45 65 85 148 212 300 390 510 750

    (m) (14) (20) (26) (45) (65) (91) (119) (155) (228)

    Horizontal (unlimited)

    28

  • of 100

    Table 7-5 Footnote