Page 1: RentalServices - Trane Mid-America · PDF file4 Rental Services Air Handling Unit • CHS-SVN01A-EN AirHandlingUnits Introduction This engineering bulletin covers the rental air handling

Installation Manual

Rental ServicesAir Handling Units

July 2008 CHS-SVN01A-EN

Page 2: RentalServices - Trane Mid-America · PDF file4 Rental Services Air Handling Unit • CHS-SVN01A-EN AirHandlingUnits Introduction This engineering bulletin covers the rental air handling

2 Rental Services Air Handling Unit • CHS-SVN01A-EN

Copyright© 2008 Trane All rights reservedThis document and the information in it are the property of Trane and may not beused or reproduced in whole or in part, without the written permission of Trane.Trane reserves the right to revise this publication at any time and to make changesto its content without obligation to notify any person of such revision or change.

TrademarksTrane, Rover, the Trane logo, are trademarks of Trane in the United States andother countries. All other brands and products referenced in this document areacknowledged to be the trademarks or registered trademarks of their respectiveholders.

Warnings and Cautions.Notice that warnings and cautions appear at appropriate intervals throughoutthis manual. Warnings are provided to alert installing parties of potential hazardsthat could result in personal injury or death, while cautions are designed to alertpersonnel to conditions that could result in equipment damage.

Your personal safety and the proper operation of the Trane Rental Servicestemporary chilled water system depend upon the strict observation of theseprecautions. Please refer to the Installation Operation Manual (IOM) for allappropriate Warning and Cautions.

© Trane All rights reserved

Page 3: RentalServices - Trane Mid-America · PDF file4 Rental Services Air Handling Unit • CHS-SVN01A-EN AirHandlingUnits Introduction This engineering bulletin covers the rental air handling

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

10,000 cfm Air Handling Unit (nom. 25 tons) . . . . . . . . . . . . . . . . . . . . .610,000 cfm Air Handling Unit Fan Curve . . . . . . . . . . . . . . . . . . . .710,000 cfm Air Handling Unit Drawing . . . . . . . . . . . . . . . . . . . . .8

25,000 cfm Air Handling Unit w/VFD . . . . . . . . . . . . . . . . . . . . . . . . . . . .925,000 cfm Air Handling Unit Fan Curve . . . . . . . . . . . . . . . . . . .1025,000 cfm Air Handling Unit Drawing . . . . . . . . . . . . . . . . . . . .11

Electrical Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

Piping Connection Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1210,000 cfm Unit Piping Manifold . . . . . . . . . . . . . . . . . . . . . . . . .1225,000 cfm Unit Piping Manifold . . . . . . . . . . . . . . . . . . . . . . . . .13

Duct Configuration Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

Controls Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

Rigging Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17

Installation/Startup Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18

Maintenance Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

Decommissioning Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

Contents

CHS-SVN01A-EN • Rental Services Air Handling Unit 3

Page 4: RentalServices - Trane Mid-America · PDF file4 Rental Services Air Handling Unit • CHS-SVN01A-EN AirHandlingUnits Introduction This engineering bulletin covers the rental air handling

4 Rental Services Air Handling Unit • CHS-SVN01A-EN

Air Handling Units

Introduction

This engineering bulletin covers the rental air handling units (AHU) available to rentfrom Trane Rental Services for temporary cooling solutions. This includes AHUtechnical information, start-up information, and unit maintenance. The informationcontained in this bulletin is provided to ensure the safe installation and operation ofthe equipment and its surroundings.

The information provided in this Engineering Bulletin is to be used as a reference foreach AHU to aid in determining unit size, power requirements, or lifting requirements.If additional information regarding a particular unit is required, please contact TraneRental Services.

Contact Trane Rental Services Marketing for availability of equipment (includingancillary items: pumps, flexible hose, flexible duct) prior to obtaining a purchase orderfrom the customer. Equipment is available on a first-come, first-serve basis, but can bereserved with a signed rental agreement.

Call Rental Services 24 x 7 at (800) 755-5115 for specific questions.

Live Electrical Components!

During installation, testing, servicing and troubleshooting of this product, itmay be necessary to work with live electrical components. Have a qualifiedlicensed electrician or other individual who has been properly trained inhandling live electrical components perform these tasks. Failure to follow allelectrical safety precautions when exposed to live electrical componentscould result in death or serious injury.

Important: All air handlers should be installed per the National Electric Code(NEC) and/or applicable state and local codes.

Note: All information contained in this document is for reference only.

! WARNING

Page 5: RentalServices - Trane Mid-America · PDF file4 Rental Services Air Handling Unit • CHS-SVN01A-EN AirHandlingUnits Introduction This engineering bulletin covers the rental air handling

CHS-SVN01A-EN • Rental Services Air Handling Unit 5

Air Handling Units

General Information

Our rental air handling units are custom Trane air handlers that have been modified foruse as rental units. The majority of the modifications are related to framing for riggingpurposes, connection of chilled water piping, and temporary duct connection.

These air handling units contain only chilled water coils and do not have heatingcapability. Each unit has been selected for use with 100% outside air. Return plenumsare available if required.

An MP580 controller with touch screen display and wireless zone sensor is includedwith each unit. In addition, each unit includes a Trane TR1 variable frequency drive(VFD) that can control the fan motor. For additional information on the unit controlssee “Controls Information” on page 15.

Page 6: RentalServices - Trane Mid-America · PDF file4 Rental Services Air Handling Unit • CHS-SVN01A-EN AirHandlingUnits Introduction This engineering bulletin covers the rental air handling

6 Rental Services Air Handling Unit • CHS-SVN01A-EN

10,000 cfm Air Handling Unit

General – RSAU0025F0 _ _Model Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .TCCANominal Tonnage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25 tonsWater Connection Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5 in. VictaulicAmbient Operating Conditions1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25–115°FSupply Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 HpFused Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .YesNumber of Electrical Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1Discharge Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . HorizontalFlex Duct Connection Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 in roundNumber of Discharge Air Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Max Discharge Static Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.82 in. ESPFilter Rack (Quantity and size)2 . . . . . . . . . . . . . . . . . . . . . (4) 24” x 24”, (2) 24” x 12”Nominal Air Flow (cfm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10,000Min/Max Air Flow (cfm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8,000/15,000Insurance Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . $35,000Selection is required for actual AHU performance.1For ambient conditions below 40°F, glycol is recommended.2Unit provided with standard 2” filters. Filter rack will accept up to 95% efficient MERV 14 filters.

Electrical DataVoltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 460V 3-phaseFrequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 HzLug(s) can accept wire up to3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . #3 AWG wireMinimum Circuit Ampacity (MCA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42.5 ampsMaximum Overcurrent Protection (MOP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 amps3Depending on unit MCA and wire used, multiple wires per phase may be required.

For additional electrical information contact Trane Rental Services.

Total Cooling CapacityEntering Chilled Water Temperature (F) Outdoor Ambient Temperature (F)

84 db / 77 wb44 909.85 MBh

Contact Trane Rental Services for specific selection information.

Water Flow RatesMinimum Standard Maximum

Coil Flow 70 gpm 151 gpm 400 gpmPressure Drop — 4.61 ft H20 —

Maximum water side pressure is 150psi (2.31’ H20 = 1 psi)

Dimensions and WeightsLength 16 ft 0 inWidth4 7 ft 4 inHeight 7 ft 6 inWeight 6,000 lbs

4Width includes permanently mounted piping manifold.

Lifting Device: Fork Lift or Crane

Page 7: RentalServices - Trane Mid-America · PDF file4 Rental Services Air Handling Unit • CHS-SVN01A-EN AirHandlingUnits Introduction This engineering bulletin covers the rental air handling

CHS-SVN01A-EN • Rental Services Air Handling Unit 7

10,000 cfm Air Handling Unit (nom. 25-tons)

10,000 cfm Air Handling Unit Fan Curve

Page 8: RentalServices - Trane Mid-America · PDF file4 Rental Services Air Handling Unit • CHS-SVN01A-EN AirHandlingUnits Introduction This engineering bulletin covers the rental air handling

8 Rental Services Air Handling Unit • CHS-SVN01A-EN

10,000 CFM Air Handling Units

10,000 cfm Air Handling Unit Drawing

Note: Drawing should be used for information only as drawing depicts factoryunit without rental modifications.

Page 9: RentalServices - Trane Mid-America · PDF file4 Rental Services Air Handling Unit • CHS-SVN01A-EN AirHandlingUnits Introduction This engineering bulletin covers the rental air handling

CHS-SVN01A-EN • Rental Services Air Handling Unit 9

25,000 CFM Air Handling Units

General – RSAU0062F0 _ _Model Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .TCCANominal Tonnage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62.5 tonsWater Connection Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 in. VictaulicAmbient Operating Conditions1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25 - 115°FSupply Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50 HpFused Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .YesNumber of Electrical Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1Discharge Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .HorizontalFlex Duct Connection Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 in. roundNumber of Discharge Air Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4Max Discharge Static Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6.00 in. ESPFilter Rack (Quantity and size)2 . . . . . . . . . .(9) 24” x 24”, (3) 24” x 12”, (3) 12” x 24”Nominal Air Flow (cfm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25,000Min/Max Air Flow (cfm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15,000/35,000Insurance Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . $45,000Selection is required for actual AHU performance.1For ambient conditions below 40°F, glycol is recommended.2Unit provided with standard 2” filters. Filter rack will accept up to 95% efficient MERV 14 filters.

Electrical DataVoltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 460V 3-phaseFrequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 HzLug(s) can accept wire up to3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1/0 AWG wireMinimum Circuit Ampacity (MCA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 ampsMaximum Overcurrent Protection (MOP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 amps3Depending on unit MCA and wire used, multiple wires per phase may be required.

For additional electrical information contact Trane Rental Services.

Total Cooling CapacityEntering Chilled Water Temperature (F) Outdoor Ambient Temperature (F)

84 db / 77 wb44 2274.6 MBh

Contact Trane Rental Services for specific selection information.

Water Flow RatesMinimum Standard Maximum

Coil Flow 110 gpm 378 gpm 820 gpmPressure Drop — 12.26 ft H20 —

Maximum water side pressure is 150psi (2.31’ H20 = 1 psi)

Dimensions and WeightsLength 18 ft 2 inWidth4 8 ft 6 inHeight 10 ft 1 inWeight 10,500 lbs

4Width does not include field installed piping manifold.

Lifting Device: Fork Lift or Crane

Page 10: RentalServices - Trane Mid-America · PDF file4 Rental Services Air Handling Unit • CHS-SVN01A-EN AirHandlingUnits Introduction This engineering bulletin covers the rental air handling

10 Rental Services Air Handling Unit • CHS-SVN01A-EN

25,000 CFM Air Handling Units

25,000 cfm Air Handling Unit Fan Curve

Page 11: RentalServices - Trane Mid-America · PDF file4 Rental Services Air Handling Unit • CHS-SVN01A-EN AirHandlingUnits Introduction This engineering bulletin covers the rental air handling

CHS-PRB009-EN • Rental Services Air Handling Unit 11

25,000 CFM Air Handling Units

25,000 cfm Air Handling Unit Drawing

Note: Drawing should be used for information only as drawing depicts factory unit without rentalmodifications.

Page 12: RentalServices - Trane Mid-America · PDF file4 Rental Services Air Handling Unit • CHS-SVN01A-EN AirHandlingUnits Introduction This engineering bulletin covers the rental air handling

12 Rental Services Air Handling Unit • CHS-SVN01A-EN

Electrical Information

Each air handling unit (AHU) has an external fused disconnect as shown in Figure 1. Inaddition to the external fused disconnect each unit has an external “start/stop” buttonon the outside of the control cabinet access door (Figure 2) and a circuit breaker insidethe control cabinet (Figure 3).

Each 10,000cfm unit is provided with a minimum of 50-ft of #8/4 600V electrical cableconnected to the external fused disconnect. Each 25,000cfm unit is provided with aminimum of 50-ft of #4/4 600V electrical cable connected to the external fuseddisconnect.

Piping Connection Configuration10,000 cfm Air Handling Unit (RSAU0025F0__)Each 10,000 cfm AHU has two 2.5-in threaded inlet chilled water connections and two2.5-in threaded outlet chilled water connections.

Piping ManifoldTo provide a single chilled water connection point for each 10,000 cfm air handlingunit, a piping manifold has been made to connect each unit’s chilled water coils. Each10,000 cfm unit has a manifold that is permanently installed on the unit for flex hoseconnection (Figure 4). The contents of the drop down kit for the 10,000 cfm units arelisted in the bill of material below. The manifold kit will ship in the mixed air chamberand can be accessed through the filter access door.

FIGURE 1 Disconnect FIGURE 2 Emergency stop FIGURE 3 Circuit breaker

Air Handling Units

Page 13: RentalServices - Trane Mid-America · PDF file4 Rental Services Air Handling Unit • CHS-SVN01A-EN AirHandlingUnits Introduction This engineering bulletin covers the rental air handling

CHS-SVN01A-EN • Rental Services Air Handling Unit 13

Air Handling Units

Bill of Material for 10,000 cfm Air Handling Unit Piping Manifold

FIGURE 4 10,000 cfm unit piping manifold

25,000 cfm Air Handling Unit (RSAU0062F0__)Each 25,000 cfm AHU has four 2.5-in threaded inlet chilled water connections and four2.5-in threaded outlet chilled water connections.

Piping ManifoldTo provide a single chilled water connection point for each 25,000 cfm air handlingunit, a piping manifold has been made to connect each unit’s chilled water coils. Each25,000 cfm unit has a manifold that must be field installed on each unit for flex hoseconnection (Figure 5). The contents of the piping manifold kit for the 25,000 cfm unitsare listed in the bill of material below. The manifold kit will ship in the mixed airchamber and can be accessed through the filter access door.

QUANTITY DESCRIPTION OF ITEMS

8 2.5” Victaulic quick-snap couplings

2 2.5” 30” pipe section

4 2.5” Victaulic 90 degree elbows

Page 14: RentalServices - Trane Mid-America · PDF file4 Rental Services Air Handling Unit • CHS-SVN01A-EN AirHandlingUnits Introduction This engineering bulletin covers the rental air handling

14 Rental Services Air Handling Unit • CHS-SVN01A-EN

Air Handling Units

Bill of Material for 25,000 cfm Air Handling Unit Piping Manifold

FIGURE 5 25,000 cfm unit piping manifoldReference the Rental Services hose engineering bulletin, CHS-PRB007-EN,for further information.

QUANTITY DESCRIPTION OF ITEMS

2 4” Manifold pipe section

2 4” Victaulic blank off

8 4” Victaulic quick-snap couplings

24 2.5” Victaulic quick-snap couplings

4 2.5” x 3” flex hose section

2 2.5” x 6” pipe section

8 2.5” Victaulic 90 degree elbows

2 4” x 6” Victaulic reducers

2 4” x 43” pipe section

4 4” Victaulic 90 degree elbows

Page 15: RentalServices - Trane Mid-America · PDF file4 Rental Services Air Handling Unit • CHS-SVN01A-EN AirHandlingUnits Introduction This engineering bulletin covers the rental air handling

CHS-SVN01A-EN • Rental Services Air Handling Unit 15

Duct Connection Configuration10,000 cfm Air Handling Unit (RSAU0025F0__)Each 10,000 cfm AHU has two 19-in diameter discharge air connections. Eachdischarge air connection has a manual damper to control air flow. Each connectionwas made to accept one 20-in diameter flexible duct.

25,000 cfm Air Handling Unit (RSAU0062F0__)Each 25,000 cfm AHU has four 19-in diameter discharge air connections. Eachdischarge air connection has a manual damper to control air flow. Each connectionwas made to accept one 20-in diameter flexible duct.

FIGURE 6 Flex Duct ConnectionReference the Rental Services flex duct engineering bulletin, CHS-PRB004-EN,for further information.

Air Handling Units

Controls InformationAll 10,000 cfm and 25,000 cfm rental air handling units come equipped with a TraneMP-580 controller (Figure 7) and Trane TR-1 VFD (Figure 8) mounted in a controlcabinet inside the unit. The controller is accessed by opening the external controlcabinet door with an emergency stop button. In order for the unit to run using theMP-580 controller and default controls program, the VFD selector switch must be in“VFD” mode (Figure 9).

The unit control program can be accessed using a laptop computer with the Rover™service tool software or the unit-mounted stand alone display. The stand alone display ismounted in a sealed cabinet on the front of the unit next to the external disconnect(Figure 10). The operator display touch screen is an intuitive operator interface formonitoring and changing building control functions. With the operator display you can:

Page 16: RentalServices - Trane Mid-America · PDF file4 Rental Services Air Handling Unit • CHS-SVN01A-EN AirHandlingUnits Introduction This engineering bulletin covers the rental air handling

16 Rental Services Air Handling Unit • CHS-SVN01A-EN

Unit Nominal Air Flow (cfm) Min Air Flow (cfm) Max Air Flow (cfm)

10,000 8,000 15,00025,000 15,000 35,000

FIGURE 7 MP-580 controller FIGURE 8 TR1 VFD FIGURE 9 VFD Selector Switch• Choose between “constant volume” or “VAV.”

• Choose specific air flow within specified range.

• Monitor space temperature, air flow, filter status, etc.

• Identify and troubleshoot problems.

• View and reset controller alarms.

The operator display includes a 7-day time clock that allows for time-of-day scheduling withtwo on/off times per day and up to 20 exception schedules per year.

Both the 10,000 cfm and 25,000 cfm units can be configured to run based on a specifiedair flow (CV) or be controlled by space temperature (VAV) using the Rover service tool orthe stand alone display. If the unit is configured as “CV” (or constant volume) the unit airflow can be specified within a certain air flow range. See chart below for air flow rangeper unit.

If the unit is configured as “VAV” the unit will be controlled by the zone set-point usingthe wireless zone sensor that is provided with each unit. The wireless zone sensor canbe found inside the control cabinet and is strapped in place for shipment. (See BAS-SVX04A-EN for additional information on wireless zone sensor.)

FIGURE 10 Unit Mounted Display FIGURE 11 Typical Status Screen

Air Handling Units

Page 17: RentalServices - Trane Mid-America · PDF file4 Rental Services Air Handling Unit • CHS-SVN01A-EN AirHandlingUnits Introduction This engineering bulletin covers the rental air handling

CHS-SVN01A-EN • Rental Services Air Handling Unit 17

Air Handling Units

Rigging GuidelinesEach air handling unit has forklift pockets and an overhead lifting frame (Figure 12).Refer to page 5 and page 7 for unit dimensions and weights.

Heavy Objects!Use a forklift/crane of suitable capacity to move the unit. Failure to properly lift unitcould result in death or serious injury or possible equipment or property-only damage.

FIGURE 12 10,000 cfm Unit in Frame

! WARNING

Page 18: RentalServices - Trane Mid-America · PDF file4 Rental Services Air Handling Unit • CHS-SVN01A-EN AirHandlingUnits Introduction This engineering bulletin covers the rental air handling

18 Rental Services Air Handling Unit • CHS-SVN01A-EN

Installation and Startup GuidelinesIn addition to the startup guidelines below, please refer to startup informationcontained in the Custom Climate Changer Installation, Operation and MaintenanceManual (CAH-SVX01A-EN), TR1 Series VFD Installation and Operation Manual (TR1-SVX10A-EN), and Wireless Zone Sensor Installation, Operation and MaintenanceManual (BAS-SVX04A-EN).

[ ] Install piping manifold supplied with unit and ensure all temporary piping isproperly secured. See piping configuration information on page 12.

[ ] To avoid flooding of unit interior install the P-trap supplied with unit. The unit P-trapis located in a bin in the mixed air chamber that is accessed through the filteraccess door.

[ ] Close all coil drains.

[ ] Install all temporary ductwork and open manual supply dampers. See ductconnection configuration information on page 15.

[ ] Connect electrical cable supplied with unit to power supply. See electricalinformation on page 12.

[ ] Turn the fused disconnect switch located on the front of the unit to the “ON”position.

[ ] Open the control cabinet door and turn the VFD selector switch to the “VFD”position.

[ ] Make sure all access doors are properly closed.

[ ] Using the unit mounted stand alone touch screen display select either “CV” or“VAV.” See page 16 for display location and explanation of the CV and VAV options.

Note: Power must be supplied to the unit to operate the touch screen display.

[ ] If the “VAV” option is selected remove the wireless zone sensor that is shippedinside the unit control cabinet and locate in the conditioned space.

[ ] Pull the red Start/Stop button on the unit control cabinet door to start the unit fan.

Air Handling Units

Page 19: RentalServices - Trane Mid-America · PDF file4 Rental Services Air Handling Unit • CHS-SVN01A-EN AirHandlingUnits Introduction This engineering bulletin covers the rental air handling

CHS-SVN01A-EN • Rental Services Air Handling Unit 19

Air Handling Units

Maintenance GuidelinesPlease refer to the Custom Climate Changer Installation, Operation and MaintenanceManual (CAH-SVX01A-EN) and Wireless Zone Sensor Installation, Operation andMaintenance Manual (BAS-SVX04A-EN) for any regular unit maintenance.

[ ] Monitor differential pressure across the unit filters using the pressure gaugemounted on the outside of the filter access door and change the filters as necessary(see pages 6 and 9 for unit filter rack quantities). Filter status can also be monitoredusing the stand alone touch screen display mounted in a cabinet on the front ofthe unit.

Decommissioning Guidelines

Reference the following guidelines for decommissioning rental AHUs prior to theirreturn at the end of a rental job. Please contact Trane Rental Services at 800-755-5115for any additional information.

[ ] Press the red Start/Stop button on the unit control cabinet door. Allow enough timefor the supply fan to come to a complete stop before opening any unit accessdoors.

[ ] Turn the fused disconnect located on the front of the unit to the “OFF” position.

[ ] Open the control cabinet door and turn the VFD selector switch to the “OFF”position.

[ ] Drain solution from the system. If the system has glycol or other anti-freezesolution, flush hoses, manifold, and coil with water. Note: Local codes andregulations apply for disposal of glycol or anti-freeze solutions.

[ ] Remove all external piping, temporary manifold pieces (see piping configurationsection on page 12), and P-trap. Return P-trap and temporary manifold pieces to thebin located in the mixed air chamber that is accessed through the filter access door.

[ ] Open all coil drains.

[ ] Remove all temporary ductwork and close manual supply dampers.

[ ] Disconnect electrical cable supplied with the unit from the power supply.

[ ] Make sure all access doors are properly closed.

[ ] Return additional hose, fittings, or cable (if furnished by Trane Rental Services) toappropriate containers for return shipment.

[ ] Notify Trane Rental Services (800-755-5115) if unit needs repair or has damage.

Page 20: RentalServices - Trane Mid-America · PDF file4 Rental Services Air Handling Unit • CHS-SVN01A-EN AirHandlingUnits Introduction This engineering bulletin covers the rental air handling

www.trane.com

Formore information, contact your local Traneofficeor e-mail us at [email protected]

Literature Order Number CHS-SVN01A-EN

Date July 2008

Supersedes New