ref611_appl_757456_ena
DESCRIPTION
ref611 application manualTRANSCRIPT
Relion® 611 series
Feeder Protection and ControlREF611Application Manual
Document ID: 1MRS757456Issued: 2011-11-18
Revision: AProduct version: 1.0
© Copyright 2011 ABB. All rights reserved
CopyrightThis document and parts thereof must not be reproduced or copied without writtenpermission from ABB, and the contents thereof must not be imparted to a thirdparty, nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a licenseand may be used, copied, or disclosed only in accordance with the terms of suchlicense.
TrademarksABB and Relion are registered trademarks of the ABB Group. All other brand orproduct names mentioned in this document may be trademarks or registeredtrademarks of their respective holders.
WarrantyPlease inquire about the terms of warranty from your nearest ABB representative.
http://www.abb.com/substationautomation
DisclaimerThe data, examples and diagrams in this manual are included solely for the conceptor product description and are not to be deemed as a statement of guaranteedproperties. All persons responsible for applying the equipment addressed in thismanual must satisfy themselves that each intended application is suitable andacceptable, including that any applicable safety or other operational requirementsare complied with. In particular, any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including butnot limited to personal injuries or death) shall be the sole responsibility of theperson or entity applying the equipment, and those so responsible are herebyrequested to ensure that all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot becompletely ruled out. In case any errors are detected, the reader is kindly requestedto notify the manufacturer. Other than under explicit contractual commitments, inno event shall ABB be responsible or liable for any loss or damage resulting fromthe use of this manual or the application of the equipment.
ConformityThis product complies with the directive of the Council of the EuropeanCommunities on the approximation of the laws of the Member States relating toelectromagnetic compatibility (EMC Directive 2004/108/EC) and concerningelectrical equipment for use within specified voltage limits (Low-voltage directive2006/95/EC). This conformity is the result of tests conducted by ABB inaccordance with the product standards EN 50263 and EN 60255-26 for the EMCdirective, and with the product standards EN 60255-1 and EN 60255-27 for the lowvoltage directive. The product is designed in accordance with the internationalstandards of the IEC 60255 series.
Table of contents
Section 1 Introduction.......................................................................5This manual........................................................................................5Intended audience..............................................................................5Product documentation.......................................................................6
Product documentation set............................................................6Document revision history.............................................................7Related documentation..................................................................8
Symbols and conventions...................................................................8Symbols.........................................................................................8Document conventions..................................................................8Functions, codes and symbols......................................................9
Section 2 REF611 overview...........................................................11Overview...........................................................................................11
Product version history................................................................11PCM600 and IED connectivity package version..........................11
Operation functionality......................................................................12Optional functions........................................................................12
Physical hardware............................................................................12Local HMI.........................................................................................13
Display.........................................................................................14LEDs............................................................................................15Keypad........................................................................................15
Web HMI...........................................................................................15Authorization.....................................................................................16Communication.................................................................................17
Section 3 REF611 standard configurations ...................................19Standard configurations....................................................................19Switch groups...................................................................................20
Input switch group ISWGAPC.....................................................21Output switch group OSWGAPC.................................................21Selector switch group SELGAPC................................................22
Connection diagrams........................................................................23Presentation of standard configurations...........................................24Standard configuration A..................................................................26
Applications.................................................................................26Functions.....................................................................................26
Default I/O connections..........................................................27Predefined disturbance recorder connections........................28
Table of contents
REF611 1Application Manual
Functional diagrams....................................................................28Functional diagrams for protection.........................................29Functional diagrams for disturbance recorder and tripcircuit supervision...................................................................35Functional diagrams for control..............................................38
Switch groups..............................................................................40Binary inputs...........................................................................41Internal signal.........................................................................45Binary outputs and LEDs........................................................47GOOSE..................................................................................68
Standard configuration B..................................................................71Applications.................................................................................71Functions.....................................................................................71
Default I/O connections..........................................................72Predefined disturbance recorder connections........................73
Functional diagrams....................................................................73Functional diagrams for protection.........................................74Functional diagrams for disturbance recorder and tripcircuit supervision...................................................................79Functional diagrams for control..............................................81
Switch groups..............................................................................83Binary inputs...........................................................................84Internal signal.........................................................................87Binary outputs and LEDs........................................................89GOOSE................................................................................105
Section 4 Requirements for measurement transformers..............109Current transformers......................................................................109
Current transformer requirements for non-directionalovercurrent protection................................................................109
Current transformer accuracy class and accuracy limitfactor....................................................................................109Non-directional overcurrent protection.................................110Example for non-directional overcurrent protection..............111
Section 5 IED physical connections.............................................113Inputs..............................................................................................113
Energizing inputs.......................................................................113Phase currents.....................................................................113Residual current...................................................................113Residual voltage...................................................................113
Auxiliary supply voltage input....................................................113Binary inputs..............................................................................114
Outputs...........................................................................................115
Table of contents
2 REF611Application Manual
Outputs for tripping and controlling............................................115Outputs for signalling.................................................................115IRF.............................................................................................116
Section 6 Glossary.......................................................................117
Table of contents
REF611 3Application Manual
4
Section 1 Introduction
1.1 This manual
The application manual contains application descriptions and setting guidelinessorted per function. The manual can be used to find out when and for what purposea typical protection function can be used. The manual can also be used whencalculating settings.
1.2 Intended audience
This manual addresses the protection and control engineer responsible forplanning, pre-engineering and engineering.
The protection and control engineer must be experienced in electrical powerengineering and have knowledge of related technology, such as communicationand protocols.
1MRS757456 A Section 1Introduction
REF611 5Application Manual
1.3 Product documentation
1.3.1 Product documentation set
Pla
nnin
g &
pur
chas
e
Eng
inee
ring
Inst
allin
g
Com
mis
sion
ing
Ope
ratio
n
Mai
nten
ance
Dec
omm
issi
onin
gde
inst
allin
g&
dis
posa
l
Application manual
Operation manual
Installation manual
Service manual
Engineering manual
Commissioning manual
Communication protocolmanual
Technical manual
Pla
nnin
g &
pur
chas
e
Eng
inee
ring
Inst
allin
g
Com
mis
sion
ing
Ope
ratio
n
Mai
nten
ance
Dec
omm
issi
onin
gde
inst
allin
g&
dis
posa
l
Pla
nnin
g &
pur
chas
e
Eng
inee
ring
Inst
allin
g
Com
mis
sion
ing
Ope
ratio
n
Mai
nten
ance
Dec
omm
issi
onin
gde
inst
allin
g&
dis
posa
l
Application manualApplication manual
Operation manualOperation manual
Installation manualInstallation manual
Service manualService manual
Engineering manualEngineering manual
Commissioning manualCommissioning manual
Communication protocolmanualCommunication protocolmanual
Technical manualTechnical manual
en07000220.vsd
IEC07000220 V1 EN
Figure 1: The intended use of manuals in different lifecycles
The engineering manual contains instructions on how to engineer the IEDs usingthe different tools in PCM600. The manual provides instructions on how to set up aPCM600 project and insert IEDs to the project structure. The manual alsorecommends a sequence for engineering of protection and control functions, LHMIfunctions as well as communication engineering for IEC 61850 and othersupported protocols.
The installation manual contains instructions on how to install the IED. Themanual provides procedures for mechanical and electrical installation. The chaptersare organized in chronological order in which the IED should be installed.
The commissioning manual contains instructions on how to commission the IED.The manual can also be used by system engineers and maintenance personnel forassistance during the testing phase. The manual provides procedures for checkingof external circuitry and energizing the IED, parameter setting and configuration as
Section 1 1MRS757456 AIntroduction
6 REF611Application Manual
well as verifying settings by secondary injection. The manual describes the processof testing an IED in a substation which is not in service. The chapters are organizedin chronological order in which the IED should be commissioned.
The operation manual contains instructions on how to operate the IED once it hasbeen commissioned. The manual provides instructions for monitoring, controllingand setting the IED. The manual also describes how to identify disturbances andhow to view calculated and measured power grid data to determine the cause of afault.
The service manual contains instructions on how to service and maintain the IED.The manual also provides procedures for de-energizing, de-commissioning anddisposal of the IED.
The application manual contains application descriptions and setting guidelinessorted per function. The manual can be used to find out when and for what purposea typical protection function can be used. The manual can also be used whencalculating settings.
The technical manual contains application and functionality descriptions and listsfunction blocks, logic diagrams, input and output signals, setting parameters andtechnical data sorted per function. The manual can be used as a technical referenceduring the engineering phase, installation and commissioning phase, and duringnormal service.
The communication protocol manual describes a communication protocolsupported by the IED. The manual concentrates on vendor-specific implementations.
The point list manual describes the outlook and properties of the data pointsspecific to the IED. The manual should be used in conjunction with thecorresponding communication protocol manual.
Some of the manuals are not available yet.
1.3.2 Document revision historyDocument revision/date Product series version HistoryA/2011-11-18 1.0 First release
Download the latest documents from the ABB Web sitehttp://www.abb.com/substationautomation.
1MRS757456 A Section 1Introduction
REF611 7Application Manual
1.3.3 Related documentationName of the document Document IDModbus Communication Protocol Manual 1MRS757461
IEC 61850 Engineering Guide 1MRS757465
Installation Manual 1MRS757452
Operation Manual 1MRS757453
Technical Manual 1MRS757454
1.4 Symbols and conventions
1.4.1 Symbols
The electrical warning icon indicates the presence of a hazardwhich could result in electrical shock.
The warning icon indicates the presence of a hazard which couldresult in personal injury.
The caution icon indicates important information or warning relatedto the concept discussed in the text. It might indicate the presenceof a hazard which could result in corruption of software or damageto equipment or property.
The information icon alerts the reader of important facts andconditions.
The tip icon indicates advice on, for example, how to design yourproject or how to use a certain function.
Although warning hazards are related to personal injury, it is necessary tounderstand that under certain operational conditions, operation of damagedequipment may result in degraded process performance leading to personal injuryor death. Therefore, comply fully with all warning and caution notices.
1.4.2 Document conventionsA particular convention may not be used in this manual.
Section 1 1MRS757456 AIntroduction
8 REF611Application Manual
• Abbreviations and acronyms in this manual are spelled out in the glossary. Theglossary also contains definitions of important terms.
• Push-button navigation in the LHMI menu structure is presented by using thepush-button icons.To navigate between the options, use and .
• HMI menu paths are presented in bold.Select Main menu/Settings.
• LHMI messages are shown in Courier font.To save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics.The function can be enabled and disabled with the Operation setting.
• Parameter values are indicated with quotation marks.The corresponding parameter values are "On" and "Off".
• IED input/output messages and monitored data names are shown in Courier font.When the function starts, the START output is set to TRUE.
1.4.3 Functions, codes and symbolsTable 1: REF611 functions, codes and symbols
Function IEC 61850 IEC 60617 IEC-ANSIProtection
Three-phase non-directionalovercurrent protection, low stage,instance 1
PHLPTOC1 3I> (1) 51P-1 (1)
Three-phase non-directionalovercurrent protection, high stage,instance 1
PHHPTOC1 3I>> (1) 51P-2 (1)
Three-phase non-directionalovercurrent protection, high stage,instance 2
PHHPTOC2 3I>> (2) 51P-2 (2)
Three-phase non-directionalovercurrent protection, instantaneousstage, instance 1
PHIPTOC1 3I>>> (1) 50P/51P (1)
Non-directional earth-fault protection,low stage, instance 1 EFLPTOC1 Io> (1) 51N-1 (1)
Non-directional earth-fault protection,low stage, instance 2 EFLPTOC2 Io> (2) 51N-1 (2)
Non-directional earth-fault protection,high stage, instance 1 EFHPTOC1 Io>> (1) 51N-2 (1)
Non-directional earth-fault protection,instantaneous stage EFIPTOC1 Io>>> 50N/51N
Directional earth-fault protection, lowstage, instance 1 DEFLPDEF1 Io> -> (1) 67N-1 (1)
Directional earth-fault protection, lowstage, instance 2 DEFLPDEF2 Io> -> (2) 67N-1 (2)
Directional earth-fault protection,high stage DEFHPDEF1 Io>> -> 67N-2
Table continues on next page
1MRS757456 A Section 1Introduction
REF611 9Application Manual
Function IEC 61850 IEC 60617 IEC-ANSITransient / intermittent earth-faultprotection INTRPTEF1 Io> -> IEF 67NIEF
Non-directional (cross-country) earth-fault protection, using calculated Io EFHPTOC1 Io>> (1) 51N-2 (1)
Negative-sequence overcurrentprotection, instance 1 NSPTOC1 I2> (1) 46 (1)
Negative-sequence overcurrentprotection, instance 2 NSPTOC2 I2> (2) 46 (2)
Phase discontinuity protection PDNSPTOC1 I2/I1> 46PD
Residual overvoltage protection,instance 1 ROVPTOV1 Uo> (1) 59G (1)
Residual overvoltage protection,instance 2 ROVPTOV2 Uo> (2) 59G (2)
Residual overvoltage protection,instance 3 ROVPTOV3 Uo> (3) 59G (3)
Three-phase thermal protection forfeeders, cables and distributiontransformers
T1PTTR1 3Ith>F 49F
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF
Three-phase inrush detector INRPHAR1 3I2f> 68
Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)
Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)
Switch groups
Input switch group1) ISWGAPC ISWGAPC ISWGAPC
Output switch group2) OSWGAPC OSWGAPC OSWGAPC
Selector switch group3) SELGAPC SELGAPC SELGAPC
Configurable timer
Minimum pulse timer (2 pcs)4) TPGAPC TP TP
Control
Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB
Auto-reclosing DARREC1 O -> I 79
Supervision
Trip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)
Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)
Measurement
Disturbance recorder RDRE1 - -
Three-phase current measurement,instance 1 CMMXU1 3I 3I
Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0
Residual current measurement,instance 1 RESCMMXU1 Io In
Residual voltage measurement RESVMMXU1 Uo Vn
1) 10 instances2) 20 instances3) 6 instances4) 10 instances
Section 1 1MRS757456 AIntroduction
10 REF611Application Manual
Section 2 REF611 overview
2.1 Overview
REF611 is a dedicated feeder IED designed for the protection, control,measurement and supervision of utility substations and industrial power systemsincluding radial, looped and meshed distribution networks with or withoutdistributed power generation. REF611 is a member of ABB’s Relion® productfamily and part of the 611 protection and control product series. The 611 seriesIEDs are characterized by their compactness and withdrawable-unit design.
The 611 series is designed to offer simplified, but powerful functionality intendedfor most applications. Once the application-specific parameters have been entered,the installed IED is ready to be put into service. The further addition ofcommunication functionality and interoperability between substation automationdevices offered by the IEC 61850 standard adds flexibility and value to end usersas well as electrical system manufacturers.
2.1.1 Product version historyProduct version Product history1.0 Product released
2.1.2 PCM600 and IED connectivity package version• Protection and Control IED Manager PCM600 Ver. 2.4 or later• REF611 Connectivity Package Ver. 1.0 or later
• Parameter Setting• Firmware Update• Disturbance Handling• Signal Monitoring• Lifecycle Traceability• Signal Matrix• Communication Management• IED Configuration Migration• Configuration Wizard• Label Printing• IED User Management• Differential Characteristics Tool
1MRS757456 A Section 2REF611 overview
REF611 11Application Manual
Download connectivity packages from the ABB web site http://www.abb.com/substationautomation
2.2 Operation functionality
2.2.1 Optional functions• Autoreclosing• Modbus TCP/IP or RTU/ASCII
2.3 Physical hardware
The IED consists of two main parts: plug-in unit and case. The content depends onthe ordered functionality.
Table 2: Plug-in unit and case
Main unit Slot ID Content optionsPlug-in
unit- HMI Small (4 lines, 16 characters)
X100 Auxiliary power/BO module
48-250 V DC/100-240 V AC; or 24-60 V DC2 normally-open PO contacts1 change-over SO contacts1 normally-open SO contact2 double-pole PO contacts with TCS1 dedicated internal fault output contact
X120 AI/BI module Only with configuration A :3 phase current inputs (1/5 A)1 residual current input (1/5 A or 0.2/1 A)1)
1 residual voltage input (60-120 V)3 binary inputs
Only with configuration B:3 phase current inputs (1/5 A)1 residual current input (1/5 A or 0.2/1 A)1)
4 binary inputs
Case X130 Optional BI/Omodule
Optional for configurations A and B: 6 binary inputs 3SO contacts
X000 Optionalcommunicationmodule
See technical manual for details about different type ofcommunication modules.
1) The 0.2/1 A input is normally used in applications requiring sensitive earth-fault protection andfeaturing core-balance current transformers.
Rated values of the current and voltage inputs are basic setting parameters of theIED. The binary input thresholds are selectable within the range 18…176 V DC byadjusting the binary input setting parameters.
Section 2 1MRS757456 AREF611 overview
12 REF611Application Manual
The connection diagrams of different hardware modules are presented in this manual.
See the installation manual for more information about the case andthe plug-in unit.
Table 3: Number of physical connections in standard configurations
Conf. Analog channels Binary channels CT VT BI BO
A 4 1 3(9)1) 6(9)1)
B 4 - 4(10)1) 6(9)1)
1) With optional BIO module
2.4 Local HMI
REF611
Overcurrent
Earth-fault
Phase unbalance
Thermal overload
AR sequence in progress
Disturb.rec.trigged
Trip circuit failure
Breaker failure
GUID-E15422BF-B3E6-4D02-8D43-D912D5EF0360 V1 EN
Figure 2: Example of 611 series LHMI
1MRS757456 A Section 2REF611 overview
REF611 13Application Manual
The LHMI of the IED contains several elements.
• Display• Buttons• LED indicators• Communication port
The LHMI is used for setting, monitoring and controlling.
2.4.1 DisplayThe LHMI includes a graphical display that supports two character sizes. Thecharacter size depends on the selected language. The amount of characters androws fitting the view depends on the character size.
Table 4: Characters and rows on the view
Character size Rows in view Characters on rowSmall, mono-spaced (6x12 pixels) 5 rows 20
Large, variable width (13x14 pixels) 4 rows min 8
The display view is divided into four basic areas.
1
3 4
2
GUID-24ADB995-439A-4563-AACE-1FAA193A8EF9 V1 EN
Figure 3: Display layout
1 Header
2 Icon
3 Content
4 Scroll bar (displayed when needed)
Section 2 1MRS757456 AREF611 overview
14 REF611Application Manual
2.4.2 LEDsThe LHMI includes three protection indicators above the display: Ready, Start andTrip.
There are also 8 programmable LEDs on front of the LHMI. The LEDs can beconfigured with the LHMI, WHMI or PCM600.
2.4.3 KeypadThe LHMI keypad contains push-buttons which are used to navigate in differentviews or menus. With the push-buttons you can give open or close commands toone object in the primary circuit, for example, a circuit breaker, a contactor or adisconnector. The push-buttons are also used to acknowledge alarms, resetindications, provide help and switch between local and remote control mode.
GUID-B681763E-EC56-4515-AC57-1FD5349715F7 V1 EN
Figure 4: LHMI keypad with object control, navigation and command push-buttons and RJ-45 communication port
2.5 Web HMI
The WHMI enables the user to access the IED via a web browser. The supportedweb browser version is Internet Explorer 7.0 or 8.0.
WHMI is disabled by default.
WHMI offers several functions.
• Programmable LEDs and event lists• System supervision• Parameter settings• Measurement display
1MRS757456 A Section 2REF611 overview
REF611 15Application Manual
• Disturbance records• Phasor diagram• Signal configuration
The menu tree structure on the WHMI is almost identical to the one on the LHMI.
GUID-CD531B61-6866-44E9-B0C1-925B48140F3F V1 EN
Figure 5: Example view of the WHMI
The WHMI can be accessed locally and remotely.
• Locally by connecting your laptop to the IED via the front communication port.• Remotely over LAN/WAN.
2.6 Authorization
The user categories have been predefined for the LHMI and the WHMI, each withdifferent rights and default passwords.
The default passwords can be changed with Administrator user rights.
User authorization is disabled by default but WHMI always usesauthorization.
Section 2 1MRS757456 AREF611 overview
16 REF611Application Manual
Table 5: Predefined user categories
Username User rightsVIEWER Read only access
OPERATOR • Selecting remote or local state with (only locally)• Changing setting groups• Controlling• Clearing indications
ENGINEER • Changing settings• Clearing event list• Clearing disturbance records• Changing system settings such as IP address, serial baud rate
or disturbance recorder settings• Setting the IED to test mode• Selecting language
ADMINISTRATOR • All listed above• Changing password• Factory default activation
For user authorization for PCM600, see PCM600 documentation.
2.7 Communication
For application specific situations where communication between IEDs and remotesystems are needed, the 611 series IEDs also support IEC 61850 and Modbus®
communication protocols. Operational information and controls are availablethrough these protocols. Some communication functionality, for example,horizontal communication between the IEDs, is only enabled by the IEC 61850communication protocol.
The IEC 61850 communication implementation supports monitoring and controlfunctionality. Additionally, parameter settings and disturbance and fault recordscan be accessed using the IEC 61850 protocol. Disturbance records are available toany Ethernet-based application in the standard COMTRADE file format. The IEDcan send and receive binary signals from other IEDs (so called horizontalcommunication) using the IEC 61850-8-1 GOOSE profile, where the highestperformance class with a total transmission time of 3 ms is supported. The IEDmeets the GOOSE performance requirements for tripping applications indistribution substations, as defined by the IEC 61850 standard. The IED cansimultaneously report events to five different clients on the station bus.
The IED can support five simultaneous clients. If PCM600 reserves one clientconnection, only four client connections are left, for example, for IEC 61850 andModbus.
1MRS757456 A Section 2REF611 overview
REF611 17Application Manual
All communication connectors, except for the front port connector, are placed onintegrated optional communication modules. The IED can be connected to Ethernet-based communication systems via the RJ-45 connector (100Base-TX) or the fibre-optic LC connector (100Base-FX). An optional serial interface is available forRS-485 communication.
Managed Ethernet switchwith RSTP support
Managed Ethernet switchwith RSTP support
Network
Network
REF611
Overcurrent
Earth-fault
Phase unbalance
Thermal overload
AR sequence in progress
Disturb.rec.trigged
Trip circuit failure
Breaker failure
REF611
Overcurrent
Earth-fault
Phase unbalance
Thermal overload
AR sequence in progress
Disturb.rec.trigged
Trip circuit failure
Breaker failure
REF611
Overcurrent
Earth-fault
Phase unbalance
Thermal overload
AR sequence in progress
Disturb.rec.trigged
Trip circuit failure
Breaker failure
REM611
Short circuit
Combined protection
Thermal overload
Motor restart inhibit
Emergency start enabled
Disturb.rec.trigged
Supervision alarm
Breaker failure
REB611
High-impedance 1 operate
High-impedance 2 operate
High-impedance 3 operate
High-impedance start
Segregated supervision
Disturb.rec.trigged
Trip circuit failure
Breaker failure
REF611 REF611 REF611 REM611 REB611
Client BClient A
GUID-A19C6CFB-EEFD-4FB2-9671-E4C4137550A1 V1 EN
Figure 6: Self-healing Ethernet ring solution
The Ethernet ring solution supports the connection of up to thirty611 series IEDs. If more than 30 IEDs are to be connected, it isrecommended that the network is split into several rings with nomore than 30 IEDs per ring.
Section 2 1MRS757456 AREF611 overview
18 REF611Application Manual
Section 3 REF611 standard configurations
3.1 Standard configurations
REF611 is available in two alternative standard configurations.
To increase the user friendliness of the IED’s standard configurations and toemphasize the IED's simplicity of usage, only the application-specific parametersneed setting within the IED's intended area of application.
The standard signal configuration can be altered by LHMI, WHMI or the optionalapplication functionality of the Protection and Control IED Manager PCM600.
Table 6: Standard configurations
Description Std. conf.Non-directional overcurrent and directional earth-fault protection A
Non-directional overcurrent and non-directional earth-fault protection B
Table 7: Supported functions
Functionality A BProtection1)2)
Three-phase non-directional overcurrent protection, low stage, instance 1 ● ●
Three-phase non-directional overcurrent protection, high stage, instance 1 ● ●
Three-phase non-directional overcurrent protection, high stage, instance 2 ● ●
Three-phase non-directional overcurrent protection, instantaneous stage, instance1
● ●
Non-directional earth-fault protection, low stage, instance 1 - ●3)
Non-directional earth-fault protection, low stage, instance 2 - ●3)
Non-directional earth-fault protection, high stage, instance 1 - ●3)
Non-directional earth-fault protection, instantaneous stage - ●3)
Directional earth-fault protection, low stage, instance 1 ●3) -
Directional earth-fault protection, low stage, instance 2 ●3) -
Directional earth-fault protection, high stage ●3) -
Transient/intermittent earth-fault protection ●4) -
Non-directional (cross-country) earth-fault protection, using calculated Io ●5) -
Negative-sequence overcurrent protection, instance 1 ● ●
Negative-sequence overcurrent protection, instance 2 ● ●
Phase discontinuity protection ● ●
Table continues on next page
1MRS757456 A Section 3REF611 standard configurations
REF611 19Application Manual
Functionality A BResidual overvoltage protection, instance 1 ● -
Residual overvoltage protection, instance 2 ● -
Residual overvoltage protection, instance 3 ● -
Three-phase thermal protection for feeders, cables and distribution transformers ● ●
Circuit-breaker failure protection ● ●
Three-phase inrush detector ● ●
Master trip, instance 1 ● ●
Master trip, instance 2 ● ●
Switch groups
Input switch group ● ●
Output switch group ● ●
Selector switch group ● ●
Configurable timer
Minimum pulse timer (2 pcs) ● ●
Control
Circuit-breaker control ● ●
Auto-reclosing o o
Supervision
Trip circuit supervision, instance 1 ● ●
Trip circuit supervision, instance 2 ● ●
Measurement
Disturbance recorder ● ●
Three-phase current measurement, instance 1 ● ●
Sequence current measurement ● ●
Residual current measurement, instance 1 ● ●
Residual voltage measurement ● -
● = Included,○ = Can be ordered as option
1) Note that all directional protection functions can also be used in non-directional mode.2) The instances of a protection function represent the number of identical function blocks available in
a standard configuration.3) Io selectable by parameter, Io measured as default.4) Io measured is always used.5) Io selectable by parameter, Io calculated as default.
3.2 Switch groups
The default application configurations cover the most common application cases,however, changes can be made according to specific needs through LHMI, WHMIand PCM600.
Section 3 1MRS757456 AREF611 standard configurations
20 REF611Application Manual
Programming is easily implemented with three switch group functions includinginput switch group (ISWGAPC), output switch group (OSWGAPC) and selectorswitch group (SELGAPC). Each switch group has several instances.
Connections of binary inputs to functions, GOOSE signals to functions, functionsto functions, functions to binary outputs and functions to LEDs have beenpreconnected through corresponding switch groups.
Change the parameter values of the switch groups to modify the real connectionlogic and the application configuration.
3.2.1 Input switch group ISWGAPCThe input switch group ISWGAPC has one input and a number of outputs. Everyinput and output has a read-only description. ISWGAPC is used for connecting theinput signal to one or several outputs of the switch group. Each output can be set tobe connected or not connected with the input separately via the “OUT_xconnection” setting.
GUID-2D549B56-6CF7-4DCB-ACDE-E9EF601868A8 V1 EN
Figure 7: Input switch group ISWGAPC
3.2.2 Output switch group OSWGAPCThe output switch group OSWGAPC has a number of inputs and one output. Everyinput and output has a read-only description. OSWGAPC is used for connectingone or several inputs to the output of the switch group via OR logic. Each input canbe set to be connected or not connected with the OR logic via the “IN_xconnection” settings. The output of OR logic is routed to switch group output.
1MRS757456 A Section 3REF611 standard configurations
REF611 21Application Manual
GUID-1EFA82D5-F9E7-4322-87C2-CDADD29823BD V1 EN
Figure 8: Output switch group OSWGAPC
3.2.3 Selector switch group SELGAPCThe selector switch group SELGAPC has a number of inputs and outputs. Everyinput and output has a read-only description. Each output can be set to beconnected with one the of inputs via the “OUT_x connection” setting. An outputcan also be set to be not connected with any of the inputs. In SELGAPC, oneoutput signal can only be connected to one input signal but the same input signalcan be routed to several output signals.
GUID-E3AEC7AB-2978-402D-8A80-C5DE9FED67DF V1 EN
Figure 9: Selector switch group SELGAPC
Section 3 1MRS757456 AREF611 standard configurations
22 REF611Application Manual
3.3 Connection diagrams
REF611
1) Optional2) The IED features an automatic short-circuit mechanism in the CT connector when plug-in unit is detached
16
17
1918
X100
67
89
10
111213
15
14
2
1
3
45
22
212324
SO2
TCS2
PO4
SO1
TCS1
PO3
PO2
PO1
IRF
+
-Uaux
20
X13012
3
45
6BI 4
BI 3
BI 2
BI 1
BI 6
BI 58
9
7
X130
12
10
11
15
13
14
18
16
17
SO3
SO2
SO1
1)
1)
2)
X120
12
3
4
567
89
1011
1213
14Io
IL1
IL2
BI 3
BI 2
BI 1
Uo
IL3
1/5A
N1/5A
N1/5A
N1/5A
N
60 -
N
210V
L1L2L3
da dn
S1
S2
P1
P2
P2
P1 S1
S2
A
N
PositiveCurrentDirection
GUID-EAC6CB29-0D2C-4714-9273-72694FB77E90 V1 EN
Figure 10: Connection diagram for configuration A
1MRS757456 A Section 3REF611 standard configurations
REF611 23Application Manual
REF611
16
17
1918
X100
67
8910
111213
15
14
2
1
3
45
22
212324
SO2
TCS2
PO4
SO1
TCS1
PO3
PO2
PO1
IRF
+
-Uaux
20
X130
12
3
45
6BI 4
BI 3
BI 2
BI 1
BI 6
BI 58
9
7
X130
12
10
11
15
13
14
18
16
17
SO3
SO2
SO1
1) Optional2) The IED features an automatic short-circuit mechanism in the CT connector when plug-in unit is detached
2)
X120
12
3
4
567
89
1011
12
14Io
IL1
IL2
BI 4
BI 3
BI 2
BI 1
IL3
1/5A
N1/5A
N1/5A
N1/5A
N
1) 1)
13
L1L2L3
S1
S2
P1
P2
P2
P1 S1
S2
PositiveCurrentDirection
GUID-6692D10C-76A4-475F-AFD9-E8CD93973428 V1 EN
Figure 11: Connection diagram for configuration B
3.4 Presentation of standard configurations
Functional diagramsThe functional diagrams describe the IED's functionality from the protection,measuring, condition supervision, disturbance recording, control and interlocking
Section 3 1MRS757456 AREF611 standard configurations
24 REF611Application Manual
perspective. Diagrams show the default functionality with simple symbol logicsforming principle diagrams.
The functional diagrams are divided into sections with each section constitutingone functional entity.
Protection function blocks are part of the functional diagram. They are identifiedbased on their IEC 61850 name but the IEC based symbol and the ANSI functionnumber are also included. Some function blocks, such as PHHPTOC, are usedseveral times in the configuration. To separate the blocks from each other, the IEC61850 name, IEC symbol and ANSI function number are appended with a runningnumber, that is an instance number, from one upwards. If the block has no suffixafter the IEC or ANSI symbol, the function block has been used, that is,instantiated, only once.
Switch groupsSwitch group information can be divided into three levels.
• The first level is a configuration overview. All switch groups in theconfiguration are presented in an overview figure. The figure provides generalinformation about the relationship between different switch groups.
• The second level presents function group information. It explains how theswitch groups belong to a special function as well as related function blocks.
• The third level presents detailed information about the switch groups. Itprovides information about a specific switch group including the logicconnection of the input and output, default connection and port description.
Conventions used in switch group figures:
• The text in the symbol indicates the logic connections of the function'sinputs or outputs. The text is a combination of a function block name and theinput or output name. They are connected with a “_” symbol.
• If there are many lines of text in an output symbol , each line indicates asignal. The switch group output is routed to all these signals.
• If there are many lines of text in an input symbol , each line indicates asignal. All signals are routed to a switch group input via an OR logic.
• The text above the connection line is the description of the port.• If there is no text in the connection line, the port description is the same as the
text in the symbol.• A dashed arrow within the switch group function box indicate the default
connection of the switch group.
1MRS757456 A Section 3REF611 standard configurations
REF611 25Application Manual
3.5 Standard configuration A
3.5.1 ApplicationsThe standard configuration for non-directional overcurrent and directional earth-fault protection is mainly intended for cable and overhead-line feeder applicationsin isolated and resonant-earthed distribution networks.
The IED with a standard configuration is delivered from the factory with defaultsettings and parameters. The end-user flexibility for incoming, outgoing andinternal signal designation within the IED enables this configuration to be furtheradapted to different primary circuit layouts and the related functionality needs bymodifying the internal functionality using PCM600.
3.5.2 FunctionsTable 8: Functions included in the standard configuration A
Function IEC 61850 IEC 60617 IEC-ANSIProtection
Three-phase non-directional overcurrentprotection, low stage, instance 1 PHLPTOC1 3I> (1) 51P-1 (1)
Three-phase non-directional overcurrentprotection, high stage, instance 1 PHHPTOC1 3I>> (1) 51P-2 (1)
Three-phase non-directional overcurrentprotection, high stage, instance 2 PHHPTOC2 3I>> (2) 51P-2 (2)
Three-phase non-directional overcurrentprotection, instantaneous stage, instance 1 PHIPTOC1 3I>>> (1) 50P/51P (1)
Directional earth-fault protection, lowstage, instance 1 DEFLPDEF1 Io> -> (1) 67N-1 (1)
Directional earth-fault protection, lowstage, instance 2 DEFLPDEF2 Io> -> (2) 67N-1 (2)
Directional earth-fault protection, high stage DEFHPDEF1 Io>> -> 67N-2
Transient/intermittent earth-fault protection INTRPTEF1 Io> -> IEF 67NIEF
Non-directional (cross-country) earth-faultprotection, using calculated Io EFHPTOC1 Io>> (1) 51N-2 (1)
Negative-sequence overcurrent protection,instance 1 NSPTOC1 I2> (1) 46 (1)
Negative-sequence overcurrent protection,instance 2 NSPTOC2 I2> (2) 46 (2)
Phase discontinuity protection PDNSPTOC1 I2/I1> 46PD
Residual overvoltage protection, instance 1 ROVPTOV1 Uo> (1) 59G (1)
Residual overvoltage protection, instance 2 ROVPTOV2 Uo> (2) 59G (2)
Residual overvoltage protection, instance 3 ROVPTOV3 Uo> (3) 59G (3)
Three-phase thermal protection forfeeders, cables and distributiontransformers
T1PTTR1 3Ith>F 49F
Table continues on next page
Section 3 1MRS757456 AREF611 standard configurations
26 REF611Application Manual
Function IEC 61850 IEC 60617 IEC-ANSICircuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF
Three-phase inrush detector INRPHAR1 3I2f> 68
Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)
Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)
Switch groups
Input switch group ISWGAPC ISWGAPC ISWGAPC
Output switch group OSWGAPC OSWGAPC OSWGAPC
Selector switch group SELGAPC SELGAPC SELGAPC
Configurable timers
Minimum pulse timer (2 pcs) TPGAPC TP TP
Control
Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB
Auto-reclosing DARREC1 O -> I 79
Supervision
Trip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)
Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)
Measurement
Disturbance recorder RDRE1 - -
Three-phase current measurement,instance 1 CMMXU1 3I 3I
Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0
Residual current measurement, instance 1 RESCMMXU1 Io In
Residual voltage measurement RESVMMXU1 Uo Vn
3.5.2.1 Default I/O connections
Table 9: Default connections for binary inputs
Binary input Default usage Connector pinsX120-BI1 Blocking of overcurrent instantaneous stage X120-1,2
X120-BI2 Circuit breaker closed position indication X120-3,2
X120-BI3 Circuit breaker open position indication X120-4,2
Table 10: Default connections for binary outputs
Binary input Default usage Connector pinsX100-PO1 Close circuit breaker X100-6,7
X100-PO2 Circuit breaker failure protection trip to upstreambreaker
X100-8,9
X100-PO3 Open circuit breaker/trip coil 1 X100-15,16,17,18,19
Table continues on next page
1MRS757456 A Section 3REF611 standard configurations
REF611 27Application Manual
Binary input Default usage Connector pinsX100-PO4 Open circuit breaker/trip coil 2 X100-20,21,22,23,24
X100-SO1 General start indication X100-10,11,12
X100-SO2 General operate indication X100-13,14,15
Table 11: Default connections for LEDs
LED Default usage1 Non-directional overcurrent operate
2 Earth fault protection operate
3 Negative-sequence overcurrent/phase discontinuity operate
4 Thermal overload alarm
5 Autoreclose in progress
6 Disturbance recorder triggered
7 Trip circuit supervision alarm
8 Circuit-breaker failure operate
3.5.2.2 Predefined disturbance recorder connections
Table 12: Predefined analog channel setup
Channel Selection and text1 IL1
2 IL2
3 IL3
4 Io
5 Uo
Additionally, all the digital inputs that are connected by default are also enabledwith the setting. Default triggering settings are selected depending on theconnected input signal type. Typically all protection START signals are selected totrigger the disturbance recorded by default.
3.5.3 Functional diagramsThe functional diagrams describe the default input, output, programmable LED,switch group and function-to-function connections. The default connections can beviewed and changed with switch groups in PCM600, LHMI and WHMI accordingto the application requirements.
The analog channels have fixed connections towards the different function blocksinside the IED’s standard configuration. Exceptions from this rule are the eight
Section 3 1MRS757456 AREF611 standard configurations
28 REF611Application Manual
analog channels available for the disturbance recorder function. These channels arefreely selectable and a part of the disturbance recorder’s parameter settings.
The analog channels are assigned to different functions. The common signalmarked with 3I represents the three phase currents. The signal marked with Iorepresents the measured residual current via a core balance current transformer.The signal marked with Uo represents the measured residual voltage via open-deltaconnected voltage transformers.
The EFHPTOC protection function block for double (cross-country) earth-faultsuses the calculated residual current originating from the measured phase currents.
3.5.3.1 Functional diagrams for protection
The functional diagrams describe the IED’s protection functionality in detail andpicture the factory default connections.
X120-BI1
LED 1
ISWGAPC1OUT_4IN
SELGAPC4OUT_1IN_10
OSWGAPC8
OR OUT
IN_1
IN_2
IN_3
IN_4
OVERCURRENT PROTECTION AND INRUSH INDICATION
PHLPTOC13I>(1)
51P-1(1)
BLOCK START
OPERATE3I
ENA_MULT
PHHPTOC13I>>(1)
51P-2(1)
BLOCK START
OPERATE3I
ENA_MULT
PHHPTOC23I>>(2)
51P-2(2)
BLOCK START
OPERATE3I
ENA_MULT
SELGAPC1OUT_1IN_1
PHIPTOC13I>>>(1)
50P/51P(1)
BLOCK START
OPERATE3I
ENA_MULTBlocking 1
INRPHAR13I2f >(1)
68(1)
BLOCK
BLK2H3I
GUID-7490603E-FE2C-4241-A98B-2CE7C935C0FB V1 EN
Figure 12: Overcurrent protection
Four overcurrent stages are offered for overcurrent and short-circuit protection.The instantaneous stage (PHIPTOC1) can be blocked by energizing the binaryinput (X120:1-2). The inrush detection block’s (INRPHAR1) output BLK2Henables either blocking the function or multiplying the active settings for any of thedescribed protection function blocks.
1MRS757456 A Section 3REF611 standard configurations
REF611 29Application Manual
All operate signals are connected to the Master Trip and to the alarm LED 1.
LED 2
EARTH-FAULT PROTECTION
DOUBLE (CROSS-COUNTRY) EARTH-FAULT PROTECTION
DIRECTIONAL EARTH-FAULT PROTECTION
INTERMITTENT EARTH-FAULT PROTECTION
DEFLPDEF1Io>->(1)
67N-1(1)
BLOCKSTART
OPERATEIo
ENA_MULT
Uo
RCA_CTL
DEFLPDEF2Io>->(2)
67N-1(2)
BLOCK
START
OPERATEIo
ENA_MULT
Uo
RCA_CTL
DEFHPDEF1Io>>->(1)
67N-2(1)
BLOCK
START
OPERATEIo
ENA_MULT
Uo
RCA_CTL
OSWGAPC9
OR OUT
IN_5
IN_6
IN_7
IN_8
IN_12
SELGAPC4OUT_2IN_11
INTRPTEF1Io>->IEF(1)
67NIEF(1)
START
OPERATE
BLK_EFBLOCK
Io
Uo
EFHPTOC1Io>>(1)
51N-2(1)
BLOCK STARTOPERATEIo
ENA_MULT
Calculated lo
GUID-7DA854F7-A732-46FD-A9D9-398B3E4150C8 V1 EN
Figure 13: Earth-fault protection
Section 3 1MRS757456 AREF611 standard configurations
30 REF611Application Manual
Three stages are offered for directional earth-fault protection. In addition, there is adedicated protection stage (INTRPTEF) either for transient-based earth-faultprotection or for cable intermittent earth-fault protection in compensated networks.
A dedicated non-directional earth-fault protection block (EFHPTOC) is intendedfor protection against double earth-fault situations in isolated or compensatednetworks. This protection function uses the calculated residual current originatingfrom the phase currents.
All operate signals are connected to the Master Trip and to alarm LED 2.
LED 2
RESIDUAL OVERVOLTAGE PROTECTION
ROVPTOV1U0>(1)
59G(1)
BLOCK START
OPERATEU0
ROVPTOV2U0>(2)
59G(2)
BLOCK START
OPERATEU0
ROVPTOV3U0>(3)
59G(3)
BLOCK START
OPERATEU0
OSWGAPC9
OR OUT
IN_9
IN_10
IN_11
SELGAPC4OUT_2IN_11
GUID-41F06B86-FFB5-4162-BF38-B85F43C88002 V1 EN
Figure 14: Residual overvoltage protection
The residual overvoltage protection (ROVPTOV) provides earth-fault protectionby detecting abnormal level of residual voltage. It can be used, for example, as a non-selective backup protection for the selective directional earth-fault functionality.The operation signal is also connected to alarm LED 2.
1MRS757456 A Section 3REF611 standard configurations
REF611 31Application Manual
LED 3
UNBALANCE PROTECTION
NSPTOC1I2>(1)
46(1)
BLOCK START
OPERATE3I
ENA_MULT
NSPTOC2I2>(2)
46(2)
BLOCK START
OPERATE3I
ENA_MULT
OSWGAPC10
OR OUT
IN_13
IN_14
IN_15
SELGAPC4IN_12 OUT_3
PDNSPTOC1I2/I1(1)
46PD(1)
BLOCK START
OPERATE3I
GUID-A367FC04-F391-48E9-9CBF-599AC625C7FF V1 EN
Figure 15: Unbalance protection
Two negative-sequence overcurrent stages (NSPTOC1 and NSPTOC2) and onephase discontinuity stage (PDNPSTOC1) are offered for unbalance protection. Thephase discontinuity protection (PDNPSTOC1) provides protection for interruptionsin the normal three-phase load supply, for example, in downed conductor situations.
The operate signals of these unbalance protections are connected to the Master Tripand to alarm LED 3.
Section 3 1MRS757456 AREF611 standard configurations
32 REF611Application Manual
X120-BI2
X100 PO2
LED 8
PHIPTOC1_OPERATEPHHPTOC2_OPERATE
PHLPTOC1_OPERATEPHHPTOC1_OPERATE
DEFHPTOC1_OPERATE
ORDEFLPTOC1_OPERATEDEFLPTOC2_OPERATE
SELGAPC3OUT_2IN_4
OSWGAPC15OUTIN_5
LED 4
THERMAL OVERLOAD PROTECTION
CIRCUIT BREAKER FAILURE PROTECTION
SELGAPC4OUT_8IN_17
OSWGAPC11OUTIN_1
SELGAPC4OUT_4IN_13
SELGAPC1OUT_2IN_2
CB Closed Position
51BF/51NBF(1)
3I
Io
START TRRET
TRBU
POSCLOSE
CB_FAULT
BLOCK
CB_FAULT_AL
CCBRBRF13I>/Io>BF(1)
T1PTTR13Ith>F(1)
49F(1)
BLK_OPR
START
OPERATE3I
BLK_CLOSE
ALARMENA_MULT
AMB_TEMP
GUID-A046A312-1E3B-4186-BBEB-2AF8C2423C5F V1 EN
Figure 16: Thermal overload and circuit-breaker failure protection
The thermal overload protection (T1PTTR1) provides indication on overloadsituations. LED 4 is used for the thermal overload protection alarm indication.
The circuit-breaker failure protection (CCBRBRF1) is initiated via the start inputby a number of different protection stages in the IED. The circuit-breaker failureprotection function offers different operating modes associated with the circuitbreaker position and the measured phase and residual currents. The breaker failureprotection has two operating outputs: TRRET and TRBU. The TRRET operateoutput is used for retripping its own breaker through the Master Trip 2. The TRBUoutput is used to give a backup trip to the circuit breaker feeding upstream. For thispurpose, the TRBU operate output signal is connected to the output PO2 (X100:8-9). LED 8 is used for backup (TRBU) operate indication.
1MRS757456 A Section 3REF611 standard configurations
REF611 33Application Manual
X120-BI3
LED 5DEFLPDEF1_OPERATE ORDEFLPDEF2_OPERATE
DEFLPDEF1_START ORDEFLPDEF2_START
NSPTOC2_OPERATENSPTOC1_OPERATE
CBXCBR1_SELECTED
PHIPTOC1_OPERATE
ORPDNSPTOC1_OPERATE
INTRPTEF1_OPERATE
AUTORECLOSING (Optional)
Always True
SELGAPC1OUT_3IN_3
OUT_6IN_10
OSWGAPC12OUTIN_7
SELGAPC4OUT_5IN_14
PHHPTOC2_OPERATE
PHLPTOC1_OPERATE
EFHPTOC1_OPERATE
PHHPTOC1_OPERATE
DEFHPDEF1_OPERATE
PHLPTOC1_START
EFHPTOC1_START
T1PTTR1_BLK_CLOSE
CB Open Position
DARREC1O->I(1)
79(1)
INT_1
INT_2
INT_3
INT_4
INT_5
INT_6
DEL_INT_2
DEL_INT_3
DEL_INT_4
RECL_ON
INHIBIT_RECL
SYNC
OPEN CB
CLOSE CB
INPRO
UNSUC_RECL
AR_ON
PROT_CRD
READY
BLK_RECL_T
BLK_RCLM_T
BLK_THERM
CB_POS
CB_READY
INC_SHOTP
CMD_WAIT
LOCKED
GUID-3F551E60-55D5-4971-8CC8-E6742AF9CAAB V1 EN
Figure 17: Autoreclosing
Autoreclosing (DARREC1) is included as an optional function.
The autoreclose function is configured to be initiated by operate signals from anumber of protection stages through the INT_1...6 inputs and by start signalsthrough the DEL_INT_2…4. It is possible to create individual autoreclosesequences for each input.
The autoreclose function can be blocked with the INHIBIT_RECL input. Bydefault, the operations of selected protection functions are connected to this input.A control command to the circuit breaker, either local or remote, also blocks theautoreclose function via the CBXCBR_SELECTED signal.
The circuit breaker availability for the autoreclose sequence is expressed with theCB_READY input in DARREC1. In the configuration, this signal is connectedwith an always true signal through the SELGAPC1. As a result, the functionassumes that the circuit breaker is available all the time.
The autoreclose sequence in progress indication INPRO is connected to the alarmLED 5.
Section 3 1MRS757456 AREF611 standard configurations
34 REF611Application Manual
3.5.3.2 Functional diagrams for disturbance recorder and trip circuitsupervision
RDRE1
C1C2C3C4C5C6C7C8C9C10C11C12C13C14C15C16C17C18C19C20C21C22C23C24C25C26C27C28C29C30C31C32
OR
C33C34C35C36C37C38C39C40
OR
OR
OR
TRIGGERED LED 6
DISTURBANCE RECORDER
PHLPTOC1_OPERATEPHHPTOC1_OPERATEPHHPTOC2_OPERATEPHIPTOC1_OPERATE
DEFHPDEF1_OPERATEDEFLPDEF1_OPERATE
DEFLPDEF2_OPERATE
ROVPTOV1_OPERATEROVPTOV2_OPERATEROVPTOV3_OPERATE
NSPTOC1_OPERATENSPTOC2_OPERATE
OSWGAPC13OUTIN_2
SELGAPC4OUT_6IN_15
PHLPTOC1_START
DEFHPDEF1_START
NSPTOC1_STARTINTRPTEF1_START
PHHPTOC1_START
PHIPTOC1_STARTPHHPTOC2_START
DEFLPDEF1_STARTDEFLPDEF2_START
ROVPTOV1_STARTROVPTOV2_STARTROVPTOV3_START
NSPTOC2_START
T1PTTR1_START
EFHPTOC1_OPERATE
INTRPTEF1_OPERATE
PDNSPTOC1_OPERATET1PTTR1_OPERATE
SELGAPC1_ Blocking 1SELGAPC1_ CB Closed Position
SELGAPC1_ CB Open Position INRPHAR1_BLK2H
CCBRBRF1_TRRETCCBRBRF1_TRBUDARREC1_INPRO
DARREC1_CLOSE_CBDARREC1_UNSUC_RECL
PDNSPTOC1_START
EFHPTOC1_START
SELGAPC1_External TripSG_1_ACTSG_2_ACTSG_3_ACTSG_4_ACTSG_5_ACTSG_6_ACT
GUID-C8E19D4D-9410-45B2-977A-4A56A0F41A48 V1 EN
Figure 18: Disturbance recorder
All start and operate signals from the protection stages are routed to trigger thedisturbance recorder or alternatively only to be recorded by the disturbancerecorder depending on the parameter settings. Additionally, the selectedautoreclose output signals and the three binary inputs from X120 are alsoconnected. The active setting group is also to be recorded via SG_1_ACT toSG_6_ACT. The disturbance recorder triggered signal indication is connected toLED 6.
Table 13: Disturbance recorder binary channel default value
Channel number Channel ID text Level trigger modeBinary channel 1 PHLPTOC1_START 1=positive or rising
Binary channel 2 PHHPTOC1_START 1=positive or rising
Binary channel 3 PHHPTOC2_START 1=positive or rising
Binary channel 4 PHIPTOC1_START 1=positive or rising
Binary channel 5 EFHPTOC1_START 1=positive or rising
Binary channel 6 DEFLPDEF1_START 1=positive or rising
Binary channel 7 DEFLPDEF2_START 1=positive or rising
Binary channel 8 DEFHPDEF1_START 1=positive or rising
Table continues on next page
1MRS757456 A Section 3REF611 standard configurations
REF611 35Application Manual
Channel number Channel ID text Level trigger modeBinary channel 9 ROVPTOV1_START 1=positive or rising
Binary channel 10 ROVPTOV2_START 1=positive or rising
Binary channel 11 ROVPTOV3_START 1=positive or rising
Binary channel 12 INTRPTEF1_START 1=positive or rising
Binary channel 13 NSPTOC1_START 1=positive or rising
Binary channel 14 NSPTOC2_START 1=positive or rising
Binary channel 15 PDNSPTOC1_START 1=positive or rising
Binary channel 16 T1PTTR1_START 1=positive or rising
Binary channel 17 PHxPTOC_OPERATE 4=level trigger off
Binary channel 18 EFHPTOC1_OPERATE 4=level trigger off
Binary channel 19 DEFxPDEF_OPERATE 4=level trigger off
Binary channel 20 ROVPTOV_OPERATE 4=level trigger off
Binary channel 21 INTRPTEF1_OPERATE 4=level trigger off
Binary channel 22 NSPTOC1/2_OPERATE 4=level trigger off
Binary channel 23 PDNSPTOC1_OPERATE 4=level trigger off
Binary channel 24 T1PPTR1_OPERATE 4=level trigger off
Binary channel 25 SELGAPC1_Blocking 1 4=level trigger off
Binary channel 26 SELGAPC1_CB_Closed 4=level trigger off
Binary channel 27 SELGAPC1_CB_Open 4=level trigger off
Binary channel 28 INRPHAR1_BLK2H 4=level trigger off
Binary channel 29 CCBRBRF1_TRRET 4=level trigger off
Binary channel 30 CCBRBRF1_TRBU 4=level trigger off
Binary channel 31 DARREC1_INPRO 4=level trigger off
Binary channel 32 DARREC1_CLOSE_CB 4=level trigger off
Binary channel 33 DARREC1_UNSUC_RECL 4=level trigger off
Binary channel 34 SELGAPC1_External Trip 4=level trigger off
Binary channel 35 SG1_ACTIVE 4=level trigger off
Binary channel 36 SG2_ACTIVE 4=level trigger off
Binary channel 37 SG3_ACTIVE 4=level trigger off
Binary channel 38 SG4_ACTIVE 4=level trigger off
Binary channel 39 SG5_ACTIVE 4=level trigger off
Binary channel 40 SG6_ACTIVE 4=level trigger off
Section 3 1MRS757456 AREF611 standard configurations
36 REF611Application Manual
X120-BI3
ORLED 7
TRIP CIRCUIT SUPERVISION
SELGAPC1OUT_3IN_3
TRPPTRC1_TRIP
TRPPTRC2_TRIP
TCSSCBR1
BLOCK ALARM
TCSSCBR2
BLOCK ALARM
SELGAPC4OUT_7IN_16
OSWGAPC14
OR OUT
IN_3
IN_4
SELGAPC2
OUT_1
IN_2 OUT_2CB Closed Position
GUID-50B079D8-AE34-4D47-BD5F-ACCBBEC0EC18 V1 EN
Figure 19: Trip circuit supervision
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3(X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blockedby the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker openposition. The TCS alarm indication is connected to LED 7.
1MRS757456 A Section 3REF611 standard configurations
REF611 37Application Manual
3.5.3.3 Functional diagrams for control
OR X100 PO3
OSWGAPC1
OR
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
OUT
IN_12
IN_13
IN_15
IN_14
X100 PO4
MASTER TRIP #1
MASTER TRIP #2
OR
OR
SELGAPC3OUT_6IN_2
SELGAPC3OUT_5IN_1
OSWGAPC2
OR
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
OUT
IN_12
IN_13
IN_15
IN_14
IN_17
TRIPCL_LKOUT
BLOCK
RST_LKOUT
TRPPTRC1
OPERATE
TRIPCL_LKOUT
BLOCK
RST_LKOUT
TRPPTRC2
OPERATE
SELGAPC1_RST_LKOUT
DARREC1_OPEN_CB
CBXCBR1_EXE_OP
SELGAPC1_External Trip
PHLPTOC1_OPERATE
PHHPTOC1_OPERATE
PHHPTOC2_OPERATE
PHIPTOC1_OPERATE
DEFLPDEF1_OPERATE
DEFLPDEF2_OPERATE
DEFHPDEF1_OPERATE
ROVPTOV1_OPERTAE
NSPTOC1_OPERATE
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
ROVPTOV2_OPERTAE
ROVPTOV3_OPERTAE
EFHPTOC1_OPETATE
INTRPTEF1_OPERATE
PHLPTOC1_OPERATE
PHHPTOC1_OPERATE
PHHPTOC2_OPERATE
PHIPTOC1_OPERATE
DEFLPDEF1_OPERATE
DEFLPDEF2_OPERATE
DEFHPDEF1_OPERATE
ROVPTOV1_OPERTAE
NSPTOC1_OPERATE
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
ROVPTOV2_OPERTAE
ROVPTOV3_OPERTAE
EFHPTOC1_OPETATE
INTRPTEF1_OPERATE
CCBRBRF1_TRRET
SELGAPC1_External Trip
SELGAPC1_RST_LKOUT
GUID-A4419861-FA17-4E12-8951-ABEB715AA740 V1 EN
Figure 20: Master trip
The operate signals from the protections and an external trip are connected to thetwo trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via thecorresponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commandsto the circuit breaker from local or remote CBXCBR1_EXE_OP or from theautoreclosing DARREC1_OPEN_CB are connected directly to the output contactPO3 (X100:15-19).
Section 3 1MRS757456 AREF611 standard configurations
38 REF611Application Manual
TRPPTRC1 and 2 provide the lockout/latching function, event generation and thetrip signal duration setting. One binary input through SELGAPC1 can be connectedto the RST_LKOUT input of the Master Trip. If the lockout operation mode isselected, it is used to enable external reset.
X120-BI2
X120-BI3
ANDTRPPTRC1_TRIP
TRPPTRC2_TRIP
CBXCBR1_EXE_OP
X100 PO1OR
DARREC1_CLOSE_CB
CIRCUIT BREAKER CONTROL
T1PTTR1_BLK_CLOSE
Always True
CBXCBR1
ENA_OPEN
SELECTEDEXE_OPEXE_CL
ENA_CLOSEBLK_OPENBLK_CLOSEAU_OPENAU_CLOSE
POSOPENPOSCLOSE
OPENPOSCLOSEPOS
OKPOSOPEN_ENAD
CLOSE_ENADITL_BYPASS
SELGAPC3OUT_1IN_3
SELGAPC1
OUT_2
IN_3
IN_2
OUT_3
IN_10 OUT_5
CB Closed Position
CB Open Position
GUID-1093EFA7-FA5F-4711-BF03-2B30C553BD72 V1 EN
Figure 21: Circuit breaker control
The ENA_CLOSE input, which enables the closing of the circuit breaker, is astatus of the Master Trip in the circuit-breaker control function block CBXCBR.An always true signal is also connected to ENA_CLOSE via SELGAPC1 bydefault. The open operation is always enabled.
1MRS757456 A Section 3REF611 standard configurations
REF611 39Application Manual
X100 SO1
X100 SO2
COMMON ALARM INDICATION 1 & 2
PHLPTOC1_OPERATE
PHHPTOC1_OPERATE
PHHPTOC2_OPERATE
PHIPTOC1_OPERATE
DEFLPDEF1_OPERATE
DEFLPDEF2_OPERATE
DEFHPDEF1_OPERATE
ROVPTOV1_OPERTAE
NSPTOC1_OPERATE
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
ROVPTOV2_OPERTAE
ROVPTOV3_OPERTAE
EFHPTOC1_OPETATE
INTRPTEF1_OPERATE
PHLPTOC1_START
PHHPTOC1_START
PHHPTOC2_START
PHIPTOC1_START
DEFLPDEF1_START
DEFLPDEF2_START
DEFHPDEF1_START
ROVPTOV1_START
NSPTOC1_START
NSPTOC2_START
PDNSPTOC1_START
ROVPTOV2_START
ROVPTOV3_START
EFHPTOC1_START
INTRPTEF1_START
OSWGAPC3
OR
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
OUT
IN_12
IN_13
IN_15
IN_14
OSWGAPC7
OR
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
OUT
IN_12
IN_13
IN_15
IN_14
SELGAPC3OUT_3IN_5
OUT_4IN_9
TPGAPC1IN1 OUT1
TPGAPC3IN1 OUT1
GUID-9AFB34C6-4203-47D4-B03D-F071504B50D3 V1 EN
Figure 22: Common alarm indication
The signal outputs from the IED are connected to give dedicated information on:
• Start of any protection function SO1 (X100:10-12)• Operation (trip) of any protection function SO2 (X100: 13-15)
TPGAPC are timers and they are used for setting the minimum pulse length for theoutputs. There are seven generic timers (TPGAPC1…7) available in the IED.
3.5.4 Switch groupsIn standard configuration A, the switch group function blocks are organized in fourgroups: binary inputs, internal signal, GOOSE as well as binary outputs and LEDs.
Section 3 1MRS757456 AREF611 standard configurations
40 REF611Application Manual
GOOSE
Binary Inputs Protection and Control
GOOSE
GOOSE
GOOSE
Binary Inputs(1...3, 4...9*)
Received GOOSE(0...19)
ISWGAPC3
INRPHAR1_BLK2H
Binary Outputs and LEDs
OSWGAPC2
OSWGAPC1
OSWGAPC16
OSWGAPC15
OSWGAPC14
OSWGAPC13
OSWGAPC12
OSWGAPC11
SELGAPC4
LEDs
SELGAPC3
Binary Outputs
OSWGAPC10
OSWGAPC9
OSWGAPC8
OSWGAPC7
OSWGAPC6
OSWGAPC5
OSWGAPC4
OSWGAPC3
Binary Outputs(1...6, 7..9*)
LEDs(1…8)
PHLPTOC1 PHHPTOC1
PHHPTOC2 PHIPTOC1
EFHPTOC1 DEFLPDEF1
DEFLPDEF2
NSPTOC1
DEFHPDEF1
NSPTOC2
INTRPTEF1 PDNSPTOC1
ROVPTOV1 ROVPTOV2
ROVPTOV3 T1PTTR1
INRPHAR1
CBXCBR1 DARREC1*
TCSSCBR1 TCSSCBR2
CCBRBRF1
Internal Signal
SELGAPC1
Binary Inputs
ISWGAPC2ISWGAPC1
SELGAPC2
Blocking
TCS Blocking
ISWGAPC9
GOOSE Blocking
ISWGAPC10
GOOSE Block CB Alarm
Trip
Start
Master trip
ISWGAPC5
BasicAngle Control
ISWGAPC4
DARREC1_PROT_CRD
* Optional Function
GUID-70D440AE-3136-411D-8A5C-56CABE711F69 V1 EN
Figure 23: Standard configuration A switch group overview
3.5.4.1 Binary inputs
The binary inputs group includes one SELGAPC and three ISWGAPCs.SELGAPC1 is used to route binary inputs to ISWGAPC or directly to IEDfunctions. ISWGAPC1 and ISWGAPC2 are used to configure the signal to blockthe protection functions. ISWGAPC5 is used to control the characteristic angle ofDEFxPDEF.
1MRS757456 A Section 3REF611 standard configurations
REF611 41Application Manual
SELGAPC1
ISWGAPC1Blocking 1
ISWGAPC5Basic Angle Control
DEFLPDEF1_RCA_CTLDEFLPDEF2_RCA_CTLDEFHPDEF1_RCA_CTL1) Optional binary inputs
PHLPTOC1_BLOCKPHHPTOC1_BLOCKPHHPTOC2_BLOCKPHIPTOC1_BLOCKEFHPTOC1_BLOCKDEFLPDEF1_BLOCKDEFLPDEF2_BLOCKDEFHPDEF1_BLOCKROVPTOV1_BLOCKROVPTOV2_BLOCKROVPTOV3_BLOCKINTRPTEF1_BLOCKNSPTOC1_BLOCKNSPTOC2_BLOCKPDNSPTOC1_BLOCKT1PTTR1_BLOCK
X120-BI1
X120-BI2
X120-BI3
X130-BI1
X130-BI2
X130-BI3
X130-BI4
X130-BI5
X130-BI6
1)
ISWGAPC2Blocking 2
PHLPTOC1_BLOCKPHHPTOC1_BLOCKPHHPTOC2_BLOCKPHIPTOC1_BLOCKEFHPTOC1_BLOCKDEFLPDEF1_BLOCKDEFLPDEF2_BLOCKDEFHPDEF1_BLOCKROVPTOV1_BLOCKROVPTOV2_BLOCKROVPTOV3_BLOCKINTRPTEF1_BLOCKNSPTOC1_BLOCKNSPTOC2_BLOCKPDNSPTOC1_BLOCKT1PTTR1_BLOCK
GUID-B37E732A-4522-4B96-BA67-A7C7020B40D5 V1 EN
Figure 24: Binary inputs
SELGAPC1SELGAPC1 has inputs from IED binary inputs. IN_1 to IN_3 are binary inputsfrom X100. IN_4 to IN_9 can be used while X130 optional card is taken into use.An always true signal is connected to IN_10. SELGAPC1 outputs are used to routeinputs to different functions. By setting SELGAPC1, binary inputs can beconfigured for different purposes.
Section 3 1MRS757456 AREF611 standard configurations
42 REF611Application Manual
SELGAPC1
Blocking 1
CCBRBRF1_POSCLOSECBXCBR1_POSCLOSESELGAPC2_IN_1
CB Closed Position
CB Open PositionDARREC1_CB_POS CBXCBR1_POSOPENSELGAPC2_IN_2
Basic Angle Control
CBXCBR1_ENA_CLOSECB Close Enable
DARREC1_CB_READY
External Trip
PROTECTION_BI_SG_2Setting Group 2
Blocking 2
PROTECTION_BI_SG_3Setting Group 3
PROTECTION_BI_SG_4Setting Group 4
ISWGAPC1_IN
ISWGAPC2_IN
X120/1-2 BI1
X120/3-2 BI2
X120/4-2 BI3
X130/1-2 BI1
X130/3-2 BI2
X130/4-5 BI3
X130/6-5 BI4
X130/7-8 BI5
X130/9-8 BI6
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
TRPTTRC1_OPERATETRPTTRC2_OPERATE
1) Optional binary inputs
X120-BI1
X120-BI2
X120-BI3
X130-BI1
X130-BI2
X130-BI3
X130-BI4
X130-BI5
X130-BI6
1)
Always True
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
OUT_10
OUT_11
OUT_12
OUT_13
ISWGAPC5_IN
DARREC1_RECL_ON
TRPTTRC1_RST_LKOUTTRPTTRC2_RST_LKOUT
TRPTTRC1/2_RST_LKOUT
GUID-A12A8C92-A8FA-46B1-A4C9-D1BAE4DE62DA V1 EN
Figure 25: SELGAPC1
ISWGAPC1ISWGAPC1 is used for general blocking. ISWGAPC1 input is routed fromSELGAPC1 output OUT_1 Blocking 1. ISWGAPC1 outputs are connected toBLOCK inputs of protection functions. Select which protection functions are to beblocked by changing the ISWGAPC1 parameters.
1MRS757456 A Section 3REF611 standard configurations
REF611 43Application Manual
ISWGAPC1
IN
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
OUT_10
OUT_11
OUT_12
OUT_13
OUT_14
OUT_15
OUT_16
Blocking 1SELGAPC1_OUT_1
PHLPTOC1_BLOCK
PHHPTOC1_BLOCK
PHHPTOC2_BLOCK
PHIPTOC1_BLOCK
EFHPTOC1_BLOCK
DEFLPDEF1_BLOCK
DEFLPDEF2_BLOCK
DEFHPDEF1_BLOCK
ROVPTOV1_BLOCK
ROVPTOV2_BLOCK
ROVPTOV3_BLOCK
INTRPTEF1_BLOCK
NSPTOC1_BLOCK
NSPTOC2_BLOCK
PDNSPTOC1_BLOCK
T1PTTR1_BLOCK
GUID-BDC462BB-B635-4BE4-932D-68010331C92B V1 EN
Figure 26: ISWGAPC1
ISWGAPC2ISWGAPC2 is used for general blocking. ISWGAPC2 input is routed fromSELGAPC1 output OUT_13 Blocking 2. ISWGAPC2 outputs are connected toBLOCK inputs of protection functions. Select which protection functions are to beblocked by changing the ISWGAPC2 parameters.
Section 3 1MRS757456 AREF611 standard configurations
44 REF611Application Manual
Blocking 2SELGAPC1_OUT_13
ISWGAPC2
IN
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
OUT_10
OUT_11
OUT_12
OUT_13
OUT_14
OUT_15
OUT_16
PHLPTOC1_BLOCK
PHHPTOC1_BLOCK
PHHPTOC2_BLOCK
PHIPTOC1_BLOCK
EFHPTOC1_BLOCK
DEFLPDEF1_BLOCK
DEFLPDEF2_BLOCK
DEFHPDEF1_BLOCK
ROVPTOV1_BLOCK
ROVPTOV2_BLOCK
ROVPTOV3_BLOCK
INTRPTEF1_BLOCK
NSPTOC1_BLOCK
NSPTOC2_BLOCK
PDNSPTOC1_BLOCK
T1PTTR1_BLOCK
GUID-56855209-1CDA-4B53-A920-3976BF96C636 V1 EN
Figure 27: ISWGAPC2
ISWGAPC5ISWGAPC5 input is routed from SELGAPC1 output OUT_4 Basic Angle Control.ISWGAPC5 outputs are connected to RCA_CTL inputs of directional earth-faultprotection functions. Select which directional earth-fault protection is controlled byISWGAPC5 input by changing the ISWGAPC5 parameters.
ISWGAPC5
IN
OUT_1
OUT_2
OUT_3
SELGAPC1_OUT_4
DEFLPDEF1_RCA_CTL
DEFLPDEF2_RCA_CTL
DEFHPDEF1_RCA_CTL
Basic Angle Control
GUID-47706B0D-5CB7-4D8D-8B07-846B87DDBDB4 V1 EN
Figure 28: ISWGAPC5
3.5.4.2 Internal signal
The internal signal group is used to configure logic connections between functionblocks. There are two ISWGAPC instances and one SELGAPC in the group.
ISWGAPC3 is used to configure which protection function enables the currentmultiplier if the INRPHAR1 function detects inrush. ISWGAPC4 is used toconfigure the cooperation between the autoreclose function and the protectionfunctions. The autoreclose function DARREC1 can block protection functions
1MRS757456 A Section 3REF611 standard configurations
REF611 45Application Manual
according to the application. SELGAPC2 is used to configure TCS blocking fromthe circuit breaker open or close position.
ISWGAPC3
PHLPTOC1_ENA_MULTPHHPTOC1_ENA_MULTPHHPTOC2_ENA_MULTPHIPTOC1_ENA_MULTEFHPTOC1_ENA_MULTDEFLPDEF1_ENA_MULTDEFLPDEF2_ENA_MULTDEFHPDEF1_ENA_MULTNSPTOC1_ENA_MULTNSPTOC2_ENA_MULTT1PTTR1_ENA_MULT
ISWGAPC4
PHLPTOC1_BLOCKPHHPTOC1_BLOCKPHHPTOC2_BLOCKEFHPTOC1_BLOCKDEFLPDEF1_BLOCKDEFLPDEF2_BLOCKDEFHPDEF1_BLOCK
SELGAPC2 TCSSCBR1_BLOCKTCSSCBR2_BLOCK
INRPHAR1_BLK2H
DARREC1_PROT_CRD
SELGAPC1_OUT_2
SELGAPC1_OUT_3
CB Closed Position
CB Open Position
GUID-A717CE52-5F4C-40C4-BF71-FBFCB900179B V1 EN
Figure 29: Internal signal
ISWGAPC3ISWGAPC3 input is routed from INRPHAR1 output BLK2H. ISWGAPC3 outputsare connected to ENA_MULT of the protection functions. Configure whichprotection function enables current multiplier while inrush is detected byINRPHAR1, by changing the ISWGAPC3 parameters.
ISWGAPC3
IN
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
OUT_10
OUT_11
INRPHAR1_BLK2H
PHLPTOC1_ENA_MULT
PHHPTOC1_ENA_MULT
PHHPTOC2_ENA_MULT
PHIPTOC1_ENA_MULT
EFHPTOC1_ENA_MULT
DEFLPDEF1_ENA_MULT
DEFLPDEF2_ENA_MULT
DEFHPDEF1_ENA_MULT
NSPTOC1_ENA_MULT
NSPTOC2_ENA_MULT
T1PTTR1_ENA_MULT
GUID-CC7AF316-6030-4959-B6EE-032E6415804C V1 EN
Figure 30: ISWGAPC3
Section 3 1MRS757456 AREF611 standard configurations
46 REF611Application Manual
ISWGAPC4ISWGAPC4 input is routed from DARREC1 output PROT_CRD. ISWGAPC4outputs are connected to the BLOCK inputs of some of the protection functions.Configure which protection function is blocked by the autoreclose function bychanging the ISWGAPC4 parameters.
ISWGAPC4
IN
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
DARREC1_PROT_CRD
PHLPTOC1_BLOCK
PHHPTOC1_BLOCK
PHHPTOC2_BLOCK
EFHPTOC1_BLOCK
DEFLPDEF1_BLOCK
DEFLPDEF2_BLOCK
DEFHPDEF1_BLOCK
GUID-E0106013-2B27-4DED-81C7-40ED4F0A94F0 V1 EN
Figure 31: ISWGAPC4
SELGAPC2SELGAPC2 inputs represent the circuit breaker closed and open position fromSELGACP1. SELGAPC2 outputs are routed to the BLOCK input of the trip circuitsupervision TCSSCBR1 and TCSSCBR2.
By default, X100 PO3 and PO4 are both used for the open circuit breaker.TCSSCBR1 and TCSSCBR2 are both blocked by the circuit breaker open position.If X100-PO3 is used for closing the circuit breaker, TCSSCBR1 needs to beblocked by circuit breaker close position (OUT_1 connection=IN_1). If X100-PO4is used for closing the circuit breaker, TCSSCBR2 needs to be blocked by thecircuit breaker close position (OUT_2 connection=IN_1).
SELGAPC2IN_1
IN_2
OUT_1
OUT_2
TCSSCBR1_BLOCK
TCSSCBR2_BLOCK
SELGAPC1_OUT_2
SELGAPC1_OUT_3
CB Closed Position
CB Open Position
GUID-4E5F2683-ED84-45AB-8636-023584763783 V1 EN
Figure 32: SELGAPC2
3.5.4.3 Binary outputs and LEDs
In standard configuration A, the signals are routed to binary outputs and LEDs areconfigured by OSWGAPCs. There are 16 OSWGAPC instances in total. They arecategorized in four groups, which include two Master trip, four start, four trip andsix alarm signals. The OSWGAPC output is connected with binary outputs andLEDs via SELGAPC3 and SELGAPC4.
1MRS757456 A Section 3REF611 standard configurations
REF611 47Application Manual
• SELGAPC3 is used to configure OSWGAPC signals to the IED's binaryoutputs. SELGAPC4 is used to configure OSWGAPC signals to LEDs.
• OSWGAPC1 and OSWGAPC2 are used for the Master trip. The inputs arerouted from the protection function's operate and the circuit breaker failure's re-trip.
• OSWGAPC3 to OSWGAPC6 are used for the start signal. The inputs are startsignals routed from the protection functions.
• OSWGAPC7 to OSWGAPC10 are used for the trip signal. The inputs areoperation signals routed from the protection functions.
• OSWGAPC11 to OSWGAPC16 are used for the alarm signal. The inputs arealarm signals routed from the protection and monitoring functions.
Section 3 1MRS757456 AREF611 standard configurations
48 REF611Application Manual
Master Trip 1
OSWGAPC2 Master Trip 2
Trip 1
Trip 2
Trip 3
Trip 4
T1PTTR1_ALARMRDRE_TRIGGEREDTCSSCBR1_ALARMTCSSCBR2_ALARMCCBRBRF1_TRBUCCBRBRF1_TRRETDARREC1_INPRODARREC1_LOCKEDDARREC1_PROT_CRDDARREC1_UNSUC_RECLDARREC1_AR_ONDARREC1_READYSELGAPC1_OUT_9TRPPTRC1_CL_LKOUTTRPPTRC2_CL_LKOUT
OSWGAPC12 Alarm 2
OSWGAPC13 Alarm 3
OSWGAPC14 Alarm 4
OSWGAPC1
OSWGAPC3
OSWGAPC11 Alarm 1
TRPPTRC1
TRPPTRC2
TPGAPC3
TPGAPC4
TPGAPC5
TPGAPC6
SELGAPC3
PHLPTOC1_OPERATEPHHPTOC1_OPERATEPHHPTOC2_OPERATEPHIPTOC1_OPERATEEFHPTOC1_OPERATEDEFLPDEF1_OPERATEDEFLPDEF2_OPERATEDEFHPDEF1_OPERATEROVPTOV1_OPERATEROVPTOV2_OPERATEROVPTOV3_OPERATEINTRPTEF1_OPERATENSPTOC1_OPERATENSPTOC2_OPERATEPDNSPTOC1_OPERATET1PTTR1_OPERATECCBRBRF1_TRRET
PHLPTOC1_STARTPHHPTOC1_STARTPHHPTOC2_STARTPHIPTOC1_STARTEFHPTOC1_STARTDEFLPDEF1_STARTDEFLPDEF2_STARTDEFHPDEF1_STARTROVPTOV1_STARTROVPTOV2_STARTROVPTOV3_STARTINTRPTEF1_STARTNSPTOC1_STARTNSPTOC2_STARTPDNSPTOC1_STARTT1PTTR1_START
PHLPTOC1_OPERATEPHHPTOC1_OPERATEPHHPTOC2_OPERATEPHIPTOC1_OPERATEEFHPTOC1_OPERATEDEFLPDEF1_OPERATEDEFLPDEF2_OPERATEDEFHPDEF1_OPERATEROVPTOV1_OPERATEROVPTOV2_OPERATEROVPTOV3_OPERATEINTRPTEF1_OPERATENSPTOC1_OPERATENSPTOC2_OPERATEPDNSPTOC1_OPERATET1PTTR1_OPERATE
OSWGAPC8
OSWGAPC7
OSWGAPC10
OSWGAPC9
1)Optional binary outputs
X100 PO1
X100 PO2
X100 SO1
X100 SO2
X100 PO3
X100 PO4
X130 SO1
X130 SO2
X130 SO3
1)
Start 1
Start 2
TPGAPC1
OSWGAPC4
OSWGAPC5 Start 3
Start 4
TPGAPC2
OSWGAPC6
OSWGAPC15 Alarm 5
OSWGAPC16 Alarm 6
TPGAPC7
IN1 OUT1
IN2 OUT2
IN1 OUT1
IN2 OUT2
IN1 OUT1
IN2 OUT2
IN1 OUT1
IN2 OUT2
IN1 OUT1
IN2 OUT2
IN1 OUT1
IN2 OUT2
IN1 OUT1
IN2 OUT2
GUID-DC487FC1-179A-44D3-90EC-0B2AB809EB67 V1 EN
Figure 33: Binary outputs
1MRS757456 A Section 3REF611 standard configurations
REF611 49Application Manual
Master Trip 1
OSWGAPC2 Master Trip 2
Trip 1
Trip 2
Trip 3
Trip 4
T1PTTR1_ALARMRDRE_TRIGGEREDTCSSCBR1_ALARMTCSSCBR2_ALARMCCBRBRF1_TRBUCCBRBRF1_TRRETDARREC1_INPRODARREC1_LOCKEDDARREC1_PROT_CRDDARREC1_UNSUC_RECLDARREC1_AR_ONDARREC1_READYSELGAPC1_OUT_9TRPPTRC1_CL_LKOUTTRPPTRC2_CL_LKOUT
OSWGAPC1
OSWGAPC3
OSWGAPC11 Alarm 1
TRPPTRC1
TRPPTRC2
SELGAPC4
PHLPTOC1_OPERATEPHHPTOC1_OPERATEPHHPTOC2_OPERATEPHIPTOC1_OPERATEEFHPTOC1_OPERATEDEFLPDEF1_OPERATEDEFLPDEF2_OPERATEDEFHPDEF1_OPERATEROVPTOV1_OPERATEROVPTOV2_OPERATEROVPTOV3_OPERATEINTRPTEF1_OPERATENSPTOC1_OPERATENSPTOC2_OPERATEPDNSPTOC1_OPERATET1PTTR1_OPERATECCBRBRF1_TRRET
PHLPTOC1_STARTPHHPTOC1_STARTPHHPTOC2_STARTPHIPTOC1_STARTEFHPTOC1_STARTDEFLPDEF1_STARTDEFLPDEF2_STARTDEFHPDEF1_STARTROVPTOV1_STARTROVPTOV2_STARTROVPTOV3_STARTINTRPTEF1_STARTNSPTOC1_STARTNSPTOC2_STARTPDNSPTOC1_STARTT1PTTR1_START
PHLPTOC1_OPERATEPHHPTOC1_OPERATEPHHPTOC2_OPERATEPHIPTOC1_OPERATEEFHPTOC1_OPERATEDEFLPDEF1_OPERATEDEFLPDEF2_OPERATEDEFHPDEF1_OPERATEROVPTOV1_OPERATEROVPTOV2_OPERATEROVPTOV3_OPERATEINTRPTEF1_OPERATENSPTOC1_OPERATENSPTOC2_OPERATEPDNSPTOC1_OPERATET1PTTR1_OPERATE
OSWGAPC8
OSWGAPC7
OSWGAPC10
OSWGAPC9
Start 1
Start 2OSWGAPC4
OSWGAPC5 Start 3
Start 4OSWGAPC6
LED1
LED2
LED3
LED4
LED5
LED6
LED7
LED8
OSWGAPC12 Alarm 2
OSWGAPC13 Alarm 3
OSWGAPC14 Alarm 4
OSWGAPC15 Alarm 5
OSWGAPC16 Alarm 6
GUID-A9F30F03-EB2B-487D-90D1-36E5CD493FF3 V1 EN
Figure 34: LEDs
SELGAPC3SELGAPC3 is used to configure the OSWGAPC outputs to the IED binaryoutputs. Master trip signals are connected to SELGAPC3 via TRPPTRC. Start, tripand alarm signals are connected to SELGAPC3 via TPGAPC. TPGAPC are timersand used for setting the minimum pulse length for the outputs.
Section 3 1MRS757456 AREF611 standard configurations
50 REF611Application Manual
SELGAPC3 outputs are connected to X100 binary outputs. If X130 optional card istaken into use, SELGAPC3 outputs also connected to the X130 binary outputs.
SELGAPC3
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
IN_14
IN_15
IN_16
IN_17
IN_18
X100 PO1
X100 PO2
X100 SO1
X100 SO2
X100 PO3
X100 PO4
X130 SO1
X130 SO2
X130 SO3
1)
1)Optional binary outputs
OSWGAPC11_OUT
OSWGAPC12_OUT
OSWGAPC13_OUT
OSWGAPC14_OUT
OSWGAPC15_OUT
OSWGAPC16_OUT
OSWGAPC5_OUT
OSWGAPC6_OUT
OSWGAPC7_OUT
OSWGAPC8_OUT
OSWGAPC9_OUT
OSWGAPC10_OUT
OSWGAPC3_OUT
OSWGAPC4_OUT
Start 1
Start 2
Start 3
Start 4
Trip 1
Alarm 1
Trip 2
Trip 3
Trip 4
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Backup Trip
CBXCBR_EXE_OP DARREC_OPEN_CB TRPPTRC1_TRIP
TRPPTRC2_TRIP
CBXCBR_EXE_CL DARREC_CLOSE_CB
CCBRBRF1_TRBU
CB Open 1
CB Close
CB Open 2
TPGAPC1IN1 OUT1
IN2 OUT2
TPGAPC7IN1 OUT1
IN2 OUT2
TPGAPC6IN1 OUT1
IN2 OUT2
TPGAPC5IN1 OUT1
IN2 OUT2
TPGAPC4IN1 OUT1
IN2 OUT2
TPGAPC3IN1 OUT1
IN2 OUT2
TPGAPC2IN1 OUT1
IN2 OUT2
GUID-3772666B-6FE9-48E5-91BF-9AA80BFD4B6E V1 EN
Figure 35:
SELGAPC4SELGAPC4 is used to configure the OSWGAPC outputs to LEDs. Master tripsignals are connected to SELGAPC4 via TRPPTRC. Start, trip and alarm signalsare connected to SELGAPC4 directly. SELGAPC4 outputs are connected toprogrammable LED1 to LED8.
1MRS757456 A Section 3REF611 standard configurations
REF611 51Application Manual
SELGAPC4IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
IN_14
IN_15
IN_16
IN_17
IN_18
LED1
LED2
LED3
LED4
LED5
LED6
LED7
LED8
Start 1
Start 2
Start 3
Start 4
Trip 1
Alarm 1
Trip 2
Trip 3
Trip 4
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
OSWGAPC11_OUT
OSWGAPC12_OUT
OSWGAPC13_OUT
OSWGAPC14_OUT
OSWGAPC15_OUT
OSWGAPC16_OUT
OSWGAPC5_OUT
OSWGAPC6_OUT
OSWGAPC7_OUT
OSWGAPC8_OUT
OSWGAPC9_OUT
OSWGAPC10_OUT
OSWGAPC3_OUT
OSWGAPC4_OUT
CBXCBR_EXE_CLDARREC_CLOSE_CB
CCBRBRF1_TRBU Backup Trip
CB Close
CB Open 1
CB Open 2
CBXCBR_EXE_OPDARREC_OPEN_CBTRPPTRC1_TRIP
TRPPTRC2_TRIP
GUID-B4946537-8289-4424-BE16-C9EDA774A4A4 V1 EN
Figure 36: SELGAPC4
Master trip OSWGAPCsOSWGAPC1 and OSWGAPC2 are used to route the protection function operatesignals to Master trip. OSWGAPC1 and OSWGAPC2 have the same inputs fromthe protection function's operate signals. The output is connected to TRPPTRCfunction. The default connections for OSWGAPC1 and OSWGAPC2 are different.
Section 3 1MRS757456 AREF611 standard configurations
52 REF611Application Manual
OSWGAPC1
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
EFHPTOC1_OPERATE
DEFLPDEF1_OPERATE
ROVPTOV2_OPERATE
ROVPTOV3_OPERATE
INTRPTEF1_OPERATE
PHLPTOC1_OPERATE
NSPTOC1_OPERATE
PHIPTOC1_OPERATE
DEFLPDEF2_OPERATE
DEFHPDEF1_OPERATE
ROVPTOV1_OPERATE
PHHPTOC2_OPERATE
PHHPTOC1_OPERATE
TRPPTRC 1_OPERATE
IN_14
IN_15
IN_16
IN_17
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
T1PTTR1_OPERATE
CCBRBRF1_TRRET
Master trip 1
GUID-1C2DBFDD-9F8B-4574-92C2-02A9D879FDA7 V1 EN
Figure 37: OSWGAPC1
1MRS757456 A Section 3REF611 standard configurations
REF611 53Application Manual
OSWGAPC2
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
EFHPTOC1_OPERATE
DEFLPDEF1_OPERATE
ROVPTOV2_OPERATE
ROVPTOV3_OPERATE
INTRPTEF1_OPERATE
PHLPTOC1_OPERATE
NSPTOC1_OPERATE
PHIPTOC1_OPERATE
DEFLPDEF2_OPERATE
DEFHPDEF1_OPERATE
ROVPTOV1_OPERATE
PHHPTOC2_OPERATE
PHHPTOC1_OPERATE
TRPPTRC 2_OPERATE
IN_14
IN_15
IN_16
IN_17
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
T1PTTR1_OPERATE
CCBRBRF1_TRRET
Master trip 2
GUID-1E93D270-E0CE-4861-A2B1-8E3974691618 V1 EN
Figure 38: OSWGAPC2
Start OSWGAPCsOSWGAPC instances 3 to 6 are used to configure the protection start signals.These four OSWGAPCs have the same inputs from the protection function startsignals. The output is routed to SELGAPC3 via TPGAPC timer, and routed toSELGAPC4 directly.
Section 3 1MRS757456 AREF611 standard configurations
54 REF611Application Manual
OSWGAPC3
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
IN_14
IN_15
IN_16
EFHPTOC1_START
DEFLPDEF1_START
ROVPTOV2_START
ROVPTOV3_START
INTRPTEF1_START
PHLPTOC1_START
NSPTOC1_START
PHIPTOC1_START
DEFLPDEF2_START
DEFHPDEF1_START
ROVPTOV1_START
PHHPTOC2_START
PHHPTOC1_START
NSPTOC2_START
PDNSPTOC1_START
T1PTTR1_START
TPGAPC1_IN1SELGAPC4_IN_5
Start 1
GUID-51366927-F89E-4879-969F-B1023B540BD1 V1 EN
Figure 39: OSWGAPC3
1MRS757456 A Section 3REF611 standard configurations
REF611 55Application Manual
OSWGAPC4
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
IN_14
IN_15
IN_16
EFHPTOC1_START
DEFLPDEF1_START
ROVPTOV2_START
ROVPTOV3_START
INTRPTEF1_START
PHLPTOC1_START
NSPTOC1_START
PHIPTOC1_START
DEFLPDEF2_START
DEFHPDEF1_START
ROVPTOV1_START
PHHPTOC2_START
PHHPTOC1_START
NSPTOC2_START
PDNSPTOC1_START
T1PTTR1_START
Start 2 TPGAPC1_IN2SELGAPC4_IN_6
GUID-E9196ACF-BA9A-483C-8FF3-4D41574BCEDE V1 EN
Figure 40: OSWGAPC4
Section 3 1MRS757456 AREF611 standard configurations
56 REF611Application Manual
OSWGAPC5
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
IN_14
IN_15
IN_16
EFHPTOC1_START
DEFLPDEF1_START
ROVPTOV2_START
ROVPTOV3_START
INTRPTEF1_START
PHLPTOC1_START
NSPTOC1_START
PHIPTOC1_START
DEFLPDEF2_START
DEFHPDEF1_START
ROVPTOV1_START
PHHPTOC2_START
PHHPTOC1_START
NSPTOC2_START
PDNSPTOC1_START
T1PTTR1_START
Start 3 TPGAPC2_IN1SELGAPC4_IN_7
GUID-FFA9885A-9816-4D9E-BF1F-C8204C73F32D V1 EN
Figure 41: OSWGAPC5
1MRS757456 A Section 3REF611 standard configurations
REF611 57Application Manual
OSWGAPC6
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
IN_14
IN_15
IN_16
EFHPTOC1_START
DEFLPDEF1_START
ROVPTOV2_START
ROVPTOV3_START
INTRPTEF1_START
PHLPTOC1_START
NSPTOC1_START
PHIPTOC1_START
DEFLPDEF2_START
DEFHPDEF1_START
ROVPTOV1_START
PHHPTOC2_START
PHHPTOC1_START
NSPTOC2_START
PDNSPTOC1_START
T1PTTR1_START
Start 4 TPGAPC2_IN2SELGAPC4_IN_8
GUID-41D82F50-DC6D-47AD-84C4-8BB5CE7A396B V1 EN
Figure 42: OSWGAPC6
Trip OSWGAPCsOSWGAPC instances 7 to 10 are used to configure the protection operate signalswhich belong to the trip group. These four OSWGAPCs have same inputs from theoperate signals of the protection functions. The output is routed to SELGAPC3 viaTPGAPC timer, and routed to SELGAPC4 directly.
Section 3 1MRS757456 AREF611 standard configurations
58 REF611Application Manual
OSWGAPC7
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
IN_14
IN_15
IN_16
EFHPTOC1_OPERATE
DEFLPDEF1_OPERATE
ROVPTOV2_OPERATE
ROVPTOV3_OPERATE
INTRPTEF1_OPERATE
PHLPTOC1_OPERATE
NSPTOC1_OPERATE
PHIPTOC1_OPERATE
DEFLPDEF2_OPERATE
DEFHPDEF1_OPERATE
ROVPTOV1_OPERATE
PHHPTOC2_OPERATE
PHHPTOC1_OPERATE
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
T1PTTR1_OPERATE
Trip 1 TPGAPC3_IN1SELGAPC4_IN_9
GUID-AB81000E-01A7-40D2-8BD4-3EBB8B125903 V1 EN
Figure 43: OSWGAPC7
1MRS757456 A Section 3REF611 standard configurations
REF611 59Application Manual
OSWGAPC8
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
IN_14
IN_15
IN_16
EFHPTOC1_OPERATE
DEFLPDEF1_OPERATE
ROVPTOV2_OPERATE
ROVPTOV3_OPERATE
INTRPTEF1_OPERATE
PHLPTOC1_OPERATE
NSPTOC1_OPERATE
PHIPTOC1_OPERATE
DEFLPDEF2_OPERATE
DEFHPDEF1_OPERATE
ROVPTOV1_OPERATE
PHHPTOC2_OPERATE
PHHPTOC1_OPERATE
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
T1PTTR1_OPERATE
Trip 2 TPGAPC3_IN2SELGAPC4_IN_10
GUID-03032E45-CF34-4D83-BFC4-02C07245E32E V1 EN
Figure 44: OSWGAPC8
Section 3 1MRS757456 AREF611 standard configurations
60 REF611Application Manual
OSWGAPC9
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
IN_14
IN_15
IN_16
EFHPTOC1_OPERATE
DEFLPDEF1_OPERATE
ROVPTOV2_OPERATE
ROVPTOV3_OPERATE
INTRPTEF1_OPERATE
PHLPTOC1_OPERATE
NSPTOC1_OPERATE
PHIPTOC1_OPERATE
DEFLPDEF2_OPERATE
DEFHPDEF1_OPERATE
ROVPTOV1_OPERATE
PHHPTOC2_OPERATE
PHHPTOC1_OPERATE
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
T1PTTR1_OPERATE
Trip 3 TPGAPC4_IN1SELGAPC4_IN_11
GUID-F48933D5-43DE-43E1-9260-D10601DFA02F V1 EN
Figure 45: OSWGAPC9
1MRS757456 A Section 3REF611 standard configurations
REF611 61Application Manual
OSWGAPC10
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
IN_14
IN_15
IN_16
EFHPTOC1_OPERATE
DEFLPDEF1_OPERATE
ROVPTOV2_OPERATE
ROVPTOV3_OPERATE
INTRPTEF1_OPERATE
PHLPTOC1_OPERATE
NSPTOC1_OPERATE
PHIPTOC1_OPERATE
DEFLPDEF2_OPERATE
DEFHPDEF1_OPERATE
ROVPTOV1_OPERATE
PHHPTOC2_OPERATE
PHHPTOC1_OPERATE
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
T1PTTR1_OPERATE
Trip 4 TPGAPC4_IN2SELGAPC4_IN_12
GUID-F0AC6293-6959-465E-A233-1D947583A2E1 V1 EN
Figure 46: OSWGAPC10
Alarm OSWGAPCsOSWGAPC instances 11 to 16 are used to configure the alarm signals whichbelong to the alarm group. These six OSWGAPCs have same inputs from the alarmsignals. The output is routed to SELGAPC3 via TPGAPC timer, and routed toSELGAPC4 directly.
Section 3 1MRS757456 AREF611 standard configurations
62 REF611Application Manual
OSWGAPC11
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
IN_14
IN_15
CCBRBRF1_TRBU
CCBRBRF1_TRRET
DARREC1_UNSUC_RECL
DARREC1_AR_ON
DARREC1_READY
T1PTTR1_ALARM
SELGAPC1_OUT_9
TCSSCBR2_ALARM
DARREC1_INPRO
DARREC1_LOCKED
DARREC1_PROT_CRD
TCSSCBR1_ALARM
RDRE_TRIGGERED
TRPPTRC1_CL_LKOUT
TRPPTRC2_CL_LKOUT
Alarm 1 TPGAPC5_IN1SELGAPC4_IN_13
External Trip
GUID-66274761-B6F9-409E-B0DE-9C0596ED4C71 V
Figure 47: OSWGAPC11
1MRS757456 A Section 3REF611 standard configurations
REF611 63Application Manual
OSWGAPC12
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
IN_14
IN_15
CCBRBRF1_TRBU
CCBRBRF1_TRRET
DARREC1_UNSUC_RECL
DARREC1_AR_ON
DARREC1_READY
T1PTTR1_ALARM
SELGAPC1_OUT_9
TCSSCBR2_ALARM
DARREC1_INPRO
DARREC1_LOCKED
DARREC1_PROT_CRD
TCSSCBR1_ALARM
RDRE_TRIGGERED
TRPPTRC1_CL_LKOUT
TRPPTRC2_CL_LKOUT
Alarm 2 TPGAPC5_IN2SELGAPC4_IN_14
External Trip
GUID-ED72F4ED-4DF4-4B13-AE0C-AAB6A03B69C7 V1 EN
Figure 48: OSWGAPC12
Section 3 1MRS757456 AREF611 standard configurations
64 REF611Application Manual
OSWGAPC13
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
IN_14
IN_15
CCBRBRF1_TRBU
CCBRBRF1_TRRET
DARREC1_UNSUC_RECL
DARREC1_AR_ON
DARREC1_READY
T1PTTR1_ALARM
SELGAPC1_OUT_9
TCSSCBR2_ALARM
DARREC1_INPRO
DARREC1_LOCKED
DARREC1_PROT_CRD
TCSSCBR1_ALARM
RDRE_TRIGGERED
TRPPTRC1_CL_LKOUT
TRPPTRC2_CL_LKOUT
Alarm 3 TPGAPC6_IN1SELGAPC4_IN_15
External Trip
GUID-85F16B67-BE18-43A3-8637-FCF29DB2E8D6 V1 EN
Figure 49: OSWGAPC13
1MRS757456 A Section 3REF611 standard configurations
REF611 65Application Manual
OSWGAPC14
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
IN_14
IN_15
CCBRBRF1_TRBU
CCBRBRF1_TRRET
DARREC1_UNSUC_RECL
DARREC1_AR_ON
DARREC1_READY
T1PTTR1_ALARM
SELGAPC1_OUT_9
TCSSCBR2_ALARM
DARREC1_INPRO
DARREC1_LOCKED
DARREC1_PROT_CRD
TCSSCBR1_ALARM
RDRE_TRIGGERED
TRPPTRC1_CL_LKOUT
TRPPTRC2_CL_LKOUT
Alarm 4 TPGAPC6_IN2SELGAPC4_IN_16
External Trip
GUID-C9EC48EA-F53F-4009-9010-5652EE3A6C95 V1 EN
Figure 50: OSWGAPC14
Section 3 1MRS757456 AREF611 standard configurations
66 REF611Application Manual
OSWGAPC15
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
IN_14
IN_15
CCBRBRF1_TRBU
CCBRBRF1_TRRET
DARREC1_UNSUC_RECL
DARREC1_AR_ON
DARREC1_READY
T1PTTR1_ALARM
SELGAPC1_OUT_9
TCSSCBR2_ALARM
DARREC1_INPRO
DARREC1_LOCKED
DARREC1_PROT_CRD
TCSSCBR1_ALARM
RDRE_TRIGGERED
TRPPTRC1_CL_LKOUT
TRPPTRC2_CL_LKOUT
Alarm 5 TPGAPC7_IN1SELGAPC4_IN_17
External Trip
GUID-CC49B32B-234A-43AB-86AF-B83FC2C10F51 V1 EN
Figure 51: OSWGAPC15
1MRS757456 A Section 3REF611 standard configurations
REF611 67Application Manual
OSWGAPC16
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
IN_14
IN_15
CCBRBRF1_TRBU
CCBRBRF1_TRRET
DARREC1_UNSUC_RECL
DARREC1_AR_ON
DARREC1_READY
T1PTTR1_ALARM
SELGAPC1_OUT_9
TCSSCBR2_ALARM
DARREC1_INPRO
DARREC1_LOCKED
DARREC1_PROT_CRD
TCSSCBR1_ALARM
RDRE_TRIGGERED
TRPPTRC1_CL_LKOUT
TRPPTRC2_CL_LKOUT
Alarm 6 TPGAPC7_IN2SELGAPC4_IN_18
External Trip
GUID-053F0EAF-B3F1-474C-91E9-76E4DC91629F V1 EN
Figure 52: OSWGAPC16
3.5.4.4 GOOSE
In the configuration, there are 20 GOOSERCV_BIN functions. EachGOOSERVC_BIN function can be connected to one received binary GOOSEsignal. The signal connection can be configured in PCM600.
• GOOSERCV_BIN instances 0 and 1 are used for blocking protectionfunctions. Signals from these two GOOSERCV_BINs are connected toISWGAPC9. ISWGAPC9 is used to configure which protection function blockis blocked.
• GOOSERCV_BIN instances 2 and 3 are used for tripping from GOOSE.Signals from these two GOOSERCV_BINs are connected to TRPPTRC1 andTRPPTRC2 trip.
• GOOSERCV_BIN instances 4 to 19 are used for blocking circuit breakeroperation. Signals from these 16 GOOSERCV_BINs are connected toISWGAPC10. ISWGAPC10 is used to configure the GOOSE input signal toblock the circuit breaker open or close operation.
Section 3 1MRS757456 AREF611 standard configurations
68 REF611Application Manual
CBXCBR1_BLK_CLOSECBXCBR1_BLK_OPEN
GOOSERCV_BIN:1
GOOSERCV_BIN:0
OR ISWGAPC9GOOSE Blcoking
GOOSERCV_BIN:3
GOOSERCV_BIN:2
ORGOOSEExternal Trip
GOOSERCV_BIN:5
GOOSERCV_BIN:4
GOOSERCV_BIN:19
OR ISWGAPC10GOOSE Block CB
PHLPTOC1_BLOCKPHHPTOC1_BLOCKPHHPTOC2_BLOCKPHIPTOC1_BLOCKEFHPTOC1_BLOCKDEFLPDEF1_BLOCKDEFLPDEF2_BLOCKDEFHPDEF1_BLOCKROVPTOV1_BLOCKROVPTOV2_BLOCKROVPTOV3_BLOCKINTRPTEF1_BLOCKNSPTOC1_BLOCKNSPTOC2_BLOCKPDNSPTOC1_BLOCKT1PTTR1_BLOCK
TRPPTRC1_OPERATETRPPTRC2_OPERATE
GUID-0B0FD851-2982-4097-B52D-ADC59E9AA638 V1 EN
Figure 53: GOOSE overview
ISWGAPC9ISWGAPC9 is used to configure which protection functions can be blocked by thereceived GOOSE signals. ISWGAPC9 inputs are received GOOSE signals fromGOOSERCV_BIN:0 and GOOSERCV_BIN:1. The outputs are connected to blockinputs of the protection functions.
1MRS757456 A Section 3REF611 standard configurations
REF611 69Application Manual
ISWGAPC9
IN
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
OUT_10
OUT_11
OUT_12
OUT_13
OUT_14
OUT_15
OUT_16
PHLPTOC1_BLOCK
PHHPTOC1_BLOCK
PHHPTOC2_BLOCK
PHIPTOC1_BLOCK
EFHPTOC1_BLOCK
DEFLPDEF1_BLOCK
DEFLPDEF2_BLOCK
DEFHPDEF1_BLOCK
ROVPTOV1_BLOCK
ROVPTOV2_BLOCK
ROVPTOV3_BLOCK
INTRPTEF1_BLOCK
NSPTOC1_BLOCK
NSPTOC2_BLOCK
PDNSPTOC1_BLOCK
T1PTTR1_BLOCK
GOOSE BlockingGOOSERCV_BIN:0_OUTGOOSERCV_BIN:1_OUT
GUID-8189C6A6-FF9A-423C-B870-06A23A20E3B3 V1 EN
Figure 54: ISWGAPC9
ISWGAPC10ISWGAPC10 is used to block the circuit breaker operation from the receivedGOOSE signals. ISWGAPC10 inputs are received GOOSE signals fromGOOSERCV_BIN:4 to GOOSERCV_BIN:19. The outputs are connected to blockthe circuit breaker's close and open operation.
ISWGAPC10
INOUT_1
OUT_2
CBXCBR1_BLK_CLOSE
CBXCBR1_BLK_OPEN
GOOSERCV_BIN:4_OUTGOOSERCV_BIN:5_OUTGOOSERCV_BIN:6_OUT...GOOSERCV_BIN:19_OUT
GOOSE Block CB
GUID-07F0B112-6C1B-452D-B2E0-BB8857AAF590 V1 EN
Figure 55: ISWGAPC10
Section 3 1MRS757456 AREF611 standard configurations
70 REF611Application Manual
3.6 Standard configuration B
3.6.1 ApplicationsThe standard configuration for non-directional overcurrent and non-directional earth-fault protection is mainly intended for cable and overhead-line feeder applicationsin isolated and resonant-earthed distribution networks.
The IED with a standard configuration is delivered from the factory with defaultsettings and parameters. The end-user flexibility for incoming, outgoing andinternal signal designation within the IED enables this configuration to be furtheradapted to different primary circuit layouts and the related functionality needs bymodifying the internal functionality using PCM600.
3.6.2 FunctionsTable 14: Functions included in the standard configuration B
Function IEC 61850 IEC 60617 IEC-ANSIProtection
Three-phase non-directional overcurrentprotection, low stage, instance 1 PHLPTOC1 3I> (1) 51P-1 (1)
Three-phase non-directional overcurrentprotection, high stage, instance 1 PHHPTOC1 3I>> (1) 51P-2 (1)
Three-phase non-directional overcurrentprotection, high stage, instance 2 PHHPTOC2 3I>> (2) 51P-2 (2)
Three-phase non-directional overcurrentprotection, instantaneous stage, instance 1 PHIPTOC1 3I>>> (1) 50P/51P (1)
Non-directional earth-fault protection, lowstage, instance 1 EFLPTOC1 Io> (1) 51N-1 (1)
Non-directional earth-fault protection, lowstage, instance 2 EFLPTOC2 Io> (2) 51N-1 (2)
Non-directional earth-fault protection, highstage, instance 1 EFHPTOC1 Io>> (1) 51N-2 (1)
Non-directional earth-fault protection,instantaneous stage EFIPTOC1 Io>>> 50N/51N
Negative-sequence overcurrent protection,instance 1 NSPTOC1 I2> (1) 46 (1)
Negative-sequence overcurrent protection,instance 2 NSPTOC2 I2> (2) 46 (2)
Phase discontinuity protection PDNSPTOC1 I2/I1> 46PD
Three-phase thermal protection forfeeders, cables and distributiontransformers
T1PTTR1 3Ith>F 49F
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF
Three-phase inrush detector INRPHAR1 3I2f> 68
Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)
Table continues on next page
1MRS757456 A Section 3REF611 standard configurations
REF611 71Application Manual
Function IEC 61850 IEC 60617 IEC-ANSIMaster trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)
Switch groups
Input switch group ISWGAPC ISWGAPC ISWGAPC
Output switch group OSWGAPC OSWGAPC OSWGAPC
Selector switch group SELGAPC SELGAPC SELGAPC
Configurable timer
Minimum pulse timer (2 pcs) TPGAPC TP TP
Control
Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB
Auto-reclosing DARREC1 O -> I 79
Supervision
Trip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)
Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)
Measurement
Disturbance recorder RDRE1 - -
Three-phase current measurement,instance 1 CMMXU1 3I 3I
Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0
Residual current measurement, instance 1 RESCMMXU1 Io In
3.6.2.1 Default I/O connections
Table 15: Default connections for binary inputs
Binary input Default usage Connector pinsX120-BI1 Blocking of overcurrent instantaneous stage X120-1,2
X120-BI2 Circuit breaker closed position indication X120-3,2
X120-BI3 Circuit breaker open position indication X120-4,2
X120-BI4 Reset of master trip lockout X120-5,6
Table 16: Default connections for binary outputs
Binary input Default usage Connector pinsX100-PO1 Close circuit breaker X100-6,7
X100-PO2 Circuit breaker failure protection trip to upstreambreaker
X100-8,9
X100-PO3 Open circuit breaker/trip coil 1 X100-15,16,17,18,19
X100-PO4 Open circuit breaker/trip coil 2 X100-20,21,22,23,24
X100-SO1 General start indication X100-10,11,12
X100-SO2 General operate indication X100-13,14,15
Section 3 1MRS757456 AREF611 standard configurations
72 REF611Application Manual
Table 17: Default connections for LEDs
LED Default usage1 Non-directional overcurrent operate
2 Earth fault operate
3 Negative-sequence overcurrent/phase discontinuity operate
4 Thermal overload alarm
5 Autoreclose in progress
6 Disturbance recorder triggered
7 Trip circuit supervision alarm
8 Circuit-breaker failure operate
3.6.2.2 Predefined disturbance recorder connections
Table 18: Predefined analog channel setup
Channel Selection and text1 IL1
2 IL2
3 IL3
4 Io
Additionally, all the digital inputs that are connected by default are also enabledwith the setting. Default triggering settings are selected depending on theconnected input signal type. Typically all protection START signals are selected totrigger the disturbance recorded by default.
3.6.3 Functional diagramsThe functional diagrams describe the default input, output, programmable LED,switch group and function-to-function connections. The default connections can beviewed and changed with switch groups in PCM600, LHMI and WHMI accordingto the application requirements.
The analog channels have fixed connections towards the different function blocksinside the IED’s standard configuration. Exceptions from this rule are the sevenanalog channels available for the disturbance recorder function. These channels arefreely selectable and a part of the disturbance recorder’s parameter settings.
The analog channels are assigned to different functions. The common signalmarked with 3I represents the three phase currents. The signal marked with Iorepresents the measured residual current via a core balance current transformer.
1MRS757456 A Section 3REF611 standard configurations
REF611 73Application Manual
3.6.3.1 Functional diagrams for protection
The functional diagrams describe the IED’s protection functionality in detail andpicture the factory default connections.
X120-BI1
LED 1
ISWGAPC1OUT_4IN
SELGAPC4OUT_1IN_10
OSWGAPC8
OR OUT
IN_1
IN_2
IN_3
IN_4
OVERCURRENT PROTECTION AND INRUSH INDICATION
PHLPTOC13I>(1)
51P-1(1)
BLOCK START
OPERATE3I
ENA_MULT
PHHPTOC13I>>(1)
51P-2(1)
BLOCK START
OPERATE3I
ENA_MULT
PHHPTOC23I>>(2)
51P-2(2)
BLOCK START
OPERATE3I
ENA_MULT
SELGAPC1OUT_1IN_1
PHIPTOC13I>>>(1)
50P/51P(1)
BLOCK START
OPERATE3I
ENA_MULTBlocking 1
INRPHAR13I2f >(1)
68(1)
BLOCK
BLK2H3I
GUID-DEF278A2-D120-437C-BC9A-180BD34C6962 V1 EN
Figure 56: Overcurrent protection
Four overcurrent stages are offered for overcurrent and short-circuit protection.The instantaneous stage (PHIPTOC1) can be blocked by energizing the binaryinput (X120:1-2). The inrush detection block’s (INRPHAR1) output BLK2Henables either blocking the function or multiplying the active settings for any of thedescribed protection function blocks.
All operate signals are connected to the Master Trip and to the alarm LED 1.
Section 3 1MRS757456 AREF611 standard configurations
74 REF611Application Manual
LED 2
EARTH-FAULT PROTECTION
SELGAPC4OUT_2IN_11
OSWGAPC9
OR OUT
IN_5
IN_6
IN_7
IN_8
EFLPTOC1Io>(1)
51N-1(1)
BLOCK STARTOPERATEIo
ENA_MULT
EFLPTOC2Io>(2)
51N-1(2)
BLOCK STARTOPERATEIo
ENA_MULT
EFIPTOC1Io>>>(1)
50N(1)
BLOCK STARTOPERATEIo
ENA_MULT
EFHPTOC1Io>>(1)
51N-2(1)
BLOCK STARTOPERATEIo
ENA_MULT
GUID-A3A385B1-89E2-4E71-9C18-183C9A1F9660 V1 EN
Figure 57: Earth-fault protection
Four stages are offered for non-directional earth-fault protection.
All operate signals are connected to the Master Trip as well as to the alarm LED 2.
1MRS757456 A Section 3REF611 standard configurations
REF611 75Application Manual
LED 3
UNBALANCE PROTECTION
NSPTOC1I2>(1)
46(1)
BLOCK START
OPERATE3I
ENA_MULT
NSPTOC2I2>(2)
46(2)
BLOCK START
OPERATE3I
ENA_MULT
SELGAPC4IN_12 OUT_3
OSWGAPC10
OR OUT
IN_9
IN_10
IN_11
PDNSPTOC1I2/I1(1)
46PD(1)
BLOCK START
OPERATE3I
GUID-4CFBCA74-5D5E-4C39-87DE-18EE2BE86C19 V1 EN
Figure 58: Unbalance protection
Two negative-sequence overcurrent stages (NSPTOC1 and NSPTOC2) and onephase discontinuity stage (PDNPSTOC1) are offered for the unbalance protection.The phase discontinuity protection (PDNPSTOC1) provides protection forinterruptions in the normal three-phase load supply, for example, in downedconductor situations.
The operate signals of these unbalance protections are connected to the Master Tripand also to alarm LED 3.
Section 3 1MRS757456 AREF611 standard configurations
76 REF611Application Manual
X120-BI2
X100 PO2
LED 8
SELGAPC3OUT_2IN_4
OSWGAPC15OUTIN_5
LED 4
THERMAL OVERLOAD PROTECTION
CIRCUIT BREAKER FAILURE PROTECTION
SELGAPC4OUT_8IN_17
OSWGAPC11OUTIN_1
SELGAPC4OUT_4IN_13
SELGAPC1OUT_2IN_2
PHIPTOC1_OPERATEPHHPTOC2_OPERATE
PHLPTOC1_OPERATEPHHPTOC1_OPERATE
EFHPTOC1_OPERATE
OREFLPTOC1_OPERATEEFLPTOC2_OPERATE
EFIPTOC1_OPERATE
CB Closed Position
51BF/51NBF(1)
3I
Io
START TRRET
TRBU
POSCLOSE
CB_FAULT
BLOCK
CB_FAULT_AL
CCBRBRF13I>/Io>BF(1)
T1PTTR13Ith>F(1)
49F(1)
BLK_OPR
START
OPERATE3I
BLK_CLOSE
ALARMENA_MULT
AMB_TEMP
GUID-05F6D382-22E2-41D8-84A3-1EC01A52B6B1 V1 EN
Figure 59: Thermal overload and circuit-breaker failure protection
The thermal overload protection (T1PTTR1) provides indication on overloadsituations. LED 4 is used for the thermal overload protection alarm indication.
The circuit-breaker failure protection (CCBRBRF1) is initiated via the start inputby a number of different protection stages in the IED. CCBRBRF1 offers differentoperating modes associated with the circuit-breaker position and the measuredphase and residual currents. CCBRBRF1 has two operating outputs: TRRET andTRBU. The TRRET operate output is used for retripping its own circuit breakerthrough Master Trip 2. The TRBU output is used to give a backup trip to the circuit-breaker feeding upstream. For this purpose, the TRBU operate output signal isconnected to the output PO2 (X100: 8-9). LED 8 is used for the backup (TRBU)operate indication.
1MRS757456 A Section 3REF611 standard configurations
REF611 77Application Manual
X120-BI3
LED 5
OR
OR
AUTORECLOSING (Optional)
Always True
OSWGAPC12OUTIN_7
SELGAPC4OUT_5IN_14
PHHPTOC2_OPERATE
PHLPTOC1_OPERATE
EFLPTOC2_OPERATE
EFHPTOC1_OPERATE
PHLPTOC1_START
EFHPTOC1_START
EFLPTOC1_OPERATE
PHHPTOC1_OPERATE
EFLPTOC1_STARTEFLPTOC2_START
NSPTOC2_OPERATENSPTOC1_OPERATE
CBXCBR1_SELECTED
EFIPTOC1_OPERATE
PDNSPTOC1_OPERATEPHIPTOC1_OPERATE
SELGAPC1OUT_3IN_3
OUT_6IN_11
T1PTTR1_BLK_CLOSE
CB Open Position
DARREC1O->I(1)
79(1)
INT_1
INT_2
INT_3
INT_4
INT_5
INT_6
DEL_INT_2
DEL_INT_3
DEL_INT_4
RECL_ON
INHIBIT_RECL
SYNC
OPEN CB
CLOSE CB
INPRO
UNSUC_RECL
AR_ON
PROT_CRD
READY
BLK_RECL_T
BLK_RCLM_T
BLK_THERM
CB_POS
CB_READY
INC_SHOTP
CMD_WAIT
LOCKED
GUID-C14CE4DE-2849-40A9-87D4-F737031DE5BF V1 EN
Figure 60: Autoreclosing
Autoreclosing (DARREC1) is included as an optional function.
The autoreclose function is configured to be initiated by operate signals from anumber of protection stages through the INT_1...6 inputs and by start signalsthrough the DEL_INT_2…4. It is possible to create individual autoreclosesequences for each input.
The autoreclose function can be blocked with the INHIBIT_RECL input. Bydefault, the operations of selected protection functions are connected to this input.A control command to the circuit breaker, either local or remote, also blocks theautoreclose function via the CBXCBR_SELECTED signal.
The circuit breaker availability for the autoreclose sequence is expressed with theCB_READY input in DARREC1. In the configuration, this signal is connectedwith an always true signal through SELGAPC1. As a result, the function assumesthat the circuit breaker is available all the time.
The autoreclosie sequence in progress indication INPRO is connected to the alarmLED 5.
Section 3 1MRS757456 AREF611 standard configurations
78 REF611Application Manual
3.6.3.2 Functional diagrams for disturbance recorder and trip circuitsupervision
LED 6
DISTURBANCE RECORDER
OSWGAPC13OUTIN_2
SELGAPC4OUT_6IN_15
OR
OR
OR
PHLPTOC1_OPERATEPHHPTOC1_OPERATEPHHPTOC2_OPERATEPHIPTOC1_OPERATE
EFHPTOC1_OPERATE
EFLPTOC1_OPERATEEFLPTOC2_OPERATE
NSPTOC1_OPERATENSPTOC2_OPERATE
EFIPTOC1_OPERATE
RDRE1C1C2C3C4C5C6C7C8C9C10C11C12C13C14C15C16C17C18C19C20C21C22C23C24C25C26C27C28C29C30C31C32C33
TRIGGERED
SELGAPC1_ CB Open Position
PHLPTOC1_START
EFIPTOC1_START
PHHPTOC1_START
PHIPTOC1_STARTPHHPTOC2_START
EFLPTOC2_STARTEFHPTOC1_START
T1PTTR1_START
PDNSPTOC1_OPERATET1PTTR1_OPERATE
SELGAPC1_ Blocking 1SELGAPC1_ CB Closed Position
INRPHAR1_BLK2HCCBRBRF1_TRRET
CCBRBRF1_TRBUDARREC1_INPRO
DARREC1_CLOSE_CBDARREC1_UNSUC_RECL
EFLPTOC1_START
NSPTOC1_STARTNSPTOC2_START
PDNSPTOC1_START
SELGAPC1_External TripSG_1_ACTSG_2_ACTSG_3_ACTSG_4_ACTSG_5_ACTSG_6_ACT
GUID-D5C64B52-5763-48FA-AC6A-14257698FEBC V1 EN
Figure 61: Disturbance recorder
All start and operate signals from the protection stages are routed to trigger thedisturbance recorder or alternatively only to be recorded by the disturbancerecorder depending on the parameter settings. Additionally, the selectedautoreclose output signals and the three binary inputs from X120 are alsoconnected. The active setting group is also to be recorded via SG_1_ACT toSG_6_ACT. The disturbance recorder triggered signal indication is connected toLED 6.
Table 19: Disturbance recorder binary channel default value
Channel number Channel id text Level trigger modeBinary channel 1 PHLPTOC1_START 1=positive or rising
Binary channel 2 PHHPTOC1_START 1=positive or rising
Binary channel 3 PHHPTOC2_START 1=positive or rising
Binary channel 4 PHIPTOC1_START 1=positive or rising
Binary channel 5 EFLPTOC1_START 1=positive or rising
Binary channel 6 EFLPTOC2_START 1=positive or rising
Binary channel 7 EFHPTOC1_START 1=positive or rising
Binary channel 8 EFIPTOC1_START 1=positive or rising
Binary channel 9 NSPTOC1_START 1=positive or rising
Binary channel 10 NSPTOC2_START 1=positive or rising
Binary channel 11 PDNSPTOC1_START 1=positive or rising
Table continues on next page
1MRS757456 A Section 3REF611 standard configurations
REF611 79Application Manual
Channel number Channel id text Level trigger modeBinary channel 12 T1PTTR1_START 1=positive or rising
Binary channel 13 PHxPTOC_OPERATE 4=level trigger off
Binary channel 14 EFxPTOC_OPERATE 4=level trigger off
Binary channel 15 NSPTOC1/2_OPERATE 4=level trigger off
Binary channel 16 PDNSPTOC1_OPERATE 4=level trigger off
Binary channel 17 T1PPTR1_OPERATE 4=level trigger off
Binary channel 18 SELGAPC1_Blocking 1 4=level trigger off
Binary channel 19 SELGAPC1_CB_Closed 4=level trigger off
Binary channel 20 SELGAPC1_CB_Open 4=level trigger off
Binary channel 21 INRPHAR1_BLK2H 4=level trigger off
Binary channel 22 CCBRBRF1_TRRET 4=level trigger off
Binary channel 23 CCBRBRF1_TRBU 4=level trigger off
Binary channel 24 DARREC1_INPRO 4=level trigger off
Binary channel 25 DARREC1_CLOSE_CB 4=level trigger off
Binary channel 26 DARREC1_UNSUC_RECL 4=level trigger off
Binary channel 27 SELGAPC1_External Trip 4=level trigger off
Binary channel 28 SG_1_ACT 4=level trigger off
Binary channel 29 SG_2_ACT 4=level trigger off
Binary channel 30 SG_3_ACT 4=level trigger off
Binary channel 31 SG_4_ACT 4=level trigger off
Binary channel 32 SG_5_ACT 4=level trigger off
Binary channel 33 SG_6_ACT 4=level trigger off
X120-BI3
ORLED 7
TRIP CIRCUIT SUPERVISION
SELGAPC1OUT_3IN_3
TRPPTRC1_TRIP
TRPPTRC2_TRIP
TCSSCBR1
BLOCK ALARM
TCSSCBR2
BLOCK ALARM
SELGAPC4OUT_7IN_16
OSWGAPC14
OR OUT
IN_3
IN_4
SELGAPC2
OUT_1
IN_2 OUT_2CB Open Position
GUID-8D5B4458-2F48-4925-AEC1-F1C49AFBEE22 V1 EN
Figure 62: Trip circuit supervision
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3(X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blockedby Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker openposition. The TCS alarm indication is connected to LED 7.
Section 3 1MRS757456 AREF611 standard configurations
80 REF611Application Manual
3.6.3.3 Functional diagrams for control
OR X100 PO3
TRIPCL_LKOUT
BLOCK
RST_LKOUT
TRPPTRC1
OPERATE
X100 PO4
MASTER TRIP #1
MASTER TRIP #2
OR
ORTRIP
CL_LKOUT
BLOCK
RST_LKOUT
TRPPTRC2
OPERATE
SELGAPC3OUT_6IN_2
SELGAPC3OUT_5IN_1
SELGAPC1OUT_4IN_4
SELGAPC1OUT_4IN_4
OSWGAPC2
OR
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
OUT
IN_12
SELGAPC1_External Trip
X120-BI4
PHLPTOC1_OPERATE
PHHPTOC1_OPERATE
PHHPTOC2_OPERATE
PHIPTOC1_OPERATE
EFLPTOC2_OPERATE
EFHPTOC1_OPERATE
EFIPOTC1_OPERATE
NSPTOC1_OPERATE
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
EFLPTOC1_OPETATE
CCBRBRF1_TRRET
OSWGAPC1
OR
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
OUT
DARREC1_OPEN_CB
CBXCBR1_EXE_OP
SELGAPC1_External Trip
PHLPTOC1_OPERATE
PHHPTOC1_OPERATE
PHHPTOC2_OPERATE
PHIPTOC1_OPERATE
EFLPTOC2_OPERATE
EFHPTOC1_OPERATE
EFIPOTC1_OPERATE
NSPTOC1_OPERATE
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
EFLPTOC1_OPETATE
X120-BI4
RST_LKOUT
RST_LKOUT
GUID-66E79F27-D704-4BD5-8778-5B1BB863D7D8 V1 EN
Figure 63: Master trip
The operate signals from the protections and an external trip are connected to thetwo trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via thecorresponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commandsto the circuit breaker from local or remote CBXCBR1_EXE_OP or from theautoreclosing DARREC1_OPEN_CB are connected directly to the output contactPO3 (X100:15-19).
1MRS757456 A Section 3REF611 standard configurations
REF611 81Application Manual
TRPPTRC1 and 2 provide the lockout/latching function, event generation and thetrip signal duration setting. One binary input through SELGAPC1 can be connectedto the RST_LKOUT input of Master Trip. If the lockout operation mode isselected, it is used to enable the external reset.
X120-BI2
X120-BI3
AND
CBXCBR1_EXE_OP
X100 PO1OR
CIRCUIT BREAKER CONTROL
Always True
CBXCBR1
ENA_OPEN
SELECTEDEXE_OPEXE_CL
ENA_CLOSEBLK_OPENBLK_CLOSEAU_OPENAU_CLOSE
POSOPENPOSCLOSE
OPENPOSCLOSEPOS
OKPOSOPEN_ENAD
CLOSE_ENADITL_BYPASS
SELGAPC3OUT_1IN_3
SELGAPC1
OUT_2
IN_3
IN_2
OUT_3
IN_11 OUT_5
TRPPTRC1_TRIP
TRPPTRC2_TRIP
DARREC1_CLOSE_CB
T1PTTR1_BLK_CLOSE
CB Closed Position
CB Open Position
GUID-04CDD1B0-F721-4CE4-A19D-B6BF96C0FB42 V1 EN
Figure 64: Circuit breaker control
The ENA_CLOSE input, which enables the closing of the circuit breaker, is astatus of the Master Trip in the circuit-breaker control function CBXCBR. Analways true signal is also connected to ENA_CLOSE via SELGAPC1 by default.The open operation is always enabled.
Section 3 1MRS757456 AREF611 standard configurations
82 REF611Application Manual
X100 SO1
X100 SO2
COMMON ALARM INDICATION 1 & 2
SELGAPC3OUT_3IN_5
OUT_4IN_9
TPGAPC1IN1 OUT1
TPGAPC3IN1 OUT1
OSWGAPC3
OR
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
OUT
PHLPTOC1_OPERATE
PHHPTOC1_OPERATE
PHHPTOC2_OPERATE
PHIPTOC1_OPERATE
EFLPTOC2_OPERATE
EFHPTOC1_OPERATE
EFIPOTC1_OPERATE
NSPTOC1_OPERATE
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
EFLPTOC1_OPETATE
OSWGAPC7
OR
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
OUT
PHLPTOC1_START
PHHPTOC1_START
PHHPTOC2_START
PHIPTOC1_START
EFLPTOC2_START
EFHPTOC1_START
EFIPOTC1_START
NSPTOC1_START
NSPTOC2_START
PDNSPTOC1_START
EFLPTOC1_START
GUID-A26141F0-6317-4DB1-BD64-BE704DF361AD V1 EN
Figure 65: Common alarm indication
The signal outputs from the IED are connected to give dedicated information on:
• Start of any protection function SO1 (X100:10-12)• Operation (trip) of any protection function SO2 (X100: 13-15)
TPGAPC are timers and used for setting the minimum pulse length for the outputs.There are seven generic timers (TPGAPC1…7) available in the IED.
3.6.4 Switch groupsIn the standard configuration B, the switch group function blocks are organized infour groups: binary inputs, internal signal, GOOSE as well as binary outputs andLEDs.
1MRS757456 A Section 3REF611 standard configurations
REF611 83Application Manual
GOOSE
Binary Inputs Protection and Control
GOOSE
GOOSE
GOOSE
Binary Inputs(1...4, 5...10*)
Received GOOSE(0...19)
* Optional Function
Binary Outputs and LEDs
OSWGAPC2
OSWGAPC1
OSWGAPC16
OSWGAPC15
OSWGAPC14
OSWGAPC13
OSWGAPC12
OSWGAPC11
SELGAPC4
LEDs
SELGAPC3
Binary Outputs
OSWGAPC10
OSWGAPC9
OSWGAPC8
OSWGAPC7
OSWGAPC6
OSWGAPC5
OSWGAPC4
OSWGAPC3
Binary Outputs(1...6, 7..9*)
LEDs(1…8)
PHLPTOC1 PHHPTOC1
PHHPTOC2 PHIPTOC1
EFLPTOC1 EFLPTOC2
EFHPTOC1
NSPTOC1
EFIPTOC1
NSPTOC2
PDNSPTOC1 T1PTTR1
INRPHAR1
CBXCBR1 DARREC1*
TCSSCBR1 TCSSCBR2
CCBRBRF1
Internal Signal
SELGAPC1
Binary Inputs
ISWGAPC2
ISWGAPC1
SELGAPC2
Blocking
TCS Blocking
ISWGAPC9
GOOSE Blocking
ISWGAPC10
GOOSE Block CB Alarm
Trip
Start
Master trip
ISWGAPC3
INRPHAR1_BLK2H
ISWGAPC4
DARREC1_PROT_CRD
GUID-76F84BA2-5219-46EA-9A19-4B9A2D229A7D V1 EN
Figure 66: Standard configuration B switch group overview
3.6.4.1 Binary inputs
Binary inputs group includes one SELGAPC and two ISWGAPCs. SELGAPC1 isused to route binary inputs to ISWGAPC or directly to IED functions. ISWGAPC1and ISWGAPC2 are used to configure the signal to block the protection functions.
SELGAPC1
ISWGAPC1Blocking 1
1) Optional binary inputs
PHLPTOC1_BLOCKPHHPTOC1_BLOCKPHHPTOC2_BLOCKPHIPTOC1_BLOCKEFLPTOC1_BLOCKEFLPTOC2_BLOCKEFHPTOC1_BLOCKEFIPTOC1_BLOCKNSPTOC1_BLOCKNSPTOC2_BLOCKPDNSPTOC1_BLOCKT1PTTR1_BLOCK
X120-BI1
X120-BI2
X120-BI3
X130-BI1
X130-BI2
X130-BI3
X130-BI4
X130-BI5
X130-BI6
1)
X120-BI4
ISWGAPC2Blocking 2
PHLPTOC1_BLOCKPHHPTOC1_BLOCKPHHPTOC2_BLOCKPHIPTOC1_BLOCKEFLPTOC1_BLOCKEFLPTOC2_BLOCKEFHPTOC1_BLOCKEFIPTOC1_BLOCKNSPTOC1_BLOCKNSPTOC2_BLOCKPDNSPTOC1_BLOCKT1PTTR1_BLOCK
GUID-ED968721-94B7-4280-A984-ADD75D5182BF V1 EN
Figure 67: Binary inputs
Section 3 1MRS757456 AREF611 standard configurations
84 REF611Application Manual
SELGAPC1SELGAPC1 has inputs from IED binary inputs. IN_1 to IN_4 are binary inputsfrom X100. IN_5 to IN_10 can be used while X130 optional card is taken into use.An always true signal is connected to IN_11. SELGAPC1 outputs are used to routeinputs to different functions. By setting SELGAPC1, binary inputs can beconfigured for different purposes.
SELGAPC1Blocking 1
CCBRBRF1_POSCLOSECBXCBR1_POSCLOSESELGAPC2_IN_1
CB Closed Position
CB Open PositionDARREC1_CB_POS CBXCBR1_POSOPENSELGAPC2_IN_2
TRPTTRC1/2_RST_LKOUT
CBXCBR1_ENA_CLOSECB Close Enable
DARREC1_CB_READY
External Trip
PROTECTION_BI_SG_3
Setting Group 2
PROTECTION_BI_SG_4
Setting Group 3
ISWGAPC2_IN
Setting Group 4
ISWGAPC1_INX120/1-2 BI1
X120/3-2 BI2
X120/4-2 BI3
X130/1-2 BI1
X130/3-2 BI2
X130/4-5 BI3
X130/6-5 BI4
X130/7-8 BI5
X130/9-8 BI6
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
1) Optional binary inputs
X120-BI1
X120-BI2
X120-BI3
X130-BI1
X130-BI2
X130-BI3
X130-BI4
X130-BI5
X130-BI6
1)
Always True
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
OUT_10
OUT_11
OUT_12
TRPTTRC1_RST_LKOUTTRPTTRC2_RST_LKOUT
DARREC1_RECL_ON
TRPTTRC1_OPERATETRPTTRC2_OPERATE
IN_11
X120/5-6 BI4X120-BI4
Blocking 2
PROTECTION_BI_SG_2
GUID-12D6969A-A486-41A3-853C-534194AD4FA9 V1 EN
Figure 68: SELGAPC1
ISWGAPC1ISWGAPC1 is used for general blocking. The ISWGAPC1 input is routed fromSELGAPC1 output OUT_1 Blocking 1. ISWGAPC1 outputs are connected toBLOCK inputs of protection functions. Select which protection functions are to beblocked by changing the ISWGAPC1 parameters.
1MRS757456 A Section 3REF611 standard configurations
REF611 85Application Manual
ISWGAPC1
IN
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
OUT_10
OUT_11
OUT_12
Blocking 1SELGAPC1_OUT_1
PHLPTOC1_BLOCK
PHHPTOC1_BLOCK
PHHPTOC2_BLOCK
PHIPTOC1_BLOCK
EFLPTOC1_BLOCK
EFLPTOC2_BLOCK
EFHPTOC1_BLOCK
EFIPTOC1_BLOCK
NSPTOC1_BLOCK
NSPTOC2_BLOCK
PDNSPTOC1_BLOCK
T1PTTR1_BLOCK
GUID-0D6CBA57-F1A5-4BBE-BF1F-34F79E876171 V1 EN
Figure 69: ISWGAPC1
ISWGAPC2ISWGAPC2 is used for general blocking. The ISWGAPC2 input is routed from theSELGAPC1 output OUT_12 Blocking 2. The ISWGAPC2 outputs are connectedto the BLOCK inputs of the protection functions. Select which protection functionsare to be blocked by changing the ISWGAPC2 parameters.
ISWGAPC2
IN
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
OUT_10
OUT_11
OUT_12
Blocking 2SELGAPC1_OUT_12
PHLPTOC1_BLOCK
PHHPTOC1_BLOCK
PHHPTOC2_BLOCK
PHIPTOC1_BLOCK
EFLPTOC1_BLOCK
EFLPTOC2_BLOCK
EFHPTOC1_BLOCK
EFIPTOC1_BLOCK
NSPTOC1_BLOCK
NSPTOC2_BLOCK
PDNSPTOC1_BLOCK
T1PTTR1_BLOCK
GUID-4E83752D-09FE-46D7-AA9F-82C9609C59E8 V1 EN
Figure 70: ISWGAPC2
Section 3 1MRS757456 AREF611 standard configurations
86 REF611Application Manual
3.6.4.2 Internal signal
The internal signal group is used to configure logic connections between functionblocks. There are two ISWGAPC instances and one SELGAPC in this group.
ISWGAPC3 is used to configure which protection function enables currentmultiplier if inrush is detected by the INRPHAR1 function. ISWGAPC4 is used toconfigure the cooperation between the autoreclose function and protectionfunctions. Autoreclose function DARREC1 can block protection functionsaccording to the application. SELGAPC2 is used to configure TCS blocking fromthe circuit breaker open or close position.
ISWGAPC3
PHLPTOC1_ENA_MULTPHHPTOC1_ENA_MULTPHHPTOC2_ENA_MULTPHIPTOC1_ENA_MULTEFLPTOC1_ENA_MULTEFLPTOC2_ENA_MULTEFHPTOC1_ENA_MULTEFIPTOC1_ENA_MULTNSPTOC1_ENA_MULTNSPTOC2_ENA_MULTT1PTTR1_ENA_MULT
ISWGAPC4
PHLPTOC1_BLOCKPHHPTOC1_BLOCKPHHPTOC2_BLOCKEFLPTOC1_BLOCKEFLPTOC2_BLOCKEFHPTOC1_BLOCK
SELGAPC2 TCSSCBR1_BLOCKTCSSCBR2_BLOCK
INRPHAR1_BLK2H
DARREC1_PROT_CRD
SELGAPC1_OUT_2
SELGAPC1_OUT_3
CB Closed Position
CB Open Position
GUID-4571B98B-EB9A-45A4-A4B4-6AC63C16D01C V1 EN
Figure 71: Internal signal
ISWGAPC3ISWGAPC3 input is routed from the INRPHAR1 output BLK2H. ISWGAPC3outputs are connected to the ENA_MULT signal of protection functions. Configurewhich protection function enables the current multiplier while inrush is detected byINRPHAR1 function, by changing ISWGAPC3 parameters.
1MRS757456 A Section 3REF611 standard configurations
REF611 87Application Manual
ISWGAPC3
IN
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
OUT_10
OUT_11
INRPHAR1_BLK2H
PHLPTOC1_ENA_MULT
PHHPTOC1_ENA_MULT
PHHPTOC2_ENA_MULT
PHIPTOC1_ENA_MULT
EFLPTOC1_ENA_MULT
EFLPTOC2_ENA_MULT
EFHPTOC1_ENA_MULT
EFIPTOC1_ENA_MULT
NSPTOC1_ENA_MULT
NSPTOC2_ENA_MULT
T1PTTR1_ENA_MULT
GUID-0FB9BAD2-E624-4310-A267-6E71E936A803 V1 EN
Figure 72: ISWGAPC3
ISWGAPC4The ISWGAPC4 input is routed from the DARREC1 output PROT_CRD.ISWGAPC4 outputs are connected to BLOCK inputs of some of the protectionfunctions. Configure which protection function is blocked by autoreclose bychanging the ISWGAPC4 parameters.
ISWGAPC4
IN
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
DARREC1_PROT_CRD
PHLPTOC1_BLOCK
PHHPTOC1_BLOCK
PHHPTOC2_BLOCK
EFLPTOC1_BLOCK
EFLPTOC2_BLOCK
EFHPTOC1_BLOCK
GUID-C935C34F-80CD-4A23-99BC-D997FC45B22F V1 EN
Figure 73: ISWGAPC4
SELGAPC2SELGAPC2 inputs are the circuit breaker closed and open positions routed fromSELGACP1. SELGAPC2 outputs are routed to the BLOCK input of the trip circuitsupervision functions TCSSCBR1 and TCSSCBR2.
By default, X100 PO3 and PO4 are both used for the open circuit breaker.TCSSCBR1 and TCSSCBR2 are both blocked by the circuit breaker open position.If X100-PO3 is used for closing the circuit breaker, TCSSCBR1 need to be blockedby the circuit breaker close position (OUT_1 connection=IN_1). If X100-PO4 is
Section 3 1MRS757456 AREF611 standard configurations
88 REF611Application Manual
used for closing the circuit breaker, TCSSCBR2 needs to be blocked by the circuitbreaker close position (OUT_2 connection=IN_1).
SELGAPC2IN_1
IN_2
OUT_1
OUT_2
TCSSCBR1_BLOCK
TCSSCBR2_BLOCK
SELGAPC1_OUT_2
SELGAPC1_OUT_3
CB Closed Position
CB Open Position
GUID-D390241C-1F0F-4AE7-A803-86931E1E0BEF V1 EN
Figure 74: SELGAPC2
3.6.4.3 Binary outputs and LEDs
In the standard configuration B, the signals route to binary outputs and LEDs areconfigured by OSWGAPCs. There are 16 OSWGAPC instances in total and theycan be categorized to four groups, including two Master trip, four start, four tripand six alarm signals. The OSWGAPC output is connected to binary outputs andLEDs via SELGAPC3 and SELGAPC4.
• SELGAPC3 is used to configure the OSWGAPC signals to IED binaryoutputs. SELGAPC4 is used to configure the OSWGAPC signals to LEDs.
• OSWGAPC1 and OSWGAPC2 are used for Master trip. The inputs are fromthe protection functions operate and breaker failures retrip.
• OSWGAPC3 to OSWGAPC6 are used for the start signal. The inputs are startsignals from the protection functions.
• OSWGAPC7 to OSWGAPC10 are used for the trip signal. The inputs areoperation signals from the protection functions.
• OSWGAPC11 to OSWGAPC16 are used for the alarm signal. The inputs arealarm signals from the protection and monitoring functions.
1MRS757456 A Section 3REF611 standard configurations
REF611 89Application Manual
Master Trip 1
OSWGAPC2 Master Trip 2
Trip 1
Trip 2
Trip 3
Trip 4
T1PTTR1_ALARMRDRE_TRIGGEREDTCSSCBR1_ALARMTCSSCBR2_ALARMCCBRBRF1_TRBUCCBRBRF1_TRRETDARREC1_INPRODARREC1_LOCKEDDARREC1_PROT_CRDDARREC1_UNSUC_RECLDARREC1_AR_ONDARREC1_READYSELGAPC1_OUT_8TRPPTRC1_CL_LKOUTTRPPTRC2_CL_LKOUT
OSWGAPC12 Alarm 2
OSWGAPC13 Alarm 3
OSWGAPC14 Alarm 4
OSWGAPC1
OSWGAPC3
OSWGAPC11 Alarm 1
TRPPTRC1
TRPPTRC2
TPGAPC3
TPGAPC4
TPGAPC5
TPGAPC6
SELGAPC3
PHLPTOC1_OPERATEPHHPTOC1_OPERATEPHHPTOC2_OPERATEPHIPTOC1_OPERATEEFLPTOC1_OPERATEEFLPTOC2_OPERATEEFHPTOC1_OPERATEEFIPTOC1_OPERATENSPTOC1_OPERATENSPTOC2_OPERATEPDNSPTOC1_OPERATET1PTTR1_OPERATECCBRBRF1_TRRET
PHLPTOC1_STARTPHHPTOC1_STARTPHHPTOC2_STARTPHIPTOC1_STARTEFLPTOC1_STARTEFLPTOC2_STARTEFHPTOC1_STARTEFIPTOC1_STARTNSPTOC1_STARTNSPTOC2_STARTPDNSPTOC1_STARTT1PTTR1_START
PHLPTOC1_OPERATEPHHPTOC1_OPERATEPHHPTOC2_OPERATEPHIPTOC1_OPERATEEFLPTOC1_OPERATEEFLPTOC2_OPERATEEFHPTOC1_OPERATEEFIPTOC1_OPERATENSPTOC1_OPERATENSPTOC2_OPERATEPDNSPTOC1_OPERATET1PTTR1_OPERATE
OSWGAPC8
OSWGAPC7
OSWGAPC10
OSWGAPC9
1)Optional binary outputs
X100 PO1
X100 PO2
X100 SO1
X100 SO2
X100 PO3
X100 PO4
X130 SO1
X130 SO2
X130 SO3
1)
Start 1
Start 2
TPGAPC1
OSWGAPC4
OSWGAPC5 Start 3
Start 4
TPGAPC2
OSWGAPC6
OSWGAPC15 Alarm 5
OSWGAPC16 Alarm 6
TPGAPC7
IN1 OUT1
IN2 OUT2
IN1 OUT1
IN2 OUT2
IN1 OUT1
IN2 OUT2
IN1 OUT1
IN2 OUT2
IN1 OUT1
IN2 OUT2
IN1 OUT1
IN2 OUT2
IN1 OUT1
IN2 OUT2
GUID-3F9B4020-ABC3-4C04-8260-C5900074AA6A V1 EN
Figure 75: Binary outputs
Section 3 1MRS757456 AREF611 standard configurations
90 REF611Application Manual
Master Trip 1
OSWGAPC2 Master Trip 2
Trip 1
Trip 2
Trip 3
Trip 4
OSWGAPC1
OSWGAPC3
OSWGAPC11 Alarm 1
TRPPTRC1
TRPPTRC2
SELGAPC4
OSWGAPC8
OSWGAPC7
OSWGAPC10
OSWGAPC9
Start 1
Start 2OSWGAPC4
OSWGAPC5 Start 3
Start 4OSWGAPC6
LED1
LED2
LED3
LED4
LED5
LED6
LED7
LED8
OSWGAPC12 Alarm 2
OSWGAPC13 Alarm 3
OSWGAPC14 Alarm 4
OSWGAPC15 Alarm 5
OSWGAPC16 Alarm 6
T1PTTR1_ALARMRDRE_TRIGGEREDTCSSCBR1_ALARMTCSSCBR2_ALARMCCBRBRF1_TRBUCCBRBRF1_TRRETDARREC1_INPRODARREC1_LOCKEDDARREC1_PROT_CRDDARREC1_UNSUC_RECLDARREC1_AR_ONDARREC1_READYSELGAPC1_OUT_8TRPPTRC1_CL_LKOUTTRPPTRC2_CL_LKOUT
PHLPTOC1_OPERATEPHHPTOC1_OPERATEPHHPTOC2_OPERATEPHIPTOC1_OPERATEEFLPTOC1_OPERATEEFLPTOC2_OPERATEEFHPTOC1_OPERATEEFIPTOC1_OPERATENSPTOC1_OPERATENSPTOC2_OPERATEPDNSPTOC1_OPERATET1PTTR1_OPERATE
PHLPTOC1_STARTPHHPTOC1_STARTPHHPTOC2_STARTPHIPTOC1_STARTEFLPTOC1_STARTEFLPTOC2_STARTEFHPTOC1_STARTEFIPTOC1_STARTNSPTOC1_STARTNSPTOC2_STARTPDNSPTOC1_STARTT1PTTR1_START
PHLPTOC1_OPERATEPHHPTOC1_OPERATEPHHPTOC2_OPERATEPHIPTOC1_OPERATEEFLPTOC1_OPERATEEFLPTOC2_OPERATEEFHPTOC1_OPERATEEFIPTOC1_OPERATENSPTOC1_OPERATENSPTOC2_OPERATEPDNSPTOC1_OPERATET1PTTR1_OPERATECCBRBRF1_TRRET
GUID-1938DEEA-E94A-4741-AB88-051B077CEFD7 V1 EN
Figure 76: LEDs
SELGAPC3SELGAPC3 is used to configure the OSWGAPC outputs to the IED binaryoutputs. Master trip signals are connected to SELGAPC3 via TRPPTRC. Start, tripand alarm signals are connected to SELGAPC3 via TPGAPC. TPGAPC are timersand used for setting the minimum pulse length for the outputs.
1MRS757456 A Section 3REF611 standard configurations
REF611 91Application Manual
SELGAPC3 outputs are connected with the X100 binary outputs. If the X130optional card is taken into use, SELGAPC3 outputs are also connected to the X130binary outputs.
SELGAPC3
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
IN_14
IN_15
IN_16
IN_17
IN_18
X100 PO1
X100 PO2
X100 SO1
X100 SO2
X100 PO3
X100 PO4
X130 SO1
X130 SO2
X130 SO3
1)
1)Optional binary outputs
OSWGAPC11_OUT
OSWGAPC12_OUT
OSWGAPC13_OUT
OSWGAPC14_OUT
OSWGAPC15_OUT
OSWGAPC16_OUT
OSWGAPC5_OUT
OSWGAPC6_OUT
OSWGAPC7_OUT
OSWGAPC8_OUT
OSWGAPC9_OUT
OSWGAPC10_OUT
OSWGAPC3_OUT
OSWGAPC4_OUT
Start 1
Start 2
Start 3
Start 4
Trip 1
Alarm 1
Trip 2
Trip 3
Trip 4
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Backup Trip
CBXCBR_EXE_OP DARREC_OPEN_CB TRPPTRC1_TRIP
TRPPTRC2_TRIP
CBXCBR_EXE_CL DARREC_CLOSE_CB
CCBRBRF1_TRBU
CB Open 1
CB Close
CB Open 2
TPGAPC1IN1 OUT1
IN2 OUT2
TPGAPC7IN1 OUT1
IN2 OUT2
TPGAPC6IN1 OUT1
IN2 OUT2
TPGAPC5IN1 OUT1
IN2 OUT2
TPGAPC4IN1 OUT1
IN2 OUT2
TPGAPC3IN1 OUT1
IN2 OUT2
TPGAPC2IN1 OUT1
IN2 OUT2
GUID-FF6B7926-5581-42ED-B604-4C05AB11C971 V1 EN
Figure 77: SELGAPC3
SELGAPC4SELGAPC4 is used to configure OSWGAPC outputs to LEDs. Master trip signalsare connected to SELGAPC4 via TRPPTRC. Start, trip and alarm signals areconnected to SELGAPC4 directly. SELGAPC4 outputs are connected withprogrammable LED1 to LED8.
Section 3 1MRS757456 AREF611 standard configurations
92 REF611Application Manual
SELGAPC4IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
IN_14
IN_15
IN_16
IN_17
IN_18
LED1
LED2
LED3
LED4
LED5
LED6
LED7
LED8
Start 1
Start 2
Start 3
Start 4
Trip 1
Alarm 1
Trip 2
Trip 3
Trip 4
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
OSWGAPC11_OUT
OSWGAPC12_OUT
OSWGAPC13_OUT
OSWGAPC14_OUT
OSWGAPC15_OUT
OSWGAPC16_OUT
OSWGAPC5_OUT
OSWGAPC6_OUT
OSWGAPC7_OUT
OSWGAPC8_OUT
OSWGAPC9_OUT
OSWGAPC10_OUT
OSWGAPC3_OUT
OSWGAPC4_OUT
CCBRBRF1_TRBU Backup Trip
CB Close
CB Open 1
CB Open 2
CBXCBR_EXE_OPDARREC_OPEN_CBTRPPTRC1_TRIP
TRPPTRC2_TRIP
CBXCBR_EXE_CLDARREC_CLOSE_CB
GUID-D815D8AC-340D-4FB8-A971-0CE6CDE5AD1F V1 EN
Figure 78: SELGAPC4
Master trip OSWGAPCsOSWGAPC1 and OSWGAPC2 are used to route the protection function operatesignals to Master trip. OSWGAPC1 and OSWGAPC2 have the same inputs fromthe protection function operates. The output is connected to the TRPPTRCfunction. The default connections for OSWGAPC1 and OSWGAPC2 are different.
1MRS757456 A Section 3REF611 standard configurations
REF611 93Application Manual
OSWGAPC1
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
EFLPTOC1_OPERATE
EFLPTOC2_OPERATE
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
T1PTTR1_OPERATE
PHLPTOC1_OPERATE
CCBRBRF1_TRRET
PHIPTOC1_OPERATE
EFHPTOC1_OPERATE
EFIPTOC1_OPERATE
NSPTOC1_OPERATE
PHHPTOC2_OPERATE
PHHPTOC1_OPERATE
TRPPTRC 1_OPERATEMaster trip 1
GUID-55CE95A2-E61E-4DA1-A888-F595AE088178 V1 EN
Figure 79: OSWGAPC1
OSWGAPC2
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
EFLPTOC1_OPERATE
EFLPTOC2_OPERATE
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
T1PTTR1_OPERATE
PHLPTOC1_OPERATE
CCBRBRF1_TRRET
PHIPTOC1_OPERATE
EFHPTOC1_OPERATE
EFIPTOC1_OPERATE
NSPTOC1_OPERATE
PHHPTOC2_OPERATE
PHHPTOC1_OPERATE
TRPPTRC 2_OPERATEMaster trip 2
GUID-239E2970-724D-47ED-9C11-8F00BB329EEB V1 EN
Figure 80: OSWGAPC2
Section 3 1MRS757456 AREF611 standard configurations
94 REF611Application Manual
Start OSWGAPCsOSWGAPC instances 3 to 6 are used to configure the protection start signals.These four OSWGAPCs have the same inputs from the protection function startsignals. The output is routed to SELGAPC3 via the TPGAPC timer and toSELGAPC4 directly.
TPGAPC1_IN1SELGAPC4_IN_5
Start 1
OSWGAPC3
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
OUT
EFLPTOC1_START
EFLPTOC2_START
NSPTOC2_START
PDNSPTOC1_START
T1PTTR1_START
PHLPTOC1_START
PHIPTOC1_START
EFHPTOC1_START
EFIPTOC1_START
NSPTOC1_START
PHHPTOC2_START
PHHPTOC1_START
GUID-37ADCAC6-7D63-4AC8-8CAA-B6D4573123FE V1 EN
Figure 81: OSWGAPC3
1MRS757456 A Section 3REF611 standard configurations
REF611 95Application Manual
TPGAPC1_IN2SELGAPC4_IN_6
Start 2
OSWGAPC4
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
OUT
EFLPTOC1_START
EFLPTOC2_START
NSPTOC2_START
PDNSPTOC1_START
T1PTTR1_START
PHLPTOC1_START
PHIPTOC1_START
EFHPTOC1_START
EFIPTOC1_START
NSPTOC1_START
PHHPTOC2_START
PHHPTOC1_START
GUID-C6DF86BC-DDC4-4680-94F1-667864F9570C V1 EN
Figure 82: OSWGAPC4
TPGAPC2_IN1SELGAPC4_IN_7
Start 3
OSWGAPC5
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
OUT
EFLPTOC1_START
EFLPTOC2_START
NSPTOC2_START
PDNSPTOC1_START
T1PTTR1_START
PHLPTOC1_START
PHIPTOC1_START
EFHPTOC1_START
EFIPTOC1_START
NSPTOC1_START
PHHPTOC2_START
PHHPTOC1_START
GUID-DC9B1877-7BC1-45C6-8E61-85750AE9B22D V1 EN
Figure 83: OSWGAPC5
Section 3 1MRS757456 AREF611 standard configurations
96 REF611Application Manual
TPGAPC2_IN2SELGAPC4_IN_8
Start 4
OSWGAPC6
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
OUT
EFLPTOC1_START
EFLPTOC2_START
NSPTOC2_START
PDNSPTOC1_START
T1PTTR1_START
PHLPTOC1_START
PHIPTOC1_START
EFHPTOC1_START
EFIPTOC1_START
NSPTOC1_START
PHHPTOC2_START
PHHPTOC1_START
GUID-EBDD8FE5-50C7-4097-A48D-E5314E4F968C V1 EN
Figure 84: OSWGAPC6
Trip OSWGAPCsOSWGAPC instances 7 to 10 are used to configure the protection operate signalswhich belong to the trip group. These four OSWGAPCs have the same inputs fromthe operate signals of the protection functions. The output is routed to SELGAPC3via the TPGAPC timer and to SELGAPC4 directly.
1MRS757456 A Section 3REF611 standard configurations
REF611 97Application Manual
TPGAPC3_IN1SELGAPC4_IN_9
Trip 1
OSWGAPC7
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
OUT
EFLPTOC1_OPERATE
EFLPTOC2_OPERATE
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
T1PTTR1_OPERATE
PHLPTOC1_OPERATE
PHIPTOC1_OPERATE
EFHPTOC1_OPERATE
EFIPTOC1_OPERATE
NSPTOC1_OPERATE
PHHPTOC2_OPERATE
PHHPTOC1_OPERATE
GUID-1DCBC895-AD32-4C02-983B-AB81D46FC2DE V1 EN
Figure 85: OSWGAPC7
TPGAPC3_IN2SELGAPC4_IN_10
Trip 2
OSWGAPC8
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
OUT
EFLPTOC1_OPERATE
EFLPTOC2_OPERATE
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
T1PTTR1_OPERATE
PHLPTOC1_OPERATE
PHIPTOC1_OPERATE
EFHPTOC1_OPERATE
EFIPTOC1_OPERATE
NSPTOC1_OPERATE
PHHPTOC2_OPERATE
PHHPTOC1_OPERATE
GUID-122AD794-D4C7-4E43-B8AE-0786F41437FF V1 EN
Figure 86: OSWGAPC8
Section 3 1MRS757456 AREF611 standard configurations
98 REF611Application Manual
TPGAPC4_IN1SELGAPC4_IN_11
Trip 3
OSWGAPC9
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
OUT
EFLPTOC1_OPERATE
EFLPTOC2_OPERATE
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
T1PTTR1_OPERATE
PHLPTOC1_OPERATE
PHIPTOC1_OPERATE
EFHPTOC1_OPERATE
EFIPTOC1_OPERATE
NSPTOC1_OPERATE
PHHPTOC2_OPERATE
PHHPTOC1_OPERATE
GUID-93D4C888-0438-4009-97DC-CDF241694E4D V1 EN
Figure 87: OSWGAPC9
TPGAPC4_IN2SELGAPC4_IN_12
Trip 4
OSWGAPC10
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
OUT
EFLPTOC1_OPERATE
EFLPTOC2_OPERATE
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
T1PTTR1_OPERATE
PHLPTOC1_OPERATE
PHIPTOC1_OPERATE
EFHPTOC1_OPERATE
EFIPTOC1_OPERATE
NSPTOC1_OPERATE
PHHPTOC2_OPERATE
PHHPTOC1_OPERATE
GUID-A4DED42E-2140-4D06-83E6-A23979821AB2 V1 EN
Figure 88: OSWGAPC10
1MRS757456 A Section 3REF611 standard configurations
REF611 99Application Manual
Alarm OSWGAPCsOSWGAPC instances 11 to 16 are used to configure the alarm signals whichbelong to the alarm group. These six OSWGAPCs have the same inputs from thealarm signals. The output is routed to SELGAPC3 via TPGAPC timer and toSELGAPC4 directly.
OSWGAPC11
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
IN_14
IN_15
CCBRBRF1_TRBU
CCBRBRF1_TRRET
DARREC1_UNSUC_RECL
DARREC1_AR_ON
DARREC1_READY
T1PTTR1_ALARM
SELGAPC1_OUT_8
TCSSCBR2_ALARM
DARREC1_INPRO
DARREC1_LOCKED
DARREC1_PROT_CRD
TCSSCBR1_ALARM
RDRE_TRIGGERED
TRPPTRC1_CL_LKOUT
TRPPTRC2_CL_LKOUT
Alarm 1 TPGAPC5_IN1SELGAPC4_IN_13
External Trip
GUID-8A337ED0-85C0-404C-BE93-C8F77FDB2928 V1 EN
Figure 89: OSWGAPC11
Section 3 1MRS757456 AREF611 standard configurations
100 REF611Application Manual
OSWGAPC12
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
IN_14
IN_15
CCBRBRF1_TRBU
CCBRBRF1_TRRET
DARREC1_UNSUC_RECL
DARREC1_AR_ON
DARREC1_READY
T1PTTR1_ALARM
SELGAPC1_OUT_8
TCSSCBR2_ALARM
DARREC1_INPRO
DARREC1_LOCKED
DARREC1_PROT_CRD
TCSSCBR1_ALARM
RDRE_TRIGGERED
TRPPTRC1_CL_LKOUT
TRPPTRC2_CL_LKOUT
Alarm 2 TPGAPC5_IN2SELGAPC4_IN_14
External Trip
GUID-B43B138E-F672-41BF-B9DA-AAD80C516D14 V1 EN
Figure 90: OSWGAPC12
1MRS757456 A Section 3REF611 standard configurations
REF611 101Application Manual
OSWGAPC13
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
IN_14
IN_15
CCBRBRF1_TRBU
CCBRBRF1_TRRET
DARREC1_UNSUC_RECL
DARREC1_AR_ON
DARREC1_READY
T1PTTR1_ALARM
SELGAPC1_OUT_8
TCSSCBR2_ALARM
DARREC1_INPRO
DARREC1_LOCKED
DARREC1_PROT_CRD
TCSSCBR1_ALARM
RDRE_TRIGGERED
TRPPTRC1_CL_LKOUT
TRPPTRC2_CL_LKOUT
Alarm 3 TPGAPC6_IN1SELGAPC4_IN_15
External Trip
GUID-CE98DECE-330C-45E7-B834-0906072EE83B V1 EN
Figure 91: OSWGAPC13
Section 3 1MRS757456 AREF611 standard configurations
102 REF611Application Manual
OSWGAPC14
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
IN_14
IN_15
CCBRBRF1_TRBU
CCBRBRF1_TRRET
DARREC1_UNSUC_RECL
DARREC1_AR_ON
DARREC1_READY
T1PTTR1_ALARM
SELGAPC1_OUT_8
TCSSCBR2_ALARM
DARREC1_INPRO
DARREC1_LOCKED
DARREC1_PROT_CRD
TCSSCBR1_ALARM
RDRE_TRIGGERED
TRPPTRC1_CL_LKOUT
TRPPTRC2_CL_LKOUT
Alarm 4 TPGAPC6_IN2SELGAPC4_IN_16
External Trip
GUID-E92BEBCD-0151-41E9-BBAD-BADC4B774605 V1 EN
Figure 92: OSWGAPC14
1MRS757456 A Section 3REF611 standard configurations
REF611 103Application Manual
OSWGAPC15
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
IN_14
IN_15
CCBRBRF1_TRBU
CCBRBRF1_TRRET
DARREC1_UNSUC_RECL
DARREC1_AR_ON
DARREC1_READY
T1PTTR1_ALARM
SELGAPC1_OUT_8
TCSSCBR2_ALARM
DARREC1_INPRO
DARREC1_LOCKED
DARREC1_PROT_CRD
TCSSCBR1_ALARM
RDRE_TRIGGERED
TRPPTRC1_CL_LKOUT
TRPPTRC2_CL_LKOUT
Alarm 5 TPGAPC7_IN1SELGAPC4_IN_17
External Trip
GUID-258C10A2-665D-4BFA-8D20-059586803C6C V1 EN
Figure 93: OSWGAPC15
Section 3 1MRS757456 AREF611 standard configurations
104 REF611Application Manual
OSWGAPC16
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
IN_14
IN_15
CCBRBRF1_TRBU
CCBRBRF1_TRRET
DARREC1_UNSUC_RECL
DARREC1_AR_ON
DARREC1_READY
T1PTTR1_ALARM
SELGAPC1_OUT_8
TCSSCBR2_ALARM
DARREC1_INPRO
DARREC1_LOCKED
DARREC1_PROT_CRD
TCSSCBR1_ALARM
RDRE_TRIGGERED
TRPPTRC1_CL_LKOUT
TRPPTRC2_CL_LKOUT
Alarm 6 TPGAPC7_IN2SELGAPC4_IN_18
External Trip
GUID-7CFDD919-7415-4AFC-B970-84688BEFD70A V1 EN
Figure 94: OSWGAPC16
3.6.4.4 GOOSE
In the configuration, there are twenty GOOSERCV_BIN functions. EachGOOSERVC_BIN function can be connected to one received binary GOOSEsignal. The signal connection can be configured in PCM600.
GOOSERCV_BIN instances 0 and 1 are used for blocking the protection functions.Signals from these two GOOSERCV_BINs are connected to ISWGAPC9.ISWGAPC9 is used to configure which protection function is blocked.
GOOSERCV_BIN instances 2 and 3 are used for tripping from GOOSE. Signalsfrom these two GOOSERCV_BINs are connected to TRPPTRC1 and TRPPTRC2trip.
GOOSERCV_BIN instances 4 to 19 are used for blocking the circuit breakeroperation. Signals from these 16 GOOSERCV_BINs are connected toISWGAPC10. ISWGAPC10 is used to configure GOOSE input signal to block thecircuit breaker open or close operation.
1MRS757456 A Section 3REF611 standard configurations
REF611 105Application Manual
CBXCBR1_BLK_CLOSECBXCBR1_BLK_OPEN
GOOSERCV_BIN:1
GOOSERCV_BIN:0
OR ISWGAPC9GOOSE Blcoking
GOOSERCV_BIN:3
GOOSERCV_BIN:2
ORGOOSEExternal Trip
GOOSERCV_BIN:5
GOOSERCV_BIN:4
GOOSERCV_BIN:19
OR ISWGAPC10GOOSE Block CB
PHLPTOC1_BLOCKPHHPTOC1_BLOCKPHHPTOC2_BLOCKPHIPTOC1_BLOCKEFLPTOC1_BLOCKEFLPTOC2_BLOCKEFHPTOC1_BLOCKEFIPTOC1_BLOCKNSPTOC1_BLOCKNSPTOC2_BLOCKPDNSPTOC1_BLOCKT1PTTR1_BLOCK
TRPPTRC1_OPERATETRPPTRC2_OPERATE
GUID-344C14FB-6F56-4A40-ADA5-639B82C77501 V1 EN
Figure 95: GOOSE overview
ISWGAPC9ISWGAPC9 is used to configure which protection functions can be blocked by thereceived GOOSE signals. ISWGAPC9 inputs are received GOOSE signals fromGOOSERCV_BIN:0 and GOOSERCV_BIN:1. The outputs are connected to blockinputs of the protection functions.
Section 3 1MRS757456 AREF611 standard configurations
106 REF611Application Manual
GOOSERCV_BIN:0_OUTGOOSERCV_BIN:1_OUT
ISWGAPC9
IN
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
OUT_10
OUT_11
OUT_12
PHLPTOC1_BLOCK
PHHPTOC1_BLOCK
PHHPTOC2_BLOCK
PHIPTOC1_BLOCK
EFLPTOC1_BLOCK
EFLPTOC2_BLOCK
EFHPTOC2_BLOCK
EFIPTOC1_BLOCK
NSPTOC1_BLOCK
NSPTOC1_BLOCK
PDNSPTOC1_BLOCK
T1PTTR1_BLOCK
GOOSE Blocking
GUID-12868AC3-B5C0-4AA9-B0C7-4E89BD5BAFE1 V1 EN
Figure 96: ISWGAPC9
ISWGAPC10ISWGAPC10 is used to block the circuit breaker operation from the receivedGOOSE signals. ISWGAPC10 inputs are received GOOSE signals fromGOOSERCV_BIN:4 to GOOSERCV_BIN:19. The outputs are connected to blockthe circuit breaker close and open operation.
ISWGAPC10
INOUT_1
OUT_2
CBXCBR1_BLK_CLOSE
CBXCBR1_BLK_OPEN
GOOSERCV_BIN:4_OUTGOOSERCV_BIN:5_OUTGOOSERCV_BIN:6_OUT...GOOSERCV_BIN:19_OUT
GOOSE Block CB
GUID-C0024745-DFB7-4849-9F43-44159D9736B9 V1 EN
Figure 97: ISWGAPC10
1MRS757456 A Section 3REF611 standard configurations
REF611 107Application Manual
108
Section 4 Requirements for measurementtransformers
4.1 Current transformers
4.1.1 Current transformer requirements for non-directionalovercurrent protectionFor reliable and correct operation of the overcurrent protection, the CT has to bechosen carefully. The distortion of the secondary current of a saturated CT mayendanger the operation, selectivity, and co-ordination of protection. However,when the CT is correctly selected, a fast and reliable short circuit protection can beenabled.
The selection of a CT depends not only on the CT specifications but also on thenetwork fault current magnitude, desired protection objectives, and the actual CTburden. The protection settings of the IED should be defined in accordance withthe CT performance as well as other factors.
4.1.1.1 Current transformer accuracy class and accuracy limit factor
The rated accuracy limit factor (Fn) is the ratio of the rated accuracy limit primarycurrent to the rated primary current. For example, a protective current transformerof type 5P10 has the accuracy class 5P and the accuracy limit factor 10. Forprotective current transformers, the accuracy class is designed by the highestpermissible percentage composite error at the rated accuracy limit primary currentprescribed for the accuracy class concerned, followed by the letter "P" (meaningprotection).
Table 20: Limits of errors according to IEC 60044-1 for protective current transformers
Accuracy class Current error atrated primarycurrent (%)
Phase displacement at rated primarycurrent
Composite error atrated accuracy limitprimary current (%)minutes centiradians
5P ±1 ±60 ±1.8 5
10P ±3 - - 10
The accuracy classes 5P and 10P are both suitable for non-directional overcurrentprotection. The 5P class provides a better accuracy. This should be noted also ifthere are accuracy requirements for the metering functions (current metering,power metering, and so on) of the IED.
1MRS757456 A Section 4Requirements for measurement transformers
REF611 109Application Manual
The CT accuracy primary limit current describes the highest fault currentmagnitude at which the CT fulfils the specified accuracy. Beyond this level, thesecondary current of the CT is distorted and it might have severe effects on theperformance of the protection IED.
In practise, the actual accuracy limit factor (Fa) differs from the rated accuracylimit factor (Fn) and is proportional to the ratio of the rated CT burden and theactual CT burden.
The actual accuracy limit factor is calculated using the formula:
F FS S
S Sa n
in n
in
≈ ×
+
+
A071141 V1 EN
Fn the accuracy limit factor with the nominal external burden Sn
Sin the internal secondary burden of the CT
S the actual external burden
4.1.1.2 Non-directional overcurrent protection
The current transformer selectionNon-directional overcurrent protection does not set high requirements on theaccuracy class or on the actual accuracy limit factor (Fa) of the CTs. It is, however,recommended to select a CT with Fa of at least 20.
The nominal primary current I1n should be chosen in such a way that the thermaland dynamic strength of the current measuring input of the IED is not exceeded.This is always fulfilled when
I1n > Ikmax / 100,
Ikmax is the highest fault current.
The saturation of the CT protects the measuring circuit and the current input of theIED. For that reason, in practice, even a few times smaller nominal primary currentcan be used than given by the formula.
Recommended start current settingsIf Ikmin is the lowest primary current at which the highest set overcurrent stage is tooperate, the start current should be set using the formula:
Current start value < 0.7 x (Ikmin / I1n)
I1n is the nominal primary current of the CT.
Section 4 1MRS757456 ARequirements for measurement transformers
110 REF611Application Manual
The factor 0.7 takes into account the protection IED inaccuracy, currenttransformer errors, and imperfections of the short circuit calculations.
The adequate performance of the CT should be checked when the setting of thehigh set stage overcurrent protection is defined. The operate time delay caused bythe CT saturation is typically small enough when the overcurrent setting isnoticeably lower than Fa.
When defining the setting values for the low set stages, the saturation of the CTdoes not need to be taken into account and the start current setting is simplyaccording to the formula.
Delay in operation caused by saturation of current transformersThe saturation of CT may cause a delayed IED operation. To ensure the timeselectivity, the delay must be taken into account when setting the operate times ofsuccessive IEDs.
With definite time mode of operation, the saturation of CT may cause a delay thatis as long as the time the constant of the DC component of the fault current, whenthe current is only slightly higher than the starting current. This depends on theaccuracy limit factor of the CT, on the remanence flux of the core of the CT, andon the operate time setting.
With inverse time mode of operation, the delay should always be considered asbeing as long as the time constant of the DC component.
With inverse time mode of operation and when the high-set stages are not used, theAC component of the fault current should not saturate the CT less than 20 times thestarting current. Otherwise, the inverse operation time can be further prolonged.Therefore, the accuracy limit factor Fa should be chosen using the formula:
Fa > 20*Current start value / I1n
The Current start value is the primary pickup current setting of the IED.
4.1.1.3 Example for non-directional overcurrent protection
The following figure describes a typical medium voltage feeder. The protection isimplemented as three-stage definite time non-directional overcurrent protection.
1MRS757456 A Section 4Requirements for measurement transformers
REF611 111Application Manual
A071142 V1 EN
Figure 98: Example of three-stage overcurrent protection
The maximum three-phase fault current is 41.7 kA and the minimum three-phaseshort circuit current is 22.8 kA. The actual accuracy limit factor of the CT iscalculated to be 59.
The start current setting for low-set stage (3I>) is selected to be about twice thenominal current of the cable. The operate time is selected so that it is selective withthe next IED (not visible in the figure above). The settings for the high-set stageand instantaneous stage are defined also so that grading is ensured with thedownstream protection. In addition, the start current settings have to be defined sothat the IED operates with the minimum fault current and it does not operate withthe maximum load current. The settings for all three stages are as in the figure above.
For the application point of view, the suitable setting for instantaneous stage (I>>>)in this example is 3 500 A (5.83 x I2n). For the CT characteristics point of view, thecriteria given by the current transformer selection formula is fulfilled and also theIED setting is considerably below the Fa. In this application, the CT rated burdencould have been selected much lower than 10 VA for economical reasons.
Section 4 1MRS757456 ARequirements for measurement transformers
112 REF611Application Manual
Section 5 IED physical connections
5.1 Inputs
5.1.1 Energizing inputs
5.1.1.1 Phase currents
The IED can also be used in single or two-phase applications byleaving one or two energizing inputs unoccupied. However, at leastterminals X120/7-8 must be connected.
Table 21: Phase current inputs included in configurations A and B
Terminal DescriptionX120-7, 8 IL1
X120-9, 10 IL2
X120-11, 12 IL3
5.1.1.2 Residual current
Table 22: Residual current input included in configurations A and B
Terminal DescriptionX120-13, 14 Io
5.1.1.3 Residual voltage
Table 23: Additional residual voltage input included in configuration A
Terminal DescriptionX120-5, 6 Uo
5.1.2 Auxiliary supply voltage inputThe auxiliary voltage of the IED is connected to terminals X100/1-2. At DCsupply, the positive lead is connected to terminal X100-1. The permitted auxiliaryvoltage range (AC/DC or DC) is marked on the top of the LHMI of the IED.
1MRS757456 A Section 5IED physical connections
REF611 113Application Manual
Table 24: Auxiliary voltage supply
Terminal DescriptionX100-1 + Input
X100-2 - Input
5.1.3 Binary inputsThe binary inputs can be used, for example, to generate a blocking signal, tounlatch output contacts, to trigger the disturbance recorder or for remote control ofIED settings.
Terminals X120/1-4 are binary input terminals. In the IED variant B, there areadditional binary inputs X120/5-6 included. Optional BIO-module BIO0006 forslot X130 can be included at the time of order.
Binary inputs of slot X120 are available with configurations A and B.
Table 25: Binary input terminals X120-1...6
Terminal DescriptionX120-1 BI1, +
X120-2 BI1, -
X120-3 BI2, +
X120-2 BI2, -
X120-4 BI3, +
X120-2 BI3, -
X120-5 BI4, +
X120-6 BI4, -
Binary inputs of slot X130 are optional for configurations A and B.
Table 26: Binary input terminals X130-1...9
Terminal DescriptionX130-1 BI1, +
X130-2 BI1, -
X130-2 BI2, -
X130-3 BI2, +
X130-4 BI3, +
X130-5 BI3, -
X130-5 BI4, -
X130-6 BI4, +
X130-7 BI5, +
Table continues on next page
Section 5 1MRS757456 AIED physical connections
114 REF611Application Manual
Terminal DescriptionX130-8 BI5, -
X130-8 BI6, -
X130-9 BI6, +
5.2 Outputs
5.2.1 Outputs for tripping and controllingOutput contacts PO1, PO2, PO3 and PO4 are heavy-duty trip contacts capable ofcontrolling most circuit breakers. On delivery from the factory, the trip signalsfrom all the protection stages are routed to PO3 and PO4.
Table 27: Output contacts
Terminal DescriptionX100-6 PO1, NO
X100-7 PO1, NO
X100-8 PO2, NO
X100-9 PO2, NO
X100-15 PO3, NO (TCS resistor)
X100-16 PO3, NO
X100-17 PO3, NO
X100-18 PO3 (TCS1 input), NO
X100-19 PO3 (TCS1 input), NO
X100-20 PO4, NO (TCS resistor)
X100-21 PO4, NO
X100-22 PO4, NO
X100-23 PO4 (TCS2 input), NO
X100-24 PO4 (TCS2 input), NO
5.2.2 Outputs for signallingOutput contacts SO1 and SO2 in slot X100 or SO1, SO2 and SO3 in slot X130(optional) can be used for signalling on start and tripping of the IED. On deliveryfrom the factory, the start and alarm signals from all the protection stages arerouted to signalling outputs.
1MRS757456 A Section 5IED physical connections
REF611 115Application Manual
Table 28: Output contacts X100-10...14
Terminal DescriptionX100-10 SO1, common
X100-11 SO1, NC
X100-12 SO1, NO
X100-13 SO2, NO
X100-14 SO2, NO
Output contacts of slot X130 are available in the optional BIO module (BIO0006).
Output contacts of slot X130 are optional for configurations A and B.
Table 29: Output contacts X130-10...18
Terminal DescriptionX130-10 SO1, common
X130-11 SO1, NO
X130-12 SO1, NC
X130-13 SO2, common
X130-14 SO2, NO
X130-15 SO2, NC
X130-16 SO3, common
X130-17 SO3, NO
X130-18 SO3, NC
5.2.3 IRFThe IRF contact functions as an output contact for the self-supervision system ofthe protection IED. Under normal operating conditions, the IED is energized andthe contact is closed (X100/3-5). When a fault is detected by the self-supervisionsystem or the auxiliary voltage is disconnected, the output contact drops off and thecontact closes (X100/3-4).
Table 30: IRF contact
Terminal DescriptionX100-3 IRF, common
X100-4 Closed; IRF, or Uaux disconnected
X100-5 Closed; no IRF, and Uaux connected
Section 5 1MRS757456 AIED physical connections
116 REF611Application Manual
Section 6 Glossary
ANSI American National Standards InstituteCT Current transformerEMC Electromagnetic compatibilityGOOSE Generic Object-Oriented Substation EventHMI Human-machine interfaceIEC International Electrotechnical CommissionIEC 61850 International standard for substation communication and
modelingIED Intelligent electronic deviceIP address A set of four numbers between 0 and 255, separated by
periods. Each server connected to the Internet is assigned aunique IP address that specifies the location for the TCP/IPprotocol.
LAN Local area networkLC Connector type for glass fibre cableLCD Liquid crystal displayLED Light-emitting diodeLHMI Local human-machine interfaceModbus A serial communication protocol developed by the Modicon
company in 1979. Originally used for communication in PLCsand RTU devices.
PCM600 Protection and Control IED ManagerRJ-45 Galvanic connector typeWAN Wide area networkWHMI Web human-machine interface
1MRS757456 A Section 6Glossary
REF611 117Application Manual
118
119
Contact us
ABB OyDistribution AutomationP.O. Box 699FI-65101 VAASA, FinlandPhone +358 10 22 11Fax +358 10 22 41094
www.abb.com/substationautomation
1MR
S75
7456
A©
Cop
yrig
ht 2
011
AB
B. A
ll rig
hts
rese
rved
.