  • 7/29/2019 Reducing the Gw Pimp Act on Commercial Refrigeration

    1/16

    Reducing the GWP Impact On

    Commercial RefrigerationL. Abbas, B. Boussand,W. Rached, B. Van Horn

    Chillventa 2012, Forum 10Nuremberg, GermanyOctober 10th, 2012

  • 7/29/2019 Reducing the Gw Pimp Act on Commercial Refrigeration

    2/16

    2

    Commercial Refrigeration Status

    R-404A is the most popular HFC refrigerant used in refrigeration

    Over 90% of HFC usage in supermarket refrigeration in Europe

    Main applications are : Supermarket refrigeration : cold storage, food cases

    Transportation : refrigerated trucks, containers

    Small commercial refrigeration

    Regulatory pressure

    It is likely that Higher GWP compounds such as R-404A will be among the firsttargeted by the future revision of the F-gas regulation

  • 7/29/2019 Reducing the Gw Pimp Act on Commercial Refrigeration

    3/16

    3

    Progression towards the 4th generation

    Montreal ProtocolODP issue

    Kyoto ProtocolGWP issue

    1st generation 2nd generation 3rd generation 4th generation

    CFC-11

    CFC-12

    HCFC-22

    HCFC-123

    HCFC-141b

    HCFC-142b

    R-507A

    R-404A

    R-422A

    . . .

    Lower GWPOptions

  • 7/29/2019 Reducing the Gw Pimp Act on Commercial Refrigeration

    4/16

    4

    Commercial R-404A substitutes with reduced GWP

    -46.3-45.3-46.5

    Bubble point

    @ 1 Atm (C)

    53%46%-GWP reduction

    vs R-404A (%) *

    -39.9-38.9-45.8Dew Point

    @ 1 Atm (C)

    Toxicity

    (ISO-817)

    Flammability

    (ISO-817)

    Class AClass AClass A

    Class 1Class 1Class 1

    R-407F

    Forane 407A

    (R-407A)R-404A

    * GWP value for 100-year time horizons according to IPCC 2007 Fourth Assessment Report

    Side-by-side comparison of commercial retrofit options with reduced GWP

  • 7/29/2019 Reducing the Gw Pimp Act on Commercial Refrigeration

    5/16

    5

    Experimental Evaluation of R-404A substitutes

    Drop-in tests

    R-404A, 4.4kW, Walk-in Freezer with matching evaporator

    Scroll Compressor Additional cooling available (liquid injection)

    2 system configurations

    Medium Temp Thermostatic Expansion Valve for indoor box temperature at -4C and-18C

    Low Temp Thermostatic Expansion Valve for indoor box temperature at -18C and -32C

    2 Outdoor Box Temperatures : 32C and 43C

  • 7/29/2019 Reducing the Gw Pimp Act on Commercial Refrigeration

    6/16

    6

    Experimental Set-up

  • 7/29/2019 Reducing the Gw Pimp Act on Commercial Refrigeration

    7/16

    7

    Medium Temperature refrigeration (-4C)

    60

    65

    70

    75

    80

    85

    90

    95100

    105

    110

    %v

    sR-404A

    R-404A R-407A R-407F

    Efficiency

    C

    apacity

    Efficiency

    C

    apacity

    Outdoor box : 43C

    60

    65

    70

    75

    8085

    90

    95

    100

    105

    110

    %vsR-404A

    R-404A R-407A R-407F

    Efficienc

    y

    Capacity

    Efficienc

    y

    Capacity

    Outdoor box : 32C

    2%

    Up to 3% increase in Efficiency demonstrated with R-407A

  • 7/29/2019 Reducing the Gw Pimp Act on Commercial Refrigeration

    8/16

    8

    100%102%Vapor refrigerant velocity

    68%73%Mass Flow

    4.75 turns5 turnsTXV adjustment

    Discharge Temperature*

    Suction Pressure

    +6C+6C

    -0.5 bar-0.6 bar

    R-407FR-407A

    Properties vs R-404A

    Outdoor box : 32C

    * With liquid injection running

    Medium Temperature refrigeration (-4C)

  • 7/29/2019 Reducing the Gw Pimp Act on Commercial Refrigeration

    9/16

    9

    60

    65

    70

    75

    80

    85

    90

    95100

    105

    110

    %v

    sR-404A

    R-404A R-407A R-407F

    E

    fficiency

    Capacity

    E

    fficiency

    Capacity

    60

    65

    70

    75

    8085

    90

    95

    100

    105

    110

    %v

    sR-404A

    R-404A R-407A R-407F

    Efficienc

    y

    Capacity

    Efficienc

    y

    Capacity

    Outdoor box : 32C

    Outdoor box : 43C

    Low Temperature refrigeration (-32C)

    R-407A is an efficient substitute to R-404A, even under extreme conditions

  • 7/29/2019 Reducing the Gw Pimp Act on Commercial Refrigeration

    10/16

    10

    91%97%Vapor refrigerant velocity

    61%68%Mass Flow

    1 turn1.25 turnsTXV adjustment

    Discharge Temperature*

    Suction Pressure

    +1C+1C

    -0.3 bar-0.3 bar

    R-407FR-407A

    Properties vs R-404A

    Outdoor box : 43C

    * With liquid injection running

    Low Temperature refrigeration (-32C)

  • 7/29/2019 Reducing the Gw Pimp Act on Commercial Refrigeration

    11/16

    11

    -4

    -18

    -32

    -4

    -18

    -32

    0

    10

    20

    30

    40

    R-407F

    R-407A

    Indoor Temperatures:-4, -18 and -32C

    Outdoor Temperatures:32, 43C

    No liquid injection

    Outdoor Temp= 32C

    Outdoor Temp= 43C

    Increase in DischargeTemp vs R-404 (C)

    Compressor Stopped:Above safety limits of compressor

    R-407A has a lower discharge

    Temperature

    Discharge Temperature Management

    R-407A has a wider range of operating conditions without liquid injection

  • 7/29/2019 Reducing the Gw Pimp Act on Commercial Refrigeration

    12/16

    12

    -4

    -18

    -32

    -4

    -18

    -32

    0

    10

    20

    30

    40

    R-407A liq

    R-407A

    Outdoor Temp= 32C

    Outdoor Temp= 43C

    Increase in DischargeTemp vs R-404 (C)

    With additional cooling,R-407A can be used in

    scroll systems, even atextreme conditions

    Discharge Temperature Management

  • 7/29/2019 Reducing the Gw Pimp Act on Commercial Refrigeration

    13/16

    13

    Reduced Carbon Footprint

    High Energy Savings

    * Outdoor 43C, Indoor -4C

    Potential Emission Reduction

    +3%

    -5%

    -6

    -4

    -2

    0

    2

    4

    RelativeCOP

    vsR-404A

    R-404A R-407A R-407F

    0

    0.2

    0.4

    0.6

    0.8

    1

    Relativevalueofdirect

    CO2emiss

    ion

    R-404A R-407A

  • 7/29/2019 Reducing the Gw Pimp Act on Commercial Refrigeration

    14/16

    14

    Forane 407A

    Performance

    Similar cooling capacity to R-404A

    Improved energy efficiency for MT applications,particularly at high ambient temperatures

    Close match to R-404A for LT applications at highambient temperatures

    For R-404A retrofit and new installations

  • 7/29/2019 Reducing the Gw Pimp Act on Commercial Refrigeration

    15/16

    15

    *under specific test conditions

    Forane 407A

    Ease of use

    May only require a TXV adjustment, no oil change required

    Approved by Compressor manufacturers including Copeland,

    Carlyle and Bitzer

    Lower discharge temperature compared to R-407F : wider rangeof operating conditions without additional cooling

    Emission Reduction

    GWP nearly 50% lower

    Efficiency up to 3% higher than R-404A and 8% higher than R-

    407F*

  • 7/29/2019 Reducing the Gw Pimp Act on Commercial Refrigeration

    16/16

    16

    Disclaimer

    The statements, technical information and recommendations contained herein are believed to be accurate as of the

    date hereof. Since the conditions and methods of use of the information referred to herein are beyond our control,

    Arkema expressly disclaims any and all liability as to any results obtained or arising from any reliance on suchinformation; NO WARRANTY OF FITNESS FOR ANY PARTICULAR PURPOSE, WARRANTY OF

    MERCHANTABILITY, OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED, IS MADE CONCERNING THEINFORMATION PROVIDED HEREIN. The user should thoroughly test any application before commercialization.

    Nothing contained herein constitutes a license to practice under any patent and it should not be construed as aninducement to infringe any patent, and the user is advised to take appropriate steps to be sure that any proposed

    action will not result in patent infringement.

    2012 Arkema Inc.

    Thank You.

    Questions?