r e joseph - washington state department of transportation · assembly ~ peen bolt conduit support...

5
APPROVED FOR PUBLICATION Washington State Department of Transportation STATE DESIGN ENGINEER 1 KEY 2 3 PHOTOCELL BREAKER ~ SPST 15 AMP - 120/240 VOLT 4 5 6 BRANCH BREAKER ~ SEE BREAKER SCHEDULE 7 SIGNAL BREAKER ~ SEE BREAKER SCHEDULE 8 9 RECEPTACLE BREAKER ~ SPST 20 AMP - 120/240 VOLT 10 RECEPTACLE (GROUNDED) ~ GFCI 20 AMP - 125 VOLT 11 12 13 POLISHED WIRE GLASS WINDOW HINGED FRONT FACING DOOR WITH 4" (IN) x 4" (IN) MINIMUM 14 15 16 SPARE BRANCH BREAKER ~ DPST 20 AMP - 120/240 VOLT 17 METAL WIRING DIAGRAM HOLDER 18 1/4" (IN) DIAMETER DRAIN HOLE ~ DRILL BEFORE GALVANIZING 19 MOUNTING HOLE ~ SEE SERVICE CABINET MOUNTING DETAILS 20 MAIN BREAKER 18-CIRCUIT PANEL BOARD ~ MINIMUM SIZE WITH SEPARATE 21 LABEL CABINET WITH BUSSWORK RATING 15 AMP - 120/277 VOLT - "T" RATED TEST SWITCH ~ SPDT SNAP ACTION - POSITIVE CLOSE PHOTOCELL MOUNTING DETAIL MESH MAY BE USED AS ALTERNATIVE MATERIAL ~ SEE 5/8" (IN) OPENINGS EQUIVALENT TO 5/8" (IN) EXPANDED STEEL FABRICATION ~ TYPE 5052 - H32 ALUMINUM WITH 5/8" (IN) x AND MOUNTING FLANGES ~ HOT-DIP GALVANIZED AFTER FROM 5/8" (IN) EXPANDED STEEL MESH WITH WELDED SEAMS PHOTOCELL ENCLOSURE ~ ENCLOSURE TO BE FABRICATED SERVICE CABINET DETAIL LEFT SIDE 21 17 PHOTOELECTRIC CONTROL ~ SEE SPECIFICATION 9-29.11(2) STANDARD ISOLATED NEUTRAL BUSS ~ 14 LUG COPPER MAIN BREAKER ~ DPST ~ SIZE PER BREAKER SCHEDULE JUMPER ASSEMBLY DETAIL BE 14 LUG TINNED COPPER ~ SEE CABINET MAIN BONDING CABINET MAIN BONDING JUMPER ASSEMBLY ~ BUSS SHALL SHEET 1 OF 5 SHEETS 120/240 SINGLE PHASE) MODIFIED (0 - 200 AMP TYPE SERVICE CABINET TYPE B STANDARD PLAN J-10.20-01 DRAW N BY: COL BY F LET CHER EXTEND INTO VERTICAL LIMITS OF THE BREAKER ARRAY(S) SLIDE LATCHES ~ DEAD FRONT PANEL BOLTS SHALL NOT HINGED DEAD FRONT WITH 1/4 TURN FASTENERS OR SECTION DOOR HINGE DETAIL DOOR HINGE DETAIL NEOPRENE GASKET CLOSED CELL 1/4" (IN) x 1 1/4" (IN) CABINET DOOR DOOR BARREL OPEN ~ 3/8" HIGH x 2" (IN) HINGE ~ 2" (IN) CABINET LAP WELD 1/8 PIANO HINGE PANEL WALL CABINET OR 1/8 PANEL DOOR A A CABINET ALTERNATE TYPE B MODIFIED (SEE NOTE 15) TYP. SIDES THREE NEOPRENE GASKET 1/4" (IN) x 5/8" (IN) PHOTOCELL ENCLOSURE MOUNTING DETAIL NUT FLANGE ENCLOSURE PHOTOCELL METAL WASHERS NUT CABINET SERVICE PRIOR TO INSTALLATION SIDES OF RUBBER WASHER SILICONE SEALER TO BOTH RUBBER WASHER ~ APPLY MACHINE BOLT 1/4" (IN) x 1" (IN) 4 1 3 2 15 TEST ON PHOTOCELL BYPASS W 5 B R 120/240 VAC { 7 SIGNAL CKT { ILL CKT A 8 6 { 16 SPARE CKT AUTOMATIC TEST OFF - PHOTOCELL { ILL CKT B 6 8 9 10 11 WIRING DIAGRAM SIZE PER NEC ~ MINIMUM SIZE #2 CABINET BONDING JUMPER ~ VENTS 6 " 3 - 4 " 1’ - 7" 18 HINGE DETAIL SEE DOOR 12 5 NOTE 6) (SEE 1 18 VENTS 5 12 HINGE DETAIL SEE DOOR RIGHT SIDE 14 FRONT 3’ - 4" 1’ - 10" 4 WARNING Hazard Arc Flash Potential LABEL "A" PHOTOCELL TEST OFF/AUTOMATIC PHOTOCELL BYPASS TEST ON 13 6" 12 5 19 19 19 19 19 10 " 2 " MI N. 19 18 18 11" 1 PHOTOCELL BYPASS TEST ON (SEE NOTE 6) STAINLESS STEEL BASE ENCLOSURE SHALL BE FABRICATED FROM TYPE 304 ON THE SIDE OR BACK OF THE SERVICE CABINET, THE METER WHEN THE UTILITY REQUIRES METER BASE TO BE MOUNTED ~ EUSERC DRAWING 305 MEETS THE REQUIREMENTS OF WITH FACTORY-INSTALLED TEST BYPASS FACILITY THAT MINIMUM, THE METER BASE SHALL BE SAFETY SOCKET BOX METER BASE PER SERVING UTILITY REQUIREMENTS ~ AS A LABEL "A" BARRIER CONTACTOR (BEHIND DEAD FRONT) ~ SEE BREAKER SCHEDULE WARNING Hazard Arc Flash Potential 3 7 2 9 10 6 6 16 20 15 14 8 PHOTOCELL TEST OFF-AUTOMATIC PHOTOCELL BYPASS TEST ON MOUNTING PANEL REMOVABLE LABEL "A" 8 SLIDE LATCH (TYP.) 11 (TYP.) 1/4 TURN FASTENER OR RIGHT HALF SERVICE CABINET DETAIL CABINET DETAIL SEE RIGHT HALF SERVICE S T A T E O F W A S H I N G T O N R E G I S T E R E D P R O F E S S I O N A L E N G I N E E R 39820 Y E L I A B H P E S O J E R O D O E H T

Upload: vuongdiep

Post on 15-Jun-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

APPROVED FOR PUBLICATION

Washington State Department of Transportation

STATE DESIGN ENGINEER

1

KEY

2

3 PHOTOCELL BREAKER ~ SPST 15 AMP - 120/240 VOLT

4

5

6 BRANCH BREAKER ~ SEE BREAKER SCHEDULE

7 SIGNAL BREAKER ~ SEE BREAKER SCHEDULE

8

9 RECEPTACLE BREAKER ~ SPST 20 AMP - 120/240 VOLT

10 RECEPTACLE (GROUNDED) ~ GFCI 20 AMP - 125 VOLT

11

12

13

POLISHED WIRE GLASS WINDOW

HINGED FRONT FACING DOOR WITH 4" (IN) x 4" (IN) MINIMUM

14

15

16 SPARE BRANCH BREAKER ~ DPST 20 AMP - 120/240 VOLT

17 METAL WIRING DIAGRAM HOLDER

18 1/4" (IN) DIAMETER DRAIN HOLE ~ DRILL BEFORE GALVANIZING

19 MOUNTING HOLE ~ SEE SERVICE CABINET MOUNTING DETAILS

20

MAIN BREAKER

18-CIRCUIT PANEL BOARD ~ MINIMUM SIZE WITH SEPARATE

21 LABEL CABINET WITH BUSSWORK RATING

15 AMP - 120/277 VOLT - "T" RATED

TEST SWITCH ~ SPDT SNAP ACTION - POSITIVE CLOSE

PHOTOCELL MOUNTING DETAIL

MESH MAY BE USED AS ALTERNATIVE MATERIAL ~ SEE

5/8" (IN) OPENINGS EQUIVALENT TO 5/8" (IN) EXPANDED STEEL

FABRICATION ~ TYPE 5052 - H32 ALUMINUM WITH 5/8" (IN) x

AND MOUNTING FLANGES ~ HOT-DIP GALVANIZED AFTER

FROM 5/8" (IN) EXPANDED STEEL MESH WITH WELDED SEAMS

PHOTOCELL ENCLOSURE ~ ENCLOSURE TO BE FABRICATED

SERVICE CABINET DETAIL

LEFT SIDE

21

17

PHOTOELECTRIC CONTROL ~ SEE

SPECIFICATION 9-29.11(2)

STANDARD

ISOLATED NEUTRAL BUSS ~ 14 LUG COPPER

MAIN BREAKER ~ DPST ~ SIZE PER BREAKER SCHEDULE

JUMPER ASSEMBLY DETAIL

BE 14 LUG TINNED COPPER ~ SEE CABINET MAIN BONDING

CABINET MAIN BONDING JUMPER ASSEMBLY ~ BUSS SHALL

SHEET 1 OF 5 SHEETS

120/240 SINGLE PHASE)

MODIFIED (0 - 200 AMP TYPE

SERVICE CABINET TYPE B

STANDARD PLAN J-10.20-01

DR

AW

N B

Y:

CO

LB

Y F

LE

TC

HE

R

EXTEND INTO VERTICAL LIMITS OF THE BREAKER ARRAY(S)

SLIDE LATCHES ~ DEAD FRONT PANEL BOLTS SHALL NOT

HINGED DEAD FRONT WITH 1/4 TURN FASTENERS OR

SECTION

DOOR HINGE DETAIL

DOOR HINGE DETAIL

NEOPRENE GASKET

CLOSED CELL

1/4" (IN) x 1 1/4" (IN)

CABINETDOOR

DOOR

BARREL

OPEN ~ 3/8"

HIGH x 2" (IN)

HINGE ~ 2" (IN)

CABINET

LAP WELD

1/8

PIANO HINGE

PANEL WALL

CABINET OR

1/8PANEL DOOR

A

A

CABINET

ALTERNATE TYPE B MODIFIED

(SEE NOTE 15)

TYP.

SIDESTHREE

NEOPRENE GASKET

1/4" (IN) x 5/8" (IN)

PHOTOCELL ENCLOSURE MOUNTING DETAIL

NUT

FLANGE

ENCLOSURE

PHOTOCELL

METAL WASHERS

NUT

CABINET

SERVICE

PRIOR TO INSTALLATION

SIDES OF RUBBER WASHER

SILICONE SEALER TO BOTH

RUBBER WASHER ~ APPLY

MACHINE BOLT

1/4" (IN) x 1" (IN)

4

1

32

15

TEST ON

PHOTOCELL BYPASS

W

5

B R

120/240 VAC

{

7

SIGNAL CKT

{

ILL CKT A

86

{

16

SPARE CKT

AUTOMATIC

TEST OFF -

PHOTOCELL

{

ILL CKT B

6 8

9

10

11

WIRING DIAGRAM

SIZE PER NEC ~ MINIMUM SIZE #2

CABINET BONDING JUMPER ~

VENTS

6"

3’ - 4"

1’ - 7"

18

HINGE DETAIL

SEE DOOR

12

5

NOTE 6)

(SEE

1

18

VENTS

5

12

HINGE DETAIL

SEE DOOR

RIGHT SIDE

14

FRONT

3’ - 4"

1’ - 10"

4

WARNING

Hazard

Arc Flash

Potential

LABEL "A"

PHOTOCELL

TEST

OFF/AUTOMATIC

PHOTOCELL

BYPASS

TEST ON

13

6"

12

5

19 19

19 19

19

10"

2"

MIN.

19

18

18

11"

1

PHOTOCELL

TEST

OFF-AUTOMATIC

PHOTOCELL

BYPASS

TEST ON

(SEE NOTE 6)

STAINLESS STEEL

BASE ENCLOSURE SHALL BE FABRICATED FROM TYPE 304

ON THE SIDE OR BACK OF THE SERVICE CABINET, THE METER

WHEN THE UTILITY REQUIRES METER BASE TO BE MOUNTED

~ EUSERC DRAWING 305MEETS THE REQUIREMENTS OF

WITH FACTORY-INSTALLED TEST BYPASS FACILITY THAT

MINIMUM, THE METER BASE SHALL BE SAFETY SOCKET BOX

METER BASE PER SERVING UTILITY REQUIREMENTS ~ AS A

LABEL "A"

BARRIER

CONTACTOR (BEHIND DEAD FRONT) ~ SEE BREAKER SCHEDULE

WARNING

Hazard

Arc Flash

Potential

3

7

2

9

10

6 6

16

20

15

14

8

PHOTOCELL

TEST

OFF-AUTOMATIC

PHOTOCELL

BYPASS

TEST ON

MOUNTING PANEL

REMOVABLE

LABEL "A"

8

SLIDE LATCH (TYP.)

11

(TYP.)

1/4 TURN FASTENER

OR

RIGHT HALF SERVICE CABINET DETAIL

CABINET DETAIL

SEE RIGHT HALF SERVICE

STAT

EOFWASHINGTON

REGISTERED

PROFESSIONAL ENGI

NEER

39820

YELI

AB

HPESOJ ERODOE

HT

APPROVED FOR PUBLICATION

Washington State Department of Transportation

STATE DESIGN ENGINEER

SHEET 2 OF 5 SHEETS

LEFT SIDE - SAFETY SOCKET BOX MOUNTING DETAIL

10 1/2"

6"

10 1/2"

6"

6"

1’ - 7"

5" MIN.

11" MAX.

(TYP.) ~ SEE DETAIL

MOUNTING BLOCK

OF DOOR

INSIDE FACE

(TYP.)

90° +/- 1°

1 1/2" (TYP.)

SAFETY SOCKET BOX

FRONT SURFACE OF

WASHER ~ EACH SIDE OF PANEL

CUT OFF AFTER ADJUSTMENT

ALL-THREAD ~ 6 PLACES (TYP.) ~

1/2" (IN) UNC S.S. x 8" (IN) LONG

(SEE NOTE 16)

THREE 1/2" (IN) S.S. NUTS (TYP.)

DIMENSION

STAND-OFF

(SEE NOTE 16)

TOP AND BOTTOM ~ SPACED EVENLY

MACHINE SCREWS, WASHERS, AND NUTS ~

FOUR 1/4-20 S.S. PANHEAD PHILLIPS

1/2" (IN) RETURN ~ WELD AT CORNERS

12-GAGE REMOVABLE PANEL

MOUNTING BLOCK DETAIL

FRONT VIEW SIDE VIEW

FOUR PLACES

TACK WELD BOLT TO NUT ~

SAME AS CABINET MATERIAL

12-GAGE ~ MATERIAL SHALL BE THE

1’ - 6 1/2"

3/32 3/32 OF MOUNTING BLOCK

WELD TO EACH END

PLATE (TYP.)

2" (IN) x 3" (IN) END

3/8"

1 1/2"

1 1/2"

3"

PLATE BEFORE WELDING

PLACE NUT AGAINST END

2"TYP.

3/32 TYP.

SIDE WALL

CABINET

120/240 SINGLE PHASE)

MODIFIED (0 - 200 AMP TYPE

SERVICE CABINET TYPE B

STANDARD PLAN J-10.20-01ELEVATION VIEW

CABINET MAIN BONDING JUMPER ASSEMBLY DETAIL

SIDE VIEW BSECTION

2 1/1

6"

(TY

P.)

1/2" MIN. (TYP.) BUSS

2" (IN) x 7 5/8" (IN) ANGLE

3/16" (IN) x 2" (IN) x

B

1/8SIDE

OTHER

TYP.

2 1/16PLACES

FOUR

TYP.

1/8

SIDE WALL

CABINET

STAINLESS STEEL ALLEN HEAD (TYP.)

CABINET SIDE WALL

PAST THE FACE OF THE NUTS

MORE THAN 3 FULL THREADS EXTEND

BOLT SO THAT NO LESS THAN 2 AND NO

ANTI-OXIDANT COMPOUND ~ CUT OFF

LIBERALLY COAT ASSEMBLY WITH

WITH TWO STAINLESS STEEL NUTS ~

1/4" (IN) x 2" (IN) STAINLESS STEEL BOLT

FLAT WASHER

STAINLESS STEEL

(TYP.)

FILLET WELD

STEEL SPRING WASHER

BELLEVILLE STAINLESS

Hinges shall have stainless steel or brass pins.

rain-tight vents.

Cabinets shall be rated NEMA 3R and shall include two

TEST OFF-AUTOMATIC". See Service Cabinet Detail.

"PHOTOCELL BYPASS TEST ON" and "PHOTOCELL

Key Number 4 name plate shall read:

Key Numbers 2, 3, 4, 6, 7, 8, 9, & 16

plate attached with screws or rivets:

shall have an appropriately engraved phenolic name

The following equipment within the service enclosure

accommodate the various sizes of equipment installed.

Dimensions shown are minimum and shall be adjusted to

equipment as shown in the breaker schedule.

allowed. Busswork shall accommodate all future

onto the busswork. Jumpering of breakers shall not be

or exceed the main breaker rating. All breakers shall bolt

All busswork shall be high-grade copper and shall equal

the photocell enclosure.

photocell without removal of the photocell unit or

enclosure to permit 360 degree rotation of the

The photocell unit shall be centered in the photocell

shall be used.

Approved PVC or polyolefin wire marking sleeves

letters and/or numbers shown on the schedules.

"TO - FROM" coded tags labeled with the code

All internal wire runs shall be identified with

photocell enclosure shall be stainless steel.

All nuts, bolts, and washers used for mounting the

A 1% tolerance is allowed for all dimensions.

stainless steel.

clamps shall be hot-dipped galvanized steel or

components shall be stainless steel. Conduit

Slotted steel channel and mounting hardware

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

NOTES (200 AMP TYPE 120/240 1ł SERVICE CABINET)

requirements.EUSERC Drawing 309

designed to meet metering portion of

The meter base portion of this service was

Standard Specification 9-29.24 (Service Cabinets).See

of the service equipment.

Utility’s requirements prior to fabrication and installation

Mounting Detail. The Contractor shall verify the serving

11" (in) shown in the Left Side - Safety Socket Box

and the front of the safety socket box to be less than the

The Utility may require the dimension between the door

enclosure, on the side, or on the back of the enclosure.

The Utility may require meter base mounting in the

Metering arrangements vary with different serving Utilities.

Core on right side door. See Door Hinge Detail.

door shall be gasketed. Install Best CX Construction

Metering equipment door shall be pad-lockable. Each

17.

more than three full threads extend past the face of the nuts.

adjustment, cut off all-thread bolts so that no less than two and no

panel to the measurement provided by the Utility Company. After

Verify the service utility stand-off dimension. Adjust the removable

with brass pin and solder in place.

prior to hot-dip galvanizing. After galvanizing, replace pin

Remove hinge pin prior to welding hinge to cabinet and

When using alternate door hinge:

used. Three pairs required.

back to back continuous slotted steel channel may be

steel channel or factory welded 1 5/8" (in) x 1 5/8" (in) 12-gage

supports, 1 5/8" (in) x 3 1/4" (in) 12-gage continuous slotted

As an alternate to the bolted or field welded strut mount

DRAWN BY: COLBY FLETCHER

PANEL

REMOVABLE

STAT

EOFWASHINGTON

REGISTERED

PROFESSIONAL ENGI

NEER

39820

YELI

AB

HPESOJ ERODOE

HT

APPROVED FOR PUBLICATION

Washington State Department of Transportation

STATE DESIGN ENGINEER

SHEET 3 OF 5 SHEETS

CABINET BRACKET MOUNTING DETAIL

SERVICE CABINET

SPRING NUT

POST

TIMBER

CHANNEL BRACKET

SLOTTED STEEL

TO UTILITY

FRONT OF SERVICE CABINET

POST MOUNT STRAP DETAIL

GALVANIZED STRAP

2" (IN) x 1/8" (IN) HOT-DIPPED

RIGHT SIDE OF SERVICE CABINET

5’ - 0"

MINIM

UM

6’ - 0"

MA

XIM

UM

LOCK WASHER, AND NUT (TYP.)

3/8" (IN) DIAM. x 1" (IN) BOLT,

OR SERVED DEVICES

TO LUMINAIRES

CONDUIT SUPPORT DETAIL

TIMBER POST

TREATED

6" (IN) x 8" (IN)

SIZE TO LENGTH

ALL-THREAD ROD (TYP.) ~

3/8" (IN) HOT-DIP GALVANIZED

SIZE TO LENGTH

RIGID METAL CONDUIT ~

1 1/4" (IN) DIAM.

STANDARD PLAN J-10.20-01

120/240 SINGLE PHASE)

MODIFIED (0 - 200 AMP TYPE

SERVICE CABINET TYPE B

STEEL CHANNEL

12-GAGE SLOTTED

1 5/8" (IN) x 1 5/8" (IN)

FRONT OF SERVICE CABINET

SINGLE POST MOUNTTWO POST MOUNT

4

CABINET

TO CONTROLLER

TO UTILITY

TIMBER POST

TREATED

6" (IN) x 8" (IN)

CONDUIT SUPPORT DETAIL

1"

(TYP.)

AND NUT (TYP.)

PLATE WASHER

HOT-DIP GALVANIZED

AND NUT (TYP.)

PLATE WASHER

HOT-DIP GALVANIZED

FLAT WASHER AND NUT (TYP.)

3/8" (IN) HOT-DIP GALVANIZED CLAMP WITH BOLT (TYP.)

TWO-PIECE CONDUIT

PLATE WASHER (TYP.)

HOT-DIP GALVANIZED

PLATE WASHER (TYP.)

HOT-DIP GALVANIZED

DR

AW

N B

Y:

CO

LB

Y F

LE

TC

HE

R

WITH BOLT (TYP.)

CONDUIT CLAMP

TWO-PIECE

FLAT WASHER AND NUT (TYP.)

3/8" (IN) HOT-DIP GALVANIZED

(SINGLE POST MOUNT ONLY) (TWO POST MOUNT ONLY)

POST MOUNTS)

(FOR SINGLE POST AND TWO

POST MOUNTS)

(FOR SINGLE POST AND TWO

(SINGLE POST MOUNT ONLY)

SIZE TO LENGTH

ALL-THREAD ROD (TYP.) ~

3/8" (IN) HOT-DIP GALVANIZED

TO LENGTH (TYP.)

METAL CONDUIT ~ SIZE

1 1/4" (IN) DIAM. RIGID

STEEL CHANNEL

12-GAGE SLOTTED

1 5/8" (IN) x 1 5/8" (IN)

TO CONTROLLER CABINET

10’ (FT) LONG

6 x 8 TREATED TIMBER POST ~

SUPPORT DETAIL

THREADS ~ SEE CONDUIT

ASSEMBLY ~ PEEN BOLT

CONDUIT SUPPORT

AND POST MOUNT STRAP DETAIL

CABINET MOUNTING DETAILS

BRACKET ~ SEE SERVICE

TO SLOTTED STEEL CHANNEL

SERVICE CABINET BOLTED

STRAP DETAIL

SEE POST MOUNT

BEVEL 1/2"

POST MOUNT ONLY)

STRAP DETAIL (SINGLE

DETAILS AND POST MOUNT

CABINET MOUNTING

THREADS ~ SEE SERVICE

CHANNEL ~ PEEN BOLT

AND NUTS FOR EACH

3/8" (IN) BOLTS, WASHERS,

TO POST ~ USE TWO

BRACKETS BOLTED

STEEL CHANNEL

12-GAGE SLOTTED

1 5/8" (IN) x 1 5/8" (IN)

+/- 1°

CONDUIT

PLUMB

SERVED DEVICES

TO LUMINAIRES OR

POST ~ 10’ (FT) LONG (TYP.)

6 x 8 TREATED TIMBER

2’ - 0"2’ - 0"

2’ - 0"

PLAN VIEW

POST MOUNTS)

MAINTENANCE PAD (FOR SINGLE POST AND TWO

9"

MAINTENANCE PAD

FOR STRUT MOUNT

~ NOT REQUIRED

FOR EACH CHANNEL)

3/8" (IN) BOLT (TWO

(THREE FOR EACH CHANNEL)

LOCK WASHER AND SPRING NUT

STEEL CHANNEL BRACKET WITH

BOLT SIZED FOR SLOTTED

STEEL CHANNEL

SLOTTED

SERVICE CABINET

1

(SEE NOTE 6)

4

SPEC. 9-07.7

STD. OF PAD ~ SEE

PLACED IN CENTER

4 x 4 ~ W4.0 x W4.0 ~

WELDED WIRE FABRIC

5’ - 0"

MINIM

UM

1

(SEE NOTE 6)

6’ - 0"

MA

XIM

UM

5 (TYP.)55 5 (TYP.)

STAT

EOFWASHINGTON

REGISTERED

PROFESSIONAL ENGI

NEER

39820

YELI

AB

HPESOJ ERODOE

HT

APPROVED FOR PUBLICATION

Washington State Department of Transportation

STATE DESIGN ENGINEER

DR

AW

N B

Y:

CO

LB

Y F

LE

TC

HE

R

FRONT OF SERVICE CABINET

1

2

3

RIGHT SIDE OF SERVICE CABINET

4

(SEE NOTE 6)

5’ - 0"

MINIM

UM

6’ - 0"

MA

XIM

UM

#4 HOOPS

BOLT (TYP.)

ANCHOR

EACH CORNER

#4 BARS

3"

TO CONTROLLER CABINET

4TO UTILITY

2

9"

CABINET

CONTROLLER

FRONT OF

2’ - 0"

POLICE PANEL

WITH APPROVED COVER (TYP.)

13" (IN) DIAM. DRAIN TILE

3

2’ - 0"

5

LOCATE DRAIN AWAY FROM ACCESS DOORS

SLOPE TO DRAIN OUTSIDE FOUNDATION ~

POLYETHYLENE OR COPPER DRAIN PIPE ~

FOUNDATION TOWARD SUMP ~ 3/8" (IN) DIAM.

4" (IN) DIAM. x 1/2" (IN) DEEP SUMP. SLOPE

TO SERVICE GROUND ~ PER

PLAN J-60.05

STANDARD

9"

OF PAD ~ SEE

PLACED IN CENTER

4 x 4 ~ W4.0 x W4.0 ~

WELDED WIRE FABRIC

SPEC. 9-07.7

STD.

OF PAD ~ SEE

PLACED IN CENTER

4 x 4 ~ W4.0 x W4.0 ~

WELDED WIRE FABRIC

SPEC. 9-07.7

STD.

ROD (TYP.)

GROUND

(TYP.)

2’ - 0"

MIN.

(TY

P.)

3"

(TYP.)

PLUMB CONDUIT +/- 1°

CONDUITS AS REQUIRED ~

5

OR SERVED DEVICES

TO LUMINAIRES

TO THE CABINET GROUNDING BUSS

GROUNDING END BUSHING AND BONDED

CABINET SHALL BE TERMINATED WITH

ALL RMC CONDUITS PENETRATING

1

D

SECTION C

C

D

12"

MA

X.

(TY

P.)

1"

1/8 @ 12

1/8 @ 12

END

FROM EACH

1" (IN) MIN.

(SEE NOTE 17)

PLAN VIEW OF SERVICE CABINET

CABINET

CONTROLLER

CABINET

SERVICE

DO

OR

3

2’ - 0"2’ - 0" CABINET BASE

1" 1"

TWO #4 HOOPS

1"

2’ - 0"

CA

BIN

ET

BA

SE

1"

1’ - 7"

2’ - 0"

1#4 BAR EACH CORNER

"X"

"X"

"X"CABINET TYPE

332 OR 334 TYPE CABINET

333SD TYPE CABINET

332D OR 334D TYPE CABINET

NEMA P44 TYPE CABINET

26"

24"

26"

46 1/2"

STD. PLAN J-10.10

PLUS 2 INCHES

"X" = WIDTH OF DOOR OPEN TO 180°

:IS NOT LISTED ON

FOR A SPECIAL DESIGN CABINET THAT

SPACING TABLETABLE)

SPACING

(SEE

TA

BLE)

SP

ACIN

G

(SE

E

STRUT MOUNT SUPPORT DETAILS

BRACKETS (TWO REQUIRED)

SLOTTED STEEL CHANNEL

1 5/8" (IN) x 1 5/8" (IN) 12-GAGE

SUPPORT DETAILS

IN FOUNDATION ~ SEE STRUT MOUNT

SLOTTED STEEL CHANNEL ~ EMBED 12" (IN) MIN.

1 5/8" (IN) x 3 1/4" (IN) 12-GAGE CONTINUOUS

STEEL CHANNEL (THREE PAIRS REQUIRED) OR

BACK-TO-BACK CONTINUOUS SLOTTED

TWO 1 5/8" (IN) x 1 5/8" (IN) 12-GAGE

(SEE NOTE 17)

(FIELD WELDED OR BOLTED)

ELEVATION VIEW

STEEL CHANNEL

CONTINUOUS SLOTTED

12-GAGE BACK TO BACK

TWO 1 5/8" (IN) x 1 5/8" (IN)

SECTION

(WELDED CONNECTION)

SHALL NOT BE GLUED TO THE COUPLING

CONDUIT STUB AND END BELL BUSHING

IF PVC CONDUITS ARE SPECIFIED,THE

SHALL BE FLUSH WITH TOP OF CONCRETE ~

CONDUITS ~ TOP OF CONDUIT COUPLINGS

INSTALL CONDUIT COUPLINGS ON ALL

ON

BETWEEN GROUND RODS AS DETAILED

MAINTAIN A 6’ (FT) MINIMUM CLEARANCE

ACHIEVE FULL GROUND PENETRATION ~

TILE(S) WITH COVER(S) AS REQUIRED TO

CONCRETE ~ MOVE ROD(S) AND DRAIN

DRIVE GROUND RODS BEFORE PLACING

STANDARD PLAN J-60.05

SHEET 4 OF 5 SHEETS

STANDARD PLAN J-10.20-01

120/240 SINGLE PHASE)

MODIFIED (0 - 200 AMP TYPE

SERVICE CABINET TYPE B

12" (IN) MAX. CENTERS

NUT ~ SPACED AT

WASHERS AND LOCK

LONG BOLT WITH TWO

3/8" (IN) DIAM. x 1 1/4" (IN)

(BOLTED CONNECTION)

DOOR

DOOR

5

(TYP.)

CONDUIT COUPLING

APPLICABLE

AS SECTION D

OR SECTION C

BOLT POINT ~ SEE

FIELD WELD OR

GROUND ROD (TYP.)

1’ - 8"

1’ - 11"

DRAINAGE WELL18" (IN) x 18" (IN) x 18" (IN)

TIE-DOWN UNITGENERATOR ANTI-THEFT

6" MIN.

6"

MIN.

(TYP.)

(TY

P.)

DO

OR

TABLE AND DETAILS NOT SHOWN

FOR CABINET DIMENSIONPLAN J-10.10

STANDARDFOUNDATION DETAILS ON

SEE CONTROLLER CABINET

STD. PLAN J-10.10SEE

REQUIRED AT EACH CORNER ~

ANCHOR BOLT (TYP.) ~ ONE

(2 PLACES)30" (IN) LEGS

#4 ~ 90° WITH

STAT

EOFWASHINGTON

REGISTERED

PROFESSIONAL ENGI

NEER

39820

YELI

AB

HPESOJ ERODOE

HT

APPROVED FOR PUBLICATION

Washington State Department of Transportation

STATE DESIGN ENGINEER

DR

AW

N B

Y:

CO

LB

Y F

LE

TC

HE

R

SHEET 5 OF 5 SHEETS

STANDARD PLAN J-10.20-01

120/240 SINGLE PHASE)

MODIFIED (0 - 200 AMP TYPE

SERVICE CABINET TYPE B

BDETAIL

CONDUIT

STRANDED

# 6 INSULATED

CLAMP (TYP.)

BRONZE GROUND

WASHERS AND SET SCREWS

WITH BRONZE U-BOLT,

BRONZE GROUND CLAMP ~

TINNED BRAIDED COPPER

# 8 AWG MIN. × 1 FT OF

PLAN VIEW

STANDARD PLAN L-20.10SEE

END OR CORNER POST (TYP.) ~

STANDARD PLAN L-20.10SEE

TYPE 3 CHAIN LINK FENCE (TYP.) ~

MAINTENANCE PAD

3’ - 6"

24"

PLAN VIEW

SEE

END OR CORNER POST (TYP.) ~

STANDARD PLAN L-20.10

SEE

TYPE 3 CHAIN LINK FENCE (TYP.) ~

STANDARD PLAN L-20.10

3’ - 6"

SEE

6’ CHAIN LINK GATE ~

PLAN L-30.10

STANDARD

24"

ELEVATION VIEW

OMITTED FOR CLARITY, SEE SHEET 4 FOR ADDITIONAL DETAILS.

FOR CONDUITS NOT SHOWN, DRAIN TILE FOR GROUNDING, DRAIN TUBES, REINFORCING STEEL, ETC.

STANDARD PLAN L-20.10SEE

TYPE 3 CHAIN LINK FENCE (TYP.) ~

STANDARD PLAN L-30.10SEE

6’ CHAIN LINK GATE ~

POST MOUNTED SERVICE CABINET WITHIN RIGHT-OF-WAY FENCE

SERVICE CABINET

SIDE VIEW

MAINTENANCE PAD

SERVICE CABINET

CONTROLLER CABINET

TIE-DOWN UNIT

GENERATOR ANTI-THEFT

ELEVATION VIEW

PAD MOUNTED SERVICE CABINET WITHIN RIGHT-OF-WAY FENCE

OMITTED FOR CLARITY, SEE SHEET 4 FOR ADDITIONAL DETAILS.

FOR CONDUITS NOT SHOWN, DRAIN TILE FOR GROUNDING, DRAIN TUBES, REINFORCING STEEL, ETC.

DISCONNECT SWITCH

SERVICE METER BASE OR

SIDE VIEW

ADETAIL

CONDUIT

STRANDED

# 6 INSULATED

WASHERS AND SET SCREWS

WITH BRONZE U-BOLT,

BRONZE GROUND CLAMP ~

3’ - 6" MIN.

(TYP.)

SERVICE CABINET

STANDARD PLAN L-20.10SEE

TYPE 3 CHAIN LINK FENCE (TYP.) ~

STANDARD PLAN L-30.10SEE

6’ (FT) CHAIN LINK GATE ~

A B

SERVICE CABINET

SERVICE CABINET

SLOPE BREAK

GROUND LINE

3’ - 6"

MIN.

A B

CONTROLLER CABINET

3’ - 6"

MIN.

PAD

MAINTENANCE

CABINET

SERVICE

FENCE

PLAN VIEW SIDE VIEW

FENCE IS PRESENT)

3’ - 6" MIN. (WHEN

SIDES WITH DOORS1’ - 6" MIN. ON ALL CABINET

SWITCH

DISCONNECT

BASE OR

SERVICE METER

SLOPE

THAN 2H : 1V

NOT STEEPER

SERVICE CABINET IN VICINITY OF CHAIN LINK FENCE

PAD MOUNTED SERVICE CABINET SIMILAR

POST MOUNTED SERVICE CABINET SHOWN,

SWITCH

OR DISCONNECT

SERVICE METER BASE

L-30.10

STANDARD PLANSEE

6’ CHAIN LINK GATE ~

STAT

EOFWASHINGTON

REGISTERED

PROFESSIONAL ENGI

NEER

39820

YELI

AB

HPESOJ ERODOE

HT