documentq

Upload: lauren-norris

Post on 09-Oct-2015

9 views

Category:

Documents


0 download

DESCRIPTION

q

TRANSCRIPT

  • 5/19/2018 Q

    1/28

    OPTIMHOStatic Distance Protection Relays

  • 5/19/2018 Q

    2/282

    OPTIMHOStatic Distance Protection Relays

    Features

    Full scheme distance relays with18, 12, 9 or 6 measuring units.

    Phase and ground distance orphase distance protection.

    Single or multiple zones.

    Optional directional earth faultprotection.

    Typical operating time: one cyclefor three phase faults.

    Optional fault location includesmutual compensation on selectedmodels.

    Optional data recording for postfault analysis and instrumentationfunctions.

    Eight independent groups ofsettings can be stored in the

    relay.

    A second blocking scheme isavailable on selected models foruse with signalling equipment.

    Integral user interface for easyaccess to relay setting and faultrecords.

    Provision for remotecommunications via modems.

    Benefits

    Wide model range for accuratematching to applications.

    Remote interrogation reducesneed for site visits.

    Precise fault location, even ondouble-circuit lines together withfault information reduces outagetime.

    Accurate fault informationprovides for in-depth faultanalysis.

    Changes to alternative groups ofsettings can be accomplishedwith a single command.

    Self diagnosis reducesmaintenance costs.

    Vertical case option eases retrofitproblems.

    Will interface with existingscheme logic.

    Fulfils basic SCADA role at noextra cost.

    Figure 1: Optimho (Type LFZP) relays

  • 5/19/2018 Q

    3/283

    Summary Chart

    Transmission and Sub-transmission Backsub transmission and distribution upmain protection main protection only

    LFZP Model 111 112 113 114 121 122 123 131 132 151

    Phase distance

    Ground distance

    DEF Fault location

    Fault location with mutual compensation

    Overhead lines

    Underground cables

    Open delta/3 limb VTs

    No. of distance elements 18 18 18 12 12 12 12 9 6 6

    Independent zones Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1

    Z2 Z2 Z2 Z2 Z2 Z2

    Z3 Z3 Z3 Z3 Z3 Z3 Z3 Z3

    Reach stepped zones Z1X Z1X Z1X Z1X Z1X Z1X Z1X Z1X Z1X

    Z1Y Z1Y Z1Y Z1Y Z1Y Z1Y Z1Y Z1Y Z1Y

    Z2 Z2 Z2

    Reversible zones

    Single pole tripping

    VT supervision

    3 phase fuse blow supervision

    Power swing blocking

    Loss of load trip feature

    No. of output contacts 24 24 24 24 16 16 16 16 16 8

    Basic

    Z1 Extension

    Acceleration

    PUR

    PUR Unblock

    Schemes POR1

    POR1 Unblock

    POR2

    POR2 WI Trip

    POR2 Unblock POR2 WI Trip Unblock

    Blocking

    Blocking 2

    Z1, Z1X, Z1Y, Z2 Phase m m m m m m c f f

    Distance Z1, Z1X, Z1Y, Z2 Ground q/m m m m q/m m c

    Characteristic Z3 Phase L L L N N N P N

    Z3 Ground Q/L L L D/N N N N

    Negative sequence volts

    DEF Zero seq current

    polarising Zero seq volts Zero seq volts+current

    = standard, = optional, m = shaped mho, f = fully crossed polarised mho, q = quadrilateral,c = shaped mho for cables, D = offset quadrilateral, N = offset lenticular, Q = D/rev q, L = N/rev m, P = N/rev f.For further information see Page 6.

  • 5/19/2018 Q

    4/284

    Applications of Optimho

    Optimho is produced in severalmodels, each suitable for a specificrange of applications. The moresophisticated models have featuresand functional abilities which canfulfil the most exacting duties.These can include ehv applicationsdepending on the fault clearancetime required. The more basicmodels have reduced hardware andsoftware to suit the simplerrequirements of sub-transmissionand distribution systems.

    Optimho complements the wellestablished Micromho andQuadramho, enhancing the alreadyoutstanding family of distanceprotection available from ALSTOM

    T&D Protection & Control Ltd.

    The range of applications includes:

    main and back-up protection ofoverhead lines and undergroundcables including transformerfeeders.

    back-up protection oftransformers, auto-transformersand shunt reactors (LFZP 151)

    protection of solid or resistance

    earthed systems. Three-pole or single-and-three-

    pole tripping, with or without theaid of a signalling channel.

    single zone relays used inmultiple zone schemes to provideultra-high reliability by additionalredundancy of protection(LFZP 121, 122 or 132 with onezone enabled).

    on-site replacement ofobsolescent electro-mechanical orswitched static distance relays.

    protection of systems with open-delta line voltage transformers or3 phase 3 limb line voltagetransformers (LFZP 131 or 132).

    phase selection to allow, forexample, a power line carrierphase comparison scheme (suchas P10) to carry out single phase

    tripping (LFZP 114).

    Principles of Operation

    All models of Optimho are fullscheme distance relays which havea full set of measuring elements foreach main zone of protection.Compared with the switched type ofscheme, the full scheme systemimproves reliability by avoiding theneed to rely on phase selectionhardware or software and byremoving dependence on a singlemeasuring unit. Full scheme distancerelays are better able to cope withinter-circuit faults on double circuitlines and evolving faults.

    The measuring element uses a micro-controller to produce a directsoftware equivalent of the hardwarephase comparator used in

    Optimhos forerunners, Micromhoand Quadramho. This phasecomparator design is well tried,having accumulated nearly tenthousand relay years of successfuloperating experience over the lastdecade at locations throughout theworld.

    Many of the other hardware andsoftware features of Quadramhohave been retained and further

    enhanced in Optimho, ensuring thehighest standards of reliability.

    Optimised Performancewith Distorted Signals

    The phase comparators and leveldetectors use logic processing toachieve immunity from maloperationdue to noise, such as harmonicdistortion, travelling wave effects,high and low frequency capacitor

    voltage transformer transients andcurrent transformer saturation.Operation of the phase comparatorsand level detectors can only occur ifthe input signals are dominated bypower frequency components.Filters are used to insure thisdominance and to optimiseoperating times.

    Hardware Structure

    All models are built up from a smallrange of standard printed circuitboards used as modular buildingblocks.

    All models use the same relay case,power supply unit, and front panel.

    The relay hardware is bus-structuredto allow printed circuit boards to beplugged into the case in differentcombinations. (See Figure 2).

    The hardware uses multiplemicrocontrollers to perform ascomparators, level detectors, etc.A main microcontroller uses thedigital bus to read outputs from thesubsidiary microcontrollers, readsignals from the outside world via

    optically coupled isolators,communicate with the user interfaceand perform scheme logic, serialcommunications, monitoring andoutput contact functions. Settings,indications, and fault records arestored in a type of memory which isunaffected by loss of dc supply.The layout of the relay case followsthe quiet region arrangementintroduced in Micromho andQuadramho, with measurement and

    control boards located in ascreened compartment and fed withsignals from the outside world viascreened isolation devices andfilters. See Figure 3.

    A vertical aspect, panel mountedversion can be used for replacingobsolescent electromechanicaldistance relays in narrow panels,with the minimum of paneldisturbance.

    Integral User Interface

    All relay settings and records areaccessible from the integral userinterface shown in Figure 4.

    The liquid crystal display (LCD)indicates how the relay initiated thelatest trip. The faulty phase andzone are indicated for trips initiatedby the distance elements. The latestalarm condition is also indicated.

    If indications are present when thesupply is lost, they are automaticallyreinstated when the supply isrestored.

  • 5/19/2018 Q

    5/285

    The date and time of the fault,location (if available), and more,are displayed by pressing READ.After the indications have beenread, they can be cleared bypressing RESET, and the READ keycan then be used to step through allthe relay settings displayed insequence.

    The cursor and SET keys, and the

    two test sockets, are only accessibleafter removing the transparent frontcover. The keys are used to selectfrom a menu of options displayedon the LCD in English, and to enternew settings into temporarymemory. The menu has a simplestructure, allowing rapidfamiliarisation.

    The SET key is used to transfertemporary entries to the permanent

    memory which determines relayaction. Accidental changes areprevented by allowing SET to beoperative only at certain points inthe menu after appropriatewarnings have been displayed.

    Figure 3: Mechanical layout of LFZP

    Figure 4: User interface on front panel

    User interface

    8 Output relays

    Statusinputs

    8 Output relays

    8 Output relays

    Trips.alarms,etc.

    Analoguebus

    Main controller board+ Schemes, settings,

    comms, monitoring diagnostics

    Fault location board+ Fault data and instrumentation

    Level detector board+ AC supply supervision

    Zone 1 and 2 board(Alternatively zones 1, 2 and3)

    + Additional reach stepped zones

    Zone 3 board+ Power swing blocking

    DEF board

    Quadrilateral

    ground fault board

    Settings fromdigital bus

    Optional boards shown inbroken outline

    AC inputs

    Analogueinput

    module

    RS232C serial link to remote terminal

    Digitalbus

    VAVBVC

    ABC

    N

    p

    VN

    7 Optical isolators

    Output auxiliaryrelays andstatus input

    optical isolators

    Fully screenedpower supplyunit enclosureTerminal blocks

    Terminal block Analogueinput module

    Measurementand control

    boards in fullyscreened

    compartment

    User interfaceon hinged front

    panel

    DISTANCEPROTECTION

    SET

    RESET ACCEPT/READ

    RELAY AVAILABLE

    PARALLEL

    SERIAL

    TRIP

    ALARM

    2 x 16 characterliquid crystal display Light emitting diodes

    Test sockets7 Keys only RESET and ACCEPT/READaccessible with front cover in place

    Figure 2: Electrical structure of LFZP

  • 5/19/2018 Q

    6/286

    Menu Options

    The menu holds an extensive rangeof options, including:

    viewing records of the LCDindications from the last fourfaults.

    printing records or settings on aportable printer plugged into theparallel test socket

    entering a relay identificationcode for use on printouts.

    comprehensive test options suchas: monitoring test points on theparallel socket; blocking outputcontacts (the relay inoperativealarm contact closes when theoutput contacts are blocked);simplified on-load directionaltesting; and closing selectedoutput contacts (for instance tocarry out a circuit breaker test)

    setting up the baud rate andprotocol for the serialcommunications.

    Settings

    The setting options allow the user toselect functions to suit each

    application. The available optionsdepend upon the model ofOptimho, but usually include:

    scheme type

    which distance zones areenabled (up to 5 zones)

    whether ground fault timedelayed zones (if fitted) areenabled

    direction of reach-stepped zones

    or of Zone 3 (if fitted) whether start indications are

    required for remote faults whichdo not result in a trip.

    eight independent groups ofsettings which are stored in therelay memory and are selectablefrom the menu.

    The menu is adaptive; for example,if Zone 2 is not required and hasbeen disabled, its time setting is

    automatically removed from themenu.

    Schemes Available

    The scheme selection varies with themodel of Optimho. Most modelshave basic distance with up to 3independent zones available,designated Z1, Z2 and Z3.Additional zones 1X and 1Y areobtained, if required, by steppingthe reach of the Zone 1 elementsafter time delays started by theZone 2 and/or Zone 3 elements.On some models Zone 2 is obtainedby stepping the reach of Zone 1,while on some other models, Zone 3is omitted.

    Models offering selectable,permissive overreach andunblocking schemes are completewith current reversal guard logic

    and open breaker echo logic.

    Models having independent Zone 1,Zone 2 and Zone 3 have additionalpermissive overreach andunblocking schemes with weakinfeed logic, also the blockingscheme. These schemes requireZone 3 to be set reverse looking.

    Single phase tripping logic isavailable in some models.

    Loss of load accelerated trippingfeature is available on some modelsfor use with 3 pole tripping.

  • 5/19/2018 Q

    7/287

    Distance Characteristics

    The phase comparator is arranged to produce several types of distancecharacteristics for the different models of Optimho. For further information seeSummary, Page 3.

    Characteristic Descriptiontype

    m Partially cross polarised shaped mho with partialsynchronous polarising for 3-phase faults. Expansionunder fault conditions is more than adequate to cover arcand tower footing resistance for most systems, withexcellent phase selection. See Figure 5.

    f Fully cross polarised (or quadrature polarised) mho withpartial synchronous polarising for 3-phase faults.Similar to type m above but used where only phase faultprotection is required.

    c Self polarised mho, with a small proportion of crosspolarising: used for ground fault protection of

    underground cables at high and medium voltages.q Quadrilateral with adaptive reactance measurement to

    avoid overreach or underreach for resistive faults withprefault load. The directional measurement is partiallycross polarised. The resistive reach setting is variable upto 150(1A relay) or 30(5A relay). The quadrilateralis used instead of type m above to cover ground faultresistance on overhead lines shorter than 15km, onresistance neutral systems, or on systems with high groundresistivity. See Figure 6.

    D Offset quadrilateral: as type q but with reverse reach for

    busbar back-up protection in Zone 3 time.N Offset lenticular with a variable aspect ratio set to avoid

    load encroachment on long lines. A circular offset settingfor shorter lines is included. The reverse reach is used forbus back-up protection in Zone 3 time. Reach steppedzones whose timers are started by Zone 3 automaticallyavoid load encroachment if Zone 3 is shaped to avoid theload impedance. See Figure 7.

    Q Selectable between type D and reverse type q.

    L Selectable between type N and reverse type m.

    P Selectable between type N and reverse type f.

    Figure 5: Resistive expansion of partially cross-polarized mho under f ault conditions for solidly grounded systems

    X

    Numbers are source impedance/relay setting ratios

    24 60

    12610

    R

  • 5/19/2018 Q

    8/288

    Remote Communications

    All the options available on themenu are also available from alocal or remote terminal via anRS232C serial communication port.Sockets are provided on both thefront and the rear of the relay fortemporary or permanent connectionrespectively. The socket on the rearcan also interface with a modem forcommunication over a suitable link,for instance a telephone line.

    The facility to bulk transfer settings,event records and meteringinformation (providing a faultlocator is fitted) is available usingALSTOM T&D Protection & ControlLtd pc based software Opticom.

    By using KITZ 103 interface unit, theOptimho can be interconnected torelays in the ALSTOM K range.The interconnection is via ashielded, twisted wire pair knownas K-Bus. Up to 32 relays may beconnected in parallel across the bus.The K-Bus is connected through asecond KITZ protocol convertoreither directly or via a modem to theRS232 port of the pc. The K-Bus isRS485 based and runs at

    64 kbits/s.From the same pc, Opticom 100(version 5.0 and higher) and anyCourier based Access Softwarepackages can be used tocommunicate with the Optimho.

    The KITZ 103 and the LFZP act as asingle slave device over K-Bus, seeFigure 8.

    For more detailed information on theapplication of Optimho over K-Bus,

    including modem connections, baudrates, bit framing and the use ofCourier features, reference shouldbe made to the following servicemanuals:

    KITZ 101/102Interface Unit R8521

    KITZ 103K-Bus to Optimho Interface R8532

    OptiCom 100/140

    Settings Databaseand File Transfer R5928

    Figure 6: Quadr ilateral ground fault characteristics

    Figure 7: Lenticular Zone 3

    Zone3

    Zone2

    Zone1

    Zone3reverse

    Directionalline

    Zones1&2

    R

    LHR

    esis

    tive

    rea

    ch

    X

    RH

    Resis

    tive

    rea

    ch

    X

    Zone 3

    Zone 3reverse

    a

    b

    0.410.67

    1.00Aspect ratios a/b

    Loadarea

    R

  • 5/19/2018 Q

    9/289

    Polarising

    The partial cross polarising signalused in various distancecharacteristics is a square wavederived from a healthy phasereference and 16% of the amplitudeof the prefault voltage. This wave isadded to the faulty phase voltage,and dominates it for close-upunbalanced fault conditions.This provides a clear directionalreference even in the presence ofcapacitor voltage transformertransients.

    The partial synchronous polarising is

    similar to partial cross polarising butis effective for 3-phase faults.Synchronous polarising is derivedfrom prefault voltage and isavailable for 16 cycles after faultincidence to cover breaker failureprotection time.

    Several cycles must elapse fromsystem energisation beforesynchronous polarising is available,so switch-on-to-fault logic is

    arranged to provide protection forclose-up 3-phase faults during thisinitial period.

    Directional Earth FaultProtection(not available in all models)

    The directional earth fault protection(DEF) has these features selectablevia the user interface:

    time delayed tripping, eitherdefinite time or inverse definiteminimum time using a selection ofbuilt-in IEC or American curves.See Figure 9.

    instantaneous high-set tripping,available if the model of Optimhohas no Zone 1 instantaneous

    ground fault elements fitted. aided tripping via permissive

    overreach, unblocking, orblocking schemes (depending onthe model), which work inconjunction with the distancescheme, sharing the samesignalling channel.

    choice of polarising for thedirectional element:

    negative sequence voltage

    derived from internal filters(compared against negativesequence current).

    zero sequence current from aseparate current input

    zero sequence voltage (in somemodels) derived internally fromVA, VBand VC.

    dual zero sequence current and

    voltage (some models only).

    The overcurrent elements use zerosequence current as the operatingquantity irrespective of the type ofpolarising used for the directionalelement.

    The negative sequence filters areself-adaptive to system frequency,allowing greater sensitivity than ispossible with fixed filters tuned tothe nominal system frequency.

    A magnetising inrush currentdetector is provided to preventmaloperation when energising in-zone transformers. The circuit usesthe principle of detectingzeros in the current lasting for aquarter-cycle or more. This methodis inherently unaffected by currenttransformer saturation, unlikesecond harmonic restraint.

    Figure 8: Typical application diagram: KBUS/LFZP 100 (Optimho) Interface Type KITZ 103

    Auxiliarysupplyvoltage

    KITZ101/102KBUS/IEC 60870 Interface+

    _

    Screen

    Screen

    All points are internally connected

    2 TX3 RX 7 Signal GND 1 Protective GND

    IBM or compatible P.C.(For pin assignmentnumbers see table)

    Auxiliarysupplyvoltage

    12

    150R

    KITZ103 KBUSLFZP 100 (Optimho)

    Interface

    LFZP 100 (Optimho) Relay +_

    All points are internally connected

    2371

    2 TX3 RX

    7 Signal GND 1 Protective GND

    12

    *

    54

    56

    150R

    Typical Kseries relay

    When Fitted

    Terminals

    Screen Link

    56

    54

    Typical Kseries relay

    Terminals

    (Rear Port)

    Table showing connections between KITZ 103 serialport and LFZP 100 (OPTIMHO) rear serial port.(For reference only. Please refer to PC user manualwhere available).

    KITZ 103 LFZP 100 (OPTIMHO) rear serial port type

    25 pin D male connector (DTE) KITZ 103 25 pin D male connector (DTE)

    1 Protective ground 1 Protective ground

    2 Transmitted data 2 Received data

    3 Received data 2 Transmitted data7 Signal ground 7 Signal ground

    Connector shell to cab le screen Connector shell to cable screen

  • 5/19/2018 Q

    10/2810

    Fault Location, FaultData Recording andInstrumentation(not available in all models)

    The fault location algorithm includescompensation for infeed into aresistive fault from remote source

    with prefault load flow. Readout ofthe fault location can be selected tobe in kilometres, miles or percent ofline length.

    Some versions of the fault locatorcan be mutually compensated ifrequired. This feature can not beused if zero sequence currentpolarising is required for the DEF.

    The fault location board alsocomputes prefault and fault voltagesand currents phase-by-phase.These values, together with negativeand zero sequence current andvoltage can be read out to allowanalysis of the power systemnetwork as it was at the time of

    fault. The duration of the fault is alsodetermined.

    At any time under healthy live lineconditions, the line voltages,currents, watts and vars can becalculated on demand. These valuescan be compared with otherinstrumentation for accuracy.

    As the fault location hardware islargely separate from that of thedistance measuring elements,protection accuracy can be cross-checked with fault location accuracyduring secondary injection tests.

    All voltages and currents are givenwith phase angle relative to prefault

    VA, and rms amplitudes in primaryor secondary terms.

    Figure 9: DEF Protection time delay trip times

    10

    1

    0.1

    OperatingTimet(second

    s)

    1 5 100

    OperatingTimet(second

    s)

    Current (Multipule of s)American curves

    Current (Multipule of s)IEC curves

    100

    Curve 5 US moderate inverse

    Curve 6 US standard inverse

    Curve 7 US very inverse

    Curve 8 US extremely inverse

    Curve 1 S tandard inverse: t = 0.140.021

    Curve 2 Very inverse: t = 13.51

    Curve 3 Ex treme ly inverse: t = 8021

    Curve 4 Longtime earth fault: t = 120

    1

    5

    0.5

    10 50

    50

    1 5 10010 50

    Curve 5

    Curve 6

    Curve 7

    Curve 8

    Curve 4

    Curve 1

    Curve 2

    Curve 3

    10

    0.1

    100

    5

    0.5

    50

    1

  • 5/19/2018 Q

    11/2811

    Figure 10: 50Hz operating times (MHO characteristic)

    Figure 11: 60Hz operating times (MHO characteristic)

    Figure 12: 50Hz operating times (quadrilateral characteristic)

    0.03

    OperatingTime(s)

    0.04

    0.02

    0.00

    0.01

    Fault location (% of relay setting)

    20 40 60 800 100

    0.03

    OperatingTime(s)

    0.04

    0.02

    0.00

    0.01

    Fault location (% of relay setting)

    20 40 60 800 100

    Source impedenceRelay setting = 1

    Minimum

    MeanMaximum

    Mean

    Minimum

    MaximumSource impedence

    Relay setting = 30

    0.03

    OperatingTime(s)

    0.04

    0.02

    0.00

    0.01

    Fault location (% of relay setting)

    20 40 60 800 100

    Maximum

    0.03

    OperatingTime(s)

    0.04

    0.02

    0.00

    0.01

    Fault location (% of relay setting)20 40 60 800 100

    Source impedenceRelay setting

    = 30Source impedence

    Relay setting= 1

    Maximum

    Mean Mean

    Minimum

    Minimum

    0.03

    OperatingTime(s)

    0.04

    0.02

    0.00

    0.01

    Fault location (% of relay setting)

    20 40 60 800 100

    Maximum

    Mean

    MinimumMinimum

    0.03

    OperatingTime(s)

    0.04

    0.02

    0.00

    0.01

    Fault location (% of relay setting)20 40 60 800 100

    Source impedenceRelay setting

    = 30 Source impedenceRelay setting

    = 1

    Maximum

    Mean

  • 5/19/2018 Q

    12/2812

    Self-Monitoring andVoltage TransformerFuse/MCB Supervision

    Optimho has comprehensivecontinuous self-monitoring. If afailure occurs, an alarm is issued byclosing the relay inoperative alarmcontact and extinguishing the relayavailable LED. Diagnosticinformation is automatically

    displayed if the failure is such that itdoes not disable the main processorand LCD.

    Monitoring of the analogue circuitsincludes (i) the dc supply and allinternal dc power supply rails, and(ii) the ac supplies and internalanalogue voltage and currentcircuits (the latter only if the modelof Optimho has voltage transformersupervision).

    The VT supervision logic can be setto block relay operation in the eventof failure of a VT fuse. The VTsupervision logic can be selectedvia the menu to self reset, or toremain sealed in until the resetbutton is pressed. All models havean optically coupled isolator tomonitor the auxiliary contact of aminiature circuit breaker if the VTsupplies are protected by an MCBinstead of fuses. Energising the

    optical isolator blocks relayoperation.

    Figure 13: 60Hz operating times (quadrilateral characteristic)

    In addition, an optional externaldevice for monitoring 3 phase fuseblow via the RELAY BLOCKED opto-isolator is available.

    Monitoring of the digital circuitsincludes (i) bus communications(ii) checking of RAM and EEPROMand (iii) watchdog circuits for everymicrocontroller. In the event offailure, trip signals originating fromthe affected part of the relay are

    blocked.In models with quadrilateral groundfault characteristics, remedial actionis performed if the quadrilateralmeasuring circuits fail.The alternative shaped mho groundfault measuring elements, located ona different board, are automaticallybrought into action to restore theground fault protection. On powersystems where most faults areground faults, this capabilityconsiderably increases the overallavailability of the relay.

    0.03

    OperatingTime(s)

    0.04

    0.02

    0.00

    0.01

    Fault location (% of relay setting)

    20 40 60 800 100

    0.03

    OperatingTime(s)

    0.04

    0.02

    0.00

    0.01

    Fault location (% of relay setting)

    20 40 60 800 100

    Source impedenceRelay setting

    = 30Source impedence

    Relay setting= 1

    Minimum

    Maximum

    Mean

    Maximum

    Mean

    Minimum

  • 5/19/2018 Q

    13/2813

    Contact Arrangements

    Most models are pre-programed togive a choice of at least two outputcontact arrangements. One of theseis arranged to give direct access tothe relays measuring units via theoutput relay contacts, so that acustomers existing protectionscheme can be operated inconjunction with Optimho ifrequired. The other arrangementstake advantage of the Optimhosown integral scheme logic.

    Other Options

    To be specified with order.

    A facility to control the setting groupselected via five optical isolators is

    available on all models.A facility to control the setting groupselected via three optical isolators isavailable on all models. Full schemeoptions are provided and threesetting groups are available.

    Selection Chart 1

    START

    Ground Fault Distance?

    Yes No

    No

    Either of the following:*voltage transformer supervision?*power swing blocking?

    Yes

    Any of the following:*week infeed POR unblocking scheme?*blocking scheme?*back-up for reverse faults?

    Yes No

    LFZP 132With DEF

    OK for open-deltaOr 3limb VTs

    Optional fault locaton

    LFZP 131With DEF

    OK for open-deltaOr 3limb VTs

    Optional fault locaton

    Yes No

    Quadrilateral groundfault elements?

    No

    Any of the following?*weak infeed POR/unblocking scheme?*blocking scheme?*backup for reverse faults?*power swing blocking?

    Yes

    LFZP 121Optional fault

    location

    Yes No

    LFZP 112Optional DEF.

    Optional fault locator

    LFZP 114Optional DEF.

    Optional fault locator

    Any of the following:*single pole tripping?*permissive undereach scheme (PUR)?*permisssive overreach Scheme (POR)?

    *unblocking scheme?*power swing blocking?

    No

    Quadrilateral groundfault elements?

    LFZP 111Optional DEF.

    Optional fault location

    Yes No

    Yes

    In some models specified above, it will be necessary to disable unwanted zonesand facilities with settings on the menu.

    LFZP 122Optional fault

    location

    DEF Scheme?Go tochart 2

    Undergroundcables?

    No

    Yes

  • 5/19/2018 Q

    14/2814

    Selection Chart 2

    Selection Chart 3

    In some models specified above, it will be necessary to disable unwanted zonesand facilities with settings on the menu.

    START

    Yes No

    Go to chart 1

    LFZP 113Optional fault location

    Optional DEF

    LFZP 123Optional fault location

    No DEF

    Yes No

    Underground cables?

    Any of the following?*single pole tr ipping? * blocking scheme?*PUR scheme? * power swing blocking?*POR scheme? * c apacitor voltage*unblocking scheme? transformers?

    START

    Any of the following:*single pole tripping?*power swing blocking?*DEF?

    Either of the following:*offset characteristic?*power swing blocking?

    LFZP 112Optional DEF.Optional fault

    location

    No

    No

    Yes

    Yes No

    Yes No

    Offset characteristic

    LFZP 151No faultlocation

    LFZP 114Optional DEF.Optional fault

    location

    LFZP 122Optional fault

    location

    Either of the following:*offset characteristic?*power swing blocking?

    YesLFZP 131

    with DEF.Optional faultlocation

    LFZP 132

    with DEF.Optional faultlocation

    Offset characteristic?

    No

    Any of the following:

    *ground fault distance?*voltage transformer supervision?*power swing blocking?

    Single Zone Distance?

    Yes

    Go to chart 1

    In some models specified above, it will be necessary to disable unwanted zonesand facilities with settings on the menu.

  • 5/19/2018 Q

    15/2815

    Figure 14: Case connection diagram for relay inputs

    A

    BCPhase rotation

    Direction of power flow for operation

    P2 P1

    S2A

    B

    C

    A B C

    N

    a b c

    Fusesor MCB

    DEF current polarisation when required

    S2

    P1P2

    2A27 2A282A25 2A26

    2B27 2B28

    2B25 2B26

    2B23 2B24

    2B21 2B22

    2A23 2A24

    2A21 2A22

    2A11 2A12

    2A9 2A10

    2A7 2A8

    2A5 2A6

    2A3 2A4

    2A1 2A2

    MMLGTest block orEquivalent

    LFZP 11119

    20

    21

    22

    23

    24

    25

    26

    15

    16

    17

    18

    27

    28

    +

    2B13 2B14 2A13 2A14

    2B 9 2 B1 0

    2B7 2B8

    2B1 2B2

    2B5 2B6

    2B11 2B12

    2B3 2B4

    15 70

    19 74

    3 58

    11 66

    78

    7 62

    23 82

    A13

    CRX

    COX

    RZ1X

    CB AUX

    MCB

    IPD

    R1

    17

    1

    9

    13

    5

    21

    External resistor boxrequired for 220/250V

    supply only

    2A17

    2B17

    2A 18

    2B18

    49

    77

    DC supply

    Signal receive

    Channel out of service

    Rest zone 1 extension

    Breaker open

    Relay blocked

    Inhibit PSB, DEF, WI.

    Reset indications

    Signal send51

    2B20 2B 19

    2A 20 2A 19

    79

    84

    64

    80

    68

    60

    72

    76

    14 2A16 2A15 2B16 2B15

    a

    b

    c

    Fusesor MCB

    Alternative voltagetransformer connectionfor LFZP 131 & 132

    Test block LFZP

    15

    16

    17

    18

    Any Trip

    S1

    Optoisolator inputs when required:

    CRX Open contac t from signalling channe l

    COX Close contact f rom s ignall ing channelRZIX Open contact f rom autoreclose relay

    CBAUX Closed circuit breaker contacts connectedin series to indicate all poles open. Requiredwith busbar VT or if the weak infeed or echofeature of POR scheme are required

    MCB Closed contact from minature circuit breakerrequired when no VT fuses are used

    RI Open contact to reset visual indications

    IPD Open contac t from autoreclose re layrequired with single phase tripping if PSBor DEF options are used. Opto must beenergised during single pole dead times

    For the unblocking mode of operation use CRX forthe unblock frequency (trip frequency) and RZIX

    for the block frequency (guard frequency)

  • 5/19/2018 Q

    16/2816

    Technical Data

    Ratings

    AC voltage Vn: 100 to 120V rms phase-phase

    AC current In: 1A or 5A rms per phase

    Frequency fn: 50Hz or 60Hz

    Operating frequency range: 47 to 51Hz or 56.4 to 61.2 HzDC Supply Vx(1): For switched mode dc/ac/dc power

    supply unit, available in three versions:

    Nominal Operative Maximumrange withstand

    48/54V 37.5 to 60V 64.8V

    110/125V 87.5 to 137.5V 150V

    220/250V 175 to 275V 300V

    There is negligible change of accuracy with change ofvoltage within the operative range of the relay.

    DC supply Vx(2): For optically coupled isolators.Supply options are the same as Vx(1).External resistor box provided for 220/250V version(see Figure 16).

    Maximum overload ratings

    AC voltage: 1.2Vnfor measuring accuracy1.5Vncontinuous withstand2.5Vnwithstand for 10s.

    AC current: 2.4Incontinuous withstand100Inwithstand for 1s (In= 1A)80Inwithstand for 1s (In= 5A)

    Burdens

    AC voltage circuits: 0.1 VA per phase at Vn

    AC current circuits: 0.08 VA per phase (In= 1A)0.5 VA per phase (In= 5A)

    DC supply (1): 18W under healthy live lineconditions at Vx(1) 28W maximum

    DC supply (2): 10mA per energised opticallycoupled isolator at Vx(2).

    Distance elements

    Range of positive sequence settings referred to line VT and CT secondaries:

    All employed zones except reverse Zone 3:

    Overhead line models 0.2 to 250(In= 1A)0.04 to 50(In= 5A)

    Underground cable models 0.1 to 125(In= 1A)0.02 to 25(In= 5A)

    Reverse Zone 3

    Overhead line models 0.04 to 250(In= 1A)

    0.008 to 50(In= 5A)

    Underground cable models 0.02 to 125(In= 1A)and LFZP 151 0.004 to 25(In= 5A)

  • 5/19/2018 Q

    17/2817

    Reach setting method is by digitally controlled analogue attenuators.Attenuation factors KZPh and KZN operate on current signals and arecommon to all zones.

    Attenuation factors KZ1, KZ1X, KZ1Y, KZ2, KZ3 and KZ3 operate onvoltage signals and are specific to Zone 1, Zone 1X, Zone 1Y, Zone 2,Zone 3 forward and Zone 3 reverse respectively. The positive sequencereach for Zone 1 is given by:

    Zone 1 = KZ1. KZPh.5/Infor overhead line models.

    Zone 1 = KZ1. KZPh. 5/2Infor underground cable models.

    Either KZ1 or KZPh is set to 1.000. To obtain the formula for each of theother zones employed, replace KZ1 by the appropriate attenuation factor forthe zone.

    Extra settings for ground fault distance:

    Residual compensation factor:

    KZN=

    ZL0 ZL1KZPh 3ZL1

    Where ZL0and ZL1are the phasor values of zero and positive sequence

    impedance of the protected line.

    Quadrilateral resistive reach settings:

    Right hand reach = KR.5/In

    Left-hand reach = KR.6/In(LFZP 111)

    Left-hand reach = KR.5/In(LFZP 121)

    Range of factors: KZPh 0.040 to 1.000 in steps of 0.001

    KZN 0.000 to 1.360 in steps of 0.001

    KZ1KZ1X

    KZ1Y 1.00 to 49.98 steps of 0.02KZ2KZ3

    KZ3 0.2 to 49.9 in steps of 0.1

    KR 1 to 30 in steps of 1

    Range of setting of Zone 3 lenticular aspect ratio:

    a/b = 1.00, 0.67 or 0.41

    Characteristic angle settings:

    Ph = arg ZL1to nearest available setting.

    Ph = 50to 85in 5steps (overhead line models)

    Ph = 45to 80in 5steps (LFZP 113 only)

    Ph = 20, 25, 30, 35, 40, 50, 60or 70 (LFZP 123 only)

    Vectorial residual compensation for ground fault distance:

    N = arg (ZL0 ZL1) to nearest available setting

    N = 50to 85in 5steps (overhead line models)

    N = 45, 35and 25to 80in 5steps (LFZP 113 and 123 only)

    Note: LFZP 113 is not designed to be used with a ground fault loop setting(2ZL1+ ZL0) /3 with an argument less than 30.

  • 5/19/2018 Q

    18/2818

    Minimum operating values of the distance measuring elements forall types of fault:

    Voltage: zero

    Current: 0.05In/KZPh.

    Accuracy: Reach: 5% at 2Inand 20C

    Dynamic range: up to 25Infor faultlocator and instrumentation up to

    56Infor distance protectionCharacteristic angle: 2

    Resetting ratio: 105%

    Timer ranges: Zone 1X timerZone 1Y timer each timer 0.10s to 9.98sZone 2 timer in steps of 0.02sZone 3 timer

    Scheme co-ordination timers used in permissiveoverreach, unblocking and blocking schemes:

    TP

    TD 0 to 98ms in steps of 2msTDW

    Timer accuracy: 1% of setting and 3ms.

    Operating time: Typical relay operating times for Zone 1 are shown inFigures 10 to 13.

    Mho characteristic (type m, f or c) 50Hz minimum: 14mstypical: 18ms

    60Hz minimum: 12mstypical: 16ms

    Quadrilateral characteristic (type q) 50Hz minimum: 16ms

    typical: 23ms

    60Hz minimum: 15mstypical: 20ms

    Reset time: The trip contacts are sealed in for 60ms following theinitial contact closure. Thereafter, the maximum resettime is 35ms.

    Power swing blocking

    Power swing detected by transit time of impedance between Zone 6 andeither Zone 2 or Zone 3 as selected. Zone 6 is offset mho or offset lenticular,with the same range of forward and reverse reach settings and aspect ratios

    as Zone 3.

    Zone 6 timer range: 20ms to 90ms in steps of 5ms

    Power swing detection regimes:

    (i) detection disabled.

    (ii) detection indicated only.

    (iii) indication plus blocking of any one or moreselected zones.

    Blocking disabled if a ground fault or (if DEF fitted) a phase fault occursduring a power swing.

  • 5/19/2018 Q

    19/2819

    Directional earth fault

    Directional measuring elements: one forward-looking, one reverse-looking:

    Current sensitivity determined by current level detector:0.05Into 0.80Inin steps of 0.05In

    Sensitivity of polarising quantity is 1V residual voltage of1.5% polarising current, as appropriate, depending uponthe type of polarising selected.

    Characteristic angle G = 10to 80in 10steps.Instantaneous trip (available only if no Zone 1 ground fault distanceelements fit):

    Setting range: 0.2Into 30Inin steps of 0.05In

    Accuracy: 5% at fn, 20C

    Aided trippingscheme: Scheme co-ordination timers:

    TPG 0 to 98ms in steps of 2msTDG

    High set current level detector 0.05In

    to 0.80Inin steps of 0.05InTime delay trip: Setting Is= 0.05Into 1.20Inin steps of 0.05In

    Time curves: eight curves and three definite time rangesshown in Figure 9.

    Time multiplier: *t = 0.025 to 1.000 in steps of 0.025

    Accuracy at fn, 20C, *t = 1, Is= 0.05Into 0.80In:

    Current: +10% 0%

    Operating time: definite time 3% over 1.3Isto 31Is

    curves 1, 2, 4, 5, 6, 7, 8 5% over 2Isto 31Is

    curve 3 7.5% over 2Isto 20Is

    Fault location and instrumentation

    Fault location positive sequence settings referred to line VT and CTsecondaries:

    Range: 0.2to 200(In= 1A)0.1to 100(In= 1A) (113/123)

    0.04to 40(In= 5A)0.02to 20(In= 5A) (113/123)

    Setting: Zone F = KZF. KZPh.5/Infor overhead line models.Zone F = KZF. KZPh.5/2Infor underground cable models.

    KZPh and residual compensation are common to the distance measuringelements.

    KZF range: 1.00 to 40.00 in steps of 0.01.

    Line length setting (in miles or km or %)

    0.00 to 99.99 in steps of 0.01

    100.0 to 999.9 in steps of 0.1

    KZM and M are provided for mutually compensating the fault locator ifrequired:

    KZM range: 0.0 to 1.36 in steps of 0.001

    M range: 50to 85in steps of 5

    Accuracy 2% at 2In, fn, 20C.

    Settings to allow for transformer ratios for instrumentation functions:

    CT ratio: 1:1 or 10 to 5000: 1 in 10:1 steps

    VT ratio: 1:1 or 10 to 9990: 1 in 10:1 steps

  • 5/19/2018 Q

    20/2820

    Block or enable reclose logic

    A normally-open or normally-closed contact is supplied on most models toblock or enable reclose respectively.

    The menu allows the following choices of logic:

    Reclose blocked or enabled on:

    Zone 1 or aided trip caused by 2 or 3 phase fault

    Zone 1 or aided trip cased by 3 phase faultZone 1X and/or Zone 1Y and/or Zone 2 timedelayed trip

    Channel out of service

    DEF instantaneous and/or aided trip and/or delayed trip.

    Voltage transformer (fuse fail) supervision

    The voltage transformer supervision (VTS) operates when zero sequencevoltage is detected without the presence of zero sequence current, by meansof the low set neutral level detector. The VTS does not limit the distance relaycurrent sensitivity or operating times for line faults even when the VTS is set toblock relay tripping.

    Nominal Vo detector setting 9.5V

    The blocking action of the VTS on distance comparators can be removed bymenu selection via the user interface.

    Switch-on to fault logic

    Menu choices allow instantaneous trip and alarm and indication for faultsoccurring on line energisation, whether bus or line voltage transformers areused:

    SOTF enabled either 0.2s or 110s after line de-energised

    (110s prevents SOTF action on auto-reclosure).SOTF trip via measuring elements.

    SOTF trip via current and voltage level detectors.

    Output contacts

    Some of the available arrangements are shown in Table 1.

    Ratings:

    Make and carry 0.2s 7500VA subject to a maximaof 30A, 300V, ac or dc.

    Carry continuously 5A ac or dc.

    Break ac: 1250VAdc: 50W resistive

    25W L/R = 0.04sSubject to a maxima of 5Aand 300V

    Durability

    Loaded contact 10,000 operations minimum

    Unloaded contact 100,000 operations minimum

  • 5/19/2018 Q

    21/2821

    High voltage withstand

    Dielectric withstandIEC 60255-5:1977 2kV rms for 1 minute between allANSI C37.90:1978 terminals and case earth.

    2kV rms for 1 minute betweenterminals of independent circuits,with terminals on each independentcircuit connected together.

    1.5kV rms for 1 minute acrossnormally open contacts

    High voltage impulseIEC 60255-5:1977 Three positive and three negative

    impulses of 5kV peak, 1.2/50s,0.5J between all terminals and allterminals and case earth.

    Insulation resistanceIEC 60255-5:1977 >100Mwhen measured at

    500V dc

    Electrical environment

    DC supply interruptionIEC 60255-11:1979 10ms interruption in the auxiliary

    supply under normal operatingconditions, without de-energising.

    High frequency disturbanceIEC 60255-22-1:1988 Class III 2.5kV peak between independent

    circuits and between independentcircuits and case earth.

    1.0kV peak across terminals of the

    same circuit.Electrostatic dischargeIEC 60255-22-2:1996 Class 3 8.0kV discharge in air with cover

    in place

    6.0kV contact discharge withcover removed.

    Fast transient disturbanceIEC 60255-22-4:1992 Class IV 4.0kV, 2.5kHz applied directly to

    auxiliary supply

    4.0kV, 2.5kHz applied directly toall inputs

    Radio frequency interferenceEMC compliances Compliance to the European89/336/EEC Commission Directive on EMC isEN50081-2:1994 claimed via the TechnicalEN50082-2:1995 Construction File route.

    Generic Standards were used toestablish conformity.

  • 5/19/2018 Q

    22/2822

    Atmospheric environment

    TemperatureIEC 60255-6:1988 Storage and transit 25C to +70C

    Operating 25C to +55C

    IEC 60068-2-1:1990 Cold

    IEC 60068-2-2:1974 Dry Heat

    HumidityIEC 60068-2-3:1969 56 days at 93% RH and 40C

    Enclosure protectionIEC 60529:1989 IP50 (dust protected)

    Mechanical environment

    VibrationIEC 60255-21-1:1988 Response Class 1

    SeismicIEC 60255-21-3:1993 Class 1

  • 5/19/2018 Q

    23/2823

    Table 1. Standard output contact case terminal connections

    Terminal LFZP 111, 112, 113, 114(Note 1) LFZP 121, 122, 123 LFZP 131,132 LFZP 151

    29-31 RIA 97Y RIA 97Y RIA 97Y RIA 97Y

    29-33 VTS 97X VTS 97X Def Trip 67N VTS 97X

    29-35 Dist Trip 21 Z Z1 Dist Trip 21 Trip 94T

    37-39 Trip A 94A Trip 94T Trip 94T Trip 94T

    41-43 Trip B 94B Trip 94T Trip 94T Trip 94T

    45-47 Trip C 94C Trip 94T Trip 94T Trip 94T

    49-51 Signal Send 85X Signal Send 85X Signal Send 85X Any Trip 94

    53-55 SOTF 98 SOTF 98 SOTF 98 Start 99

    30-32 Time delayed 21/67N(T) Z1X + Z1Y(T) Z1X/Z1Y(T) Z1X + Z1Y + Z2(T) Z1X/Z1Y/Z2(T) (Note 2)

    30-34 DEF Trip 67N Z2(T) Z2(T) Z3(T) Z3(T) (Note 3)

    30-36 Aided Trip 94Y Z3(T) Z3(T) Def(T) 67N(T)

    38-40 Trip A 94A Aided Trip 94Y Aided Trip 94Y

    42-44 Trip B 94B Trip 94T Any Trip 94

    46-48 Trip C 94C Any Trip 94 Signal Stop 85Y (Note 4)

    50-52 Bar 96 Bar 96 Bar 96

    54-56 Start 99 Start 99 Start 99

    57-59 Trip A 94A

    57-61 Trip B 94B

    57-63 Trip C 94C

    65-67 Trip A 94A

    69-71 Trip B 94B

    73-75 Trip C 94C

    77-79 Any Trip 94

    81-83 PSB 95

    Notes:

    1. When 3 phase tripping scheme is used,94A, 94B, 94C and 94 all respond as 94T.

    2. Z1X/Z1Y(T) in LFZP 132.

    3. Z2(T) in LFZP 132.

    4. Trip 94T in LFZP 132.

    Key to contact functions.

    97Y Relay inoperative alarm. 94Y Aided trip.

    97X Voltage transformer supervision 94 Any trip

    95 Power swing blocking. 94A Trip pole A of breaker.

    21 Distance trip. 94B Trip pole B of breaker.

    67N DEF trip. 94C Trip pole C of breaker.

    98 Switch on to fault trip. 94T Trip all poles of breaker.

    Z1 Zone 1 trip. 96 Block autoreclose.

    Z1X(T) Zone 1X time delay trip. 85X Signal send.

    Z1Y(T) Zone 1Y time delay trip. 85Y Signal stop.

    Z2(T) Zone 2 time delay trip. 99 DEF element operated (forward or reverse)

    21/67N(T) Any time delay trip.or any Zone 1, 2 or 3 element.

  • 5/19/2018 Q

    24/2824

    Figure 15a: Arrangement and outline: Optimho panel mounting vertical

    Figure 15b: Arrangement and outline: Optimho panel mounting horizontal

    T.B.

    T.B.

    T.B.

    25 way 'D' connector detail

    14

    13

    25

    1

    Terminal block detail

    2

    27

    28 28 way maxEach way accepting:-

    2M4 Ring terminalsor24,8 x 0,8Snap-on terminalsor1 Ring+1 Snap-on terminal

    1

    414.00

    177.00

    Hingedpanel

    Rear view

    25 way 'D'connector

    Power supplyM4 earth

    connections

    BoardRef1234567

    89101112137oror

    Description

    Opto isolatorOutput relayOutput relayOutput relayAssy fault locator module3 Zone gnd fault quadSee below

    Level detectorDirectional earth fault1 Zone offset lenticularProcessorAC input 2AC input 12 Zone mho ph & gnd1 Zone mho reversibleZone 3 ph (2 channel)

    Board No.

    ZJ0133ZJ0140 003ZJ0140 001ZJ0140 002GJ0277 000ZJ0132

    ZJ0136ZJ0139ZJ0131ZJ0138ZJ0135ZJ0134ZJ0130ZJ0146ZJ0129

    1234

    Input/Output

    Processing

    ACinput

    Front view

    1213

    2956

    5784

    411.00 362.60

    24.20

    159.00

    168.00

    Panel cut-out detail

    4 Holes4,4

    10.00

    312.00

    32.00

    157.00

    Bottom view

    Front view

    1110

    9 7 58 6

    Ribbon cable

    25 way 'D' connector detail

    14

    13 25

    1

    Terminal block detail

    2

    27 28

    28 way maxEach way accepting:-2M4 Ring terminalsor24,8 x 0,8Snap-on terminalsor1 Ring+1 Snap-on terminal

    1

    T.B. T. B. T. B.

    414.00

    177.00(4U)

    Hinged panel

    Front view

    32.00 312.00

    10.00

    157.00

    Side view

    Rear view

    25 way 'D'connector

    Power supply

    M4 earth connection

    BoardRef123456789

    101112

    137oror

    Description

    Opto isolatorOutput relayOutput relayOutput relayAssy fault locator module3 Zone gnd fault quadSee belowLevel detectorDirectional earth fault1 Zone offset lenticularProcessorAC input 2

    AC input 12 Zone mho ph & gnd1 Zone mho reversibleZone 3 ph (2 channel)

    Board No.

    ZJ0133ZJ0140 003ZJ0140 001ZJ0140 002GJ0277 000ZJ0132

    ZJ0136ZJ0139ZJ0131ZJ0138ZJ0135

    ZJ0134ZJ0130ZJ0146ZJ0129

    1 2 3 4

    Input/Output

    Processing ACInput

    Front view (panel removed)

    5

    67891011

    1213

    29

    56

    57

    84

    411.00362.6024.20

    159.00 168.00

    Panel cut-out detail

    4 Holes 4,4

    Ribboncable

  • 5/19/2018 Q

    25/2825

    Figure 15c: Arrangement and outline: Optimho rack mounting

    Figure 16: Outline - external component box

    25 way 'D' connector detail

    14

    13 25

    1

    Terminal block detail

    2

    27 28

    28 way maxEach way accepting:-2M4 Ring terminals

    or24,8 x 0,8Snap-on terminalsor1 Ring+1 Snap-on terminal

    1

    T.B. T. B. T. B.

    483.00

    465.10

    177.00(4U)

    Hinged panel Front view

    101.60

    37.70

    34.00 312.00

    10.00

    157.00

    Side view

    Fixing slot10,6 long x 7 wide

    1 2 3 4

    Input/Output

    Processing ACinput

    Front view (panel removed) Rear view

    25 way 'D'connector

    Power supplyM4 earth connection

    BoardRef123456

    789

    101112137oror

    Description

    Opto isolatorOutput relayOutput relayOutput relayAssy fault locator module3 Zone gnd fault quad

    See belowLevel detectorDirectional earth fault1 Zone offset lenticularProcessorAC input 2AC input 12 Zone mho ph & gnd1 Zone mho reversibleZone 3 ph (2 channel)

    Board No.

    ZJ0133ZJ0140 003ZJ0140 001ZJ0140 002GJ0277 000ZJ0132

    ZJ0136ZJ0139ZJ0165ZJ0138ZJ0135ZJ0134ZJ0130ZJ0146ZJ0129

    567891011

    12

    13

    28 way maxEach way accepting:2 - M4 ring terminalsor2 - 4,8 x 0,8 Snap-on terminalsor1 - Ring + 1 - Snap-on terminal

    M4 earth connection

    155

    2

    27 28

    Perforated cover

    Channel used whenmounted in Midosscheme. (See note)

    120M4 tapped panel fixing holesscrews not provided10

    121

    15

    36.3

    Terminal screws: M4 x 8 brass cheese head

    with lockwashers are provided

    Note: Where the box is to be fitted into aMidos scheme it should be positionedbetween relays, not at a tier end.Rack mounting schemes require theaddition of joining strips and spacers.

  • 5/19/2018 Q

    26/2826

    Cases

    The relay is housed in a multi-module Midos case suitable for rackor panel mounting, as shown inFigure 15.

    Weight: 15kg.

    Other InformationAn LFZP accessory kit is available tofacilitate commissioning and test.

  • 5/19/2018 Q

    27/2827

    Information Requiredwith Order

    LFZP model required (see SummaryChart page 3)

    Whether DEF required (if optionalfor model selected)

    Whether fault location required(if optional for model selected)

    Nominal current rating In: 1A or 5A

    Frequency fn: 50Hz or 60Hz

    Voltage of dc supply Vx(1):48/54V, 110/125V or 220/250V

    Voltage of dc supply Vx(2):48/54V, 110/125V or 220/250V

    Mounting arrangements: rack, panelhorizontal, panel vertical, semi

    projection

    Whether the block auto-reclosecontact 961 is to be a normally-open or normally-closed contact

    Whether the signal send contact85X-1 is to be a normally-open ornormally-closed contact

    Advice is available when theinformation requested above isdifficult to specify

    Requests for advice should include: current and voltage transformer

    ratios

    positive and zero sequenceimpedances of the protectedfeeder or full details of the feederlengths and construction

    source impedances or fault levelsfor both minimum and maximumplant conditions

  • 5/19/2018 Q

    28/28

    St Leonards Works, Stafford, ST17 4LX England

    Tel: 44 (0) 1785 223251 Fax: 44 (0) 1785 212232 Email: [email protected] Internet: www.alstom.com

    1999 ALSTOM T&D Protection & Control Ltd

    Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure shouldonly be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.

    ALSTOM T&D Protection & Control Ltd cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.

    Publication R4056R 039920 CPS Printed in England.

    ALSTOM T&D Protec tion & Control Ltd