protection basics_r2 (1)
TRANSCRIPT
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 1/90
1GE Consumer & Industrial
ultilin
Protection Fundamentals
By
Craig Wester, John Levine
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 2/90
2GE Consumer & Industrial
ultilin
Outline
• Introductions• Tools
– Enervista Launchpad
– On – Line Store – Demo Relays at ISO / Levine
• Discussion of future classes
• Protection Fundamentals• ANSI number handout, Training CD’s
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 3/90
3GE Consumer & Industrial
ultilin
Introduction
• Speakers: – Craig Wester – GE Multilin Regional Manager
– John Levine – GE Multilin Account Manager
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 4/90
4GE Consumer & Industrial
ultilin
Objective
• We are here to help make your job easier.This is very informal and designed aroundISO Applications. Please ask question.
We are not here to “preach” to you. • The knowledge base on GE Multilin
Relays varies greatly at ISO. If you have aquestion, there is a good chance there are3 or 4 other people that have the samequestion. Please ask it.
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 5/90
5GE Consumer & Industrial
ultilin
Tools
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 6/90
6GE Consumer & Industrial
ultilin
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 7/90
7GE Consumer & Industrial
ultilin
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 8/90
8GE Consumer & Industrialultilin
Demo Relays with Ethernet
• Working with James McRoy and Dave
Curtis
• SR 489
• SR 750
• G30
• MIF II• Training CD’s
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 9/90
9GE Consumer & Industrialultilin
Demo Relays at L-3
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 10/90
10GE Consumer & Industrialultilin
Future Classes• GE Multilin Training will be the 2nd Friday of
every month. We will cover: – March – Basics, Enervista Launchpad, ANSI numberand what they represent, Uploading, downloading,Training CD’s, etc.
– April – 489 Relay
– May – MIF II relay – June - 750 Relay
– July - UR relay basic including Enervista Engineer
– August – UR F60 and F35 relays
– September – G30 and G60 including Transformer andGenerator in same zone
– October – Communications and security
– November - Neutral Grounding Resistors
– December – Ct’s and PT’s
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 11/90
11GE Consumer & Industrialultilin
Protection Fundamentals
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 12/90
12GE Consumer & Industrialultilin
Desirable Protection Attributes
• Reliability: System operate properly – Security: Don’t trip when you shouldn’t
– Dependability: Trip when you should
• Selectivity: Trip the minimal amount to clear thefault or abnormal operating condition
• Speed: Usually the faster the better in terms ofminimizing equipment damage and maintaining
system integrity• Simplicity: KISS
• Economics: Don’t break the bank
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 13/90
13GE Consumer & Industrialultilin
Selection of protective relays requires compromises:• Maximum and Reliable protection at minimum
equipment cost
• High Sensitivity to faults and insensitivity to maximum
load currents
• High-speed fault clearance with correct selectivity
• Selectivity in isolating small faulty area
• Ability to operate correctly under all predictable power
system conditions
Art & Science of Protect ion
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 14/90
14GE Consumer & Industrialultilin
• Cost of protective relays should be balancedagainst risks involved if protection is not
sufficient and not enough redundancy.
• Primary objectives is to have faulted zone’sprimary protection operate first, but if there are
protective relays failures, some form of
backup protection is provided.
• Backup protection is local (if local primary
protection fails to clear fault) and remote (if
remote protection fails to operate to clear
fault)
Art & Science of Protect ion
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 15/90
15GE Consumer & Industrialultilin
Primary Equipment & Components
• Transformers - to step up or step down voltage level
• Breakers - to energize equipment and interrupt fault current
to isolate faulted equipment
• Insulators - to insulate equipment from ground and other
phases
• Isolators (switches) - to create a visible and permanent
isolation of primary equipment for maintenance purposes
and route power flow over certain buses.
• Bus - to allow multiple connections (feeders) to the same
source of power (transformer).
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 16/90
16GE Consumer & Industrialultilin
Primary Equipment & Components• Grounding - to operate and maintain equipment safely
• Arrester - to protect primary equipment of sudden
overvoltage (lightning strike).
• Switchgear – integrated components to switch, protect,
meter and control power flow
• Reactors - to limit fault current (series) or compensate for
charge current (shunt)
• VT and CT - to measure primary current and voltage and
supply scaled down values to P&C, metering, SCADA, etc.
• Regulators - voltage, current, VAR, phase angle, etc.
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 17/90
17GE Consumer & Industrialultilin
Types of Protection
Overcurrent• Uses current to determine magnitude of fault – Simple
– May employ definite time or inverse time curves
– May be slow – Selectivity at the cost of speed (coordination stacks)
– Inexpensive
– May use various polarizing voltages or ground current
for directionality – Communication aided schemes make more selective
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 18/90
18GE Consumer & Industrialultilin
Instantaneous Overcurrent Protection (IOC) &
Definite Time Overcurrent
• Relay closest to fault operates
first• Relays closer to source
operate slower
• Time between operating forsame current is called CTI(Clearing Time Interval)
Distribution
Substation
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 19/90
19GE Consumer & Industrialultilin
(TOC) Coordination
• Relay closest to fault operates
first• Relays closer to source
operate slower
• Time between operating forsame current is called CTI
Distribution
Substation
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 20/90
20GE Consumer & Industrialultilin
• Selection of the curves
uses what is termed as a
“ time multiplier ” or
“time dial” to effectively
shift the curve up or
down on the time axis
• Operate region lies
above selected curve,
while no-operate region
lies below it
• Inverse curves can
approximate fuse curve
shapes
Time Overcurrent Protection (TOC)
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 21/90
21GE Consumer & Industrialultilin
Multiples of pick-up
Time Overcurrent Protection
(51, 51N, 51G)
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 23/90
24GE Consumer & Industrialultilin
Differential
• Note CT polarity
dots
• This is athrough-current
representation
• Perfect
waveforms, nosaturation
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 24/90
25GE Consumer & Industrialultilin
Differential
• Note CT
polarity dots
• This is aninternal fault
representation
• Perfectwaveforms, no
saturation
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 25/90
26GE Consumer & Industrialultilin
Types of Protection
Voltage• Uses voltage to infer fault or abnormal
condition
• May employ definite time or inverse time
curves• May also be used for undervoltage load
shedding – Simple
– May be slow
– Selectivity at the cost of speed (coordinationstacks)
– Inexpensive
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 26/90
27GE Consumer & Industrialultilin
Types of Protection
Frequency• Uses frequency of voltage to detect power
balance condition
• May employ definite time or inverse time
curves• Used for load shedding & machinery
under/overspeed protection – Simple
– May be slow
– Selectivity at the cost of speed can be expensive
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 27/90
28GE Consumer & Industrialultilin
Types of Protection
Power• Uses voltage and current to determine
power flow magnitude and direction
• Typically definite time – Complex
– May be slow
– Accuracy important for many applications
– Can be expensive
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 28/90
29GE Consumer & Industrialultilin
Types of Protection
Distance (Impedance) – Uses voltage and current to determine impedance of
fault
– Set on impedance [R-X] plane
– Uses definite time – Impedance related to distance from relay
– Complicated
– Fast
– Somewhat defined clearing area with reasonableaccuracy
– Expensive
– Communication aided schemes make more selective
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 29/90
30GE Consumer & Industrialultilin
Impedance
• Relay in Zone 1 operates first
• Time between Zones is calledCTI
Source
A B
21 21
T 1
T 2
Z A
Z B
R
X Z L
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 30/90
Generation-typically at 4-20kV
Transmission-typically at 230-765kV
Subtransmission-typically at 69-161kV
Receives power from transmission system and
transforms into subtransmission level
Receives power from subtransmission system
and transforms into primary feeder voltage
Distribution network-typically 2.4-69kV
Low voltage (service)-typically 120-600V
Typical
Bulk
PowerSystem
33GE Consumer & Industrialultilin
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 31/90
34GE Consumer & Industrialultilin
1. Generator or Generator-Transformer Units
2. Transformers
3. Buses
4. Lines (transmission and distribution)5. Utilization equipment (motors, static loads, etc.)
6. Capacitor or reactor (when separately protected)
Unit Generator-Tx zone
Bus zone
Line zone
Bus zone
Transformer zone Transformer zone
Bus zone
Generator
~
XFMR Bus Line Bus XFMR Bus Motor
Motor zone
Protection Zones
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 32/90
35GE Consumer & Industrialultilin
1. Overlap is accomplished by the locations of CTs, the key source forprotective relays.
2. In some cases a fault might involve a CT or a circuit breaker itself, which
means it can not be cleared until adjacent breakers (local or remote) are
opened.
Zone A Zone B
Relay Zone A
Relay Zone B
CTs are located at both sides of CB-fault between CTs is cleared from both remote
sides
Zone A Zone B
Relay Zone A
Relay Zone B
CTs are located at one side of CB-fault between CTs is sensed by both relays,
remote right side operate only.
Zone Overlap
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 33/90
40GE Consumer & Industrialultilin
1. One-line diagram of the system or area involved
2. Impedances and connections of power equipment, system
frequency, voltage level and phase sequence
3. Existing schemes
4. Operating procedures and practices affecting protection
5. Importance of protection required and maximum allowed
clearance times
6. System fault studies
7. Maximum load and system swing limits
8. CTs and VTs locations, connections and ratios
9. Future expansion expectance
10. Any special considerations for application.
What Info is Required to Apply Protection
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 34/90
C37.2:
Device
Numbers
• Partial listing
41GE Consumer & Industrialultilin
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 35/90
42GE Consumer & Industrialultilin
One Line Diagram
• Non-dimensioned diagram showing how
pieces of electrical equipment are
connected
• Simplification of actual system
• Equipment is shown as boxes, circles and
other simple graphic symbols
• Symbols should follow ANSI or IEC
conventions
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 36/90
43GE Consumer & Industrialultilin
1-Line Symbols [1]
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 38/90
45GE Consumer & Industrialultilin
1-Line Symbols [3]
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 39/90
46GE Consumer & Industrialultilin
1-Line Symbols [4]
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 40/90
47GE Consumer & Industrialultilin
1-Line [1]
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 41/90
1-Line [2]
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 42/90
49GE Consumer & Industrialultilin
3-Line
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 43/90
52GE Consumer & Industrialultilin
CB Trip Circuit (Simplified)
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 44/90
CB C il Ci it M it i
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 45/90
56GE Consumer & Industrial
ultilin
CB Coil Circuit Monitoring:
T with CB Closed; C with CB Opened
CB C il Ci it M it i
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 46/90
57GE Consumer & Industrial
ultilin
CB Coil Circuit Monitoring:
Both T&C Regardless of CB state
Current Transformers
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 47/90
58GE Consumer & Industrial
ultilin
• Current transformers are used to step primary system currents
to values usable by relays, meters, SCADA, transducers, etc.
• CT ratios are expressed as primary to secondary; 2000:5, 1200:5,
600:5, 300:5
• A 2000:5 CT has a “CTR” of 400
Current Transformers
St d d IEEE CT R l
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 48/90
59GE Consumer & Industrial
ultilin
• IEEE relay class is defined in terms of the voltage a CT
can deliver at 20 times the nominal current rating
without exceeding a 10% composite ratio error.
For example, a relay class of C100 on a 1200:5 CT means that
the CT can develop 100 volts at 24,000 primary amps
(1200*20) without exceeding a 10% ratio error. Maximum
burden = 1 ohm.
100 V = 20 * 5 * (1ohm)
200 V = 20 * 5 * (2 ohms)
400 V = 20 * 5 * (4 ohms)
800 V = 20 * 5 * (8 ohms)
Standard IEEE CT Relay
Accuracy
St d d IEEE CT B d (5 A )
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 49/90
61GE Consumer & Industrial
ultilin
Standard IEEE CT Burdens (5 Amp)(Per IEEE Std. C57.13-1993)
Current into the Dot Out of the Dot
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 50/90
62GE Consumer & Industrial
ultilin
Current into the Dot, Out of the Dot
Current out of the dot, in to the dot
Voltage Transformers
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 51/90
63GE Consumer & Industrial
ultilin
VP
VS
Relay
• Voltage (potential) transformers are used to isolate and step
down and accurately reproduce the scaled voltage for the
protective device or relay
• VT ratios are typically expressed as primary to secondary;
14400:120, 7200:120
• A 4160:120 VT has a “VTR” of 34.66
Voltage Transformers
T i l CT/VT Ci it
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 52/90
64GE Consumer & Industrial
ultilin
Typical CT/VT Circuits
Courtesy of Blackburn, Protective Relay: Principles and Applications
CT/VT Ci it C i G d
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 53/90
65GE Consumer & Industrial
ultilin
CT/VT Circuit vs. Casing Ground
• Case ground made at IT location
• Secondary circuit ground made at first point of
use
Case
Secondary Circuit
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 54/90
66GE Consumer & Industrial
ultilin
Equipment Grounding
– Prevents shock exposure of personnel
– Provides current carrying capability for the
ground-fault current
– Grounding includes design and construction ofsubstation ground mat and CT and VT safety
grounding
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 55/90
67GE Consumer & Industrial
ultilin
System Grounding
– Limits overvoltages
– Limits difference in electric potential through local
area conducting objects
– Several methods
• Ungrounded
• Reactance Coil Grounded
• High Z Grounded• Low Z Grounded
• Solidly Grounded
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 56/90
68GE Consumer & Industrial
ultilin
1. Ungrounded: There is no intentional
ground applied to the system-
however it’s grounded through
natural capacitance. Found in 2.4-
15kV systems.
2. Reactance Grounded: Total system
capacitance is cancelled by equal
inductance. This decreases thecurrent at the fault and limits voltage
across the arc at the fault to decrease
damage.
X0 <= 10 * X1
System Grounding
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 58/90
70GE Consumer & Industrial
ultilin
5. Solidly Grounded: There is a
connection of transformer orgenerator neutral directly to station
ground.
Effectively Grounded: R0 <= X1, X0
<= 3X1, where R is the systemfault resistance
System Grounding
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 59/90
76GE Consumer & Industrial
ultilin
Basic Current Connections:How System is Grounded
Determines How Ground Fault is Detected
Medium/High
Resistance
Ground
Low/No
Resistance
Ground
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 60/90
77GE Consumer & Industrial
ultilin
Substation Types
• Single Supply
• Multiple Supply
• Mobile Substations for emergencies
• Types are defined by number of
transformers, buses, breakers to provide
adequate service for application
Industrial Substation Arrangements
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 61/90
78GE Consumer & Industrial
ultilin
Industrial Substation Arrangements(Typical)
Industrial Substation Arrangements
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 62/90
79GE Consumer & Industrial
ultilin
Industrial Substation Arrangements(Typical)
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 63/90
Utility Substation Arrangements
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 64/90
81GE Consumer & Industrial
ultilin
Breaker-and-a-half –allows reduction of
equipment cost by using 3 breakers for
each 2 circuits. For load transfer and
operation is simple, but relaying is
complex as middle breaker is responsible
to both circuits
Utility Substation Arrangements
Bus
1
Bus 2
Ring bus –advantage that one
breaker per circuit. Also each
outgoing circuit (Tx) has 2 sources
of supply. Any breaker can be taken
from service without disrupting
others.
(Typical)
Utility Substation Arrangements
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 65/90
82GE Consumer & Industrial
ultilin
Double Bus: Upper Main and
Transfer, bottom Double Main bus
Main bus
Aux. bus
Bus 1
Bus 2
T i e
b r e a k e r
Utility Substation Arrangements
Main
Reserve
Transfer
Main-Reserved and Transfer
Bus: Allows maintenance of any
bus and any breaker
(Typical)
Switchgear Defined
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 66/90
83GE Consumer & Industrial
ultilin
Switchgear Defined• Assemblies containing electrical switching,
protection, metering and management devices• Used in three-phase, high-power industrial,
commercial and utility applications
• Covers a variety of actual uses, including motor
control, distribution panels and outdoorswitchyards
• The term "switchgear" is plural, even whenreferring to a single switchgear assembly (never
say, "switchgears")• May be a described in terms of use:
– "the generator switchgear"
– "the stamping line switchgear"
A Good Day in System
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 67/90
91GE Consumer & Industrial
ultilin
A Good Day in System
Protection……
– CTs and VTs bring electrical info to relays
– Relays sense current and voltage and declare
fault
– Relays send signals through control circuits tocircuit breakers
– Circuit breaker(s) correctly trip
What Cou ld Go Wrong Here????
A Bad Day in System
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 68/90
92GE Consumer & Industrial
ultilin
A Bad Day in System
Protection……
– CTs or VTs are shorted, opened, or their wiring is – Relays do not declare fault due to setting errors,
faulty relay, CT saturation
– Control wires cut or batteries dead so no signal issent from relay to circuit breaker
– Circuit breakers do not have power, burnt trip coil
or otherwise fail to trip
Protect ion Systems Typ ical ly are
Designed for N-1
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 69/90
93GE Consumer & Industrial
ultilin
Protection Performance Statistics
• Correct and desired: 92.2%
• Correct but undesired: 5.3%• Incorrect: 2.1%
• Fail to trip: 0.4%
Contribution to Faults
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 70/90
94GE Consumer & Industrial
ultilin
Contribution to Faults
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 71/90
95GE Consumer & Industrial
ultilin
Fault Types (Shunt)
AC & DC Current Components
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 72/90
99GE Consumer & Industrial
ultilin
AC & DC Current Components
of Fault Current
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 73/90
100GE Consumer & Industrial
ultilin
Variation of current with time
during a fault
Useful Conversions
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 74/90
102GE Consumer & Industrial
ultilin
Useful Conversions
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 75/90
103GE Consumer & Industrial
ultilin
Per Unit System
Establish two base quantities:
Standard practice is to define
– Base power – 3 phase
– Base voltage – line to line
Other quantities derived with basic powerequations
Per Unit Basics
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 76/90
104GE Consumer & Industrial
ultilin
Per Unit Basics
Short Circuit Calculations
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 77/90
105GE Consumer & Industrial
ultilin
Short Circuit Calculations
Per Unit System
Per Unit Value = Actual QuantityBase Quantity
Vpu
= Vactual
Vbase
Ipu = Iactual
Ibase
Zpu = Zactual Zbase
Sh t Ci it C l l ti
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 78/90
106GE Consumer & Industrial
ultilin
Short Circuit Calculations
Per Unit System
Short Circuit Calculations
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 79/90
107GE Consumer & Industrial
ultilin
Short Circuit Calculations
Per Unit System – Base Conversion
Zpu = Zactual Zbase
Zbase = kV 2base
MVA base
Zpu1 = MVA base1 kV 2
base1 X Zactual
Zpu2 = MVA base2 kV 2
base2 X Zactual
Zpu2 =Zpu1 x kV 2base1 x MVA base2
kV 2base2 MVA base1
A St d f F lt
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 80/90
120GE Consumer & Industrial
ultilin
A Study of a Fault…….
Fault Interruption and Arcing
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 81/90
Fault Interruption and Arcing
121GE Consumer & Industrial
ultilin
A Fl h H d
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 82/90
122GE Consumer & Industrial
ultilin
Arc Flash Hazard
Arc Flash Mitigation:
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 83/90
123GE Consumer & Industrial
ultilin
Problem Description
– An electric arc flash can occur if a conductive object getstoo close to a high-amp current source or by equipment
failure (ex., while opening or closing disconnects, racking
out)
• The arc can heat the air to temperatures as high as 35,000 F, andvaporize metal in equipment
• The arc flash can cause severe skin burns by direct heat exposure
and by igniting clothing
• The heating of the air and vaporization of metal creates a pressure
wave (arc blast) that can damage hearing and cause memory loss(from concussion) and other injuries.
• Flying metal parts are also a hazard.
Methods to Reduce
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 84/90
124GE Consumer & Industrial
ultilin
Methods to Reduce
Arc Flash Hazard
– Arc flash energy may be expressed in I2t terms,so you can decrease the I or decrease the t tolessen the energy
– Protective relays can help lessen the t byoptimizing sensitivity and decreasing clearing time
• Protective Relay Techniques
– Other means can lessen the I by limiting fault
current• “Non-Protective Relay Techniques”
Non-Protective Relaying Methods
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 85/90
125GE Consumer & Industrial
ultilin
Non Protective Relaying Methods
of Reducing Arc Flash Hazard
– System designmodifications increase
power transformer
impedance
• Addition of phase reactors
• Faster operating breakers
• Splitting of buses
– Current limiting fuses
(provides partial protection
only for a limited currentrange)
– Electronic current limiters (thesedevices sense overcurrent and
interrupt very high currents with
replaceable conductor links
(explosive charge)
– Arc-resistant switchgear (thisreally doesn't reduce arc flash
energy; it deflects the energy
away from personnel)
– Optical arc flash protection via
fiber sensors – Optical arc flash protection via
lens sensors
Protective Relaying Methods
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 86/90
126GE Consumer & Industrial
ultilin
of Reducing Arc Flash Hazard
– Bus differential protection (thisreduces the arc flash energy by
reducing the clearing time
– Zone interlock schemes where
bus relay selectively is allowed
to trip or block depending onlocation of faults as identified
from feeder relays
– Temporary setting changes to
reduce clearing time during
maintenance
• Sacrifices coordination
– FlexCurve for improvedcoordination opportunities
– Employ 51VC/VR on feeders
fed from small generation to
improve sensitivity and
coordination – Employ UV light detectors with
current disturbance detectors
for selective gear tripping
Arc Flash Hazards
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 87/90
Arc Flash Hazards
128GE Consumer & Industrial
ultilin
Arc Pressure Wave
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 88/90
Arc Pressure Wave
129GE Consumer & Industrial
ultilin
Copy of this presentation are at:
8/10/2019 Protection Basics_r2 (1)
http://slidepdf.com/reader/full/protection-basicsr2-1 89/90
133
GE Consumer & Industrialultilin
py p
www.L-3.com\private\Levine