Proposed Changes to PTCS Air Source Heat Pump Specifications

April 18, 2006 RTF Meeting

Bob Davis, Ecotope

Page 2: Proposed Changes to PTCS Air Source Heat Pump Specifications April 18, 2006 RTF Meeting Bob Davis, Ecotope

Overview of Changes

• PTCS Provider requirements/duties enumerated (major addition)

• Technician reporting requirements more completely described

• Duct location designation made more generic• Controls section slightly expanded and clarified• Refrig. charge section expanded and clarified• Wording changes added throughout to distinguish

between new installs and service

Page 3: Proposed Changes to PTCS Air Source Heat Pump Specifications April 18, 2006 RTF Meeting Bob Davis, Ecotope

PTCS Provider Reqs

• Expanded Section 1• Text addresses PTCS

Provider role– Training on specs

– Data mgmnt

– Tech registry

– Data review

– Field QA

Page 4: Proposed Changes to PTCS Air Source Heat Pump Specifications April 18, 2006 RTF Meeting Bob Davis, Ecotope

Duct Language Changes

• Section 3.2

• Unconditioned/cond-

itioned space language taken out (left up to specific programs to define)

• New section 8.2.3 says new duct systems should meet PTCS tightness requirements

Page 5: Proposed Changes to PTCS Air Source Heat Pump Specifications April 18, 2006 RTF Meeting Bob Davis, Ecotope

Controls Changes/Addition

• Was Section 4.3/4.4; now Section 5• Aux heat staging/sequencing language removed• Added sentence to clearly specify no aux heat

allowed in Stage 1 call• Single capacity compressor: added explicit

sentence saying discharge air sensor control not allowed

• Multi-stage compressor: added option to allow discharge air sensor staging temperature warmer than 85° F (current req) as long as ODT is installed

Page 6: Proposed Changes to PTCS Air Source Heat Pump Specifications April 18, 2006 RTF Meeting Bob Davis, Ecotope

Refrigerant Checks (formerly Section 5.4, now Section 7)

• Complying methods now more specific:– Operating pressures (year-

round)– Capacity check (ditto)– Superheat/subcooling

(summer)

• Documentation– CheckMe– ACRx– New HP start up form– “other approved method”

Page 7: Proposed Changes to PTCS Air Source Heat Pump Specifications April 18, 2006 RTF Meeting Bob Davis, Ecotope

Summary

• Recommend acceptance of revised/amended HP specs

• Need to come up with language for dual-fuel “hybrid” systems

• Need to revise/amend ground/water-source HP specs