project report by manish yadav

Upload: manish-yaduvanshi

Post on 05-Apr-2018

237 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/31/2019 Project Report by manish yadav

    1/53

    UTTAR PRADESH RAJYA VIDYUT UTPADAN NIGAM LIMITED.

    PARICHHA THERMEL POWER PLANT

    JHANSI(U.P.)

    Duration-: From 6 June to 17 July

    SUBMITTED TO-: SUBMITTED BY-:

    ExNiraj Kumar Tiwari Manish YadavEr.Akhileshkumar B.Tech 4

    thyear

    ElectricalEngg.

    Roll No. 09ee25I.E.T M.J.P.R.U BAREILLY(U.P.)

    ACKNOWLEDGEMENTI am extremely thankful & indebted to the numerous UPVUNL Engineers, who

    provided vital information about the functioning of their respective department

    thus helping me to gain an overall idea about the working of organization. I am

    highly thankful for the support& guidance of each of them.

    I am highly indebted to my project guide, Mr. AKHILESH KUMAR (AE), Mr.

    ASHUTOSH PATHAK (JE) for giving me his valuable time and helping me to grasp

    the variousconcepts of switchyard equipments and their control instruments and

    their testing.

    Last but not the least I would like to thank my parents & all my fellow trainees

    who have been a constant source of encouragement & inspiration during my

    studies & have always provided me support in every walk of my life.

  • 7/31/2019 Project Report by manish yadav

    2/53

    MANISH YADAV

    B.TECH FINAL YEAR

    ELECTRICAL ENGINEERINGI.E.T. M.J.P.R.U. BAREILLY (UP)

    PREFACEA thermal power plant uses energy liberated from the combustion of coal and

    uses it to water into steam. This steam is used to convert the mechanical energyinto electrical energy. The steam is used to rotate the turbine which is connected

    to generator which produced uniform electric field, the flux linked with it

    changes, thereby producing e.m.f of varying voltage. Thus an ac power is

    generated.

    In a thermal power plant an electronic control is required for controlling the

    plant. In practical situation we have to check whether ignition of coal taking place

    properly or not, because at a particular time, only fixed amount of coal needs to

    be present in the boiler. Suppose the ignition of coal taking place properly, then

    the amount of coal that accumulates goes on increasing and at particular instant

    can use a blast. Hence electronic control in required.

    Similarly in pressure sensors are required to measure the pressure on the wall

    boiler due to steam and the amount of pressure handling capacity. Thus if the

    temperature of steam increase or amount of pressure steam increase, then the

    pressure exerted on the wall may exceed safety level.So again electronic control is

    required.

  • 7/31/2019 Project Report by manish yadav

    3/53

    INTRODUCTIONAlmost all coal,nuclear, geothermal, solar thermal electric, and waste incineration

    plants, as well as many natural gas plant are thermal. Natural gas is frequently

    combusted in gas turbine as boilers. The waste heat from a gas turbine can be

    raise steam, in a combined cycle plant that improves overall efficiency. Powerplant burning coal, oil, or natural gas are often referred to collectively as fossil-

    fuel power plants. Some bio mass fueled thermal power plant, which do not use

    co- generation are sometimes referred to as conventional power plants.

    Commercial electric utility power station are most usually constructed on a very

    large scale and designed for continuous operation. Electric power plant typically

    three phase or individual-phase electrical generators to produce alternating

    current (ac) electric power at a frequency 50 hz to 60 hz, (which is an ac sine wave

    per second ) depending on its location of world. Other large companies or

    institutions may have only there own usually smaller power plant to supplyheating or electricity to their facilities, especially if heat or steam is created

    anyway for other purpose. Such shipboard power plants are general lower plant

    capacity than full-size electric company plants , but otherwise have many

    similarities except that typically the main steam turbines mechanically turn the

    propulsion propellers, either through reduction gears or directly by same shaft.

    The steam power plant in such ships also providesteam to separate smaller

    turbines driving electric generators to supply electricity in the ship.

    In some industrial, large institutional facilities, or other populated areas, there are

    combined heat and power (CHP) plants, often called co-generation plant, which

    produce both power and heat for facility or districe9 heating or industrial

    applications. AC electrical power can be stepped up to very high voltage for long

    distance transmission with minimum power loss of power. Steam and hot power

    loss energy when pipe over substantial distance, so carrying heat energy by steam

    or hot water is often only worthwhile within a local area of facility., such as steam

    distribution for a ship or industrial facility or hot water in a local municipality.

    HISTORY OF INDUSRTYThe name of power plant is PARICHHA THERMAL POWER PLANT, its foundationwas laid in 1979 and it started producing electricity in 1983. It is a state owed,

    semi-government project. It has six units which are generating electricity. Two of

    110 MW, two of 210 MW and two of 250 MW.So total installed capacity is 1140

    MW. Presently it is 3rd

    ranking project of U.P.

  • 7/31/2019 Project Report by manish yadav

    4/53

    This project is thermal based power project, in which combustion of coal is used

    to convert water to steam and then steam is used to rotate the turbine. The

    rotation drives a AC generator, thereby producing AC power.

    All thermal power project need continuous supply of water thus they are built

    near the river. A dam has been constructed for this purpose of collection of water,by the name of PARICHHA DAM. It is situated on bank of BENTWA river. Coal is

    also required for the project and it is supplied from mines of Bihar.

    The plant is spread in an area of 500 acres of land. The turbine, boiler and their

    associated auxiliaries have been manufactured and supplied by M/s BHEL. All

    protecting instruments have been supplied by M/s KOTA COMPANY. The steel is

    supplied by SAIL & TISCO.

    GENERAL LAYOUT OF THERMAL POWER PLANT

  • 7/31/2019 Project Report by manish yadav

    5/53

    Following equipment are used in power plant-:

    1)Cooling tower 8)Surface condensor

    2)Cooling water pump 9) Intermediate pressure turbine

    3)Transmission line 10)Steam control valve

    4)Step-up transformer 11)High pressure turbine

    5)Electrical generator 12)Deaerater

    6)Low pressure steam turbine 13)Feed water heater

    7)Condensate pump 14)Coal conveyer

    16)Coalpulverizer 23)Economizer

    17)Boiler steam drum24)Air preheater

    18)Bottom ash hooper25)Precipitator

    19)Superheater26) Induced draft fan

    20)Forced draft fan27)Flue gas stack

    21)Reheater

    22)Combustion air intake

    STEAM GENERATOR AND AUXILIARY SYSTEM

  • 7/31/2019 Project Report by manish yadav

    6/53

    Steam generator is a device which convert water into steam. It is not just like

    heating device which we used for domestic purpose. The steam generator of unit

    producesuper heated steam at almost constant temperature of 810 k (kelvine). To

    get such a high temperature water and air heated in multistage process and more

    ever for an efficient steam generator design is little bit more complex in order toget high thermal efficiency. Basically it require three thing, and they are air, water

    and fuel. The basic auxiliary are as follow-:

    PRIMARY AIR FAN-:They are used to insert the fresh air (primary air) from the environment into the

    air pre-heater. The pressure at the out let is less than the pressure at the inlet to

    maximize the flow of fresh air. As during peak hours more steam is required than

    the average, so with the help of these we get the desired flow rate.

    No. of PD fan 2 Supplier: BHEL

    AIR PREHEATER-:The air pre heater warm the incoming air from primary air by fan by transferring

    the heat from the out going flue gas which increase the efficiency of the boiler by

    reducing the usefull heat loss in the flue gas. Even in the winter the temperature

    of the top of the boiler house around 30*C , so in this way we make good use of

    hot air that would otherwise wasted.

    DRAFT SYSTEM-:The air is used for combustion in boiler and the product produce in the boiler is

    released in atmosphere by draft system.These are two type:

    1) Forced draft system

    2) Induced draft system

    FORCED DRAFT SYSTEM-:These fans are used to draw air from the air pre-heater into the boiler. The

    pressure at the outlet is less than the pressure at the inlet to maximize the flow of

    air. The motor is used in the fan is 3 phase induction motor which rotate at very

    high speed approximately 1440 rpm.

    No. of FD fan:2 Supplier:BHEL

    INDUCED DRAFT FAN-:To maintain the flow of waste gas at appropriate rate we installed induced draft

    fan in between electro precipitator and the chimney. It act as the suction fan

    which suck the waste gas from the electrostatic precipitator. It is designed with

  • 7/31/2019 Project Report by manish yadav

    7/53

    the ductwork, economizer, air preheater and air pollution control equipment

    under all operating conditions.

    No. of ID fan-: 3 Supplier: BHEL

    BUNKER-:

    They are the large drum shaped structure body used to collect crshed coal fromthe conveyer belt. They have cone shaped structure at there bottom used to

    transformer the coal under the effect of gravity into feeder. In bunkers any

    unwanted material such as stone are removed from the coal before being transfer

    to feeder.

    FEEDER-:

    They are used to feed the mills. They are just bellow the bunkers and received thecrushed coal from them and transfer it to mills at desired rate. They decide that,

    how much quantity of coal should be delivered to mills.

    MILLS-:Ball mill, a type of grinder, is a cylindrical devise used in grinding of crushed coal

    received from feeders. In the mills coal is grinded to a fine powder from which we

    called as pulverized coal. We pulverized the coal to increase the efficiency of coal,

    because efficiency of coal in finely powdered is higher than its crushed from.

    Power plants mills can operate continuously, fed at one end and discharged at

    other end

    ECONOMISER-:It is nothing but a heat exchanger. In boiler economizers are the heat exchange

    device that heat fluids, usually water, up to but not normally beyond the boiling

    point of that fluid. Economizer are so named because they can make use of

    enthalpy in fluid stream that are hot, therefore increasing the boiler efficiency.

    They are a device fitted to the boiler which save energy by using the exhaust gas

    from the boiler to preheat the cold water used to fill it.

    DEAERATOR-:It is a device that is used for the removal of air and other dissolved gas from the

    feed water to steam-generating boiler. In particular, dissolved oxygen in boiler

    feed water will cause serious corrosion damage in steam system attaching to the

    wall of the metal piping and other metallic equipment and from oxide(rust).

    Water also combine with the dissolved carbonic acid that cause further corrosion.

  • 7/31/2019 Project Report by manish yadav

    8/53

    In unit the deaerator is designed to remove oxygen down to level 6ppb by weight.

    Unit havesprey type deaerator which serve as both deaeration section as wll as

    boiler feed water storage tank.

    No. of deaerator :1 type: sprey type Supplier:BHEL

    FURNACE-:It is large rectangular shaped structure used as the place to burn pulverized coal.

    It transfer energy to the water by chemical reaction of burning pulverized coal.

    The water enters the boiler through a section in the convection process pass

    called the economizer. From the economizer it passes to the steam drum. Once

    the water enters the steam drum it goes down the down comers to the lower

    inlet water wall headers. From the inlet headers the water rises through the

    water walls and is eventually turned into steam due to the heat being generatedby the burners located on the front and rear water walls. As the water is turned

    into steam/ vapor is passed through a series of steam and water separators and

    then dryers inside the steam drum. The steam separator and dryers removes

    water droplet from the steam and the cycle through the water walls is repeated.

    This process is known as natural convection.

    STEAM DRUM-:It is a standard feature of water tube boiler. It is a reservoir of water/ steam at the

    top end of the water tubes. The drum store the steam generated in the water

    tubes and act as the phase separator for the steam mixture. The difference in thedensities between hot and cold water helps in the accumulation of the hotter

    water and saturated steam into the steam drum. It is generally made from high

    carbon steel with high tensile strength and its working temperature around 400*C

    and pressure well above 350 psi(2.4 MPa). The separated steam is taken out from

    the top section of the drum for the upper heating purpose. The watyer which

  • 7/31/2019 Project Report by manish yadav

    9/53

    sseparated out from the steam is collected at the bottom of the steam drum flow

    down through the down comer pipes to header and water drum.

    SUPER HEATER-:The unit have super heater section in the steam generating furnace (boiler). It is a

    device used to covert saturated steam into dry steam of temperature around537*C and pressure of around 600 psi. super heated increases the efficiency of

    steam turbine.

    Type : Radiant type super heater

    REHEATER :As its name indicate, it is a equipment that is used to reheat the steam. After

    losing some temperature and pressure in the high pressure turbine steam is

    return back to re-heater section of the boiler where it regain some temperature

    and pressure. Reheater increase the efficiency of the steam turbine.

    ELECTROSTATIC PRECIPITATOR-:Due to burning of pulverized coal we get bottom ash and fly ash as the by

    product. Bottom ash as its name indicate at the bottom of the boil and removed

    time to time. But flue ash come along with the waste gases we use electrostatic

    precipitator. It remove particle from a flowing gas using the force of induced

    electrostatic charge. ESP are highly efficient device that minimally impede the

    flow of gases through the device, and can easily remove fine particle matter. It

    remove up to 99.5% flue ashes from the waste gases.FLUE GAS STACK-:It is tall vertical, almost cylindrical structure used to deliver waste gases at such

    height so that they can not create pollution.

    No. of chiney:1 height:150 m

    SOOT BLOWER:Continuous or frequent on line cleaning of furnace, boiler, air preheater,

    economizer heating surface is necessary to maintain the performance and

    efficiency. Here soot blower is steam operated.

    TURBINE AND AUXILLIARY SYSTEMThe steam turbine haveauxilliary systems enabling them to work satisfactorily and

    safely. The steam turbine generator being rotating equipment generally has a

    heavy, large diameter shaft. The shaft therefore requires not only supports but

    also has to be kept in the position while running. To minimize the frictional

    resistance to the rotation, the shaft rotates , are lined with a low friction material

  • 7/31/2019 Project Report by manish yadav

    10/53

    like Babbit metal. Oil lubrication is provide to further reduce the friction between

    shaft and bearing surface and to limit the heat generated.

    STEAM TURBINE-:It is mechanical device that extract thermal energy from the pressurized steam,and convert it into rotary motion. The steam turbine is a form of heat engine that

    drives much of its improvement in thermodynamic efficiency through the use of

    multi stage in the expansion of the steam, which result in a closer approach to the

    ideal reversible process. There are three turbines used in power plant-:

    Steam turbine

    1) High pressure steam turbine (impulse type)

    2) Intermediate pressure steam turbine (impulse type)

    3) Low pressure turbine (reaction type)

  • 7/31/2019 Project Report by manish yadav

    11/53

    Systematic flow of fluid impulse and reaction turbine

    In extract type steam turbine, we extract some amount of steam at particular

    temperature to perform some other work. In this unit we extract some steam

    from low, intermediate and high pressure turbine to heat the condensate which

    again feed to the boiler.

    No. of low pressure heater:3

    No. of high pressure heater:4

    Some steam is also extract from high pressure turbine to run boiler feed pump

    known as turbine drive boiler pump.

    RATING-:MW-210

    RPM-3000

    Main steam pressure - 150 kg/cm2

    No. of low pressure turbine - 1

    No. of high pressure turbine - 1

    No of intermediate pressure turbine-1

    Main steam temperature - 537*c

    Insulation class - F

    Gas pressure - 4 bar(G)Type - THR1108/44

    Spec. -IEC:34

    THREE PHAES GENERATOR(TURBO GENERATOR)-:

  • 7/31/2019 Project Report by manish yadav

    12/53

    An electric generator is a device that convert mechanical energy (rotational

    energy of shaft) into electrical energy. It work on the principle of electromagnetic

    induction and generate electricity according to the fairadeys law. The shaft of the

    generator is rigidly coupled with the shaft of the steam turbine. When the shaft of

    steam turbine rotate, the shaft of the generator is also rotate, since this shaft isplaced in magnetic field created by three phase winding at the stator, hence three

    phase electricity is generated.

    RATING-:

    KW - 250000

    P.F. - .85 LAG

    KVA - 294100

    VOLTS - 16500

    STATOR

    AMPS - 10291VOLTS - 299

    ROTER

    AMPS - 2497

    RPM - 3000

    FREQUENCY (hz) - 50

    PHASE - 3

    CONNECTION - YY

    COOLANT - HYDROGEN

    EXCITER-:An electric generator that uses field coils rather than permanent magnets will

    require a current flow to be present in the field for the device to be able to work.

    If the field coils are not powered, the rotor in a generator can spin without

    producing any usable electric energy. To excite the coil of stator winding we have

    a separate arrangement known as exciter. It provide current to the stator winding

    which create magnetic field inside the generator.

    CONDENSER-:the primary purpose of a condenser and circulating water is to remove the latent

    heat from the stem exhausted from the exhaust end of the turbine and to

    transfer the latent heat so removed to the circulating water which is the medium

    for dissipating this heat to the atmosphere. A secondary purpose is to recover the

    condensate resulting from the phase change in the exhaust steam and recirculate

  • 7/31/2019 Project Report by manish yadav

    13/53

    it as the working fluid in the cycle. This purpose is accomplished in to steps. In the

    first step, the condenser is supplied with circulating water which serves as a

    medium for absorbing the latent heat in the condensing exhaust steam. Here the

    source of this circulating water is pochampad dam. In the second step, the heated

    circulating water is rejected to the natural body of water or recirculatedsourcewhich .in turn, transfer the heat to the atmosphere, principally by evaporative

    cooling effect.

    COOLING TOWER-:These tower is used to extract heat from the circulating water by the phenomena

    of evaporation. Hot circulating water from the tubes of the condenser istransferred to the cooling tower with the help of pipes and tunnels. Cooling tower

    pump are erected nearer to the cooling tower to uplift the hot circulating water

    to the top of the tower.

    In an induced draft mechanical cooling tower, atmospheric air enters the louvers

    at the bottom perimeter of the tower, flows up throws the fill, usually counter

    flow to the falling water droplets. And is ejected to the atmosphere in saturated

    condition thus carrying off the operating load of heat picked up in the condenser.

    In convectional tower about 75% of the cooling takes place be evaporation and

    the remainder by heat conduction; the ratio depends on the humidity of theentering air and various factor.

    COOLING WATER MAKE UP:Make must be continuously added to the tower collecting basin to replace water

    lost by evaporation and drift. Here the makeup water must be softened to

    prevent scaling of heat transfer surfaces; this will be accomplished by means of

  • 7/31/2019 Project Report by manish yadav

    14/53

    cold lime softening. Also the circulating water is treated with bi-oxides and

    inhibitors while in use to kill algae, preserve the fill , and prevent metal corrosion

    and fouling. Algae control is accomplished by means of chlorine injection acid and

    phosphate feeds are used for pH control and to keep that surfaces clean.

    ASH HANDLING SYSTEMThere are two types of ash are produced in the combustion of fuel-:

    1) Bottom ash

    2) Fly ash

    BOTTOM ASH-:Bottom ash refers to the non-combustible constitution of coal with traces of

    combustible embedded in forming clinkers and sticking to hot side walls of a coal-

    burning furnace during its operation. The clinker lumps get crushed to small sizes

    by clinker grinders mounted under water and fall down into through from where

    a water ejector takes them out to a sump. From there it is pumped out by suitable

    rotary pumps to dumping yard for away.

    FLY ASH-:Fly ash is one of the residues generated in the combustion of the coal. Fly ash is

    generally captured from the chimney of coal fired power plant, and is one of two

    types of ash that jointly are known as coal ash the other bottom ash is removed

    from the bottom of the coal furnace. Depending upon the source and makeup of

    coal being burned, the components of fly ash vary considerably, but all fly ash

    includes substantial of silicon oxide (SiO2) and calcium oxide (CaO), both beingendemic ingredients in many coal bearing rock strata.

    FLY ASH CLLECTION AND DISPOSAL-:Fly ash is captured and removed from the flue gas by electronic precipitator or

    fabric bag filters located at the outlet of the furnace and before the induced draft

    fan. The fly ash is periodically removed from the collection hoppers below the

    precipitators or bag filters. Generally, the fly ash us pneumatically transported to

    storage silos for subsequent transport by trucks or railroad cars.

    BOTTOM ASH COLLECTION AND DISPOSAL-:At the bottom of the furnace, there is a hopper for collection of bottom ash. This

    hopper is always filled with water to quench the ash and clinkers falling down

    from the furnace. Some arrangements is included to crush the clinkers and

    bottom ash to a storage site.

    OTHER SYSTEMS

  • 7/31/2019 Project Report by manish yadav

    15/53

    1.MONITERING, CONTROL AND ALRM SYSTEM:Most of the power plant operational control are automatic. However, at times,

    manual intervention may be required. Thus the plant is provided with monitors

    and alarm systems that alert the plant operators when certain operating

    parameters are seriously deviating from their normal range. In unit we have acontrol unit at the floor where turbine- generator is located. That control unit

    have connection from all over the plant. In that control unit we have technician as

    well as supervisor to supervise the smooth running of the plant. If any thing is

    going wrong, or not working, they get information about that fault in their

    system. And then some person will go that section or to replace tat section.

    2. BATTERY SUPPLIED, EMERGENCY LIGHT AND

    COMMUNICATION-:

    A central battery system consisting of lead acid cell units is provided to supplyemergency electric power, when needed to essential items such as the power

    plants control systems, communication systems, damage free shut down of the

    units in an emergency situation.

    3.BUS DUCT-:At the turbo generator, the electricity which produced is of very high current. To

    carry this high current electricity to step-up transformer we used bus duct.

    Bus duct are special type of transmission equipment capable to handle very high

    value of current (bus duct transmit electricity of 16200 amps).

  • 7/31/2019 Project Report by manish yadav

    16/53

    PROJECT REPORT

    ON

    SWITCH YARD

  • 7/31/2019 Project Report by manish yadav

    17/53

    1.INTRODUCTION-:A switchyard is essentially a hub for electrical power sources. For instance a

    switchyard will exist at a generating station to coordinate the exchange of power

    between the generators and the transmission lines in the area. A switchyard will

    also exist when high voltage lines need to be converted to lower voltage for

    to consumers.From switch yard power is distributed to the variousdepartment of

    power plant and supplied to grid.Switchyard consists of the airinsulated

    aluminium bus type and of highvoltage SF6insulated dead tank circuitbreakers

    arranged in a ring bus configuration.Each circuit breaker are equipped with a no-

    load breaker, air insulated switch on eachside.An isolating disconnect switchare

    installed in eachgenerator transformerconnection to the bus.Inswitchyard, a

    power transformer is used to step up or step down the voltage.Current voltage

    transformers are located at points within the switch yard to provide for metering

    and relaying. Control,protection and monitoring for the switch yard will be

    located in the switch yard relay room of electrical building. Interface with SCADA

    system are provided. The communication between the facility switch yard and the

    control building facilitated.

  • 7/31/2019 Project Report by manish yadav

    18/53

    ONE LINE DIAGRAM OF 400KV SWITCH YARD

  • 7/31/2019 Project Report by manish yadav

    19/53

    ABOUT-:

    Switchyard is located 30 meters east of the main power house building.400 kV

    switchyard is having two numbers of double main and one transfer bus system. It

    consist of 8 bay which contains two interconnecting transformer (ICT), isolator,

    circuit breaker, earth switches, wave trap, current transformer, capacitor voltage

    transformer etc. 400 kV is designed to limit the switching surge over voltage to

    2.5 p.u. and sustain surge over voltage to 1.5 p.u.

    The symmetrical fault current is 40 kA (rms). The basic insulation level (BIL) is

    1425 kV. The switching surge is 1050 kV. Each bus comprise of three phase strung

    buses with two sub conductors per phase. ACSR MOOSE conductors are used for

    stringing on the gentries of the switchyard. It is tied up with double tension string

    assembly in twin bundles with 100mm sub conductor spacing. For connecting the

    breaker with isolator 4 IPS aluminum tubular buses in each bay are used. Twoconnect the main bus 1 to main bus 2 with bus coupler which is stable on bay 5.

    But there are no 400 kV line so the power is transmitted to 220 kV line to various

    area.

    1)The three line of 220 kV is transmitted to BANDA.

    2)The two line of 132 kV is transmitted to MAINPURI.

    SWITCHYARD TYPE-:(i)Conventional Air Insulated Type

    (ii)Gas Insulated Type

    (iii)Hybrid Type

    (I)Conventional Air Insulated Type-:

    In Air Insulated Switchyard busbars and connectors are visible. In this

    switchyardCircuit Breakers and Isolators, Transformers, Current Transformers

    Potential Transformers etc. are installed in the outdoor. Busbars are supported

    on the post Insulators or Strain Insulators. Substations have galvanized steel

    structures for supporting the equipment, insulators and incoming and outgoing

  • 7/31/2019 Project Report by manish yadav

    20/53

    lines are the primary criteria for these switchyard andoccupy a large area for

    installation.

    (II)Gas Insulated Type-:In Gas Insulated switchyard variousequipments like Circuit Breakers, Current

    Transformers, Voltage Transformers, Busbars, Earth Switches, Surge Arrestor

    Isolators etc are in the form of metal enclosed SF6 gas modules. The modules are

    assembled in accordance with the required Configuration. The various live parts

    are enclosed in the metal enclosures (modules) containing SF6 gas at high

    pressure. Thus the size of Power Substation reduces to 8% to 10% of the air

    insulated power substation.

    (III)Hybrid Type-:Hybridswitchyard are the combination of both conventional and Gas

    insulated substation. Some bays in a switchyard are Gas Insulated Type

    and some are air insulated type. The design is based on convenience, Local

    Conditions available, area available and Cost.

  • 7/31/2019 Project Report by manish yadav

    21/53

    DISCUSSIONS OF SWITCHYARD SCHEMES-:

    SCHEME 1-:Main and Transfer Bus Scheme

    SCHEME 2-:

    Sectionalised double main and transfer bus

  • 7/31/2019 Project Report by manish yadav

    22/53

    SCHEME 3-:

    One and half breaker scheme

    EQUIPMENT USED IN SWITCHYARD-:

    1)POWER TARNSFORMER

  • 7/31/2019 Project Report by manish yadav

    23/53

    2)BUS BAR

    3)ISOLATOR

    4)EARTH SWITCH

    5)CIRCUIT BREAKER

    6)LIGHTENING ARRESTOR

    7)CURRENT TRANSFORMER

    8)CAPACITIVE VOLTAGE TRASFORMER

    9)WAVE TRAP

    10)PROTECTIVE RELAYS

    11) CORONA RING

    12)SCADA SYSTEM

    1.POWER TRANSFORMERTransformer is a static equipment, which converts electrical energy from one

    voltage to another.There are two power transformer used for generating and transmission of power

    supply one which generating transformer and another is interconnecting

    transformer.

    GENERATING TRANSFORMER-:The power delivered from the turbo-generator is step up by generating

    transformer to high voltage. The star-delta connection is used . The voltage are

    step up from 16.5Kv to 400kv.

    RATINGS-:Types of cooling - ONAN ONAF OFAF

    Rated power - HV IV LV

    (MVA) 189 252 315

    Rated voltage - 400 16.5

  • 7/31/2019 Project Report by manish yadav

    24/53

    (KV)

    Type - Auto transformer

    Vector group - YNd11

    Frequency - 50

    (HZ)No of phase - 3

    TRANSFORMER CONSTRUCTION-:

    CORE-:Core is manufactured from lamination of solid grain oriented silicon steel, which

    gives very low specific loss at operating flux densities. joints of the lamination are

    designed such that the electromagnetic flux is always in the direction of grainorientation. The core clamping structure is designed such that it take cares of all

    the forces produced in the winding in the event of any short circuit.

    WINDING-:1)Windings are made from paper insulated copper conductors which are

    transposed at regular intervals throughout the winding for ensuring equal flux

    linkage and current distribution between strands.

    2)interleaved or shielded construction is adopted for the high voltage windngs to

    ensures uniform distribution of impulse voltage. Insulation spacers in the winding

    are arranged such that oil is directed through the entire windings for ensuring

    proper cooling.

    COOLING-:For ONAN/ONAF cooling, oil flows through winding and external cooler unit

    attached to the tank by thermo-syphonic effect.

    For OF AF/OD AF/OF WF cooling, the oil is directed through the winding by oil

    pumps provide in the external cooling unit.

    External cooler units consists of pressed steel sheet radiators mounted directly on

    the tank or separate cooler banks for air cooled transformers and oil to water

    heat exchangers for water cooler transformers.

  • 7/31/2019 Project Report by manish yadav

    25/53

    CONSERVATOR-:Conservator are provided to take care of the expansion and contraction of

    transformer oil, which takes place during normal operation of the transformer.

    Wherever specified flexible separators or air cell if provided in the conservator

    can prevent direct contact of air with the transformer oil.

    A smaller oil expansion vessel is provided for the Off Load Tap Changer.

    Magnetic oil level gauge is fitted on the main conservator which can give alarm

    /trip in the event of the oil level falling below the pre-set levels due to any reason.

    PRESSURE RELIEF DEVICE-:A device for avoiding high oil pressure build inside the transformer during fault

    conditions is fitted on the top of the tank. The pressure relief device allows rapid

    release of excessive pressure that may be generated in the event of serious fault.

    This device is fitted with an alarm/trip switch.

    A bright colour coded mechanical indicator pin in the cover moves with the valve

    disc during the operation of the pressure relief device and is held in position by an

    O ring in the pin bushing .The indicator may be reset manually by pushing itdownward until it reset on the valve disc.

    GAS & OIL ACTUATED (BUCCHOLZ) RELAY-:Gas and oil actuated relay is fitted in the feed pipe from the transformer tank to

    the expansion vessel for collection of gas. If generated in the oil. The relay

    operates on the fact that almost every type of the fault in an oil immersed

    transformer gives rise to generation of gas. This gas is collected in the body of the

    relay, and is used to closed the alarm switch. In the event of any severe fault, the

    sudden increase in oil pressure causes an oil surges towards the expansion vesseland this is used to closed the trip contacts. This oil surges will impinge on the flap

    fitted to trip element causing it to rotate about its axis and thus bringing the

    mercury switch to the closed circuit position, which in turn operates the tripping

    device.

  • 7/31/2019 Project Report by manish yadav

    26/53

    In the event of serious oil loss from the transformer, both alarm and trip elements

    operate in turn in the manner previously described for gas collection.

    Two brass petcocks are fitted at the top of the relay body, the outlets of which are

    threaded to take a bleed pipe if required for collection of gas samples.

    SILICAGEL BREATHER-:Expansion and contraction of oil cause breathing action. The silicageldehydrating

    breather absorbs any humidity in the air breathed. An oil seal in the air intake

    prevents external moisture being absorbed when no breathing occurs.

    The breather container is filled with silica gel crystals. It is arranged such that the

    air breathed must pass through it. The desiccant contains blue and white crystals.

    When the silica gel is fully active, the blue crystals will have a deep blue colour

    and changes to pink as it absorbs moisture. When saturated with moisture and

    the charge contained should be replaced. The gel removed from the breather may

    be arranged for regeneration and preserved for future use.

    WINDING TEMERATURE INDICATORS-:The winding temperature relay indicates the winding temperature of the

    transformer and operates the alarm, trip and cooler control contacts. This

    instrument operates on the principle of thermal imaging and it is not an actualmeasurement.

    Winding temperature indicator consists of a sensor bulb in oil filled pocket in the

    transformer tank cover. The bulb is connected the instrument housing by means

    of two flexible capillaries tubes. One capillary is connected to the measuring

    bellow of the instrument and the other to a compensation bellow. The measuring

    system is filled with a liquid, which changes its volume with rising temperature.

    OIL TEMPERATURE INDICATOR-:The oil temperature indicator consist of a sensor bulb, capillary tube and a dial

    thermometer, the sensor bulb is fitted at the location of hottest oil. The sensor

    bullb and capillary tube are fitted with an evaporation liquid. The vopour pressure

    varies with temperature and is transmitted to a bourden tube inside the dial

  • 7/31/2019 Project Report by manish yadav

    27/53

    thermometer, which moves in accordance with the change in pressure, which is

    proportional to the temperature.

    BUSHING-:The high voltage connections pass from the windings to terminal bushing.Terminal bushing upto 36 kv class, 3150 amperes, are normally of plain porcielain

    and oil communicating type. the oil inside the condenser bushing will not be

    communicating with the oil inside transformer.

    While connecting the overhead transmission line conductor to the bushing

    terminal, ensure that the line pull is limited to the cantilever strength of the

    bushing. The cantilever strength of bushing as per IS:

    2099 for various types of bushing are as shown below.

    Rated voltage

    (kv)

    Cantilever strength(kg.)

    3150 (amps)

  • 7/31/2019 Project Report by manish yadav

    28/53

    Tap changers of power transformer are specifically of two types-

    1.On Load Tap Changer

    2.Off Load tap Changer

    OFF LOAD TAP CHANGER-:In the case of off load tap changer, tap changing takes only when the transformer

    is de-energized. The equipment consists of an operating handle, pointer, a non

    corrosive indicator plate and a latch. Taps can be changed by lifting the latch and

    turning the handle. The latch will drop into place on the indicator plate when the

    new position is reached. A flat and pin that fills into a slotted sleeve on the drive

    shaft connects the external mechanism with the internal tap changer. A stuffing

    box seals against oil leakage around the operating handle shaft. A pair of heavy

    copper bars supported from the operating shaft from the moving contacts. The

    stationary contacts are mounted on a bakelite panel with tap leads connected tothem.

    The Generating Transformer is OFF-LOAD tap changer.

    ON LOAD TAP CHANGER-:ON-LOAD tap changer is the device for changing the tapping connection of a

    winding. Whilest the transformer is on load.

    The on load tap changer will be a self-contained unit housed in the main

    transformer tank. Since some amount of arcing takes place during the switching

    operations from one tap to other, the oil inside the tap selector will deterioratedfaster. Hence, this oil cannot be allowed to mix with the oil in the main

    transformer. On load tap changer is provided with a separate conservator and oil

    surge relay.

    The tap changer is operated by a motor operated driving mechanism by local are

    remote control and a handle is fitted for manual operation emergency.

    The tap changer can be designed for changing the taps.

    1. Manually

    2. Automatically

    3. From remote

    INTECONNECTING TRANSFORMER-:It receives the power from the generating transformer at high voltage. It also an

    auto-transformer and has delta-star connection. It has three terminal HV, IV and

  • 7/31/2019 Project Report by manish yadav

    29/53

    LV. HV side is 400kv, IV side is 220kv and IV side is 33kv. The construction are

    going to same as generating transformer.

    RATINGS-:

    Types of cooling - ONAN ONAF OFAFRated power - HV IV LV

    (MVA) 189 252 315

    63 84 105

    Rated voltage - 400 220 33

    (KV)

    Rated current - 273.12 496.59 1103.52

    (A)364.16 662.11 1471.36455.20 827.64 1839.20

    Type - Auto transformerVector group - YNd11

    Frequency - 50

    (HZ)

    Insulation level - SI1050 LI950 LI950

    (KV) LI1300 AC 38

    AC 38 AC 95

    No of phase - 3

    Core & coil mass - 1,30,000

    (kg)Tank & fitting mass - 70,000

    Mass of oil - 77,000

    Total mass - 2,77,000

    Volume of oil - 86,500

    Max. temperature - tap oil 50

    rise over an *c 55

    ambient of 50 *C AVG WDG. 55 55 55

    MAX NORM MIN

    There are some other transformer are used to drive equipment stabled in power

    plant. These transformer are listed below-:

    1) Unit auxiliary transformer

    2) Station auxiliary transformer

  • 7/31/2019 Project Report by manish yadav

    30/53

    UNIT AUXILIARY TRANSFORMER-:This is step down transformer with transformation ratio of generator terminal to

    unit auxiliary voltage (16.5/6.6kv) with an ON-LOAD tap changer.

    STATION AUXILIARY TRANSFORMER-:This is a step down transformer with transformation ratio of grid voltage to the

    station auxiliary supply level (220/6.6kv) with ON-LOAD tap changer.

    2.BUS BAR-:In the event distribution for a large installation is at higher than generator

    voltage, e.g. 34.5 kV, or in the event an interconnection with a local utility is

    necessary, a switchyard will be required. The switching structure will be erected

    to support the insulators, disconnecting switches, potential and currenttransformer, and the terminations for the generator step-up transformer and

    transmission line.

    Structure of galvanized steel or aluminum are most often used. Where the switch

    yard is located close to ocean, the salt laden atmosphere may be extremely

    corrosive to aluminum requiring the use of galvanized steel.

    Either copper or aluminum, tubular buses will be employed depending upon the

    atmosphere, with aluminum generally begins less expensive. Copper bus

    economics will be bolted; aluminum connection must be welded. For isolated oroverseas establishment, only copper buses should be used. A corrosive

    atmosphere will preclude the use of aluminum.

    3.ISOLATOR-:In electrical engineering , a disconnector or isolator switch is used to make sure that an

    electrical circuit can be completely de-energized for service or maintainence . such switches

    are often found in electrical distribution and industrial application where machinery must

    haveits source of driving power removed for adjustment or repair. High voltage insulation

    switch are used in electrical switchyard toallow isolation of apparatus such as circuit

    breaker and transformer and transmission line for maintainence.

    In switchyard following type isolator are used-:

  • 7/31/2019 Project Report by manish yadav

    31/53

    1)Sequential L isolator

    2)Pantograph isolator

    SEQUENTIAL ISOLATOR-:The sequential isolators two post type in which the moving contacts movesthrough 90* on its axis.

    PANTOGRAPH ISOLATOR-:

    The pantograph isolator has two moving contact arms designed in scissor like fashion, which

    move only 20* on its axis. While closing, the linkages of pantograph are brought nearer by

    rotating the insulator column. In closed position the upper two arms of the pantograph closed

    on the overhead station bus bar giving a grip. The current is carried by upper bus bar to lower

    bus bar through the conducting arms of the pantograph. While opening, the rotating insulator

  • 7/31/2019 Project Report by manish yadav

    32/53

    column is rotated about its axis. Thereby the pantograph blades collapse in in vertical plane

    and vertical isolation is obtained between line terminal and pantograph upper terminal.

    Pantograph isolators cover less floor area. Each pole can be located at a suitable point and the

    three poles need not be one line, can be located in a one line at desired angle with the bus

    axis.

    RATING-:

    Type - PG

    voltage (kv) - 420

    BIL (kv) - 1425

    Switching IMP (kv) - 1050

    Pf (kv) - 520/610

  • 7/31/2019 Project Report by manish yadav

    33/53

    Weight (kg) - 470

    STC KA/SEC (IK/TK) - 40KA/ 1SEC

    Frequency (hz) - 50

    Current (A) - NA

    Type of drive - R.G. BOM

    Control voltage (DC) - 220 kv

    Weight of drive (kg) - 130

    Motor voltage (v) - 415

    4.EARTH SWITCH-:

    Earth switches are devices which are normally used to earth a particular system to avoid any

    accident which may happen due to induction on account on live adjoining circuit. These do

    not handle any appreciable current.

    RATING-:

    Type - HCB

    voltage (kv) - 420

    BIL (kv) - 1425

    Switching IMP (kv) - 1050/1145

    Pf (kv) - 520/610

    Weight (kg) - 780

    STC KA/SEC (IK/TK) - 40KA/ 1SEC

    Frequency (hz) - 50

    Current (A) - NA

    Type of drive - R.G. BOM

    Control voltage (DC) - 220 kv

    Weight of drive (kg) - 40

  • 7/31/2019 Project Report by manish yadav

    34/53

    5.CIRCUIT BREAKER-:

    A circuit breaker is automatically operated electrical switch designed to protect an electrical

    circuit from damaged caused by overload or short circuit. Its basic function is to detect the

    fault condition and, by interrupting continuity, to immediately discontinue electrical flow.

    Unlike a fuse, which operates once and then has to be replaced, a circuit breaker can be reset(either manually or automatically)to resume normal operation. Circuit breaker are made in

    varying sizes, from small device that protect an household appliance up to large switch gear

    designed to protect high voltage circuits feeding an entire city. Once a fault is detected,

    contacts within the circuit breaker must open to interrupt the circuit, some mechanically-

    stored energy contain within the breaker is used to separate the contacts, although some of

    the energy required may be obtained from the fault current itself. small circuit breaker may

    be manually operated, larger units have solenoids to the trip mechanism, and electric motor

    to restore energy of the springs.

    The circuit breaker contacts must carry the lad currents without excessive heating, and must

    also withstand the heat of the arc produced when interrupting the circuit. Contacts are made

    of copper or copper alloys, silver alloys and other materials. When a current is interrupted, an

    arc is generated. This arc may be contained, cooled and extinguished in a controlled way, so

  • 7/31/2019 Project Report by manish yadav

    35/53

    that the gap between the contacts can again withstand the voltage in the circuit. Different

    circuit breaker is use vacuum, air, insulating gas or oil as the medium in which the arc forms.

    TYPES OF CIRCUIT BRAEKER-:

    High voltage breaker are nearly always solenoid operated, with the current sensing protective

    relays operated through current transformers.

    High voltage breaker are broadly classified by the medium used to extinguish the arc.

    1) Bulk oil

    2) Minimum oil

    3) Ail blast

    4) Vacuum

    5) Sf6

    In switchyard only sf6 circuit breaker is used. The breaker uses sf6 (sulpher-hexa fluoride) for

    extinction purpose. The gas has an excellent current interrupting and insulating properties,

    chemically, it is one of the most stable compound in the pure state and under normal

    condition it is physically inert, non-flammable, non-toxic and odor less and there is no danger.

    Sf6 breaker called as maintenance free breaker, has simple construction with few moving

    parts:

  • 7/31/2019 Project Report by manish yadav

    36/53

    The fission products created during breaking and not fully recombined are, either precipitated

    as metallic fluoride or absorbed by a static filter which also absorbs the residual moisture.

    Since no gas is exhausted from the breaker and very little compressed air is required for

    operation. Since sf6 gas is inert and stable at normal temperature, contacts do not settler from

    oxidization or other chemical reaction, where in oil or air type breakers oxidation of contacts

    would cause high temperature rise.

    During the arcing period sf6 is blown axially along the arc. The gas removes the heat from the

    arc by axial convection and radial dissipation. As a result, the arc diameter reduces during the

    decreasing mode of the current wave. The diameter becomes small during the current zero

    and the arc extinguished. Due to its electro negativity, and low arc time constant, the sf6 gas

    regains its dielectric strength rapidly after the current zero, the rate of rise of dielectric strength

    is very high and the time constant is very small.

    RATING OF SF6 CIRCUIT BREAKER-:

    Company name - AREVA

    Type - GL 316

    Rated voltage (KV) - 420

    Normal current (A) - 2000

    Frequency (HZ) - 50Voltage across openContact (KV rms) - 610

    to earth (KV rms) - 520

    Lightening impulse with Stand v (KVp) - 1425

    Switching surge withstand v (KVp) - 1050

    First pole to clear factor - 1.3

    Short time withstand current (KA) - 40

    Duration of short circuit (S) - 0 1

    Short circuit breaking current

    Symmetrical (KA) - 40

    Asymmetrical (KA) - 49

  • 7/31/2019 Project Report by manish yadav

    37/53

    Short circuit making current (KVAp) -100

    Out of phase breaking current (KArms) -10

    Operating sequence - 0-0.3 S - W3 min - W

    Line charging breaking current (A) - 600

    Sf6 has pressure at 20*c , 1013hpa - 0 8.5

    (MPa)

    6.LIGHTENING ARRESTOR-:High voltage power system experiences overvoltage that arise due to natural lightening or the

    inevitable switching operation. Under these overvoltage conditions, the insulation of the

    power system equipment are subjected to electrical stress which may lead to catastrophic

    failure.

  • 7/31/2019 Project Report by manish yadav

    38/53

    Broadly, three type of over-voltages occure in power system :

    1) Temporary over-voltage

    2) Switching over-voltage

    3) Lightening over-voltage

    The duration of three over-voltages vary in the range of microseconds to sec depending upon

    the type and nature of over-voltages.

    Conventionally, the over-voltageprotection is obtain by the use of lightening/ surge arrestors.

    Under normal operating voltages, the impedance of lightening arrestor, placed in the parallel

    to the equipment to be protected, is very high and allow the equipment to perform its

    respective function. Whenever the over voltage appears across the terminals, the impedance

    of the arrestor collapses in such a way that the power system equipment would not

    experiences the over-voltage. As soon the overvoltage disappears, the arrestor recovers its

    impedance back. Thus the arrestor protects the equipment from the over-voltage.

    7.CURRENT TRANSFORMER-:

    Current transformer (CT) are instrument transformer that are used to supply a reduced of

    current to meters, protective relays, and other instruments. CTs provide isolation from high

    voltage primary, permit grounding to the secondary for safety, and step-down the magnitude

    of the measured current to a value that can be safely handled by the instruments.

    TYPE-:

    1)The CTs shall be of ring type or window type.

    2)The secondary leads shall be terminated within with copper rose contact terminals with

    arrange for sealing purpose.

    3)Polarity (both for primary and secondary lead) shall be marked.4)The CT shall be varnished, fiberglass tape insulated or cast resin, air cooled type. only super

    enameled electrolytic grade copper wires shall be used.

  • 7/31/2019 Project Report by manish yadav

    39/53

    TECHNICAL DETAIL-:

    1 Higher system voltage KV 245

    2 Short time current KA 40 for 3 sec

    3 Frequency HZ 50

    4 Insulation level KV/KVp 460/1050

    5 Class of accuracy 0.5

    6 Supply system 3ph solidly grounded neutral system

  • 7/31/2019 Project Report by manish yadav

    40/53

    8.CAPACITOR VOLTAGE TRANSFORMER-:

    In high and extra high voltage transmission system, capacitor voltage transformers (CVTs) are

    used to provide potential outputs to metering instruments and protective relays. In addition,

    when equipped with carrier accessories, CVT can used for power line carrier (PLC) coupling.

    A capacitive voltage transformer (CVT) is a transformer used in power system to step down

    extra high voltage signals and provide low voltage signals either for measurement or to

    operate a protective relay. In the most basic form the device consists three main part :

    Two capacitors across which the voltage signal is split, and inductive element is used to tune

    the device to the supply frequency and a transformer used to isolate and further step down

    the voltage for instrumentation or protective relay. The device has at least four terminals, a

    high voltage terminals for connection of high voltage signal, a ground terminal and at least one

    set of secondary terminals for connection to the instrumentation or protective relay. CVTs are

    typically single phase device used for measuring voltage in excess of on hundred kilovolts

    where the use of voltage transformers would be uneconomical. In practice the first capacitor,

    C1, is often replaced by a stack of capacitor connected in series. This result a large voltage drop

    across the stack of capacitors that replaced the first capacitor and a comparatively small

    voltage drop across the second capacitor, C2, and hence the secondary terminals.

  • 7/31/2019 Project Report by manish yadav

    41/53

    INSULATING SYSTEM-:

    The external insulation is provided by the porcielain housing and co-ordinated

    with the capacitor stack, consisting of virtually identical so that the axial voltage

    distribution from the line terminal to the ground is essentially uniform. Thecapacitor elements have a mixed dielectric material consisting of alternative layer

    of propylene film and kraft paper. The electromagnetic unit is housed in an oil-

    filled tank at the base of capacitor stack. Mineral oil is used as the insulating

    medium instead of air because of its superior insulating and heat transfer

    properties. The use of an oil-filled base tank remove the need for space heater in

    the secondary terminal. This result more reliable and cost effective design.

    INSULATIG OIL-:

    We use insulating oil with excellent dielectric strength, aging, and gas absorbing

    properties. The synthetic oil is used for the capacitor units possesses superior gas

    absorption properties resulting in exceptionally low partial discharge with high

    inception voltage ratings. The oil is used for EMU is premium naphthenic mineral

    oil. The oil is filtered, vacuum dried and degassed within house processing. It

    contains no PCB.

    CAPACITOR STACK-:

    The capacitor stack is a voltage divider which provides a reduced voltage at the

    intermediate voltage bushing for a given voltage applied at the primary terminal.

    the capacitor stack is a multi-capacitor unit assembly. Each unit is housed in an

    individual insulator and is fitted with an aluminum. A cast aluminum covers in the

    top of the upper capacitor assembly and is fitted with an aluminum terminal. an

    adapter for mounting a line trap on the top of the CVT can be provide with an

    optional HV terminal. the capacitor units are mechanically coupled together by

    means of stain less steel hardware passing through the corrosion resistant castaluminum housing. The mechanical connection also establishes the electrical

    connection between capacitor units.

    There are some part of capacitor voltage transformer-:

    1)Primary terminal 11) Ferro-resonance subpression device

  • 7/31/2019 Project Report by manish yadav

    42/53

    2)Cats aluminum bellow housing 12)Secondry terminals

    3)Stainless steel expansion bellow 13) Oil level sight glass

    4)Compression spring 14)Aluminum terminal box

    5)Insulated voltage connection 15)Immediate transformer

    6)Capacitor elements 16)Oil/air block

    7)Insulator 17) Oil sampling device

    8)Voltage divider tap connection 18)Compansating reactor

    9)Cast epoxy bushing 19)Aluminum cover plate

    10)HF terminal connection

  • 7/31/2019 Project Report by manish yadav

    43/53

    1)High voltage terminal

    2)Compensation reactor

    3)Intermediate voltage transformer

    4)Ground terminal

    5)Ferro resonance subpression device

    6)Damping resistor7)Carrier terminal

    8)Over voltage protective device

    9)Secondry terminals

    10)Link

  • 7/31/2019 Project Report by manish yadav

    44/53

    9.WAVE TRAP-:

    Line trap also known as wave trap.What it does is trapping the high frequency

    communicationsignals sent on the line from the remote substation and diverting

    them to the telecom/teleportation panel in the switchyard control room(throughcoupling capacitor and LMU).This is relevant in Power Line Carrier Communication

    (PLCC)systems for communication among various switchyard without dependence

    on the telecom company network. The signals areprimarilly teleportation signal

    and in addtion,voice and data communication signals.

    The Line trap offers high impedance to the high frequency communication signals

    thus obstructs the flow of these signals in to the substation busbars. If there were

    not to be there, then signal loss is more and communication will be

    ineffective/probably impossible.

    CONSTRUCTION-:

    MAIN COIL-:

    The main coil winding are encapsulated by winding continuous filament

    fiberglass. That has been impregnated with a specially selected epoxy resinharden

    system. Theepoxy resinfiberglass composite is then curve according to

    a programmed temperature schedule.

    TUNING PACK-:

    Tuning pack is connected in parallel with the main coil to provide a

    highimpedance to the desired carrier frequency.

    LIGHTENING ARRESTORS-:The line traps are protected by a lighting arrestors against high voltage

    surgescaused by atmospheric effects or switching operations.

  • 7/31/2019 Project Report by manish yadav

    45/53

    CKT DIAGRAM OF WAVETRAP-:

  • 7/31/2019 Project Report by manish yadav

    46/53

    RESPONSE OFF WAVETRAP-:

    10.PROTECTIVE RELAYS-:

    Protective relaying is one of the several features of power system design. Everypart of the power system is protected. The protecting relaying is used to give an

    alarm or to cause prompt removal of any element from power system from

    service when that elements behave abnormally.

    The relays are compact and self-contained devices which can sense abnormal

    conditions. Whenever abnormal condition occur, the relay contacts get closed this

    is turn closes the trip circuit of circuit breaker.

    For switchyard protection following types relays are used-:

    1) Overcurrent relay

    2) Earth fault relay

    3)REF relay

    4) Differential relay

  • 7/31/2019 Project Report by manish yadav

    47/53

    5) Directional relay

    6) Over flux relay

    7) Buchholz relay

    8) IDMT relay

    RESTRICTED EARTH FAULT PROTECTION RELAY-:

    The REF protection method is a type of "unit protection" applied to transformers

    or generators andis more sensitive than the method known as differential

    protection.

    An REF relay works by measuring the actual current flowing to earth from the

    frame of the unit. If that current exceeds a certain preset maximum value of

    milliamps (mA) then the relay will trip tocut off the power supply to the unit.

    DIFFERENTIAL RELAY-:

    Differential protection can also be used to protect the windings of a transformer

    by comparing thecurrent in the power supply's neutral wire with the current

    in the phase wire. If the currents areequal then the differential protection relay

    will not operate. If there is a current imbalance then thedifferential protection

    relay operates.

    REF protection is applied on transformers in order to detect ground faults on a

    given winding moresensitively than differential protection.

    DIRECTIONAL RELAY-:

    Directional relays have protection zones that include all of the power system

    situated in only onedirection from the relay location. (This is in contrast to

    magnitude relays which are not directional, i.e., they trip based simply on themagnitude of the relay.

    IDMT RELAY-:

    The IDMT relay work on the induction principle, where an aluminum or copper

    disc rotatesbetween the poles of electromagnet and damping magnet. The fluxes

  • 7/31/2019 Project Report by manish yadav

    48/53

    induce eddy current in thedisc which interact and produce rotational torque. The

    disc rotates to a point where it operates apair of contact that breaks the circuit

    and removes the fault condition.

    11.CORONA RING-:A corona ring, also called anti-corona ring, is a toroid of (typically) conductive

    material located inthe vicinity of a terminal of a high voltage device. It is

    electrically insulated. Stacks of more spacedrings are often used. The role of the

    corona ring is to distribute the electric field gradient and lower its maximum

    values below the corona threshold, preventing the corona dischargeCorona

    rings are typically installed on very high voltage power line insulators.

    Manufacturerssuggest a corona ring on the line end of the insulator for above

    230 kV and on both ends for above500 kV. Corona rings prolong lifetime of

    insulator surfaces by suppressing the effects of coronadischarge.

    CORONA RING

    12.SCADA SYSTEM OF UPRVUNL-:In SCADA system measured values, i.e. analogue (measured value) data (MW,

    MVAR, V, HZ Transformer Tap Position), and open/closed status information, i.e.

    digital data (circuit breaker/isolator position i.e. on/off status), are transmitted

    through telecommunication channels to respective sub-LCDs. For this purpose

    remote terminal units at 400kv and 220kv have been installed. System values

  • 7/31/2019 Project Report by manish yadav

    49/53

    &status information below132 KV have not been picked up for data transmission,

    except for 33KV Bus isolator position andLV side of generators. Secondary

    side of Current Transformers (CT) and Potential transformer(PT) are

    connected with 'Transducers'. The output of transducers is available in dc current

    form (inthe range of 4mA to 20mA). Analogue to digital converter converts thiscurrent into binary pulses. Different inputs are interleaved in a sequential

    form and are fed into the CPU of the RTU. The output of RTU, containing

    information in the form of digital pulses, is sent to subLDC through

    communication links. Depending upon the type of communication link,

    the output of RTU is connected, directely or through modem, with the

    communication equipment. At subLDC end, data received from RTU is fed into the

    data servers. In general, a SCADA system consists of a database, displays and

    supporting programmes.In UPRVUNL,subLDCs use all major functional

    areas of SCADA except the 'Supervisory Control/Command' function. The briefoverview of major'functional areas' of SCADA system is as below:

    1. COMMUNICATION-:

    Sub LCDs computer communities with all RTU station under its control, through

    a communication system. RTU polling, message formatting,

    polynomialchecking and message retransmission on failure are the

    activities of 'Communications' functional area.

    2) DATA PROCESSING-:After receipt of data through communication system it is processed. Data

    process function has three sub-functions i.e.

    i) Measurements

    ii) Counters

    iii) Indications

    i)'Measurements retrieved from a RTU are converted

    to engineering units and linearized , if necessary. The measurement arethen placed in database and are checked against variouslimits which if exceeded

    generate high or low limit alarms.

  • 7/31/2019 Project Report by manish yadav

    50/53

    i i )The system has been set-up to col lect 'Counters ' at regular

    in ter val s: ty pic all y 5 or 10minutes. At the end of the hour the units is

    transferred into appropriate hour slot in a 24-hour archive/history.

    iii) Indications' are associated with status changes and protection. For thosestatuses that arenot classified as 'alarms', logs the change on the appropriate

    printer and also enter it into acyclic event list. For those statuses, which are

    defined as an 'alarms' and the indicationgoes into alarm, an entry is made

    into the appropriate alarm list, as well as in the event list. For those statuses,

    which are defined as an 'alarms' and the indicationgoes into alarm, an

    entry is made into the appropriate alarm list, as well as in the event listand

    anaudible alarm is generated in the sub-LDC.

    ALARM/EVENT LOGGING-:The alarm and event logging facilities are used by SCADA dataprocessing

    system. Alarms are grouped into different categories and are given

    differentpriorities. Quality codes are assigned to the recently received

    data for any 'limit violation'and 'status changes'. Alarms are acknowledged

    from single line diagram (or alarm lists) ondisplay terminal in LDCs

    MANUAL ENTRY-:There is a provision of manual entry of measured values, counters

    andindications for the important sub-station/powerhouse, which are

    uncovered by an RTU or some problem is going on in its RTU, equipment,

    communication path, etc.

    AVERAGE OF MEASURED VALUES-:As an option, the SCADA system supports averaging of all analogue

    measurements. Typically, the averaging of measured values over a period of 15

    minutes is stored to provide 24 hours trend.

    HISTORICAL DATA STORAGE (HDR)-:The HDR, i.e. 'archive', subsystem maintains a historyof selected system

    parameters over a period of time. These are sampled at a pre-selectedinterval

    and are placed in historical database. At the end of the day, the data is

    saved for later analysis and for report generation.

  • 7/31/2019 Project Report by manish yadav

    51/53

    INTERACTIVE DATA GRNERATION-:Facilities have been provided in such a way that an off-line copy of the

    SCADA database can be modi f ied a l lowing the add i t ion of new

    RTUs,pickup points and communication channels.

    SUPERVISORY CONTROL/REMOTE COMMAND-:This function enables the issue ofremotecontrol commands to the switchyard

    equipment e.g. circuit breaker command.

    FAIL-OVER -:A 'Fail-over' subsystem is also provided to secure and maintain a

    database ofdevices and their backups. The state of the device is maintainedindicating whether it is 'on-line' or 'failed'. There is a 'backup' system, which

    maintains database on a backup computer and the system is duplicated.

  • 7/31/2019 Project Report by manish yadav

    52/53

    .

  • 7/31/2019 Project Report by manish yadav

    53/53