progress_ report_1 (90180517489)

Upload: godex7

Post on 04-Apr-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 progress_ report_1 (90180517489)

    1/22

    PROGRESS REPORT

    OF

    SIX MONTHS INDUSTRIAL TRAINING

    AT

    NFI AUTOMATION INSTITUTE

    IN

    AUTOMATION

    Supervised By: Submitted By:Er. Rohit Kaushal Rajinder singh

    Er. Rajveer 90180517484

    Electrical Engineering

  • 7/29/2019 progress_ report_1 (90180517489)

    2/22

  • 7/29/2019 progress_ report_1 (90180517489)

    3/22

    1. BASIC SYMBOLS USED IN AUTOMATION AND PLC

    1.1 Contact Normally Open

    Contacts are used in association with coils in contact relays. They can be normally open (NO) or

    normally closed (NC). These two types characterize the electrical behavior of contacts when they

    are not activated, i.e. when the coil to which they are associated is not activated. As soon as the

    coil has a current going through it, contacts to which it is associated change their status.

    Normally open (NO) contacts close, and normally closed (NC) contacts open. These two

    contacts work as opposites. A normally open (NO) contact blocks the passage of current in a

    circuit when not activated. Once activated, the contacts allow the passage of electrical current.

    On the other hand, a normally close (NC) contact allows the passage of electrical current when

    not activated and blocks it when activated. When the coil is under voltage, the contacts to which

    it is associated change their status instantly. For this reason, they are sometimes called instant

    contacts to differentiate them from delay contacts.

    1.2 Contact Normally Close

    Contacts are used in association with coils in the electrical behavior of contacts when they are

    not activated, i.e. when the coil to which they are associated is not activated. As soon as the coil

    has a current going through it, contacts to which it is associated change their status. Normallyopen (NO) contacts close, and normally closed (NC) contacts open. These two contacts work as

    opposites. A normally open (NO) contact blocks the passage of current in a circuit when not

    activated. Once activated, the contacts allow the passage of electrical current. On the other hand,

    a normally close (NC) contact allows the passage of electrical current when not activated and

    blocks it when activated. When the coil is under voltage, the contacts to which it is associated

    change their status instantly. For this reason, they are sometimes called instant contacts to

    differentiate them from delay contacts.

  • 7/29/2019 progress_ report_1 (90180517489)

    4/22

    1.3 Rising Edge Contact

    Rising edge and falling edge contacts are associated with a coil. They detect a change of state, 0 -

    ->1 or 1 --> 0 A rising edge contact is a normally open contact that acts on the rising edge of the

    intensity of the current that travels along the coil to which it is associated. When the current

    starts traveling the coil, the rising edge contact closes momentarily, for a time equivalent to 1

    simulation cycle. A falling edge contact is a normally open contact that acts on the falling edge

    of the intensity of the current that travels along the coil to which it is associated. When the

    current stops traveling the coil, the falling edge contact closes momentarily, for a time equivalent

    to 1 simulation cycle. A rising edge or falling edge contact has to have the same tagname than

    the coil to which it is associated. Also see .

    1.4 Falling Edge Contact

    Rising edge and falling edge contacts are associated with a coil. They detect a change of state, 0 -

    ->1 or 1 --> 0 A rising edge contact is a normally open contact that acts on the rising edge of the

    intensity of the current that travels along the coil to which it is associated. When the current

    starts traveling the coil, the rising edge contact closes momentarily, for a time equivalent to 1

    simulation cycle. A falling edge contact is a normally open contact that acts on the falling edge

    of the intensity of the current that travels along the coil to which it is associated. When the

    current stops traveling the coil, the falling edge contact closes momentarily, for a time equivalent

    to 1 simulation cycle. A rising edge or falling edge contact has to have the same tagname than

    the coil to which it is associated. Also see .

  • 7/29/2019 progress_ report_1 (90180517489)

    5/22

    1.5 Coil

    A coil is made of a rolled up copper wire. When the coil has current going through it, an electro-

    magnetic force is generated in its core. The coil is used in many electrical applications, in contact

    relays for example. In contact relays, the electro-magnetic force generated by the passage of the

    current in the coil opens or closes the contacts of the relay that are associated with the coil. Three

    types of coils are available in the Electrical control workshop, they are the coil, and the coil latch

    and the coil unlatch. When a coil in under voltage, the normally open contacts associated with it

    close whereas the normally closed contacts associated with it open. When the coil is no longer

    under voltage, the contacts take back their initial status. The coil latch works as the coil except

    that the contacts that are associated with it stay in their activated status even if the coil latch is no

    longer under voltage. That way, when the coil latch is under voltage, the normally open contacts

    close and the normally closed contacts open. The coil unlatch allows the contacts that were

    activated by a coil latch to take back their initial status. When the coil unlatches is activated, the

    normally open contacts become open again and the normally closed contacts become closed

    again. The contacts will remain in that status even if the coil unlatches is no longer under

    voltage. In Automation Studio, the coil has to have the same tag names than the contacts to

    which it is associated.

    1.6 Indicator Light

    The indicator light is used to indicate the status of a component in a control system. Its color is

    usually associated with the task to be done. For example, red can be used for the indicator light

    of a push button used as an emergency stop button. Also, the indicator light of a push button

    authorizing the start of an automatisms cycle is usually green. The indicator light can work with

    voltages varying between 6 and 120 Volts, in AC as well as DC current. Models supporting a

    small current use LED (light emitting diode). They occupy a small space and have a longer life

    span; they consume little energy and have a low maintenance cost compared to neon or

    incandescent type lights. In some applications, (a current limiting device) allows the indicator

    light to work under a lower current than the one in the control circuit. This device cans a

    transformer or more commonly a resistor. The working principle behind the indicator light using

  • 7/29/2019 progress_ report_1 (90180517489)

    6/22

    LEDs relies on an important characteristic of electronics. It uses a special p-n junction that emits

    light when it is under direct current (when the anode-cathode voltage is positive).

    1.7 Single-Phase Motor

    The single-phase motor transforms electrical energy into mechanical energy. The main

    parameters of the motor are its power and rotation speed. The single-phase motor can be

    connected between two power lines of 120 or 240 Volts or, between a power line and a neutral.

    The single-phase motor is made of a mobile part called the rotor and a static part called a stator.

    The stator has a main coil turned to form poles. The number of poles gives the rotation speed of

    the motor and they always come in an even number. The rotor is composed of a cylinder made of

    sheet metal that has been punctured at the ends to form notches destined to receive conductors.

    The conductors of the rotor are made of bare copper bars that are fitted in the notches. When a

    voltage is applied on the stators coil, an alternate magnetic flux is generated. The variation of

    this magnetic flux induces alternate current in the conductors of the rotor. The presence of this

    induced current in the magnetic field created by the stators turn, produces an electro -magnetic

    force that makes the rotor turn. In industrial applications, the power of motors is usually

    expressed in horse power (HP). Finding its equivalent in the International System is done by the

    relation 1HP = 746 W. The single-phase motors are used in applications that require little power,

    like machine tool and fans. In those applications, the power generated by the motor varies from a

    fraction of HP to a few HP.

  • 7/29/2019 progress_ report_1 (90180517489)

    7/22

    1.8 Three-Phase Motor

    The three-phase motor requires a tri-phase current. It is very sturdy and reliable but its power

    output tends to be poor under small load.

    1.9 LED

    The LED is used to see the logical state of the digital circuit where the LED is connected. The

    logical state can be either 0 or 1. The component color undergoes a change according to the

    logical state of its input signal.

    1.10 Fuse

    A fuse is a protection device. It can shut down a circuit in which the current going through is too

    high (for example, in a short circuit situation). The fuse is calibrated to support a maximum

    intensity for the circuit. As long as the intensity does not go over the set intensity value, the fuse

    acts as a wire and does not influence the circuit. If the intensity of the current goes over the set

    value, the internal element of the fuse melts rapidly, opening the circuit. All the voltage goes to

    the terminals of the fuse and no current can circulate in the circuit. Fuses are usually made of a

    zinc or silver filament enclosed in a glass, ceramic or fiber tube. The heat generated from the

    current going through the circuit provokes, if it goes over the maximum intensity set for the fuse,

    the melting of the filament and consequently, the opening of the circuit. Fuses are often used in

    control circuits of motors.

  • 7/29/2019 progress_ report_1 (90180517489)

    8/22

    1.11 Power Supply L1

    A power supply line is characterized by its voltage and supplies the electrical power to circuits

    and motors. For example, a triple-phase motor supply needs three power lines, one for each of

    the phases. In industrial and domestic electrical installations, power supply is available from the

    local power company. The electrical company supplies many types of power sources, mainly a

    triple-phase 600 Volts system with three lines and a triple-phase 208/120 Volts system with four

    lines. The 600 Volts supply with three lines is used in industrial installations as a motive force

    for the drive of triple-phase motors. The 208/120 Volts supply system with four lines supplies

    three power lines with 208 Volts line to line and a neutral. A line to neutral connection is used to

    supply a 120 Volts single-phase voltage. All three lines can be used to supply 208 Volts line to

    line triple-phase motors. Each 208 Volts line to line bus can be combined with the neutral to

    supply 120 Volts lighting circuits. In triple-phase power circuits, the line to neutral voltage is

    equal to the line to line voltage divided by 1,73. For example, from a line to line 208 Volts triple-

    phase supply it is possible to obtain a 208/1,73 = 120 Volts line to line single-phase supply.

    1.12Power Supply L2

    A power supply line is characterized by its voltage and supplies the electrical power to circuits

    and motors. For example, a triple-phase motor supply needs three power lines, one for each of

    the phases. In industrial and domestic electrical installations, power supply is available from the

    local power company. The electrical company supplies many types of power sources, mainly a

    triple-phase 600 Volts system with three lines and a triple-phase 208/120 Volts system with four

    lines. The 600 Volts supply with three lines is used in industrial installations as a motive force

    for the drive of triple-phase motors. The 208/120 Volts supply system with four lines supplies

    three power lines with 208 Volts line-to-line and a neutral. A line to neutral connection is used to

    supply a 120 Volts single-phase voltage. All three lines can be used to supply 208 Volts line-to-

    line triple-phase motors. Each 208 Volts line-to-line bus can be combined with the neutral to

    supply 120 Volts lighting circuits. In triple-phase power circuits, the line to neutral voltage is

    equal to the line-to-line voltage divided by 1,73. For example, from a line-to-line 208 Volts

  • 7/29/2019 progress_ report_1 (90180517489)

    9/22

    triple-phase supply it is possible to obtain a 208/1,73 = 120 Volts line-to-line single-phase

    supply.

    1.13 Power Supply L3

    A power supply line is characterized by its voltage and supplies the electrical power to circuits

    and motors. For example, a triple-phase motor supply needs three power lines, one for each of

    the phases. In industrial and domestic electrical installations, power supply is available from the

    local power company. The electrical company supplies many types of power sources, mainly a

    triple-phase 600 Volts system with three lines and a triple-phase 208/120 Volts system with four

    lines. The 600 Volts supply with three lines is used in industrial installations as a motive force

    for the drive of triple-phase motors. The 208/120 Volts supply system with four lines supplies

    three power lines with 208 Volts line-to-line and a neutral. A line to neutral connection is used to

    supply a 120 Volts single-phase voltage. All three lines can be used to supply 208 Volts line-to-

    line triple-phase motors. Each 208 Volts line-to-line bus can be combined with the neutral to

    supply 120 Volts lighting circuits. In triple-phase power circuits, the line to neutral voltage is

    equal to the line-to-line voltage divided by 1,73. For example, from a line-to-line 208 Volts

    triple-phase supply it is possible to obtain a 208/1,73 = 120 Volts line-to-line single-phase

    supply.

    1.14 Neutral

    The neutral is used in electrical power circuits as a reference for the voltage on a single-phase ortriple-phase line. It is also used in triple-phase supply circuits to supply a smaller voltage than

    the line to line voltage. In triple-phase power circuits, the combination of a power line with a

    neutral allows the supply of a smaller voltage than the line to line voltage. For example, the

    combination of a 208 Volts triple-phase line to line power line with the neutral, has an output

    supply of 120 Volts line to neutral. In triple-phase circuits, the line to neutral voltage is equal to

  • 7/29/2019 progress_ report_1 (90180517489)

    10/22

    the line to line voltage divided by 1,73. For example, with a triple-phase supply of 208 Volts line

    to line, it is possible to obtain a single-phase supply of 208/1,73 = 120 Volts line to neutral.

    Sockets for ordinary domestic current are composed of two terminals. One terminal is connected

    to the single-phase 120 or 240 Volts line (depending on the country) and the other terminal is

    connected to the neutral.

    1.15 Ground

    The ground is equal to 0 Volts. It represents the reference by which the voltages

    are measured. The term ground is used because one of the wires of a supply cord in

    electrical installations is always linked to the ground by a low resistance wire. In

    reality, in the case of commercial and residential buildings, this connection is done

    by the water supply pipe located at the entrance of the building. In certain cases,

    the ground is also called the common. In electrical installations, the main objective

    of the ground is to reduce the danger of electrical shocks. Domestic electrical

    appliances with a metallic casing are required to have a ground wire on their

    casing. Such is the case for electric stoves, and water heaters for example. In that

    type of appliance, the plug socket, has a third terminal used to connect the casing

    to the ground. In industrial installations, the ground is usually achieved through a

    grid stuck in the ground. All motors and machines in factories are fitted with a

    ground.

  • 7/29/2019 progress_ report_1 (90180517489)

    11/22

    1.16 Power Supply 24 Volts

    The power supply 24V is a source of 24 Volts.

    1.17Common (0 Volts)

    The common component is the equivalent to the Ground component but it is for circuits in DC

    current.

    1.18 Pushbutton Normally Open

    Push buttons do the same thing as switches activated by finger pressure. They constitute the link

    between the user and the circuit. Push buttons can be normally open (NO) or normally closed

    (NC). Usually, push buttons have a return spring i.e. a spring that brings back the push button to

    its initial position as soon as the button is released. That is why push buttons are said to be

    momentary contact switches. Push buttons are made of a manual actuator and a contact. The typeof push button depends on the type of contact. Contacts can be normally open (NO) or normally

    closed (NC). If the push button is normally open (NO), activating the switch closes the contact.

    However, if the push button is normally closed (NC), activating the switch opens the contact. In

    simulation diagrams, push buttons can be associated with switches that have the same tagname.

    This association can be done with same type switches or opposite type switches.

  • 7/29/2019 progress_ report_1 (90180517489)

    12/22

    1.19 Pushbutton Normally Close

    Push buttons do the same thing as switches activated by finger pressure. They constitute the link

    between the user and the circuit. Push buttons can be normally open (NO) or normally closed

    (NC). Usually, push buttons have a return spring i.e. a spring that brings back the push button to

    its initial position as soon as the button is released. That is why push buttons are said to be

    momentary contact switches. Push buttons are made of a manual actuator and a contact. The type

    of push button depends on the type of contact. Contacts can be normally open (NO) or normally

    closed (NC). If the push button is normally open (NO), activating the switch closes the contact.

    However, if the push button is normally closed (NC), activating the switch opens the contact. In

    simulation diagrams, push buttons can be associated with switches that have the same tag name.

    This association can be done with same type switches or opposite type switches.

    1.20 Toggle Switch Normally Open

    A toggle switch is used to control a connection between two points by opening and closing the

    arm switch.

    1.21 Limit Switch Normally Open

    Limit switches are associated with mechanical position sensors. They can be normally open

    (NO) or normally closed (NC). They are made of two contacts, a mobile one and a fixed one. At

    rest status, the NO limit switch is open and blocks the current. However, the NC limit switch is

    closed allowing the passage of current. Limit switches allow the detection of a position or the

    limitation of a translation movement. For example, when a cylinder rod comes in contact with

    the roller of the position sensor to which it is associated, the mobile contact of the switchchanges position which provokes the status change for the limit switch. In fact, for a NO limit

    switch, the mobile contact presses against the fixed contact and the switch closes. In the case of a

    NC limit switch, the mobile contact moves away from the fixed contact and the switch opens.

    Once the position sensor is no longer activated, the mobile contact of the limit switch takes back

    its initial position, under the action of a return spring. The switch takes back its rest status. Limit

  • 7/29/2019 progress_ report_1 (90180517489)

    13/22

    switches need to have the same tag name that the mechanical position sensors to which they are

    associated. Mechanical position sensors are components from other workshops.

    1.21 Limit Switch Normally Close

    Limit switches are associated with mechanical position sensors. They can be normally open

    (NO) or normally closed (NC). They are made of two contacts, a mobile one and a fixed one. At

    rest status, the NO limit switch is open and blocks the current. However, the NC limit switch is

    closed allowing the passage of current. Limit switches allow the detection of a position or the

    limitation of a translation movement. For example, when a cylinder rod comes in contact with

    the roller of the position sensor to which it is associated, the mobile contact of the switch

    changes position which provokes the status change for the limit switch. In fact, for a NO limit

    switch, the mobile contact presses against the fixed contact and the switch closes. In the case of a

    NC limit switch, the mobile contact moves away from the fixed contact and the switch opens.

    Once the position sensor is no longer activated, the mobile contact of the limit switch takes back

    its initial position, under the action of a return spring. The switch takes back its rest status. Limit

    switches need to have the same tag name that the mechanical position sensors to which they are

    associated. Mechanical position sensors are components from other workshops.

    1.22 Limit Switch Normally Close

    Limit switches are associated with mechanical position sensors. They can be normally open

    (NO) or normally closed (NC). They are made of two contacts, a mobile one and a fixed one. At

    rest status, the NO limit switch is open and blocks the current. However, the NC limit switch is

    closed allowing the passage of current. Limit switches allow the detection of a position or the

    limitation of a translation movement. For example, when a cylinder rod comes in contact with

    the roller of the position sensor to which it is associated, the mobile contact of the switch

    changes position which provokes the status change for the limit switch. In fact, for a NO limit

    switch, the mobile contact presses against the fixed contact and the switch closes. In the case of a

    NC limit switch, the mobile contact moves away from the fixed contact and the switch opens.

  • 7/29/2019 progress_ report_1 (90180517489)

    14/22

    Once the position sensor is no longer activated, the mobile contact of the limit switch takes back

    its initial position, under the action of a return spring. The switch takes back its rest status. Limit

    switches need to have the same tag name that the mechanical position sensors to which they are

    associated. Mechanical position sensors are components from other workshops.

    1.23 Limit Switch Normally Close

    Limit switches are associated with mechanical position sensors. They can be normally open

    (NO) or normally closed (NC). They are made of two contacts, a mobile one and a fixed one. At

    rest status, the NO limit switch is open and blocks the current. However, the NC limit switch is

    closed allowing the passage of current. Limit switches allow the detection of a position or the

    limitation of a translation movement. For example, when a cylinder rod comes in contact with

    the roller of the position sensor to which it is associated, the mobile contact of the switch

    changes position which provokes the status change for the limit switch. In fact, for a NO limit

    switch, the mobile contact presses against the fixed contact and the switch closes. In the case of a

    NC limit switch, the mobile contact moves away from the fixed contact and the switch opens.Once the position sensor is no longer activated, the mobile contact of the limit switch takes back

    its initial position, under the action of a return spring. The switch takes back its rest status. Limit

    switches need to have the same tag name that the mechanical position sensors to which they are

    associated. Mechanical position sensors are components from other workshops.

  • 7/29/2019 progress_ report_1 (90180517489)

    15/22

    1.24 Position Switch

    The 2 position switches make it possible to connect the line 1 (initial position) or the line 2. The

    change of state is triggered by a click on the pushbutton. The arrow of the symbol indicates the

    conducting line.

    1.25Position Switch

    The 3 position switches make it possible to connect the line 1 or the line 2. Initially, the switch is

    in the neutral position 3. The change of state is triggered by a click on the pushbutton. The arrow

    of the symbol indicates the current conducting line or the neutral position.

  • 7/29/2019 progress_ report_1 (90180517489)

    16/22

    2.0 Basic Instruction IN plc programming:

    2.1 General:

    LD Load A contact

    LDI Load B contactAND Series connection- A contact

    ANI Series connection- B contact

    OR Parallel connection- A contact

    ORI Parallel connection- B contact

    ANB Series connection (Multiple Circuits)

    ORB Parallel connection (Multiple circuits)

    MPS Store the current result of the internal PLC operations

    MRD Reads the current result of the internal PLC operations

    MPP Pops (recalls and removes) the currently stored result

    2.2 Output:

    OUT Output coil

    SET Latch (ON

    RST Clear the contacts or the registers

    2.3 Timers, Counters:96 TMR 16-bit timer

    97 CNT 16-bit counter

    97 DCNT 32-bit counter

    2.4 Main control:

    MC Master control Start

    MCR Master control Reset

    2.5 Rising-edge/falling-edge detection:

    90 LDP Rising-edge detection operation

    91 LDF Falling-edge detection operation

    92 ANDP Rising-edge series connection

    93 ANDF Falling-edge series connection

  • 7/29/2019 progress_ report_1 (90180517489)

    17/22

    94 ORP Rising-edge parallel connection

    95 ORF Falling-edge parallel connection

    2.6 Rising-edge/falling-edge output:

    89 PLS Rising-edge output

    99 PLF Falling-edge output

    2.7 End:

    END Program end

    2.8 Other:

    NOP No operation

    P PointerI Interrupt program marker

    98 INV Inverting operation

    2.9 Step ladder:

    STL Step transition ladder start command

    RET Step transition ladder return command

    3.0 Transmission Comparison:

    10 CMP Compare

    11 ZCP Zone compare

    12 MOV Data Move

    13 SMOV Shift move

    14 CML Compliment

    15 BMOV Block move

    16 FMOV Fill move

    17 XCH Data exchange

    18 BCD Convert BIN data into BCD

    19 BIN Convert BCD data into BIN

  • 7/29/2019 progress_ report_1 (90180517489)

    18/22

    3.1 Four Fundamental Operations of Arithmetic:

    20 ADD Perform the addition of BIN data

    21 SUB Perform the subtraction of BIN data

    22 MUL Perform the multiplication of BIN data

    23 DIV Perform the division of BIN data

    24 INC Perform the addition of 1

    25 DEC Perform the subtraction of 1

    3.2 Contact Type Logic Operation:

    3.2.1 Contact Type Compare Instruction:

    224 LD= Comparison contact is ON when S1 = S2 is true

    225 LD> Comparison contact is ON when S1 > S2 is true

    226 LD< Comparison contact is ON when S1 < S2 is true

    228 LD Comparison contact is ON when S1 S2 is true

    229 LD= Comparison contact is ON when S1 S2 is true

    232 AND= Comparison contact is ON when S1 = S2 is true

    233 AND> Comparison contact is ON when S1 > S2 is true

    234 AND< Comparison contact is ON when S1 < S2 is true

    236 AND Comparison contact is ON when S1 S2 is true

    237 AND= Comparison contact is ON when S1 S2 is true

    240 OR= Comparison contact is ON when S1 = S2 is true

    241 OR> Comparison contact is ON when S1 > S2 is true

    242 OR< Comparison contact is ON when S1 < S2 is true

    244 OR Comparison contact is ON when S1 S2 is true

    245 OR= Comparison contact is ON when S1 S2 is true

  • 7/29/2019 progress_ report_1 (90180517489)

    19/22

    PLC Exercises

    1) Devise a circuit that can be used to start a motor and then after a delay of 10 sec start

    a pump. When the motor is switched off there should be delay of 10 sec before the

    pump is off.

    2) Device a circuit in which

    When X1 is pressed Y0 gets ON, Y1,Y2 get off,

    When X1 is pressed again Y1 gets ON and Y0, Y2 get OFF

    When X1 is pressed again Y2 gets ON and Y0, Y1 get OFF

    (Interlocking mechanism)

    Study and use the following commands:

    MOV, INC, DEC, MUL, ADD, SUB, ZCMP

    3) Switch on a Lamp after 5 sec, now using mov command change the timer to 10

    second and change back to 5 sec. You have 1 maintained button and 2 push buttons

    only. Maintained button to switch on/off the lamp. Other two push button for

    changing the time from 5 to 10 sec and vice-versa

    4) Device a circuit in which Y0 is on only when X1 is pressed in 10 sec. just after start of

    the machine(X0). Otherwise if X1 is pressed after 10 sec. Nothing should happen.

    5) Device a circuit in which if X1 does not get pressed just after 5 second after output Y0

    is on by pressing X0, alarm (Y1) is ON and blinking with frequency of 2Hz.6) Device a circuit, in which if X0 is pressed once Y0 should ON and when X0 is pressed

    again Y0 should turn off.

    7) Device a circuit, in which

    When X1+X2+X3 > Y0 ON FOR 5 SEC THEN OFF

    X4+X2+X1 > Y1 ON FOR 6 SEC THEN OFF

    X4+X5+X6 -> Y2 ON FOR 7 SEC THEN OFF

    Cycle should repeat

    8) Use one push button (X1) turn ON Y0 in following sequence:Y0 on for 2 sec. then off for 2 sec. then on for 3 sec. then off for 3 sec then on for 4 sec.

    then continuously off.

    9) When you press X0 Y0 and Y1 should blink after a delay of 2 sec continuously andwhen you press X1 Y0 and Y1 should blink after a delay of 3 sec.

    10) Start a bulb as soon as PLC run and stop the bulb as soon as PLC stops.

  • 7/29/2019 progress_ report_1 (90180517489)

    20/22

    11) You have 5 outputs Y0, Y1, Y2, Y3, Y4 When M0 is pressed All five should ON

    When M1 is pressed Y1, Y2, Y3 should OFF

    When M2 is pressed

    Y4 should off and Y1 should ON When M3 is pressed Y2, Y3 gets ON and Y0 goes OFF and Y4 goes ON again

    (take M0~M3 as maintained button and dont use set-reset commands)

    12) I have a constant K10 in D0

    Multiply it with 100

    Add 56 to it

    Subtract 14 from it

    Finally store it in D10

    13) Design electrical circuit to start 220 V motor with 24 PLC output.

    14) Automatic Cold Drink making machine:

    Use X0Main selector switch to ON/OFF the machine

    Use X1 & X2 as push buttons for selecting small/large cup

    Make a small beep (Y3)of 2 sec when cup is filled

    Blink an LED when cup is filling

    Make an arrangement to change (increment or decrement) the timing of timers

    for both small and large cups

    (Assume small cup gets filled in 5 sec and big cups filled in 10 sec.)

  • 7/29/2019 progress_ report_1 (90180517489)

    21/22

    PLC Exercise -2

    1) A toggle start switch and a limit switch (LS1) on a safety gate must both be on before a

    motor is energized.

    2) While the motor is energized, it must remain energized until a limit switch (LS2) is

    activated. This second limit switch indicates the turn off of motor.

    3) A cycle counter should also be included to allow counts of parts produced. When this

    value exceeds 5 the machine should shut down and a light lit up.

    4) A safety check should be included. If the solenoid has been on for more than 5 seconds,

    it suggests that the cylinder is jammed or the machine has a fault. If this is the case, themachine should be shut down and maintenance light turned on.

    5) Write ladder logic for a motor starter that has a start and stop button that uses latches

    .Write the same ladder logic without latches.

    6) Design ladder logic that uses a timer and counter to measure a time of 50.0 days

    7) Develop the ladder logic that will turn on an output (light), 15 seconds after switch (A)

    has been turned on

    8) Develop the ladder logic that will turn on a output (light), after a switch (A) has been

    closed 10 times. Push button (B) will reset the counters

    9) Develop a program that will latch on an output (B), 20 seconds after input (A) has been

    turned on. The timer will continue to cycle up to 20 seconds, and reset itself, until A has

    been turned off. After the third time the timer has timed to 20 seconds, B will be

    unlatched

    10) A motor will be connected to a PLC and controlled by two switches. The GO switch willstart the motor, and the STOP switch will stop it. If the motor is going, and the GO

    switch is thrown, this will also stop the motor. If the TOP switch was used to stop the

    motor, the GO switch must be thrown twice to start the motor. When the motor is

    running, a light should be turned on (a small lamp will be provided).

    11) In dangerous processes it is common to use two palm buttons that require a operator to

    use both hands to start a process (this keeps hands out of presses, etc.). To develop this

  • 7/29/2019 progress_ report_1 (90180517489)

    22/22

    there are two inputs that must be turned on within 0.25s of each other before a

    machine cycle may begin.

    12) Write a ladder logic program that does what is described below.

    - When button A is pushed, a light will flash for 5 seconds.- The flashing light will be on for 0.25 sec and off for 0.75 sec.

    - If buttonA has been pushed 5 times the light will not flash until the system is reset.

    - The system can be reset by pressing button B

    13) Write a program that will turn on a flashing light for the first 15 seconds and then off.

    Dont use start stop button

    14) Write a program that only uses one timer. When an input A is turned on a light will be

    on for 10 seconds. After that it will be off for two seconds and then again on for 5

    seconds. After that the light will not turn on again until the input A is turned off