(process) separators

42
ت نف نا ص ری اد ره به زی و ا ه اند ا ت ر ک ر ش( و یک ا) Common course (process) Separators ت ی مد آ و سع و ت ق و ی ق تح وزش، م ور ی ر شه1391

Upload: others

Post on 04-Apr-2022

40 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: (process) Separators

زی و بهره برداری صنایع نفت (ایکو ) شرکت راه اندا Common course

(process)

Separators

موزش، تحقیق و توسعوآمدیریت 1391شهریور

Page 2: (process) Separators

seprators

2

Objectives: Upon completion of the unit the trainees should be able to:

Explain the classification, flow patterns, internal devices of separators commonly used in oil

industries.

Understand principals of separation.

Understand the application of separators.

Understand important parameters of operation and troubleshooting.

Contents:

1. Description of separators.

2. Design of separators.

3. Application.

4. Operation.

5. Troubleshooting.

Page 3: (process) Separators

seprators

3

SEPARATORS

INTRODUCTION

A separator is a vessel in which a mixture of fluids that are not soluble in each other are

segregated from one another. In the oilfield, separators are used to segregate gas from

liquid; or one liquid such as condensate from another liquid, such as water.

There are more separators in oil and gas process facilities than any other type of other

process equipment. Sometimes they are called scrubbers, accumulators, flash tanks, or

other names. Regardless of what the vessel is called its function is to segregate 2 or more

fluids … usually gas and liquid; and the operating procedures are the same.

Production Separators On Offshore Platform

Page 4: (process) Separators

seprators

4

1- DESCRIPTION OF SEPARATORS

A – Classification

Separators are classified in two ways : the position or shape of the vessel, and the number

of fluids to be segregated. Two vessel shapes are commonly used:

1. Horizontal

2. Vertical

The number of fluids to be segregated is usually two or three. If there are two fluids, such

as gas and liquid, the separator is referred to as a 2-phase type, if three fluids are

segregated, such as gas, oil and water, the vessel is a 3-phase type. The number of phases

refers to the number of streams that leave the vessel and not the number of phases that are

in the inlet stream.

For example, well stream separators frequently have gas, oil and water in the inlet stream,

but only gas and liquid are segregated in the vessel. The liquid flows to another separator,

where oil and water are segregated. Consequently, a 2-phase separator is one in which the

inlet stream is divided into two fluids, and a 3-phase will have three products.

Each of the vessel shapes can be either 2-phase or 3-phase. In other words, we can have a

horizontal 2-phase, a horizontal 3-phase, a vertical 2-phase, and so on (Figures 1 –5).

Some well streams contain sand or other solid particles which are removed in a separator.

Special internal devices are provided to collect and dispose of solid materials. They are not

considered another fluid phase in the classification of the vessel.

Horizontal wellhead separator

B – Flow Patterns

The flow in horizontal or vertical separators is similar for 2-phase separators : the mixture

enters the side or end, the lighter fluid (usually gas) passes out the top, and the heavier

fluid is withdrawn at the bottom.

Page 5: (process) Separators

seprators

5

Figure 1

Page 6: (process) Separators

seprators

6

Figure 2

Page 7: (process) Separators

seprators

7

Figure 3

Page 8: (process) Separators

seprators

8

Figure 4

Page 9: (process) Separators

seprators

9

Flow in a centrifugal separator, such as that shown in Figure 5, is somewhat different than

that in conventional types. The vessels are usually vertical and depend on centrifugal

action to segregate the fluids. The inlet is directed to flow around the wall of vessel or

inside a centrifugal element in a swing motion. The heavier liquid moves to the outside,

Figure 5

Page 10: (process) Separators

seprators

10

and drops collect on the wall and fall on the bottom. The lighter fluids collect in the middle

of the vessel and flow up the outlet pipe.

Flow in a 3-phase vessel can be in one of several manners as shown in Figure 6. The 3-

phase inlet stream enters the side; gas flows out the top and liquid settles to bottom. Oil

floats on the water and is withdrawn out the side of the vessel. Water is withdrawn at the

bottom.

This type of liquid collection would be used with water and distillate, where a clean

separation occurs. The disadvantage of the system is that the water level is controlled at

the interface with oil, and if any foam or emulsion is present at that point, it will interfere

with the action of the level control float.

Another method of control in a 3-phase vertical separator is shown in the upper right hand

drawing of Figure 6. In this vessel, the water falls to the bottom of the vessel on the left

side, and flows into the water chamber of the right side, where it is withdrawn with a level

controller. Oil is withdrawn on the left side with a level controller. An emulsion at the oil-

water interface will not interfere with the operation of the level controller on the water or

oil streams. The disadvantage is that the liquid flow path in the vessel is more complex and

the additional internals take up space normally reserved for separation.

Liquid flow in a horizontal separator is usually a variation of one of the two schemes

shown in Figure 6 In the middle drawing, the oil and water settle to the bottom in the left

hand portion of the vessel. The oil layer floats on the water spills over the weir and is

withdrawn with a level controller. The water remains on the left side of the weir and is

withdrawn with a controller. The level control float is subject to problems with emulsion at

the water-oil interface.

The lower drawing in Figure 6 indicates the flow pattern with no interface control. Oil

spills into the bucket and is withdrawn with a level controller. The water flows along the

bottom of the vessel into the chamber on the right, where it is withdrawn.

Centrifugal separators are normally used for gas-liquid separation. They are smaller than

conventional units.

C – Separator Internal Devices.

A wide variety of mechanical devices are used inside a separator to improve its efficiency

and simplify its operation. The most commonly used devices are:

1. Deflector plates (Figure1). A deflector plate is used in gas-liquid separators in front of

the inlet nozzle on the vessel. The plate can be flat or dished. As the inlet stream strikes it,

the fluid falls to the bottom and the gas flows around the plate. In a vertical vessel, the

Page 11: (process) Separators

seprators

11

deflector may divert the inland stream around the wall of the vessel to create a centrifugal

action.

2. Mist pads (Figures 1 and 3). Mist pads are most frequently used in gas-liquid separators

to remove the mist from the gas. The pad is made mostly of closely woven wire that is 10

to 20 cm [4 to 8 in.] thick. It is held in place by a sturdy grid which prevents it from being

swept out or torn by a sudden surge of gas. Mist pads are also used in oil-water separators

to aid in segregating the two liquids. They can be of value in breaking an emulsion of oil

and water.

Page 12: (process) Separators

seprators

12

Figure 6

Page 13: (process) Separators

seprators

13

3. Coalescing plates (Figures 1, 2 and 3 ). Several configurations are available from

different vendors. They are used in some gas-liquid vessels to remove liquid from the gas

these are often called a vane pack.

4. Straightening vanes (Figure 1). These are also used in gas-liquid vessels. They are

used when hydrate or paraffin prevents the use of mist pads.

5. Filter elements (Figure 2 and 4 ). Filters and used to remove solid particles and mist

from gas and oil-water vessels. The separator usually contains a quick-opening closure for

access to allow for replacement of the elements.

6. Coalescing material (Figure 4). Excelsior and hay are the most commonly used

material. In special applications, pellets with coalescing properties are used. The material

must be held in place with a grid or perforated plate. A manhole is usually included on the

vessel to allow replacement of the material. Coalescing material is used in oil-water

separating vessels.

7. Weir (Figure 2). Its function has been described.

8. Centrifugal devices (Figures 1 and 3). These are used in gas-liquid separators. They

impart a swirling action to the inlet stream that concentrates the liquid phase on the outer

wall of the device.

9. Horizontal baffles (Figure 1). These are used in gas-liquid separators to prevent waves

in the liquid phase. They are usually located near the liquid level in the vessel.

10. Vortex breakers (Figure 1). There are used on all separators on the liquid draw off

nozzle to prevent a vortex from forming, Which would allow some gas to flow out the

liquid line.

11. Float shield (Figure 3). This device is used when an internal float is used to control the

liquid level. It prevents the float from flopping around from wave action in the liquid.

12. Water jets (Figure 7). Water jets are sometimes called sand jets. Their purpose is to

spray the sides and bottom of the vessel with a high pressure stream of water or other

liquid to fluidize sand or other solid particles so they can be drained from the bottom.

Page 14: (process) Separators

seprators

14

13. Sand cones (Figure 7). These are used in vessels that have a continual flow of sand or

other solid particles. The solids collect in the cone, and are periodically flushed out. Water

jets are usually included with the cones.

Figure 7

Page 15: (process) Separators

seprators

15

D - Construction and Vessel Codes

Most separators operate under pressure. They are usually made of steel and built in

accordance with rigid pressure vessel specifications. The heads and shell are usually made

of steel, and all seams are welded. If server corrosion is anticipated, the separator may be

lined with a corrosion resistant material such as monel or stainless steel. If salt water is the

corrosive agent, protection can be provided with a coating or special paint or tar.

Most internals are also made of steel and welded to the wall or head of the vessel. If man

ways are provided, the internals may be bolted in place so they can be removed for

cleaning or repair.

Virtually all pressure vessels used in the hydrocarbon industry are constructed in

accordance with the applicable pressure vessel code. The code provisions dictate the

mechanical construction of the vessel, e.g. wall thickness, welding techniques, nozzle

reinforcement, etc. The vessel sizing criteria is set by factors to be discussed in the

following section.

The pressure vessel code used in the U.S. is the ASME pressure vessel code, section III,

division I. In the U.K. the code is the BS 5500.

For a process engineer, perhaps the most important specifications are the wall thickness

equations. These allow calculation of:

1. Design wall thickness which can be used to estimate vessel weight, cost and lifting

requirements.

2. MAWP of vessel in-service which has experienced metal loss due to corrosion, erosion,

or mechanical damage.

For the ASME code,

0.6tR

SEP

0.6PSE

PRt

Where:

t = wall thickness, in.

P = design pressure, psig

R = internal radius of vessel, in.

S = maximum allowable stress value of steel, psi

E = joint efficiency of welds

A number of commercial steels are used for vessel construction.

2- DESIGN OF SEPARATORS

A – Principles of Separation

Two factors are necessary for separators to function:

Page 16: (process) Separators

seprators

16

1. The fluids to be segregated must be insoluble to each other.

2. One fluid must be lighter than the other.

Separators depend upon the effect of gravity to segregate the fluids. If the fluids are

soluble in each other, no separation is possible by gravity alone. For example, a mixture of

distillate and crude oil will not separate in a vessel because they dissolve in each other.

They must be separated in a distillation process.

Since a separator depends on gravity to segregate the fluids, the ease which two fluids can

be segregated depends upon the weight of the fluids. Gas usually weighs about 5% as

much as oil, and the two will separate in a few seconds. On the other hand, oil may weigh

only three-fourths as much as water, and separation may take several minutes. The primary

factor that affects separation is that of the difference in the weights of the fluids.

You recall the density of a fluid is the weight of 1 cubic meter [1cubic foot] of the

material. Water has the density of 1000 kg/m3 [62.4 Ib/ft

3]. Crude oil density is about 800

kg/m3 [50 Ib/ft

3]. The density of gas will depend primarily upon its pressure. The density

of 1 m3 of natural gas at 5200 kPa pressure is about 36 kg/m

3 [density of 1 ft

3 of natural

gas at 750 psia is about 2.25 Ib/ft3]; but at 102 kPa [15 psia], density of gas is only 1.6

kg/m3 [0.1 Ib/ft

3].

It would appear gas having a density of 36 kg/m3 [2.25 Ib/ft

3] would instantly separate

from crude oil that weighs 800 kg/m3 [50 Ib/ft

3]. About 95% separation will occur almost

instantly. However, some liquid will remain in the gas in a fine mist, and it must settle out

for separation to be complete. If mist is not removed from the gas in the separator, it will

eventually settle out in the gas flow lines-possibly in a burner-and could cause serious

problems.

A common example of coalescing occurs when water drops form on the windshield of a

car as it is driven in a fog. As the tiny water drops, which make up the fog, strike the

windshield, they combine with other drops and eventually form a drop large enough to run

down the glass.

The first 6 internal devices listed previously are all forms of coalescers. In each device,

liquid drops adhere to the device and combine with other drops until a large drop forms

that will fall out. The effectiveness of separation will depend upon the amount of

coalescing area that is present.

In order to understand the way separation takes place, we will concern ourselves with

segregating a mixture of gas and oil into its components. As we mentioned, the ease with

which two fluids will separate depends upon the difference in weight of the two fluids. The

greater the difference in weight, the easier the separation.

Page 17: (process) Separators

seprators

17

In the process of segregating gas from liquid, we actually have two separate stages:

1. Separate liquid mist from the gas phase.

2. Separate gas in the form of foam or froth from the liquid.

Droplet of liquid mist will settle out from gas, provided:

1. The gas remains in the separator long enough for the mist to drop out.

2. The flow of the gas through the separator is slow enough so that no turbulence occurs

which will keep the gas stream stirred up and prevent liquid from setting out.

The difference in weight of gas and liquid will determine the maximum flow rate of gas

that will allow the liquid to settle out. For example, most of the mist droplets will drop out

of gas at 5200 kPa [750 psia] as long as the gas is moving in the separator less than 30

cm/s [1 ft/sec]. In other words we make the separator large enough so that the gas travels

from the inlet nozzle to the outlet nozzle at a rate of 30 cm/s [1ft/sec] or less.

We said that gas at 5200 kPa [750 psia] weighed about 36 kg/m3 [2.25 Ib/ft

3], whereas, it

weighed only 1.6 kg/m3 [0.1 Ib/ft

3] at 102 kPa [15 psia]. Since its density is lower at 102

kPa [15psia], the oil droplets will settle out faster because there is a greater difference in

weight between low pressure gas and oil. Consequently, the gas can flow faster in a low

pressure separator. In fact, it can flow at 152 cm/s [5 ft/sec] and not interfere with liquid

droplets as they fall out.

Page 18: (process) Separators

seprators

18

Gas bubbles in the liquid will break out of the liquid in most oil field applications in 30 to

60 seconds. The length of time the liquid remains in the vessel is called its residence time.

If we want a liquid to have a residence time of 60 seconds, and the inlet flow rate is 380

L/min [100 gpm], we make the liquid portion of the vessel large enough to hold 380 L

[100 gal] for one minute.

If the gas does not break out of the liquid in the separator, it will eventually come out in

the storage tank somewhere, and will require costly recompression to boost pressure back

up to that in the separator.

Another reason the gas and liquid steam leaving the separator must be pure is that the

presence of one in the other will make accurate flow measurements impossible. When

liquid contains gas bubbles, the volume of the mixture is increased by the volume of the

gas in it. Liquid mist in gas will also cause the flow measurement to read high.

B – Design of Separators

Separators are designed in two steps:

1. Determine the size of the vapor section in which liquid droplets will settle out.

2. Determine the size of the liquid section in which gas bubbles will break out.

The size of the vapor section is determined by first calculating the velocity of gas in the

vessel. From knowledge of the gas flow rate we can then calculate the area needed for

vapor flow and the diameter.

For oil gas separators, the gas velocity can be calculated from equation 1.

Page 19: (process) Separators

seprators

19

0.5

V

VLS

KV

ρ

ρρ

Where:

V = maximum allowable vapor velocity, m/s (ft/sec)

Ks = Separator sizing parameter m/s [ft/sec]

L = Liquid density, kg/m3 [Ibm/ft

3]

V = Vapor density, kg/m3 [lbm/ft

3]

Typical separator sizing parameters are shown below:

Ks

m/s ft/sec

Vertical 0.05 - 0.10 0.16 - 0.34

Horizontal 0.12 - 0.15 0.40 - 0.50

Most oil companies size the vapor portion of the separators using a Ks value within the

ranges shown above. The allowable gas velocity in horizontal separators is higher than in

vertical separators because there is less interference between the gas velocity and the

gravitational force acting on the droplet. A typical production/process separator is

designed to remove most of the droplets 150 m and larger by gravity. Small droplets

(down to about 30m) are removed in the mist extractor. Many of the droplets smaller

than 30 m are not removed from the gas carry over into the downstream equipment. This

is not usually a serious problem but can be troublesome in some instances. Examples

include systems where the downstream equipment includes glycol dehydrators, mol sieve

dehydrators or reciprocating compressors. In these cases an additional “high efficiency”

separator such as a filter separator or cyclone type is installed.

Once the allowable velocity in the vapor section has been determined, the area for vapor

flow is calculated from the equations below:

A = qa/V = /4 d2

2

VF V

a4qd

2a

Where:

A = area available for vapor flow, m2 [ft

2]

q = actual vapor flow rate, m3/s [ft

3/sec]

V = allowable vapor velocity, m/s [ft/sec]

Page 20: (process) Separators

seprators

20

d = vessel diameter, m [ft]

= 3.1416

Fv = correction factor for horizontal separator

The actual flow rate, qa, can be calculated from the standard flow rate qs from the equation:

Z Ts

T

P

sP

400 86

sqaq

Where:

qs = standard flow rate, std m3/d [scf/d]

Ps = standard pressure (usually 101.3 kPa or 14.7 psia)

P = actual separator pressure, kPa [psia]

T = actual separator temperature, K [R]

Ts = standard temperature (usually 288 k, 520R)

Z = gas compressibility factor.

For horizontal separators, liquid occupies part of the vessel cross-section so the liquid level

affects the vapor flow rate. In order to determine the actual vessel diameter the area

calculated in equation 2 must be divided by a correction factor Fv which corrects for the

liquid in the vessel. Fv may be estimated from Figure 8.

Figure 8

Example: Calculate the diameter of the vessel required to separate a 0.8 sp. gr. oil from a

0.65 sp. gr. natural gas at 6000 kPa [870 psia] and 40C [104F]. The gas compressibility

factor is 0.86 and the gas flow rate is 2.0 std m3/d [70 MMscf/d].

SI:Gas density 3Kg/m 50.5

14)(313)(0.86)(8.3

(0.65)(6000)(29)

ZRT

(P)(MW)v ρ

Page 21: (process) Separators

seprators

21

Liquid density, L = (1000)() = (1000)(0.8) = 800 kg/m3

For a vertical separator, Ks = 0.06 m/s

0.23m/s

0.5

50.5

50.58000.06

0.5

V

VLsK v velocity, gas Allow able

ρ

ρρ

For a horizontal separator, Ks = 0.12 m/s, v = 0.46 m/s

Calculate actual gas flow rate,

/s3

0.365m0.86 2888

313

6000

101.3

400 86

000 000 2aq

Calculate diameter-vertical separator (Fv = 1.0),

56in. 1.42m6)(0.63)(3.14)(0.4

(4)(0.365)

Fv Vπ

a4qd

Horizontal separator (assume hL/d =0.43)

[50in.] 1.26m3)(1.0)(3.14)(0.2

(4)(0.365)a4qd

Fv Vπ

English:Gas density, 3/ftmIb 3.15

73)(564)(0.86)(10.

0.65)(870)(29)(

Liquid density, L = (62.4)(0.8) = 49.92

For a vertical separator KS = 0.20 ft/s. Allowable gas velocity.

ft/s 0.76

0.5

3.15

3.1549.92 0.20

0.5

sKv

For a horizontal separator, Ks = 0.40 ft/s, v = 1.5 ft/s

Calculate actual gas flow rate,

/s3

ft 12.770.86870

564

870

14.7

86400

000 000 70aq

Calculate diameter-vertical separator (Fv =1.0),

ft 4.66)(0.63)(3.14)(0.7

(4)(12.77)

Fv Vπ

aq 4d

Horizontal separator (Fv= 0.63), ft 4.1)(0.63)(3.14)(1.5

(4)(12.77)

Fv vπ

a4qd

Once we have found the area needed for vapor flow we must determine the size of the

liquid handling portion of the vessel. For gas-oil separation, the required residence time in

the liquid is 2-3 min-to prevent carry under of gas bubbles (blow-by). The liquid holding

volume is equal to the liquid rate multiplied by the retention time

Page 22: (process) Separators

seprators

22

1440

tL

qV

Where:

V = liquid volume, m3 [ft

3]

qL = liquid rate, m3/d [ft

3/d]

t = retention time, min

Once the liquid volume has been calculated, it is an easy matter to calculate the total vessel

height required to separate the liquid and vapor. This is illustrated in the following

example.

Example: Estimate the height of the vertical separator in the previous example if the

oil-gas ratio in the separator is 981 m3/m

3 [5000 scf/bbl].

SI:liquid rate = (20 000 000/891) = 2245 m3/d

For a retention time of 2 min, 3m 3.1

1440

(2245)(2)V

The diameter of the vessel is 1.22 m, so the vertical height required to hold the liquid

(ignore the head) is

1.96m2

2)(3.14)(1.4

(4)(3.1)

2d π

v 4L

The vapor disengaging space above the liquid level is usually 1.5 to 2 times the vessel

diameter. If we use the factor 2 in this case, the vapor disengaging space is

(1.42)(2) = 2.84m

Total vessel height = 2.84 + 1.96 = 4.8m

Additional height may be required for slugging or surging flows or for

operator response.

English: liquid rate = (70 000 000/5000) = 14 000 BPD

For a retention time of 2 min

3109ftbbl 1

1440

(14000)(2)V 4.9

ft 6.62

)(3.14)(4.6

(4)(109)

2d π

(4)(V)L

Vapor disengaging space = (2)(4.6) = 9.2 ft

Total height = 6.6 + 9.2 = 15.8 ft

For horizontal separators the liquid retention calculation is required to determine the

normal liquid level in the vessel. The vapor capacity is then rechecked after Fv can be

determined and the calculation proceeds until a properly sized separator can be found.

Most horizontal separators have an L/D ratio of 3:1 to 5:1, with higher pressure vessels

Page 23: (process) Separators

seprators

23

using the higher L/D. Let’s check the size of the horizontal separator using the previous

example. Assume L/D = 5:1.

If we ignore vessel heads, the liquid contained in the horizontal separator is:

32.9m0.376.3

21.26

4

3.14

LLF

2d

4

π

LV

3100ft0.3720.5

24.1

4

3.14

so at (hL/d) = 0.4 the vessel has nearly adequate liquid capacity and the calculated

separator size of 1.26 m is OK!

Horizontal separators are generally preferred in crude oil separation because the extra

cross-sectional area makes 3-phase separation easier and allows more time to destabilize

foam. Compare the cross-sectional area in the vertical separator A = 1.6 m2 [17.2 ft

2] to

that in the horizontal separator A = 5.7 m2 [61.4 ft

2].

Figure 9a and 9b provide an easy solution to estimate the diameter of horizontal

separators. Once the vapor disengaging area and liquid residence volume have been

calculated it is easy to enter the table and determine the vessel size.

Example: Using the numbers from the previous example estimate the required vessel

size for the horizontal separator.

SI:A = q/v = 0.365/0.46 = 0.79 m2 VL = 3.1 m

3

From Figure 9a, d = 1.3m

English:A = q/v = 12.77/1.5 = 8.5 ft2 VL = 19.4 bbl

From Figure 9b, d = 54 in.

The procedures presented for sizing separators are for estimating purposes only. An actual

design would take into account slugging, surging, control philosophy and other factors.

However, they can be used in checking the size of separators in your plant. If you check

the size of separators in your plant and find one or more that appears too small, you should

bring it to the attention of your supervisor so that the size can be accurately determined.

In the example used for sizing separators, we assumed that only gas and oil were present in

the vessel. If water had been present, we would have taken it into consideration in sizing

the liquid section of the vessel. The liquid section would have to be large enough to

provide the residence time for both the oil and water. This will be discussed later.

Page 24: (process) Separators

seprators

24

Figure 9a

Page 25: (process) Separators

seprators

25

Figure 9b

One other point: Even though water is present, the vapor disengaging area is based on the

difference in gravity of the gas and oil, and not the gas and water. Water is heavier than oil

and, consequently, it will separate faster from gas than oil will. Since it is more difficult to

Page 26: (process) Separators

seprators

26

separate gas from oil, we design the vessel on this basis, and the water will drop out before

the oil does.

C – Selection of Separator Internals

Internal devices are used in separators to speed up the separation process to reduce the size

and cost of the separator. Proper selection of internals can reduce the cost of a separator as

much as 50%.

Most of the internal devices are installed in the vapor section to remove liquid droplets

from the gas. The separator sizing procedures are based on separators containing a mist

pad only. The diameter will increase approximately 20% if there is no pad or other

coalescing device in the vapor section.

Selection of internal devices will depend upon the composition and quality of the stream

entering the separator. Coalescing devices should not be installed if there is a likelihood

they will become plugged with wax, sand, hydrate or other corrosive products. A stainless

steel mist pad can be installed in a corrosive gas stream without danger of becoming

plugged with corrosive products. However, coalescing plates, straightening vanes, and

centrifugal devices should not be used when there is a likelihood of fouling from dirt, wax

or hydrate.

Centrifugal devices are highly effective in removing mist from gas as long as the flow of

gas is high enough to maintain a proper velocity in the centrifugal device. These devices

are most effective when the inlet stream is mostly gas flowing at a fairly constant rate.

Vortex breakers should always be installed in each liquid outlet line. Without these

devices, a funneling effect may occur when liquid is withdrawn, and gas will flow out the

funnel with liquid.

An inlet deflector plate is another internal device that can be used in all separators. This

device stops the liquid from entering the separator and prevents it from flowing out the

middle of the vessel and thereby reducing the effectiveness of the vapor disengaging

space.

A float shield should be installed on all separators containing an internal float used to

control level in the vessel. If the float is in an external cage, no protection is required

inside the vessel.

Water jets should be installed if there is a likelihood of an accumulation of sand or dirt in

the bottom of the vessel. These are most frequently used on wellhead separators to remove

sand produced in the well stream.

The following shows the application and limitations on internal devices:

Page 27: (process) Separators

seprators

27

D – Application of Internal Devices Used in Separators.

Internal device Purpose of devices or situation where devices should not

be used

Mist pad a. remove liquid mist from gas.

b. Break oil-water emulsion

c. Not used where hydrate, wax or dirt may be present

Deflector plate a. separate liquid from gas

b. used in all services

Coalescing plate a. Remove liquid mist from gas

b. Separate oil from water

c. Not used where hydrate, corrosion, wax or dirt may

be present

Straightening Vanes a. Remove liquid mist from gas

b. Separate oil from water

c. Not used where hydrate, corrosion, wax or dirt may

be present

Filter elements a. Remove solid particles from gas or liquid

b. Separate oil from water

c. Remove mist from gas

d. Not used where wax or hydrate may be present

Coalescing materials a. Separate oil from water

b. Not used when wax is present

E – Common Application of Horizontal and Vertical Separators

Type Application

Horizontal 1. High gas-oil ratio streams.

Page 28: (process) Separators

seprators

28

2. Oil-water segregation where long residence time is required.

Vertical 1. Low gas-oil ratio streams

3. Where a high level of liquid must be held to prevent a pump

from vapor locking, or maintain a liquid seal.

The designation of high or low gas-oil ratio is rather arbitrary. Following are specific

instances in which high or low GOR’s usually occur:

Low Gas-Oil Ratio High Gas-Oil Ratio

1. Oil well streams 1. Gas well streams

2. Flash tanks in dehydration and

sweetening plants

2. Gas pipeline scrubbers

3. Compressor suction scrubbers

3.Fractionators reflux

accumulators

4. Fuel gas scrubbers

The terms flash tank, accumulator and scrubber are commonly used for specific

applications of separators. The vessels are gas-liquid separators.

3. OPERATION

A – Start-Up

1. If the vessel is empty, close a block valve in each liquid outlet line from the vessel to

prevent possible leakage through a control valve in the liquid line.

2. If the vessel has a pressure controller, it should be set at about 75% of the normal

control pressure, and slowly bring it up to a normal pressure after the vessel is in service.

This will prevent pressure relief devices from opening in the event the pressure controller

is out of adjustment and allows the pressure to build up above operating pressure.

3. If the vessel has low level shutdown devices, they must be deactivated or liquid must be

added to the vessel to a point above the low level devices.

4. Check the flow lines out of the vessel to see that each stream leaving the vessel flows in

the proper direction.

5. Slowly open the inlet stream to the vessel.

6. When the liquid level reaches the range of level controllers, place level controllers in

service and open the block valves that were closed in step 1.

7. Adjust level and pressure controllers to stabilize their operation.

Page 29: (process) Separators

seprators

29

B – Shut-Down

1. Close a valve in the inlet stream.

2a. Close valves in liquid outlet line to prevent liquid from leaking out.

2b. If the vessel must be drained, open the by-pass line on the level control valves, or

adjust the level controllers so the level control valves stay open until the vessel has

drained. Close block valves in the liquid outlet lines after draining.

3. If the vessel must be depressured, close a block valve in the gas outlet line.

4. Depressor the vessel by opening a valve in the line from the vessel to the vent or blow

down system.

5. If possible, leave a small positive pressure on the vessel while it is shutdown to prevent

air from entering so that it will not have to be purged prior to start-up.

Page 30: (process) Separators

seprators

30

C – Routine Operation

1. Routine operating checks are observing the various level, pressure, temperature and

flow control instruments to see that they are controlling within the proper range.

2. Diaphragm-operated control valves should be stroked occasionally to see that they will

fully open and close without restriction.

3. Gauge glasses should be drained periodically to prevent scale or debris from

accumulating in the lines or gauge valves and causing them to show false levels.

4. If the vessel has filters or coalescing chambers, the pressure drop across them should be

observed for an increase which indicated a build-up of solid particles, and the need to

replace or clean them.

Page 31: (process) Separators

seprators

31

– Control

Separators have two major control points:

1. Pressure control 2. Level control

each will be discussed separately.

1. Pressure Control

The gas capacity of a separator increases as its operating pressure rises. Increasing the

pressure reduces the actual volume of gas, and thereby lowers the velocity of gas in the

vessel. Pressure is regulated with a pressure controller, which regulates the flow of gas

leaving the vessel. The control valve is often a butterfly valve to minimize pressure losses

across the valve.

Pressure control is sometimes accomplished by sending the pressure control signal directly

to the governor on a compressor. This is a very popular control scheme when the

compressor driver is a variable speed such as a gas turbine.

Page 32: (process) Separators

seprators

32

2. Level Control

a- 2-phase separators

The point at which you hold the level of liquid in the separator can have a significant

effect on the operation of the vessel, particularly in a horizontal separator. The level of

liquid needs to be high enough so that the volume of liquid in the vessel will provide the

desired residence time for gas bubbles to break out. If the liquid level is too high, the

liquid residence time will be more than is required. This will not affect the quality of the

liquid that is withdrawn from the vessel, but it will reduce the vapor disengaging space and

can result in some liquid carryover in the outlet gas stream.

The liquid level control point in a vertical separator usually will not have much effect on

the quality of the gas out of the vessel, because the vapor space is usually more than 100

cm [39 in.] high, and a change of a few centimeters [inches] will have little effect.

However, on a horizontal separator, a small change in the liquid level can have a

significant effect on the vapor disengaging space, particularly on a small diameter vessel.

From the above you can see that changing the level 8cm [3 in.], changes the volume of

vapor space by 20%. The change would be less in a larger diameter vessel.

The point at which the level controller should be set will depend upon the flow rates of

liquid and gas entering the vessel. If the gas rate is above design, and the liquid rate is less,

you should run with a lower level to allow more room in the vessel for vapor disengaging.

Page 33: (process) Separators

seprators

33

On the other hand, if the liquid rate is up, and the gas rate is down, you should raise the

level in order to provide more liquid residence time.

Effect of 8cm [3 in.] change in 96 cm [38 in.] Diameter horizontal separator on

volumes of liquid and gas in vessel

It is often difficult to determine whether the liquid residence time is sufficient to allow gas

bubbles to break out. If it is dumping into an atmospheric tank, you might get some idea of

its gas contact by observing the amount of gas that is being vented from the tank.

If the gas leaving a separator flows to another process vessel, then liquid carryover will

usually fall out in it. If liquid carryover is noticed, it often can be stopped by lowering the

liquid level. Generally, liquid carryover in the gas stream will cause more operating

problems than gas bubbles in the liquid stream. Consequently, it is usually better to hold

the liquid level on the low side rather than the high side in horizontal separators.

This is a good place to pause for a minute and discuss level controllers. Most level

controllers use an external cage with displacer element. The displacer element senses the

buoyant force of the fluid in the cage and transmits the signal to the controller via a torque

tube. When the level in the separator rises, the level controller senses the rise and signals

the control valve in the liquid outlet line to open to allow more liquid to flow out.

Conversely, when the level drops, the level controller signals the control valve to close.

Most level controllers will hold a constant level inside the separator as long as the flow of

liquid is fairly constant. However, if the flow of liquid increases, the level of separator will

Page 34: (process) Separators

seprators

34

rise and remain at the higher point until the flow rate drops, or until the level set point in

the controller is lowered. The amount of offset depends on the proportional band (gain) of

the controller. Most level controllers use narrow proportional band settings so the offset is

minimal.

If a level controller is equipped with reset, the controller will hold a constant level inside

the separator when there is a change in the liquid flow rate leaving the vessel. However,

most oilfield level controllers do not use a reset, and the level will change each time there

is a change in flow rate.

b. 3-phase separator level control

A 3-phase separator is one in which the outlet streams are gas and two liquids. In almost

every 3-phase separator, one of the liquids is oil; the other one is usually water, but it may

be glycol, brine, amine, or any other liquid that is not soluble in oil. For our discussion, we

will assume they are oil and water. The operating principles will be the same for any two

liquids that are not soluble in each other.

The term water cut is used in the oilfield to denote the percentage to total liquid that is

water. A 20% water cut would be 20% water and 80% water and 80% oil. A low water cut

usually means less than 10% water; a high water cut is more than 50%.

Level control in separators making water and oil is little more involved because control of

the water level will affect the residence time of both the water and oil. Furthermore, these

vessels are often in a service in which the quantities of water and oil change drastically

during the operation of the separator.

For example, a new oil well might make 7000 m3/d of gas, 40 m

3/d of oil and 1m

3/d water

[250 Mcf/d of gas, 250 bbl/d of oil and 6 bbl/d of water]. After five years the production

may change to 11000 m3/d of gas, 30 m

3/d of oil and 15 m

3/d of water [400 Mcf/d of gas,

200 bbl/d of oil and 100 bbl/d of water]. During the early stages of production, most of the

liquid section is filled with oil. The water level is operated near its lowest control point.

After 5 years, the water level must be raised in order to provide sufficient residence time

for the higher water production.

Control of the water level in the above case was accomplished with a level controller

having its displacer element partially immersed in water and the remainder in oil. The

displacer element that is used on the controller must be designed for the difference in

density of the oil and water that are in the vessel. A float used to control the level of oil in

a gas-oil interface would not function in an oil-water interface.

In order to avoid a displacer element at the oil-water interface one of the methods shown

on the following drawing is used.

Page 35: (process) Separators

seprators

35

In the vertical separator shown below, the oil level is changed by resetting the oil level

controller. In the horizontal separator, the level in the oil setting chamber is fixed by the

height of the weir on the oil bucket. The volume of oil within the bucket is relatively

small, and no significant change in the oil setting volume will result from a change in level

within the bucket.

In most separators, the total liquid setting volume is fairly constant. The percentage of the

total volume that is used for oil and water setting depends upon the location of the

interface. It is determined by the level of water in the water chamber.

The location of the interface is affected by two factors:

1. Difference in density of water and oil.

2. Level of water in the water chamber.

The effect of changing the water level on the interface level is shown on the next page for

an oil having a relative density of 0.75 [an API gravity of 57]. You will see that changing

the water level 1 unit moves the interface level 4 units, and significantly from 76 cm to 79

cm [30 to 31 in.]; the volume of the water setting section increases from 22% to 33%,

which is a 50% increase in volume. The water residence time will increase 50%. The oil

settling volume changes from 78% to 67%, which is a 14% reduction.

The effect of water level on the interface level also applies to vertical separators shown on

the following page.

Page 36: (process) Separators

seprators

36

The oil-water interface is often difficult to detect. Wood, rags, scale, corrosion products

and dirt that sink in oil but float on water will accumulate at the interface. This material

tends to promote foam or and emulsion of water and oil. Consequently, there may be no

clear-cut interface, but instead, a layer of trash and oil-water emulsion will form between

the oil and water. The mixture will cause erratic action of the level controller.

It is not unusual for a gauge glass to show a distinct interface when this layer is in the

separator. The following illustrates this.

Liquid in gauge glass is clean oil and water. Trash layer in separator does not show in

gauge glass.

If one of the gauge glass connections to the vessel is in the trash layer, the glass may fill

with the material, and an interface cannot be seen. When this occurs, the trash layer should

be drained from the vessel.

Page 37: (process) Separators

seprators

37

Page 38: (process) Separators

seprators

38

When one gauge glass connection is in trash layer, the entire gauge glass may fill with

trash and no oil-water interface is visible.

If the displacer element on the water level controller is immersed in a layer of trash and

emulsion, it may not be able to distinguish a difference in density between oil and water,

and will not operate properly.

Page 39: (process) Separators

seprators

39

4- TROUBLESHOOTING

The cause of an operating problem is found by a process of elimination. Each event which

can cause the problem is checked until the culprit is found. The proper sequence for

checking the various causes is to eliminate the easy ones first. These are the instruments:

pressure gauges, control valve positions, controller output pressures, gauge glasses, flow

meters, etc. In making these checks, be sure that the instruments are working properly, and

not giving a false reading. Once the easy causes are checked and eliminated, the more

difficult causes are checked.

A – Troubleshooting procedure for liquid carryover in outlet gas stream

Another important part of troubleshooting is that of maintaining an overall perspective of

the total process, and not just the troublesome equipment. Upsets at front end of a plant

often show up at the back end. Find the source of the problem before attempting to locate

the cause.

TROUBLESHOOTING PROCEDURE FOR LIQUID CARRYOVER IN

OUTLET GAS STREAM

CAUSE OF CARRYOVER TROUBLESHOOTING

PROCEDURE

1. High inlet gas flow rate Check gas flow rate and cut back to

design rate.

2. High liquid level which

cuts down vapor disengaging

space

Check liquid level. Blow down gauge

glass-lower level to design point.

3. Coalescing plates, mist

pad, or centrifugal device is

plugged.

a. check temperature and pressure to

determine if hydrate has formed. Lower

pressure to melt hydrate.

b. measure pressure drop across device.

It should be less than 10 kPa [2psi]. If

pressure drop across mist pad is 0, pad

may have torn or come loose from its

mounting. Pressure drop measurement

should be made at design gas flow rate.

High pressure drop indicates plugging

internally inspect and clean if necessary.

Page 40: (process) Separators

seprators

40

4. Excessive wave action in

liquid

Install horizontal baffles.

5. Operating pressure is

below design

Check pressure and raise to design or

lower gas rate in proportion to reduction

in pressure.

6. Liquid density is less than

design

Check liquid density. If it is less than

design, gas rate will have to be cut in

proportion to reduction in density.

B – Troubleshooting procedure for inability to hold constant liquid level

CAUSE OF CHANGING

LEVEL

TROUBLESHOOTING

PROCEDURE

1. Float is totally covered

with liquid

a. clean gauge class to get accurate level

reading

b. If float cage is external, drain it to be

sure pipes between cage and vessel are

not plugged.

c. when gauge glass and float cage are

clean, check to see if float is covered

with liquid.

d. Manually drain enough liquid from

vessel so that ½ of float is immersed.

e. Put level controller in service.

2. Liquid level is below float

Note: level controller will not

function if the liquid level is

above or below float. The

float must be partially

immersed in liquid in order

for controller to work.

a. Perform steps a and b above

b. If level is below float, close valve in

liquid outlet line to allow level to rise

until float is ½ covered.

c. Put level controller in service

3. Liquid flow rate has a. If level controller does not have reset,

Page 41: (process) Separators

seprators

41

changed. the level controller will have to be

changed each time the liquid flow rate

makes a significant change.

b. If the controller has reset, it can be

adjusted to take care of changes in liquid

flow rate.

4. Liquid enters vessel in

slugs. Level controller does

not react fast enough to drain

liquid.

a. Lower set point in level controller.

b. Lower proportional band setting.

c. In some cases it may be helpful to

install a valve positioner on the level

control valve in order for it to open

rapidly.

5. Wave action is causing

internal float to move.

Install float shield.

6. Level control valve is not

operating properly.

a. Check valve action to see that it is not

closing when it is supposed to open.

b. Stroke valve to full open and closed

positions to see that the spring tension is

not too tight or too loose, and that

nothing is under the valve seat to prevent

it from closing.

c. Check liquid flow rate with valve fully

open to see that there is no restriction in

the line.

7. Level controller shows no

response to change in level

a. Manually twist torque tube or float arm

to see that controller shows response. If

there is no response, repair controller. If

controller shows response, float has

apparently dropped off, or liquid level is

above or below float.

b. Check liquid level as described in

items 1 and 2.

Page 42: (process) Separators

seprators

42

c. Manually open and close drain valve

so that the liquid level travels the full

length of the float. If the controller shows

no response, the float has fallen off.

8. float in oil-water interface

is totally immersed in

emulsion.

a. Check for emulsion in vessel by

draining a line connected to the vessel

near the float.

b. Drain emulsion from vessel if it is

present.

9. Density of oil has changed

so that float will not respond

to change in level .

a. Check density of oil.

b. If it is different from design, consult

level control supplier to get a new float.

The gauge glass that indicates the liquid level is probably the most important operating

device on a separator. It is also one of the easiest devices to plug with dirt and debris, and

cause it to show a false level. Gauge glasses should be cleaned with a brush or with a

chemical solution at frequent intervals; and the gauge valves should be blown down as

required to prevent an accumulation of dirt in them.