pqm power quality management - westek...rev. c1 january 2011 adf m pqm power quality management®...

2
Rev. C1 January 2011 AD F M www.reinhausen.com PQM Power Quality Management ® Aktive Leistungsfilter AcF-P3 für Niederspannung Active Power Filter AcF-P3 for Low Voltage NEW PQM 100-AcF 400 V ... 690 V

Upload: others

Post on 14-Jul-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PQM Power Quality Management - Westek...Rev. C1 January 2011 ADF M PQM Power Quality Management® Aktive Leistungsfilter AcF-P3 für Niederspannung Active Power Filter AcF-P3 for Low

Rev. C1 January 2011

ADF

M

www.reinhausen.com

PQM Power Quality Management® Aktive Leistungsfilter AcF-P3 für Niederspannung Active Power Filter AcF-P3 for Low Voltage

NEW

PQM 100-AcF 400 V ... 690 V

Page 2: PQM Power Quality Management - Westek...Rev. C1 January 2011 ADF M PQM Power Quality Management® Aktive Leistungsfilter AcF-P3 für Niederspannung Active Power Filter AcF-P3 for Low

Technische Daten Technical Data

400 V PQM 100-AcF3-400

Model PQM 100-AcF3-400/100-P3

PQM 100-AcF3-400/200-P3

PQM 100-AcF3-400/300-P3

Rated power, nominal 400V 70 kVA 140 kVA 210 kVA

Compensation current capacity 100 Arms 200 Arms 300 Arms

System voltage* 208 – 480 V

Frequency* 50/60 Hz (± 2 %)

Number of phases 3 wire type

Connection type 3 phase with and without neutral (TN, TT, IT)

Harmonic current compensated Global compensation or specified harmonics up to 50th order

Power dissipation < 1900 W < 3800 W < 5700 W

Maximum air flow requirement 600 m3/h 1200 m3/h 1800 m3/h

Dimensions 800 x 600 x 2000 mm (w x d x h)

Weight 290 kg 380 kg 470 kg

690 V PQM 100-AcF3-690

Model PQM 100-AcF3-690/100-P3

PQM 100-AcF3-690/200-P3

PQM 100-AcF3-690/300-P3

Rated power, nominal 690V 120 kVA 240 kVA 360 kVA

Compensation current capacity 100 Arms 200 Arms 300 Arms

System voltage* 480 – 690 V

Frequency* 50/60 Hz (± 2 %)

Number of phases 3 wire type

Connection type 3 phase with and without neutral (TN, TT, IT)

Harmonic current compensated Global compensation or specified harmonics up to 50th order

Power dissipation < 2050 W < 4100 W < 6150 W

Maximum air flow requirement 600 m3/h 1200 m3/h 1800 m3/h

Dimensions 800 x 600 x 2000 mm (w x d x h)

Weight 290 kg 380 kg 470 kg

General

Rate of harmonic reduction Better than 98 %

Current compensation of cos φ Up to 1.0

Expandability Up to 8 PQM 100-ACF3 units in parallel

Response time < 1 ms

Noise level < 60 dB

Environment 0 to 95% RH non-condensing, max. altitude 1000 m

Operation temperature 0 to 40 °C continuous, < 25 °C recommended

Cabinet colour Cabinet RAL 7035 (beige)

Protection class IP 20 according to IEC 529

Environmental conditions Chemical 3C3, Mechanical 3S3

Electromagnetic compatibility EN 61000-6-2, EN 61000-6-4

Certificates CE

www.reinhausen.com

© Maschinenfabrik Reinhausen GmbH Wiebestraße 46, 10553 Berlin, Germany PQM Power Quality Management® fon: (+49) 30 / 33 09 15 -1, fax: -25 E-mail: [email protected] Alte Chaussee 73, 99102 Erfurt-Waltersleben, Germany www.reinhausen.com/pq fon (+49) 361 / 30 10 -30, fax: -320

Bitte beachten: Die in allen Publikationen enthaltenen Angaben können in Details von dem gelieferten Produkt abweichen. Änderungen bleiben vorbehalten.

Please note: The data in our publications may differ from the data of products delivered. We reserve the right to make changes without notice.

PQ-FL-ACF/01de/en – 1110/100 – PQ – Printed in Germany