SMC POWER GENERATION UNIT
Type
TITAN 130 , 17MVA Each
From Solar Turbines
Infrastructure
Complete MV/LV station
PMS
Connection
Synchronized in Between
connected to the Grid
Technical data
Length: 18.1 mWidth: 6.8 m
Height (including fittings): 12.5 m
Weight (including lube oil): 125.0 t
Operating temperature: –20°C–+40°CStorage temperature: –20°C–+60°C
1.1 PackageOverall dimensions and weight (approximate values)
Ambient conditions
Turbine type: Titan 130 (T-20501)
Compressor type: Axial
Compressor no of stages: 14
Compression ratio: 17.1:1
Compr. stages with IGV: 6
Combustion chamber type: Annular
No of injectors standard: 21No of stages gas producer turbine: 3
Gas producer turbine speed: 11197 rpmType of radial bearing: Hydrodynamic, tilt-padType of axial bearing: Hydrodynamic, tilt-pad
1.2 Turbine
Gearbox type: High speed, two stage, star-
compound, epicyclicalRated output speed: 1500 rpm
Nominal voltage – Temperature
class: 11000V - Class H
Nominal power: 17000 kVAManufacturer: Leroy Somer
Power factor: 0.8Frequency: 50 Hz
1.3 Gearbox
1.4 Generator
Total wall thickness: 100 mm
Thickness of outer steel plate and
roof panels:3 mm
Thickness of inner steel plate: 1 mmDamping material: Mineral wool
Ventilation air flow: 100000 m3/h
1.5 Power train enclosure
Package (Power train enclosure & modular air filtration system uplifted)
5
1 Base-frame 2 Gas turbine 3 Speed reduction gearbox 4 AC synchronous generator 5 Fuel delivery system 6 Lube oil system 7 Package control room 8 Soundproof power train enclosure9 Access to enclosure roof & filtration system10 Electrostatic filter 11 Oil cooling system, options:
a) Lube oil/air cooler (Available in our package)
b) Lube oil/water cooler12 Air filtration system 13 Combustion air cooling coil (Not available in our package)
Major components of the Gas Turbine
1 Coupling2 Gearbox3 Air inlet 4 Compressor stages 5 Compressor diffuser 6 Combustor, comprising of an annular combustion chamber and fuel injectors7 Three-stage turbine8 Turbine exhaust diffuser9 Bleed valve duct10 #3 tilt-pad journal bearing11 #2 tilt-pad journal bearing12 #1 tilt-pad journal and thrust bearing
1 Coupling2 Gearbox3 Air inlet 4 Compressor stages 5 Compressor diffuser 6 Combustor, comprising of an annular combustion chamber and fuel injectors7 Three-stage turbine8 Turbine exhaust diffuser9 Bleed valve duct10 #3 tilt-pad journal bearing11 #2 tilt-pad journal bearing12 #1 tilt-pad journal and thrust bearing
GAS TURBINE OPERATION
The turbine has a single-shaft design.
In single shaft the air compressor, the turbine, and
the gearbox are mounted which is mechanically
connected to the generator.
The turbine extracts the energy from the gas flow
downstream of the combustion section and drives
the compressor section. The turbine also drives the gearbox
The speed reduction gearbox transmits the power from the gas turbine to the electrical
generator.
Rotating parts
Static parts
Viewed from DE side
FLANGED SLEEVE BEARING
FRAME LENGTH ACCORDING TO POWER RATING
TERMINAL BOX
DE END SHIELD
NDE END SHIELD
AC synchronous generator Modular & Compact Design
GAS STATION
SYSTEM NO.: S10395
INLET: 8” ANSI B16.5 600#
OUTLET: 4” ANSI B16.5 300#
FLUID: NATURAL GAS
FLOW: 25 MMSCFD
INLET PRESSURE: 40 TO 70 Barg
OUTLET PRESSURE: 32 Barg
DESIGN PRESSURE: 93/49 Barg
WORKING
TEMPERATURE: 10 TO 20⁰C
DESIGN TEMPERATURE: 60⁰C
Process Data
DIESEL STATION
MODEL: MACFUGE 053 OM M 3 S
01
MIXTURE TO SEPARATE: Liquid/liquid/solid
NOMINAL CAPACITY: 18000 l/h
DIESEL WASHING
CAPACITY: 15000 l/h
BOWL VOLUME: 20 litres
SLUDGE CHAMBER
CAPACITY: 7 litres
BOWL MAX. ROTATIONAL
SPEED: 6700 rpm
ENGINE POWER: 15 kW
VOLTAGE/PHASES/POLES: 380/3/4
START TIME: 300 sec
STOP TIME: 480 sec
Filtration System:
Two tanks are installed each of 700,000 litres, one for raw diesel and the other after filtration.
DIESEL GENERATOR
MAKE: CUMMINS
MODEL: KTA-50-G3
INJECTOR TORQUE: 90 Inch-Lbs.
ADVERTISED HP: 1470
IDLE SPEED: 700 – 900 RPM
Engine Technical Details:
Two diesel generators are installed each of 1250 kVA for turbine start-up.
NOMINAL VOLTAGE –
TEMPERATURE CLASS: 415V - Class H
NOMINAL POWER: 1250 kVA
MANUFACTURER: Stamford
POWER FACTOR: 0.8
FREQUENCY: 50 Hz
Generator Technical Details:
Turbine Gas Consumption per KWH Generation
7671 71
74
99
120
107
98
65
126
126
134 133131
8
86
128
98
60
0
66
77
0
138
97 97
136
154
0 0 0
99.08
0
20
40
60
80
100
120
140
160
180
0
5
10
15
20
25
30
MW
H P
RO
DU
CED
PER
UN
IT G
AS
CO
NSU
MP
TIO
N
Dec. 2018 Gas Consumption Per KWH
GT5 TOTAL MWH
10
7.25
6.75
4.38
43.25
0
2
4
6
8
10
12
0.00
5.00
10.00
15.00
20.00
25.00
11/15/2018 11/16/2018 11/17/2018 11/18/2018 11/19/2018 11/20/2018 11/21/2018 11/22/2018 11/23/2018 11/24/2018 11/25/2018 11/26/2018 11/27/2018 11/28/2018 11/29/2018 11/30/2018
Per KWH Gas Consumption
MWH
Per KWH Gas Consumption at different generation
Peak-to-Peak load test
Full Island Operation (All
four turbines on dirty line)
Synchronisation between turbines
Perfect load sharing between
three turbines
Test Performed on Turbines
Managing the different possible configurations
Configuration according to the
production needs and the availability of the
power sources
The PMS will warn the operator in case the
network is not configured
The PMS is designed to interface and control the future generators
GT5 and GT6
Power Management System (PMS)
SUBSTATION TECHNICAL DETAILS
Double circuit line of 132kv
Two step-down transformer (132/33kv)
of 63MVA for clean and dirty line
All the protection relay are coordinated through
GPS system
Fast Data Recording (FDR) is installed for
power quality analysis in each feeder
CLEAN BB
SYN01
DIRTY BB
STATCOM SWB
SWG1 SWG2
MCS11kV IF CABIN SUPPLY
IF PLANT
GT1 GT5 GT4 GT2
EAF LF
S/S AUXILIARY
SINGLE LINE DRAWING
SLD EXPLANATION
➢The 33kV turbine distribution board (SYN-01) is installed in MediumVoltage Room.
➢The turbine power supply is distributed to 33kV Clean and dirty bus-bar of Substation via step-up transformer (11/33kV) of 20MVA
➢In Substation, we have the distribution of power for the whole plant.
➢The dirty bus-bar is connected to EAF, LF and StatCom
➢The Clean bus-bar is connected to all auxiliary load of the plantincluding rolling mill, ASP, IF, etc via step-down transformer (33/11kV)of 35MVA and 20MVA (dedicated for IF)