portable rental solutions 5 ton

1
Total Capacity [2] Sensible Capacity [2] BTUH BTUH 57,100 41,200 Cooling Operating Range [3] 65° F - 115° F Refrigerant Type R-410a Compressor Type Scroll Filter Filter Size Type MERV 8, Pleated Disposable 24 x24 x2 Evaporator Coil Face Area Evaporator Coil Rows deep Sq. Ft. 3.7 3 Evaporator Maximum ESP CFM in-wc HP 2000 1.5 1.5 Condenser Coil Face Area Condenser Coil Rows Deep Sq. Ft. 6.39 3 Condenser Air Movement Type Belt Drive Blower Condenser Maximum ESP CFM in-wc HP 3000 1 2 208/230-1-60 Op. A [4] FLA MCA kW [5] 42.7 48.1 55.6 10.2 208/230-3-60 FLA MCA kW [5] 31.5 36.6 10.5 480-3-60 FLA MCA kW [5] 14.8 17.2 11.0 Available Electric Heat 10 kw (1 Phase) / 15kw (3 Phase) 208/230-3-60 10 kw FLA MCA kW [5] 56.1 70.1 11.7 208/230-3-60 15 kW FLA MCA kW [5] 46.9 58.6 16.9 460-3-60 15kW FLA MCA kW [5] 21.4 26.7 17.0 Approximate Net Unit Weight 670 Lbs. [6] TECHNICAL DATA PAC5N[1]ASA Cooling WITHOUT Electric Heat Heating WITH Electric Heat [1] Voltage Codes (*): 1 = 208/230-1-60 3 = 208/230-3-60 4 = 460-3-60 [2] Entering Air 80° F DB / 67° F WB with 95° F Outdoor Ambient [3] Extended operating range feasible with optional accessories [4] Operating amps at ARI conditions listed in not [2] above at 208 volts [5] kW at 0.8 Power Factor and 208 or 460 Volts [6] Electric heat adds approximately 25 lbs. Portable Rental Solutions, Inc. P.O. Box 340 Hewitt, TX 76643 Phone: 800-699-8998 Fax: 469-574-7924

Upload: shane1977

Post on 15-Aug-2015

120 views

Category:

Documents


2 download

TRANSCRIPT

Total Capacity [2]Sensible Capacity [2]

BTUHBTUH

57,10041,200

Cooling Operating Range [3] 65° F - 115° FRefrigerant Type R-410aCompressor Type ScrollFilterFilter Size

Type MERV 8, Pleated Disposable24 x24 x2

Evaporator Coil Face AreaEvaporator Coil Rows deep

Sq. Ft. 3.73

EvaporatorMaximum ESP

CFMin-wc

HP

20001.51.5

Condenser Coil Face AreaCondenser Coil Rows Deep

Sq. Ft. 6.393

Condenser Air Movement Type Belt Drive BlowerCondenserMaximum ESP

CFMin-wc

HP

300012

208/230-1-60 Op. A [4]FLA

MCAkW [5]

42.748.155.610.2

208/230-3-60 FLAMCA

kW [5]

31.536.610.5

480-3-60 FLAMCA

kW [5]

14.817.211.0

Available Electric Heat 10 kw (1 Phase) / 15kw (3 Phase)

208/230-3-6010 kw

FLAMCA

kW [5]

56.170.111.7

208/230-3-6015 kW

FLAMCA

kW [5]

46.958.616.9

460-3-6015kW

FLAMCA

kW [5]

21.426.717.0

Approximate Net Unit Weight 670 Lbs. [6]

TECHNICAL DATA PAC5N[1]ASA

Cooling WITHOUT Electric Heat

Heating WITH Electric Heat

[1] Voltage Codes (*): 1 = 208/230-1-60 3 = 208/230-3-60 4 = 460-3-60[2] Entering Air 80° F DB / 67° F WB with 95° F Outdoor Ambient[3] Extended operating range feasible with optional accessories[4] Operating amps at ARI conditions listed in not [2] above at 208 volts[5] kW at 0.8 Power Factor and 208 or 460 Volts[6] Electric heat adds approximately 25 lbs.

Portable Rental Solutions, Inc.P.O. Box 340

Hewitt, TX 76643Phone: 800-699-8998

Fax: 469-574-7924