pid tuning and controllability sigurd skogestad ntnu, trondheim, norway
TRANSCRIPT
PID Tuning and Controllability
Sigurd SkogestadNTNU, Trondheim, Norway
Tuning of PID controllers SIMC tuning rules (“Skogestad IMC”)(*)
Main message: Can usually do much better by taking a systematic approach
One tuning rule! Easily memorized
References: (1) S. Skogestad, “Simple analytic rules for model reduction and PID controller design”, J.Proc.Control, Vol. 13, 291-309, 2003(2) S. Skogestad, ``Tuning for smooth PID control with acceptable disturbance rejection'', Ind.Eng.Chem.Res, 45 (23), 7817-7822
(2006).
(*) “Probably the best simple PID tuning rules in the world”
• k’ = k/τ1 = initial slope step response c ≥ 0: desired closed-loop response time (tuning parameter)
For robustness select (1) : c ¸ (gives Kc ≤ Kc,max) For acceptable disturbance rejection select (2) : Kc ≥ Kc,min = ud0/ymax
Need a model for tuning
Model: Dynamic effect of change in input u (MV) on output y (CV)
First-order + delay model for PI-control
Second-order model for PID-control
Step response experiment Make step change in one u (MV) at a time Record the output (s) y (CV)
First-order plus delay process
Step response experiment
k’=k/1
STEP IN INPUT u (MV)
RESULTING OUTPUT y (CV)
Delay - Time where output does not change1: Time constant - Additional time to reach 63% of final changek : steady-state gain = y(1)/ u k’ : slope after response “takes off” = k/1
Model reduction of more complicated model
Start with complicated stable model on the form
Want to get a simplified model on the form
Most important parameter is usually the “effective” delay
half rule
Approximation of zeros
Derivation of SIMC-PID tuning rules PI-controller (based on first-order model)
For second-order model add D-action.For our purposes it becomes simplest with the “series” (cascade)
PID-form:
Basis: Direct synthesis (IMC)
Closed-loop response to setpoint change
Idea: Specify desired response T = (y/ys)desired
and from this get the controller. Algebra:
IMC Tuning = Direct Synthesis
Integral time Found: Integral time = dominant time constant (I = 1) Works well for setpoint changes Needs to be modified (reduced) for integrating
disturbances
Example. “Almost-integrating process” with disturbance at input:G(s) = e-s/(30s+1)
Original integral time I = 30 gives poor disturbance responseTry reducing it!
gc
d
yu
Example: Integral time for “slow”/integrating process
IMC rule:I = 1 =30
Reduce I to improve performance. This valuejust avoids slow oscillations:I = 4 (c+) = 8
(see derivation next page)
Derivation integral time: Avoiding slow oscillations for integrating process. Integrating process: 1 large Assume 1 large and neglect delay
G(s) = k e- s /(1 s + 1) ¼ k/(1s) = k’/s PI-control: C(s) = Kc (1 + 1/I s) Poles (and oscillations) are given by roots of closed-loop polynomial
1+GC = 1 + k’/s ¢ Kc ¢ (1+1/Is) = 0 or I s2 + k’ Kc I s + k’ Kc = 0 Can be written on standard form (0
2 s2 + 2 0 s + 1) with
To avoid oscillations must require ||¸ 1: Kc ¢ k’ ¢ I ¸ 4 or I ¸ 4 / (Kc k’) With choice Kc = (1/k’) (1/(c+)) this gives I ¸ 4 (c+)
Conclusion integrating process: Want I small to improve performance, but must be larger than 4 (c+) to avoid slow oscillations
Summary: SIMC-PID Tuning Rules
One tuning parameter: c
Some special cases
One tuning parameter: c
Note: Derivative action is commonly used for temperature control loops. Select D equal to time constant of temperature sensor
Selection of tuning parameter cTwo cases
1. Tight control: Want “fastest possible control” subject to having good robustness
• (1) S. Skogestad, “Simple analytic rules for model reduction and PID controller design”, J.Proc.Control, Vol. 13, 291-309, 2003
2. Smooth control: Want “slowest possible control” subject to having acceptable disturbance rejection
• (2) S. Skogestad, ``Tuning for smooth PID control with acceptable disturbance rejection'', Ind.Eng.Chem.Res, 45 (23), 7817-7822 (2006).
(1) TIGHT CONTROL
Example. Integrating process with delay=1. G(s) = e-s/s. Model: k’=1, =1, 1=1 SIMC-tunings with c with ==1:
IMC has I=1
Ziegler-Nichols is usually a bit aggressive
Setpoint change at t=0 Input disturbance at t=20
TIGHT CONTROL
1. Approximate as first-order model with k=1, 1 = 1+0.1=1.1, =0.1+0.04+0.008 = 0.148Get SIMC PI-tunings (c=): Kc = 1 ¢ 1.1/(2¢ 0.148) = 3.71, I=min(1.1,8¢ 0.148) = 1.1
2. Approximate as second-order model with k=1, 1 = 1, 2=0.2+0.02=0.22, =0.02+0.008 = 0.028Get SIMC PID-tunings (c=): Kc = 1 ¢ 1/(2¢ 0.028) = 17.9, I=min(1,8¢ 0.028) = 0.224, D=0.22
TIGHT CONTROL
Tuning for smooth control
(2) Will derive Kc,min. From this we can get c,max using SIMC tuning rule
(2) SMOOTH CONTROL
Tuning parameter: c = desired closed-loop response time
(1) Selecting c= (“tight control”) is reasonable for cases with a relatively large effective delay
Other cases: Select c > for slower control smoother input usage
less disturbing effect on rest of the plant less sensitivity to measurement noise better robustness
Question: Given that we require some disturbance rejection. What is the largest possible value for c ? Or equivalently: The smallest possible value for Kc?
Closed-loop disturbance rejection d0
ymax
-d0
-ymax
SMOOTH CONTROL
Kc
u
Minimum controller gain for PI-and PID-control:Kc ¸ Kc,min = |ud0|/|ymax|
|ud0|: Input magnitude required for disturbance rejection|ymax|: Allowed output deviation
SMOOTH CONTROL
Minimum controller gain:
Industrial practice: Variables (instrument ranges) often scaled such that
Minimum controller gain is then
Minimum gain for smooth control )Common default factory setting Kc=1 is reasonable !
SMOOTH CONTROL
(span)
Example
Does not quite reach 1 because d isstep disturbance (not not sinusoid)
Response to disturbance = 1 at input
c is much larger than =0.25
SMOOTH CONTROL
Application of smooth control Averaging level control
VqLC
Reason for having tank is to smoothen disturbances in concentration and flow. Tight level control is not desired: gives no “smoothening” of flow disturbances.
Derivation of tunings:Minimum controller gain for acceptable disturbance rejection:
Kc ¸≥ Kc,min = |ud0|/|ymax|Where in our case
|ud0| = |q0| - expected flow change [m3/s] (input disturbance) |ymax| = |Vmax| - largest allowed variation in level [m3]
Integral time:From the material balance (dV/dt = q – qout), the model is g(s)=k’/s with k’=1.
Select Kc=Kc,min = |q0| |Vmax| . SIMC-Integral time for integrating process:
I = 4 / (k’ Kc) = 4 |Vmax| / |q0| = 4 ¢ residence time
provided tank is nominally half full (so |Vmax| = V) and q0 is equal to the nominal flow.
SMOOTH CONTROL LEVEL CONTROL
If you insist on integral actionthen this value avoids cycling
Rule: Kc ¸ |ud0|/|ymax| ( ~1 in scaled variables) Exception to rule: Can have even smaller Kc (< 1)
if disturbances are handled by the integral action. Happens when c > I = 1
Applies to: Process with short time constant (1 is small)
For example, flow control
SMOOTH CONTROL
Kc: Assume variables are scaled with respect to their span
Summary: Tuning of easy loops Easy loops: Small effective delay ( ¼ 0), so closed-
loop response time c (>> ) is selected for “smooth control”
Flow control: Kc=0.5, I = 1 = time constant valve (typically, 10s to 30s)
Level control: Kc=2 (and no integral action) Other easy loops (e.g. pressure control): Kc = 2, I =
min(4c, 1) Note: Often want a tight pressure control loop (so may have
Kc=10 or larger)
SMOOTH CONTROL
Kc: Assume variables are scaled with respect to their span
More on level control
Level control often causes problems Typical story:
Level loop starts oscillating Operator detunes by decreasing controller gain Level loop oscillates even more ......
??? Explanation: Level is by itself unstable and
requires control.
LEVEL CONTROL
Integrating process: Level control
LEVEL CONTROL
• Level control problem has– y = V, u = qout, d=q
• Model of level: V(s) = (q - qout)/s– G(s)=k’/s, Gd(s)= -k’/s (with k’=1)
• Apply PI-control: u = c(s) (ys-y); c(s) = Kc(1+1/Is) • Closed-loop response to input disturbance:
y/d = gd / (1+gc) = I s / (I/k’ s2 + Kc I s + Kc)• The denominator can be rewritten on standard form
– (02 s2 + 2 0 s + 1) with 0
2 = I/k’¢Kc and 2 0 = I
– Algebra gives:
– To avoid oscillations we must require 1, or Kc¢k’ ¢I > 4• The controller gain Kc must be large to avoid oscillations!
VqLC
VqLC
qLC
This is the basis for the SIMC-rule for the minimumintegral time
How avoid oscillating levels?
LEVEL CONTROL
• Simplest: Use P-control only (no integral action)• If you insist on integral action, then make sure
the controller gain is sufficiently large• If you have a level loop that is oscillating then
use Sigurds rule (can be derived):
To avoid oscillations, increase Kc ¢I by factor f=0.1¢(P0/I0)2
where P0 = period of oscillations [s]I0 = original integral time [s]
Actually, 0.1 = 1/π2
Case study oscillating level We were called upon to solve a problem with
oscillations in a distillation column Closer analysis: Problem was oscillating reboiler
level in upstream column Use of Sigurd’s rule solved the problem
LEVEL CONTROL
LEVEL CONTROL
Identifying the model
Model identification from step response General: Need 3 parameters:
Delay 2 of the following: k, k’, 1
(Note relationship k’ = k/1)
Two approaches for obtaining 1:
1. Initial response: ( + 1) is where initial slope crosses final steady-state
2. (+1)= 63% of final steady state If disagree: Initial response is
usually best, but to be safe use smallest value for 1 (“fast response”) as this gives more conservative PID-tunings 1 = 16 min for this case
0 50 100 150 200 250 3000.095
0.1
0.105
0.11
0.115
0.12
0.125
0.13
0.135
0.14
BOTTOM V: -0.5
xB
1=16 min / 19 min
63%
k
k’
Model identification from step response
Generally need 3 parameters
BUT For control: Dynamics at “control time scale” (c) are important
“Slow” (integrating) process (c< 1/5): May neglect and use only 2 parameters: k’ and
g(s) = k’ e- s / s
“Delay-free” process (c > 5θ): Need only 2 parameters: k and 1
g(s) = k / (1 s+1)
0 10 20 30 40 50 600.9949
0.995
0.995
0.9951
0.9951
0.9952
0.9952
0.9953
0.9953
0.9954
c > 5θ = 5: “Delay-free” (neglect θ)
1 ¼ 200, 1
time
c = desired response time
c
c < τ1/5 = 40: “Integrating” (neglect τ1)
“Integrating” process (c < 1/5): Need only two parameters: k’ and From step response:
0 2 4 6 8 102.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8Response on stage 70 to step in L
7.5 min
2.62-2.19
Example.
Step change in u: u = 0.1Initial value for y: y(0) = 2.19Observed delay: = 2.5 minAt T=10 min: y(T)=2.62Initial slope:
y(t)
t [min]
“Delay-free” process (c > 5 )
Example:
First-order model: = 0 k= (0.134-0.1)/(-0.5) = -0.068 (steady-state gain) 1= 16 min (63% of change)
0 50 100 150 200 250 3000.095
0.1
0.105
0.11
0.115
0.12
0.125
0.13
0.135
0.14
BOTTOM V: -0.5
xB
16 min
63%
Step response experiment: How long do we need to wait?
NORMALLY NO NEED TO RUN THE STEP EXPERIMENT FOR LONGER THAN ABOUT 10 TIMES THE EFFECTIVE DELAY ()
Conclusion PID tuningSIMC tuning rules
1. Tight control: Select c= corresponding to
2. Smooth control. Select Kc ¸
Note: Having selected Kc (or c), the integral time I should be selected as given above
Cascade control
CC
TCTs
xB
CC: Primary controller (“slow”): y1 = xB (“original” CV), u1 = y2s (MV)TC: Secondary controller (“fast”): y2 = T (CV), u2 = V (“original” MV)
Tuning: 1. First tune TC (based on response from V to T)2. Close TC and tune CC(based on response from Ts to xB)
Primary controller (CC)sets setpoint to secondary controller (TC).
Tuning of cascade controllers• Want to control y1 (primary CV), but have “extra” measurement y2
• Idea: Secondary variable (y2) may be tightly controlled and this helps control of y1.
• Implemented using cascade control: Input (MV) of “primary” controller (1) is setpoint (SP) for “secondary” controller (2)
• Tuning simple: Start with inner secondary loops (fast) and move upwards
• Must usually identify new model experimentally after closing each loop.
• One exception: Serial process with “original” input (u) and outputs (y1) at opposite ends of the process, and y2 in the middle.– Inner (secondary-2) loop may be modelled with gain=1 and effective
delay=(c+
Cascade control serial process(“exception”) d=6
G1u2
y1
K1
ys G2K2
y2y2s
Cascade control serial process d=6
Without cascade
With cascade
G1u
y1
K1
ys G2K2
y2y2s
Tuning cascade control: serial process Inner fast (secondary) loop:
P or PI-control Local disturbance rejection Much smaller effective delay (0.2 s)
Outer slower primary loop: Reduced effective delay (2 s instead of 6 s)
Time scale separation Inner loop can be modelled as gain=1 + 2*effective delay (0.4s)
Very effective for control of large-scale systems
Controllability
(Input-Output) “Controllability” is the ability to achieve acceptable control performance (with any controller)
“Controllability” is a property of the process itself Analyze controllability by looking at model G(s) What limits controllability?
CONTROLLABILITY
Recall SIMC tuning rules
1. Tight control: Select c= corresponding to
2. Smooth control. Select Kc ¸
Must require Kc,max > Kc.min for controllability
)
Controllability
initial effect of “input” disturbance
max. output deviation
y reaches k’ ¢ |d0|¢ t after time ty reaches ymax after t= |ymax|/ k’ ¢ |d0|
CONTROLLABILITY
ControllabilityCONTROLLABILITY
• More general disturbances. Requirement becomes (for c=):
• Conclusion: The main factors limiting controllability are – large effective delay from u to y ( large)– large disturbances (k’d |d0| / ymax large)
• Can generalize using “frequency domain”: |Gd(j¢0.5/max)| ¢|d0| = |ymax|
Following step disturbance d0:Time it takes for output yto reach max. deviation
Example: Distillation column
CONTROLLABILITY
0 1 2 3 4 5 6 7 8 9 10-2
0
2
4
6
8
10
12
14
16x 10
-3
time [min]
Response to 20% increase in feed rate (disturbance) with no control
xB(t)
xD(t)
ymax=0.005
time to exceed bound = ymax/k’d |d| = 3 min
Controllability: Must close a loop with time constant (c) faster than 1.5 min toavoid that bottom composition xB exceeds max. deviationIf this is not possible: May add tank (feed tank?, larger reboiler volume?) to smooth disturbances
Data for “column A”Product purities:xD = 0.99 § 0.002, xB=0.01 § 0.005(mole fraction light component)Small reboiler holdup, MB/F = 0.5 min
Max. delay in feedbackloop, max = 3/2 = 1.5 min
Example: Distillation column
CONTROLLABILITY
0 1 2 3 4 5 6 7 8 9 10-2
0
2
4
6
8
10
12
14
16x 10
-3
0 1 2 3 4 5 6 7 8 9 10-2
0
2
4
6
8
10
12
14
16x 10
-3
time [min]
Increase reboiler holdup to MB/F = 10 min
xB(t)
3 min 5.8 min
xB(t)
Original holdup Larger holdup
With increased holdup: Max. delay in feedback loop: = 2.9 min
Distillation example: Frequency domain analysis
CONTROLLABILITY
10-3
10-2
10-1
100
101
10-1
100
101
Effect of F on xB
max
Frequency where |Gd(j)| for feed disturbance crosses 0.5 (max): d = 0.3 min-1
) Need response time c · max = 0.5/d = 1.7 min
Agrees with previous result (1.5 min)
Frequency-dependent gains |Gd(j)|Column A with small reboiler holdup.LV-configuration
zF on xB
Other factors limiting controllability
CONTROLLABILITY
Input limitations (saturation or “slow valve”): Can sometimes limit achievable speed of response
Unstable process (including levels): Need feedback control for stabilization ) Makes sure inputs do not saturate in stabilizing loops