User Manual
ORAND Co., LTD.
D IG IT L P R TS FE ED ERON TROLLER
O P C 5 T HO P C 1 T H
-
8/13/2019 pds-23
2/15
1
[Table of Contents]1.Product appearance and functions
1.1 The front of product1.2 The side and the inside of product
2.Installation2.1 Selection of input power2.2 Connection of output power2.3 Connection of a feedback sensor2.4 Connection of voltage remote controller
external VR/0-5V remote control2.5 Connection of an external sensor2.6 Connection of the synchronous output for running
3.Operation3.1 Standard operation3.2 Constant amplitude control operation3.3 Run/stop control by the external input
EXS: PLC3.4 Temporary run/stop control by the sensor
input SENS: OVER-FLOW
4.Parameter set-up5.Specifications of product function6.The function of protection and alarm* Appendix wiring diagram schematic for the operation connectedbetween Bowl Feeder and Hopper
. Copyright
. Precautions
-
8/13/2019 pds-23
3/15
2
1. Product appearance and functionsThe OPC-100TH, 50TH Parts Feeder Controller, as a controller for adjusting
frequency/voltage which applies full digital control PWM inverter controlling the width
of pulse in the high speed RISC CPU, is available to ensure the stable output voltage and
frequency in the weak circumstance comparing to the analog PWM generation system and
possible to have memory.
It has no concern with 50Hz/60Hz input frequency and enables a user to set up each
parameter with the functions of external sensor input control, synchronous signal outputfor running, one touch memory, soft start/stop, on/off timer and others. Thus, it is easy
to apply to various feeders and possible to get any operation liked with external
instrument. It is also available for a feeder having heavy worker load or high frequencyprecision to get constant amplitude control operation through feedback by using an
electronic vibrating sensor (option).
The appearance and main functions are as follows.
1.1 Product Front
RUN
STOP M2
M1
PARA
SET/VF
FBK
FBK
RUN
VRLCK
V/F FINE
OFF
ON
PARTS FEEDER CONTROLLER
OPC-000TH
6.RUN State Dot LED. Lighting during running. Flicking during pause by an external
sensor. Lights-out when it stops completely
7.Feed-Back State Dot LED. Lighting When the FB operates. Flickering when the FB pauses. Lights-out when the FB is not set up
("Fb-oF")
9.VR Lock Dot LED. Lighting when any key or VR does
not operate for a certain time.. When it is lighted, the VR is not
controlled. Lock is released when any key is
pressed
2.STOP Key. Stop when it is pressed shortly
at the state of run. When the power is turned on with
it pressed, voltage/frequency/parameter return to the initialvalues of shipment
1.RUN Key. Run when it is pressed. Not operate during over-current,
overheating and error
3.Memory Key1/Memory Key2. When it is pressed long, the present
frequency/voltage/parameter arememorized (write)
. When it is pressed shortly, thememorized frequency/voltage/parameterare converted to the present operationconditions (read)
4.UP/Down Key. Change the values of the present
frequency, voltage or parameter.. Continue to be pressed when the
frequency or voltage is displayed.Then, fast sending is achieved.
8.7-segment indicator. Frequency, voltage, parameter, error
code and others are indicated innumber or letter
10.Parameter set-up key. When it is pressed while the
operation stops, it becomesparameter set-up mode. Whenever itis pressed, the items of parameterare changed.
. It returns to frequency indicatingmode if there is no any operationfor a certain time.
11.SET/VF/FBK Key. Parameter set-up mode: When it is
pressed, the present value is savedas a set-up value.
. Voltage/ frequency indicating mode
-Whenever it is pressed shortly,voltage/frequency indicating modesrepeat converting.Whenever it is pressed long, thepause and run of FB function repeat(to set up the "Fb-on")
12.fine adjust VR for voltage/frequency. It is used for precise adjustment with
an up/down key when frequency orvoltage is set up
. The voltage and frequency are variablewithin 50V and 20Hz respectively.
5.Power switch
-
8/13/2019 pds-23
4/15
3
1.2 The side and the inside of product
3.Input port for external start. Run/stop external input port4.Input port for sensor 1.Input port for external sensor
(over-flow)
1.Feedback sensor connecting port. Connection of vibrating sensor
for constant amplitude operation. The sensor is on separate sale
(option)
6.Synchronous signal output portfor running. Normal close (NC) based on COM
Normal open (NO) output
7.Output power port. Controlled PWM AC power output
8.Input power port
2.External VR connecting port foradjusting voltage Note. connector : 5051-03
5.Set-up of sensor 1 type. NPN/PNP selection
3.Input port for external sensor 2.Input port for external sensor
(over-flow)
4.Solenoid valve 2 connecting port
Solenoid Valve Control Board on separate sale
G
SN2
+12
SO2B
SO2A
SO1B
SO1A
2.Set up the senso r 2 type.Selection of NPN/PNP
1.Set up the number of availablesensors
.1Sensor/2Sensor
5.Solenoid valve 1 connecting port
OUTB
OUTA
FG
FG
INA
INB
NC
COM
NO
GEXS+12G
SN1+12
Heat Sink
Transformer
EXVR
FB
220
9.FUSE10.Switch for selecting input power. 110/220V selection
(220V when shipping)
SWITCH FUSE
Applicable to only OPC-50TH
3
2
1
3
2
1
GND
0~5V 2
3
1
[External VR][0~5V Control]
EXVR EXVR
VR: 10K-B
GND
3
2
1
10k(recommended)
Note
-
8/13/2019 pds-23
5/15
4
2.Installation2. 1 The sele ctio n of inpu t powe r
The selection of input power has been set up 220V when shipping. If a user wants to use
110V, turn off the power and convert the input power selecting switch inside the productto 110V.
2. 2 The conn ecti on of outp ut powe rIt is required to connect the output power port to the connector in reference with the
diagram of [product appearance and functions] supplied with the product.
2. 3 The conn ecti on of feed back sens orIt is required to connect the joining connector of feedback sensor to the "FB" port
located inside the product, and tighten the sensor by matching the vibrating direction
and the indicating direction "" of the sensor. For accurate operation, it is necessary
to connect the earth (FG) port of output power to the feeder earth, and also it isrequired to set up the parameter after connecting the sensor in order to use thefeedback (refer to [the set-up of parameter]). The feedback sensor is on separate sale
(option).
2. 4 The conn ecti on of volt age remo te cont roll erexternal VR/0-5V remove control
This product has a connecting port for external VR or 0-5V remote control as the
industry standard voltage control system. It is recommended to use 10 B-type for the
external VR [Refer to the product appearance and functions]. When it is connected, it is
automatically prohibited to use the voltage control function of the VR in the body and
the up/down key (activated by only frequency control function). The 0-5V voltage control
is designed to vary output voltage in comparison with control voltage. Refer to the
diagram of [the product appearance and functions].
OPC-100TH, OPC-50THPARTS FEEDER CONTROLLER PARTS FEEDER
SENSOR
AC Input110V/220V
SYNC
EXSON/OFFCONTROL
SENS 1,2
FB-SEN
OUT-AC
External deviceON/OFF
(FB SENSOR)
(OVER-FLOW SENSOR)
[Wiring diagram schematic]
External VR connecting port
ON
OFF
V/F FINE
SOL 1,2 SOLENOID
-
8/13/2019 pds-23
6/15
5
2. 5 The conn ecti on of exte rnal sens or SN1/ SN2It enables to control the ON/OFF of the product by connecting the external sensor. It
is available to use wet contacts (photo coupler, neighboring sensor, etc) or dry
contacts (relay contact, switch, etc) and also set up the change of logically positive
and negative polarities of input. (Refer to [the set-up of parameter]).
2. 6 The conn ecti on of the sync hron ous outp ut sign al forrunning SYNC
It is available to operate an external instrument by synchronizing the signal of run/stop. In case that several products are used, it allows them to run and stop at the
same time by controlling one.
Internal input part
NC used
NO usedNO
COM
NC
Run
Stop
[The connection of external sensor]
External instrument
[The connection of external sensor]
Internal input part
+12V
GND
SN1/SN2
+12V
SENSOR Input Contact Input
External controller Open Collector Input
V
+
-
External Voltage Input(12~24V)
-
8/13/2019 pds-23
7/15
6
3.1 Standard operationIt is recommended to follow the following sequence when it operates without using a
feedback sensor.
Press the run key after adjusting frequency to the maximum and voltage to the middle
while the power is switched on.
Find out the resonance frequency which has the biggest vibration by adjusting
frequency If there is no feedback during operation, deviate that from the resonance
point slightly because the change of vibration is sensitive due to the external
influence at the resonance point.
Adjust the amplitude of vibration by adjusting voltage
Find out the optimum point by repeating the above (2) and (3).
It is convenient to use the V/F FINE VR when the fine adjustment of frequency or
voltage is required.
It is convenient to memorize by using the memory keys (M1, M2) if necessary.
Change the parameter if necessary (refer to the set-up of parameter).
Press the stop key when the operation is complete.
The method of frequency adjustment
. The frequency indication/set-up mode is activated when the V/F (SET) key is pressed
at the voltage indication/set-up mode, or the parameter set-up mode is released.
. The 7-segments are indicated as "Fxxx.x" at the frequency indication/set-up mode.
. Adjust the frequency by using the up/down ( / ) key, but the V/F FINE VR is
recommended for precise adjustment around the resonance frequency.
. If any key or VR is not handled for a certain time, the VR is locked and the "VRLCK"
dot LED is turned on.
. The VR lock is automatically released if any key is handled.
The method of voltage adjustment
. The voltage indication/set-up mode is activated when the V/V (SET) key is pressed at
the frequency indication/set-up mode.
. The 7-segments are indicated as "Fxxx.x" at the voltage indication/set-up mode.
. Adjust the frequency by using the up/down ( / ) key, but the V/F FINE VR is
recommended for precise adjustment around the resonance frequency.
. If any key or VR is not handled for a certain time, the VR is locked and the "VRLCK"
dot LED is turned on.
. The VR lock is automatically released if any key is handled.
The method of key memory(frequency/voltage/parameter)
. Press the memory key ([M1]/[M2]) that a user wants to memorize until it beeps with the
7-segments flickered. Then, the present frequency, voltage and parameter are memorized.
The method of running with the memorized values of key (frequency/voltage/parameter)
. Press and release the memory key ([M1]/[M2]) that a user wants to read, then, the
frequency/voltage/parameter which have been memorized in the key are converted to
the present running values.
3.Operation
-
8/13/2019 pds-23
8/15
7
3.2 Constant amplitude control operationThe control operation using a vibrating sensor follows the following sequence.
Tighten a vibrating sensor to the parts feeder, and switch the power on after
connecting the connector of vibrating sensor to the [FB] port within the product.
Press the [para] key at several times to indicate "Fb-xx", and press [] or []
key to indicate "Fb-on". Then, press the [set] key. When the "FBK" lamp flickers,
the function of feedback pauses.
If necessary, press the [para] key again to indicate "Fbxxx", and press up the
[set] key after setting up the period of feedback.
Press the [stop] key to return to the frequency indicating mode.
Press the [run] key after setting up frequency and voltage properly.
Adjust the resonance point and the optimized running vibration by setting
frequency and voltage.
Press the [FBK] key for a long time at the state of running until it beeps to
activate the function of feedback which has paused for a moment (The "FBK" lamp
changes form flickering to lighting.
If necessary, write to the memory key(M1/M2).
(Cautions)
1.The memory key, voltage & frequency adjusting key and VR are not activated during
feedback.2. When the amplitude of vibration is set up again, it is necessary to adjust
voltage and frequency after pausing the function of feedback ("FBK" lamp flickers)
and reactivate the feedback by pressing the [FBK] key at the state of running.3. When the [FBK] key is long pressed until it beeps, the constant amplitude running
(FBK lamp lights) and its pause (FBK lamp flickers) repeat.
For general information of other operations, refer to the standard operation.
3. 3 Run/ stop cont rol by the exte rnal inpu t EXS: PLCIt is possible to control run/stop by using an external signal such as PLC except
[run]/[stop] key of the OP panel. It is also possible to input the dry contact such as
switch, relay contact and others and wet contact, open collector such as sensor output.
The run/stop control by an external input follows the following sequence.
Connect the external input controller to the [EXS] ports in the side and the inside
of the product. (refer to "the connection of external sensor" of "installation")
Press the [para] key at several times to indicate "ES-xx", and press [] or []
key to adjust the logical polarity of the connected input instrument. Then, press
the [set] key. (refer to [the set-up of parameter]).
Activate the control by using an external input.
(Note) It is available to use the function of [run]/[stop] key of OP panel when the
control is activated by an external input.
-
8/13/2019 pds-23
9/15
8
3. 4 Temp orar y run/ stop cont rol by the Sens or inpu tSENS: over-flow
It is available to stop the operation temporary by an external sensor signal such as
over-flow at the state of "run".
It is all possible to input the dry contacts such as switch and relay contact and wet
contact, open collector such as sensor output.
Besides, it enables a user to set up the delay time during running and stop directly
with "on delay timer" and "off delay timer. Therefore, it is easy to perform a fine
control for over-flow and others.
The temporary run/stop control by an external input follows the following sequence.
Connect the external input controller to the [EXS] ports in the side and the inside
of the product. (refer to "the connection of external sensor" of "installation")
Set up parameters of logical polarity of sensor input, on delay timer and off delay
timer values. (refer to [the set-up of parameter]). Activate the control by using an external input at the state of "run" The run dot
LED flickers during pause by a sensor
(Cautions) The function of "run"/"stop" by the OP panel or external input run/stop
controls takes precedence of this function, that is, this function meansthe operation at the state of "run".
Example of the multiple run/stop control for external input
EXS SYNC EXS EXS EXS EXSExternal
ON/OFF Signal
ON
OFF
V/F FINE V/F FINEON
OFF
ON
OFF
V/F FINEON
OFF
V/F FINE ON
OFF
V/F FINE
SLAVEMASTER
ON
OFF
V/F FINE V/F FINEON
OFF
ON
OFF
V/F FINE ON
OFF
V/F FINE ON
OFF
V/F FINE
EXSEXS EXS EXS EXSExternal
ON/OFF Signal
-
8/13/2019 pds-23
10/15
9
Indication
order
Indication
(mode) Description Scope Shippingvalue
1 onxx x Sensor input on timer(sensor control on timer)
.Set up the time to the start of operationafter the input is on
0.1~10.0 Sec(0.1Sec step)
0.1
2 oFxx x Sensor input Off Time(Sensor Control Off Timer)
. Set up the time to the stop of operation afterthe input is off
0.1~10.0 Sec
(0.1Sec step) 0.1
3 Sn xx Set up the logical polarity of sensor input
.no : Normal Open
.nc : Normal Close -edge trig system
nonc
no
4 ES xx Set up the logical polarity of external start
input (Ext. start).no : Normal Open.nc : Normal Close -edge trig system
nonc
no
5 SLux x Set up the slow-up (soft start) time 0.1~3.0 Sec(0.1Sec step) 0.16 SLdx x Set up the slow-down (soft stop) 0.1~3.0 Sec(0.1Sec step) 0.17 Fb xx Set up the yes or no of feedback control on : yesoF : no oF8 Fbxxx Set up the period of feedback..If the bowl is big, it takes long period 0~1000 mSec(1 mSec step) 1009 vr xx Set up the control range of voltage adjust VR* ( )means 110V input 10(5)~90(45)V(10V step) 50(25)
10 Lnxxx Indicate the selection of input power
.Selected Line Voltage Display
.Location of input power selection switch
220110
220
11 100TH
50tH Indicate the product model number
(for management) - -
12 vErxx Indicate the firmware version (for management) - -
4. The set-up of p arameterThis product indicates parameters in both letter and number and has a parameter set-up
key separately so that a user can recognize each parameter easily.
The sequence of set-up are as follows.
Move to the mode that a user wants to set up by pressing the [para] key. Whenever
the key is pressed, the state of indication (mode) changes and the present setting
parameter is indicated.
Change of the indicated parameter
.Whenever [] / [] key, the indication flickers and parameter changes.
.For the input of parameter in number, press the [] / [] key for a long time,
then, it is sent fast..When the [set] key is pressed, it beeps long and the present indicated information
is set up. (If the [set] key is not pressed, it is invalid and the previous
information is maintained). Press the [stop] key or leave it as it is, the frequency indication mode is
reactivated after a while.
(Note) If the power is switched on while the [stop] key is pressed, all parametersreturn to the initial values when shipping.
-
8/13/2019 pds-23
11/15
10
5.SpecificationsItems OPC-50TH OPC-100TH Remarks
Rated input .AC110V/220V 50-60Hz.Set-up with an internal selecting switch
O
U
T
P
U
T
Voltage
Method of set-up Up/down key & internal VR, external VR, 0-5V
Scope of set-up 0~100V/0~200V
Resolution of
set-up 0.1V
Frequency
Method of set-up Up/Down Key or internal VR
Scope of set-up 40~400Hz
Resolution of
set-up 0.1Hz
Maximum allowable current 5A 10A
Operating system PWM system
C
O
N
T
R
OL
Control system Full digital control by RISC CPU
Run
Stop
Control
External input.on/off control by external input (PLC).Dry/wet contact (12V, 24V).Set up the change of input polarity :positive/negative
Sensor input
(2 ports)
.Pause/run at the state of run (overflow)
.Dry/wet contact (12V, 24V)
.Set up the change of input: Positive/negative polarity,PNP/NPN
.Set up the on delay timer: 0 - 10. Osec, O.1sec step
.Set up the off delay timer: 0 - 10. Osec, O.1sec step
.Sensor power: DC12V 100mA
Panel handling RUN,STOP Key
Running synchronous signal 3 port output (COM,NC,NO)Soft Start Set up 0.1-3.0 sec(0.1s step, up/down key)
Soft Stop Set up 0.1-3.0 sec(0.1s step, up/down key)
Constant amplitude control Feedback control by an vibrating sensor(option)
Solenoid valve
.220V x 2 port output
(option)
.Selection of 1 or 2 sensors
NONE
Memory function .2-Channel(M1/M2 Key)
.One-Touch Read/Write (voltage frequency, parameter)
Data memory method EEPROM
Indic
ation
7-Segment Indicate voltage, frequency, parameter, error code
Dot LED Indicate Run, feedback, VR lock
The function of protection Stop the running when over-current, over-temperature, and
ring the alarm
Alarm method .Indicate the error code (flickering)
.Ring the alarm
Cooling system Natural air-cooling
Usage conditionsAmbient temp 0 ~ 40
Ambient moisture 10 ~ 90%
Sourc
es
Weight 1.5 Kg 1.75Kg
Appearance 61(W)151(D)150(H) 72(W)151(D)150(H)
-
8/13/2019 pds-23
12/15
11
Error code Troubles Solutions
Err01 EEPROM Write Error.Writing error of EEPROM .Required to repairErr02 Overheat error.Internal heat-sink is over-heated
.Turn off the power and remove the cause ofoverheat. Then, wait for a certain time soas to get natural cooling.
Err03 Over-current error.Over-current flow
.Turn off the power and remove the cause of
over-current
Err04 Feedback sensor not connected error
.Parameter has been set up to "Fb-on"
but the FB sensor is not connected
.Check the connection and state of FB sensor
.Adjust the sensor parameter to "Fb-oF"
Err05 Excessive level error of feedback
senor
.Excessive vibration of FB sensor
.Adjust the output level of sensor bychanging the location/direction of FBsensor
6.The function of protection and alarmThis product activates the function of protection if there is any trouble caused by
the carelessness of a user or environment. It also indicates error code on the7-segments and rings the alarm.
Troubles based on the error code and solutions are as follows
-
8/13/2019 pds-23
13/15
12
Wiring diagram schematic for the operation connected
between BOWL Feeder and Hopper. The hopper is activated only when the Bowl feeder runs
INB
FG
OUTA
OUTB
INA
FG
NO
COM
NC
+12
SN1
G
+12
EXS
G
BOWL FEEDER
BOWL FEEDER
HOPPER
INB
FGOUTA
OUTB
INA
FG
NO
COM
NC
+12
SN1
G
+12
EXS
G
HOPPER
OUT-AC
AC Input110V/220V
Sensor
OUT-AC
AC Input110V/220V
LevelSensor
[Appendix]
-
8/13/2019 pds-23
14/15
13
CopyrightThe intellectual property of this product and the copyright of the statement have
been reserved to the Orand Corporation. It is prohibited to use or copy without
permission.
It is allowed to change the contents of this statement to improve the functions of the
product.
Precautions It is recommended to use the product within the rated voltage and rated current of
input/output power.It is dangerous to damage the product or fire
It is prohibited to disassemble, repair or convert at randomIt is possible to damage or malfunction the product
It is recommended to connect the input/output voltage without powerIt is dangerous to damage the product or receive an electric shock
It is necessary to connect the earth port of input/output power to groundingIt prevents an electric shock if electricity leaks and reduces the noise of power
The rated voltage has been set up to 220V when shipping. Therefore, it isrecommended to select the input power selecting switch inside the product to110V if a user wants to use 110V,
-
8/13/2019 pds-23
15/15
O R A N D C o . , L T D .
W W W . O R A N D. C O . K R
740-6 Daelim 3-Dong Yeongdeungpo-Gu
Seoul, Korea
T E L 82-2-836-4744~5
F A X 82-2-836-4746
* It is allowed to change the contents of this manual to improve the functions
of the product. 2005.5. edit