pcd software & commissioning guide...pcd software & commissioning guide rickard 2018 open...

9
PCD SOFTWARE & COMMISSIONING GUIDE RICKARD 2018 PRESSURE CONTROL DAMPER PRESSURE CONTROL DAMPER PRESSURE CONTROL DAMPER HARDWARE & SOFTWARE HARDWARE & SOFTWARE HARDWARE & SOFTWARE COMMISSIONING GUIDE COMMISSIONING GUIDE COMMISSIONING GUIDE PRESSURE CONTROL DAMPER PRESSURE CONTROL DAMPER PRESSURE CONTROL DAMPER HARDWARE & SOFTWARE HARDWARE & SOFTWARE HARDWARE & SOFTWARE COMMISSIONING GUIDE COMMISSIONING GUIDE COMMISSIONING GUIDE

Upload: others

Post on 03-Sep-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PCD SOFTWARE & COMMISSIONING GUIDE...PCD SOFTWARE & COMMISSIONING GUIDE RICKARD 2018 Open the MLM Application and click connect. If you are using a USB module, click on the USB tab

  PCD SOFTWARE & COMMISSIONING GUIDE

RICKARD 2018

PRESSURE CONTROL DAMPER PRESSURE CONTROL DAMPER PRESSURE CONTROL DAMPER HARDWARE & SOFTWARE HARDWARE & SOFTWARE HARDWARE & SOFTWARE

COMMISSIONING GUIDECOMMISSIONING GUIDECOMMISSIONING GUIDE

PRESSURE CONTROL DAMPER PRESSURE CONTROL DAMPER PRESSURE CONTROL DAMPER HARDWARE & SOFTWARE HARDWARE & SOFTWARE HARDWARE & SOFTWARE

COMMISSIONING GUIDECOMMISSIONING GUIDECOMMISSIONING GUIDE

Page 2: PCD SOFTWARE & COMMISSIONING GUIDE...PCD SOFTWARE & COMMISSIONING GUIDE RICKARD 2018 Open the MLM Application and click connect. If you are using a USB module, click on the USB tab

  PCD SOFTWARE & COMMISSIONING GUIDE

RICKARD 2018

MLM CONNECTION SCHEMATIC

MLM SOFTWARE 

MAXIMUM 15 DIFFUSERS, 150M INTER‐DIFFUSER CABLES AND 20 CABLE SECTIONS (INCLUDES INTER‐DIFFUSER AND INTER‐DIFFUSER CABLE EXTENSIONS) 

MCU 

ADD MCU’S TO CONNECT A MULTIPLE OF 60 DIFFUSERS  

MAXIMUM PSU TO  MCU LENGTH 120m 

MAXIMUM 15 PCDs, MAXIMUM 3‐CORE INTER‐PCD CABLE LENGTH ‐  30m EACH 

MAXIMUM PSU TO  MCU LENGTH 120m 

MAXIMUM PSU TO  MCU LENGTH 120m 

MAXIMUM PSU TO  MCU LENGTH 120m 

MAXIMUM 15 DIFFUSERS, 150M INTER‐

DIFFUSER CABLES AND 20 CABLE SECTIONS 

(INCLUDES INTER‐DIFFUSER AND INTER‐

DIFFUSER CABLE EXTENSIONS) 

USE TERMINATION  

RESISTORS  ON EACH END 

OF THE DIFFUSER NETWORK 

USE TERMINATION  

RESISTORS ON EACH END 

OF THE DIFFUSER NETWORK 

USE TERMINATION  

RESISTORS ON EACH END 

OF THE DIFFUSER NETWORK 

USE TERMINATION  

RESISTORS  ON EACH END 

OF THE PCD  NETWORK 

USE TERMINATION  

RESISTORS ON EACH  

END OF THE DIFFUSER 

NETWORK 

USE TERMINATION  

RESISTORS ON EACH  

END OF THE DIFFUSER 

NETWORK 

USE TERMINATION  

RESISTORS ON EACH  

END OF THE DIFFUSER 

NETWORK 

USE TERMINATION  

RESISTORS ON EACH  

END OF THE PCD 

NETWORK 

IF FITTED WITH HEATING,  

EACH DIFFUSER COMES  

WITH A 220V SOCKET 

PSU (110‐240V) 

PSU (110‐240V) 

PSU (110‐240V) 

MAXIMUM 15 DIFFUSERS, 150M INTER‐

DIFFUSER CABLES AND 20 CABLE SECTIONS 

(INCLUDES INTER‐DIFFUSER AND INTER‐

DIFFUSER CABLE EXTENSIONS) 

IF FITTED WITH HEATING,  

EACH DIFFUSER COMES  

WITH A 220V SOCKET 

IF FITTED WITH HEATING,  

EACH DIFFUSER COMES  

WITH A 220V SOCKET 

Page 3: PCD SOFTWARE & COMMISSIONING GUIDE...PCD SOFTWARE & COMMISSIONING GUIDE RICKARD 2018 Open the MLM Application and click connect. If you are using a USB module, click on the USB tab

  PCD SOFTWARE & COMMISSIONING GUIDE

RICKARD 2018

Make sure the terminator resistor is plugged into the last connector if the PCD is the last one in the chain of PCDs.

To connect PCD to a series of PCDs, plug in the 3-core interlinking cable, and connect to the next PCD in the chain. alone.

Connect the sensor cable to the pressure sensor. Connect the sensor cable to the PCD. Thereafter mount the pres-sure sensor to the appropriate place in the duct. The pressure sen-sor should be placed half way to 2/3 down the duct to get a repre-sentative pressure.

To connect the PCDs to the MLM system, connect the RJ9 cable to the MCU. Connect to the next available channel.

Connect the RJ9 cable to the PCD.

HARDWARE INSTALLATION

Termination resistor

Page 4: PCD SOFTWARE & COMMISSIONING GUIDE...PCD SOFTWARE & COMMISSIONING GUIDE RICKARD 2018 Open the MLM Application and click connect. If you are using a USB module, click on the USB tab

  PCD SOFTWARE & COMMISSIONING GUIDE

RICKARD 2018

Plug in and switch on the power socket. You can also connect to a single PCD and commission it with a USB connection which is plugged directly to your computer.

Page 5: PCD SOFTWARE & COMMISSIONING GUIDE...PCD SOFTWARE & COMMISSIONING GUIDE RICKARD 2018 Open the MLM Application and click connect. If you are using a USB module, click on the USB tab

  PCD SOFTWARE & COMMISSIONING GUIDE

RICKARD 2018

To set-up Rickard diffusers, you need to install Rickards MLM software. If it is not installed follow the following instructions to install it. Go to http://www.rickardair.com

http://www.rickardair.com/controls-support-0

Click on the 32 or 64 bit MLM Tool depending if you have a 32 or 64 bit PC and download the file.

Page 6: PCD SOFTWARE & COMMISSIONING GUIDE...PCD SOFTWARE & COMMISSIONING GUIDE RICKARD 2018 Open the MLM Application and click connect. If you are using a USB module, click on the USB tab

  PCD SOFTWARE & COMMISSIONING GUIDE

RICKARD 2018

Double click on the file you downloaded and follow these steps.

Page 7: PCD SOFTWARE & COMMISSIONING GUIDE...PCD SOFTWARE & COMMISSIONING GUIDE RICKARD 2018 Open the MLM Application and click connect. If you are using a USB module, click on the USB tab

  PCD SOFTWARE & COMMISSIONING GUIDE

RICKARD 2018

Page 8: PCD SOFTWARE & COMMISSIONING GUIDE...PCD SOFTWARE & COMMISSIONING GUIDE RICKARD 2018 Open the MLM Application and click connect. If you are using a USB module, click on the USB tab

  PCD SOFTWARE & COMMISSIONING GUIDE

RICKARD 2018

Open the MLM Application and click connect.

If you are using a USB module, click on the USB tab and type in the serial number written on the USB black box. Click Connect

If you are connecting through a MCU module. Make sure your Com-puters IP address is setup correctly. Please go to the Help menu on the MLM application and select “Launch Help” for instructions.

Go to Hardware and PC setup to connect to MCU in the contents menu. Set your PC’s IP address correctly.

Click Connect.

Click on the UDP tab and type in the MCU’s default IP address i.e. 192.168.0.251. Click Connect.

Page 9: PCD SOFTWARE & COMMISSIONING GUIDE...PCD SOFTWARE & COMMISSIONING GUIDE RICKARD 2018 Open the MLM Application and click connect. If you are using a USB module, click on the USB tab

  PCD SOFTWARE & COMMISSIONING GUIDE

RICKARD 2018

The PCD will appear like this on the MLM interface. If you have PCDs connected in one zone they will appear next to each other.

To set the pressure setpoint click on the top left corner of the PCD and the side options will appear. Click on Setpoint and enter the set-point value and then click Write.