Autotransformer
3
All the criteria are identical to standard transformer having a turns ratio, a.
-
8/14/2019 part 8 emachines EEP 3243
4/19
4
C onventional Transformer C onnected
as an Autotransformer The following rules apply :Current in any winding should not exceed its nominal currentrating.Winding voltage should not exceed its nominal voltage rating.Ampere-turns of the both windings are equal.
-
8/14/2019 part 8 emachines EEP 3243
5/19
5
C onts.S ame mutual flux links both windings.If current in winding flows from H1 to H2, the current in other winding must flow from X2 to X1 and vice versa.The voltages add when terminals of opposite polarity areconnected together. The voltages subtract when H 1 and X1 areconnected together.
-
8/14/2019 part 8 emachines EEP 3243
6/19
C ont.
6
-
8/14/2019 part 8 emachines EEP 3243
7/19
Voltage Transformer ( V T)Also called potential transformer which used for metering and protection in high-voltage circuits.
7
-
8/14/2019 part 8 emachines EEP 3243
8/19
C ont.They are designed to present negligibleburden to the supply being measuredand to have a precise voltage ratio toaccurately step down high voltages sothat metering and protective relayequipment can be operated at a lower potential.The nominal secondary voltage isusually rated for 69 V or 120 V at ratedprimary voltage.
8
-
8/14/2019 part 8 emachines EEP 3243
9/19
C ont.VT are used to measure or monitor the transmission linesand to isolate the meteringequipment from the main lines.1 terminal of the secondarywinding is always groundedand the distributedcapacitance between windingsmakes the winding to beisolated.
9
-
8/14/2019 part 8 emachines EEP 3243
10/19
C ont.S imilar construction withconventional transformer butgreat insulation between winding
to withstand HV.Basic Impulse Insulation (BIL)expresses the transformer'sability to withstand lightning and
switching surges.
10
-
8/14/2019 part 8 emachines EEP 3243
11/19
C urrent Transformer ( C T)CT is a measurement device designed to provide acurrent in its secondary coil proportional to thecurrent flowing in its primary.
CT are commonly used in metering and protectiverelaying in the electrical power industry where theyfacilitate the safe measurement of large currents,often in the presence of high voltages.
11
-
8/14/2019 part 8 emachines EEP 3243
12/19
C ont.The highly accurate current ratio and smallphase angle are achieved by keeping theexciting current small.The CT safely isolates measurement andcontrol circuitry from the high voltagestypically present on the circuit beingmeasured. The nominal secondary current isusually 5A, irrespective of primary current.
12
-
8/14/2019 part 8 emachines EEP 3243
13/19
C ont.The insulation betweenwinding must be great towithstand the full line-neutralvoltage, including line surgesand one of the secondaryterminal is grounded.
13
-
8/14/2019 part 8 emachines EEP 3243
14/19
C ont.Care must be taken that the secondarywinding is not disconnected from itsburden while current flows in theprimary, as this will produce a
dangerously high voltage across theopen secondary and may permanentlyaffect the accuracy of the transformer.For safety reasons, we must first short-circuit the secondary winding thanremove the component.
14
-
8/14/2019 part 8 emachines EEP 3243
15/19
Toroidal C T
15
-
8/14/2019 part 8 emachines EEP 3243
16/19
C ont.The primary is a singleconductor that simply passesthrough the center or less center of the ring.If the secondary possesses Nturns the transformer ratio is N.This transformer is simple and
inexpensive and widely used inLV and MV indoor installation.