owner’s manual pentek intellidrive - … 2 important safety instructions save these instructions -...

24
293 Wright Street, Delavan, WI 53115 Phone: 866-9 PENTEK (866-973-6835) Fax: 800-426-9446 www.pumps.com OWNER’S MANUAL PENTEK INTELLIDRIVE Installation/Operation/Parts For further operating, installation, or maintenance assistance call: 866-9PENTEK (866-973-6835) PID10, PID20, PID50 ©2012 PN957 (08/14/12)

Upload: vuongdang

Post on 31-Mar-2018

216 views

Category:

Documents


1 download

TRANSCRIPT

293 Wright Street, Delavan, WI 53115Phone: 866-9 PENTEK (866-973-6835)Fax: 800-426-9446www.pumps.com

OWNER’S MANUAL

PENTEK INTELLIDRIVE™

Installation/Operation/Parts

For further operating, installation, or maintenance assistance call:

866-9PENTEK (866-973-6835)

PID10, PID20, PID50

©2012 PN957 (08/14/12)

Safety 2

Important Safety InstructionsSAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during installation, operation, and maintenance of the PENTEK INTELLIDRIVE Variable Frequency Drive (VFD).

This is the safety alert symbol. When you see this symbol on your PENTEK INTELLIDRIVE or in this manual, look for one of the following signal words and be alert to the potential for personal injury!

indicates a hazard which, if not avoided, will result in death or serious injury.

indicates a hazard which, if not avoided, could result in death or serious injury.

indicates a hazard which, if not avoided, could result in minor or moderate injury.NOTICE addresses practices not related to personal injury.Carefully read and follow all safety instructions in this manual and on the PENTEK INTELLIDRIVE.Keep safety labels in good condition. Replace missing or damaged safety labels.

Risk of high-voltage electrical shock from EMI/RFI filter inside drive. Can shock, burn or kill if the front cover of the PENTEK

INTELLIDRIVE is open or removed while power is connected to the Drive or the Drive is running. The front cover of the Drive must be closed during operation.• Makeallwiringconnections,thencloseand

fasten the cover before turning on power to drive.• NEVER open the box when power is connected to

Drive. • Beforedoinganyserviceormaintenanceinside

Drive or when connecting or disconnecting any wires inside Drive:1. DISCONNECT power.2. WAIT 5 minutes for retained voltage

to discharge.3. Open box.

• Beforestartinganywiringorinspectionprocedures, check for residual voltage with a voltage tester.

• NEVER connect power wiring to Drive before mounting the box.

• NEVER handle or service Drive with wet or damp hands. Always make sure hands are dry before working on Drive.

• NEVER reach into or change the cooling fan while power is applied to Drive.

• NEVER touch the printed circuit board when power is applied to Drive.

Risk of fire. Can cause severe injury, property damage or death if installed with incorrect or inadequate circuit breaker protection. To ensure protection in the event of an internal fault in the PENTEK INTELLIDRIVE, install the Drive on an independent branch circuit protected by a circuit breaker (see Table 2 for circuit-breaker sizing), with no other appliances on the circuit.

Risk of burns. The Drive can become hot during normal operation. Allow it to cool for 5 minutes after shut-down and before handling it to avoid burns.NOTICE To avoid damage to Drive or problems with Drive:• Connectoutputcablesto3-wire and 3-phase

submersible motors as follows: RedtoR,YellowtoY,BlacktoB. Any other order will reverse the motor rotation

and may damage the motor.• Connectoutputcablesto2-wire 1-phase

submersible motors as follows: ConnecttoYandBonly. Connect Ground to green screw.• Aboveground3-phasemotorsmayhavedifferent

lead colors. Generally connect output leads as follows:

RtoL1,YtoL2,BtoL3. Verify rotation after startup.• Donotmodifyequipment.• Donotusepowerfactorcorrectioncapacitors

as they will damage both motor and PENTEK

INTELLIDRIVE.• Donotremoveanypartsunlessinstructedtodo

so in Owner’s Manual.• DonotuseamagneticcontactoronDrivefor

frequent starting/stopping.• DonotinstalloroperateDriveifitisdamagedor

parts are missing.• BeforestartingDrivethathasbeeninstorage,

always inspect it and test operation.• Donotcarryoutamegger(insulationresistance)

test on the control circuit of the Drive.• Donotallowlooseforeignobjectswhichcan

conduct electricity (such as screws and metal fragments) inside Drive box at any time. Do not allow flammable substances (such as oil) inside Drive box at any time.

• GroundDriveaccordingtotherequirementsofthe National Electrical Code Section 250, IEC 536 Class 1, or the Canadian Electrical Code (as applicable) , and any other codes and ordinances that apply.

• Allinstallation,servicework,andinspectionsmust be done by qualified electrician.

Table of Contents 3

Owner’s InformationPENTEK INTELLIDRIVE Model No. _________________________

PENTEK INTELLIDRIVE Serial No. _________________________

Pump Model No. _________________________

Pump Serial No. _________________________

Motor Model No. _________________________

Motor Service Factor Amps _________________________

Pressure Tank Model No. _________________________

Pressure Tank Serial No. _________________________

Dealer/Installer: _____________________________________________

_____________________________________________

Installer Phone No. _________________________

Date of Installation _________________________

Wire Lengths in Feet (Meters):CircuitBreakertoDrive _________________________

PENTEK INTELLIDRIVE to Motor _________________________

Supply Voltage _________________________

Note to Installer: Record the data listed above for future reference. Give manual to end user or attach to PENTEK INTELLIDRIVE when installation is complete.

EMI/RFI Filter

Risk of electric shock. Can shock, burn or kill.• Drive’sinternal

components retain high voltage for up to 5 minutes after input power is disconnected.

• EMI/RFIFiltercarrieshigh voltage when pump is running.

• Disconnectpowerandwait 5 minutes before opening PENTEK INTELLIDRIVE cover.

Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Owner’s Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10In itial Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-12Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-16I/O Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-18Additional Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-22Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Description 4

Specifications/RatingsInput Voltage ........... 1-Phase 230VAC Nominal (190–265VAC)Input Frequency ......................................................... 50/60HzAmbient Tempature Range ............ -4 to 122 °F (-20° to 50 °C)Output Connections ..................3-Phase, 3-Wire/1-Phase or

1-Phase/2-WireMax Motor Cable Length .......................................... 1,000 feetEnclosure ....................................................................... Type 1

Table 1 - Specifications

Model Max HP

Input Phase

Motor Operation

Max Amps

PID10 1.01 2-wire, 3-wire,

3-phase10.5

PID20 2.0 13.5PID50 5.0 1 3-phase 18.0

The PENTEK INTELLIDRIVE is specifically designed to operate 4” submersible pumps and 3-phase above ground pumps in water well and residential booster applications. Each Drive is rated for maximum output amp rating. Any use of Drive outside of intended design parameters will void warranty. If Drive is used with above ground motors not rated for a Variable Frequency Drive, maximize motor life by limiting lead length to 25 ft. Refer to pump Owner’s Manual and the National Electrical Code for proper wire size.

Each carton contains:• PENTEK INTELLIDRIVE Variable Frequency Drive•PressureTransducer•10’PressureTransducerCable•QuickStartGuide•Owner’sManual

PENTEK INTELLIDRIVE Model Number Structure

Transducer; install in straight pipe downstream of tank, at least one foot away frompipe fittings on each side.

Gnd

(3 phase only)

PENTEK INTELLIDRIVE™

Gnd

Figure 1 - A typical residential installation layout

PIDXX

Product FamilyPID - PENTEK INTELLIDRIVE

HP Range10 = up to 1.0 HP20 = up to 2.0 HP50 = up to 5.0 HP

The PID10 and PID20 will operate a 1-phase 2-wire, 1-phase 3-wire, and 3-phase motor up to the HP range of the Drive. The PID50 only operates a 3-phase motor up to 5 HP.

Description 5

TransducerThe PENTEK INTELLIDRIVE uses a 4-20mA, 0-100PSI pressure transducer to control motor speed (max is 300 PSI transducer).The transducer (see Figure 1) senses pressure in the pipe and converts it to an electrical signal. The Drive senses and processes the signal in the PID (Proportional, Integration, Derivative) control. When operating in AUTOSTART mode, the Drive increases and decreases the speed of the pump motor as needed to maintain constant pressure in the piping system.

KeypadThe keypad programs the Drive, monitors the status of the pump, and displays faults if they occur. Each button has a unique function, as described in Figure 2. The LCD display shows a text display of the status of the Drive’s operation. Other LEDs light up to indicate when certain buttons are pressed or certain events occur.

FanThe Drive uses a thermostatically controlled internal fan which operates automatically when necessary to cool the Drive components.

Figure 2 - PENTEK INTELLIDRIVE keypad functions

Stops the motor.

Power is ON to Drive.

A fault has occurred.

Selects menu items and confirms numeric value changes.

Displays Drive’s current operating condition and changes display

parameters.

Changes display to previous screen.

Drive is in Warning Mode (TPM); refer to Troubleshooting section.

Changes internal pressure setpoint from 15 PSI to transducer max -3PSI

(default is 60 PSI).

Runs the Drive at 45Hz (with no pressure control) to allow installer to

pump out well.*

Up and down arrows scroll through menus and change numeric values.

Toggles between English, Spanish, and French (default is English).

Resets fault that stopped Drive/pump.

With code, locks and unlocks password protected keys.

Left and right arrows move cursor.

Shows last 15 faults.

Checks for line fill, then starts pump in constant pressure mode.

Views and changes parameters.

Installation 6

Table 2 - Circuit Breaker and Wire Sizes.

Motor Drive Model Volts Motor HP

Wire Size*Circuit Breaker** Generator (kVA)***

Input Output

2-wirePID10

230

1/2 14 1415

2.2

3/412 12

3.1

1 20 4.4

PID20 1-1/2 10 10 25 5.3

3-wire

PID10

1/2 14 14

15

2.3

3/412 12

3.0

1 3.5

PID201-1/2

10 10 255.3

2 5.8

3 phase

PID10

1/214

14 15

2.1

3/4 2.8

112

3.4

PID201-1/2

1220 4.4

210

25 5.5

PID503 10 30 7.3

5 6 8 50 12.6

* AWG will change depending on the length of wire. See Tables 3-6.** With properly-sized circuit breakers, the Drive is protected from short circuit on the input and the output. There is no risk of fire or electrical shock due to a short circuit. The Drive has NEC Class 10 overload protection.*** Minimum 240V generator size.NOTICE Information in Tables 3-6 applies ONLY to PENTEK® motors. For other motors, refer to motor manufacturer specifications for wire sizing.

Table 3 - Service Entrance to Drive - 1 Phase, 2-Wire 40°C Ambient, and 5 percent Voltage Drop, 60C and 75C Insulation (copper only).

Motor Rating Maximum Cable Length in feet (M)

Volts HP SFA 14 AWG 12 AWG 10 AWG 8 AWG 6 AWG 4AWG

230

1/2 4.7 447 (136) 712 (217) 1000 (305) –

3/4 6.2 341(104) 542 (165) 864 (263) 1000 (305)

1 8.1 261(79) 415 (126) 661 (202) 1000 (305)

1 1/2 10.4 203 (62) 323 (98) 515 (157) 816 (249) 1000 (305)

2 12.2 173 (53) 275 (84) 439 (134) 696 (212) 1000 (305)

3 10.1 209 (64) 333 (101) 530 (162) 840 (256) 1000 (305)

5 17.5 121(37) 192 (59) 306 (93) 485 (148) 754 (230) 1000 (305)

Installation 7

Table 4 - AWG Wire Sizing, Drive to 1-Phase, 2-Wire Motor, 40°C Ambient, and 5 percent Voltage Drop, 60C and 75C Insulation (copper only).

Motor P/NMotor Rating Maximum Cable Length in feet (M)

Volts HP SFA 14 AWG 12 AWG 10 AWG 8 AWG 6 AWG

P42B0005A2-01

230

1/2 4.7 447 (136) 712 217) 1000 (305) –

–P42B0007A2-01 3/4 6.2 341 (104) 542 (165) 864 (263) 1000 (305)

P42B0010A2-01 1 8.1 261 (80) 415 (126) 661 (201) 1000 (305)

P42B0015A2-01 1 1/2 10.4 203 (62) 323 (98) 515 (157) 816 (249) 1000 (305)

Table 5 - AWG Wire Sizing, Drive to 3-Wire, 1-Phase Motor, 40°C Ambient, and 5 percent Voltage Drop, 60C and 75C Insulation (copper only).

Motor P/NMotor Rating Maximum Cable Length in feet (M)

Volts HP SFA 14 AWG 12 AWG 10 AWG 8 AWG 6 AWG

P43B0005A2-01

230

1/2 4.8 440 (134) 700 (213) 1000 (305) –

–P43B0007A2-01 3/4 6 352 (107) 560 (171) 893 (272) 1000 (305)

P43B0010A2-01 1 7.3 289 (88) 460 (140) 734 (224) 1000 (305)

P43B0015A2-01 1 1/2 10.9 194 (59) 308 (94) 492 (150) 778 (237) 1000 (305)

P43B0020A2-01 2 12.2 173 (53) 275 (84) 439 (134) 696 (212) 1000 (305)

Table 6 - AWG Wire Sizing, Drive to 3-Phase Motor, 40°C Ambient, and 5 percent Voltage Drop, 60C and 75C Insulation (copper only).

Motor P/NMotor Rating Maximum Cable Length in feet (M)

Volts HP SFA 14 AWG 12 AWG 10 AWG 8 AWG 6 AWG 4 AWG*

P43B0005A3

230

1/2 2.9 728 (222) 1000 (305) –

__

P43B0007A3 3/4 3.9 541 (165) 861 (262) 1000 (305)

P43B0010A3 1 4.7 449 (137) 715 (218) 1000 (305)

P43B0015A3 1 1/2 6.1 346 (105) 551 (168) 878 (268) 1000 (305)

P43B0020A3 2 7.6 278 (85) 442 (135) 705 (215) 1000 (305)

P43B0030A3 3 10.1 209 64) 333 (101) 530 (162) 840 (256) 1000 (305)

P43B0050A3 5 17.5 306 (93) 485 (148) 754 (230) 1000 (305)

*Installations that require wire gauge larger than 6 AWG will require an external junction box. Run 6 AWG wire from the Drive into the junction box, then make external connections with wire nuts to appropriately sized wire.

8Installation 8

Mounting the DriveTo mount the Drive as shown in Figure 6, follow this procedure:1. First, remove the cover by backing out screw

at bottom of front cover.2. Push on backplate with thumbs while pulling

the cover toward you with index fingers, creating a gap. See Figures 3 and 4.

3. Pull bottom of cover towards you; liftup on cover and remove. See Figure 5.

4. With the cover removed, permanently mount the Drive using the top slotted hole, plus either the three bottom holes (for flat surface mounting) or the center bottom hole (for attaching to a post or stud). See Figure 6.

Gap

Figure 3 - Seperate cover and backplate

Figure 4 - Gap between cover and backplate

Figure 5 - Pull out bottom of cover

5. Ensure the Drive’s ventilation holes are not blocked and there is enough space around it to allow free air flow (minimum 3” clearance on top, bottom, and sides). See Figure 6. Once the Drive is mounted, electrical wiring can be connected.

6. To reattach the Drive cover, hook the top of it on backplate (be sure to leave a gap). Lower bottom of cover into place. Push cover evenly against backplate, eliminating the gap. See Figure 7.

7. Replace screw at bottom of front cover.

Figure 6 - Attaching Drive to wall

Typical 230VAC Circuit Breaker(Double Width)

Figure 7 - Reattaching Drive cover

9Installation 9

01+ 01+ I1+ I1- I2+ I2- V+ V- AI+ AI- P N SD CARD

Transducer Cable Connections

Submersible Motor: 3-Ph./ 3-W. 1-Ph., follow colors as above.

Submersible Motor: 1-Ph./ 2-W., connect to Y and B, any order.

Above-Ground Motors: L1 to R, L2 to Y, L3 to B; verify rotation.

Output Ground Screw

Input Power Connections

Input Ground Screws

Red

Yellow

Black

Green/Yellow (Ground)Green/Yellow

(Ground)

Motor Connections

Red to AI+

Black to AI–

Green Cable Shield/Screw

Figure 9 - Basic Wiring Connections for Startup

WiringTo allow for ease of wiring, the enclosure wiring area is free of electronics other than the terminals. Conduit holes and knockouts are located so that the wire can be fed straight through to the connectors, with minimal bending. The terminals accept 6-14 AWG wire.Installations that require larger wire gauge than 6 AWG will require an external junction box. Run 6 AWG wire from the Drive into the junction box, then make external connections with wire nuts to appropriately sized wire. NOTICE For convenience in wiring, the input and motor terminals unplug from the box. Pull them down to remove them for ease of access, as shown in Figure 9.Verify that the terminal connectors are completely seated when you replace them. It is best practice

to connect all output wires (larger wire gauge) first, then all input wires.

Pump ConnectionsIf the PENTEK INTELLIDRIVE is used with above ground motors not rated for Variable Frequency Drive use, maximize motor life by limiting lead length to 25 ft. Refer to the pump owner’s manual, the National Electrical Code, and local codes for proper wire size.The output of the Drive is single phase (2-wire or 3-wire) or 3-phase, depending on motor selection during startup.The output power terminals (motor wire connections) are located on the lower right side of the Drive and are labeled R (Red), Y (Yellow), andB(Black).SeeTables2through6forsuggestedwire sizes.Feed the motor cable through the 3/4” conduit hole on the bottom right side and into the appropriate terminals. If the wire is large enough to require a larger conduit hole, remove the 1-1/4” knockout and use the appropriate conduit connections. Attach the motor ground wire to the grounding screw, located to the upper right of the terminal block. Attach the motor power wires to the terminals as shown in Figure 9.

Figure 8 - Pull input and motor terminals down to remove, making wiring easier.

10Installation 10

Pressure Tank RecommendationsMinimum tank size is two gallons. Use a pre-charged pressure tank with Drive, as shown in Table 6. The tank size must equal at least 20 percent of the pump’s rated flow in gallons per minute (GPM), but cannot be less than two gallons capacity. For example, a pump rated at 7 GPM would require a tank of two gallons capacity or larger. A pump rated at 50 GPM would require a 10 gallon tank or larger. Tanks larger than 10 gallons can be used, but may require adjustment of Wake Delay parameter.

Table 7 - Control Pressure Set Point and Tank Pre-Charge Pressure Values (PSI).

Pressure Point

Setting (PSI)

Precharge Pressure

(PSI)

Pressure Point

Setting (PSI)

Precharge Pressure

(PSI)

25 18 65 46

30 21 70 49

35 25 75 53

40 28 80 56

45 32 85 60

50 35 90 63

55 39 95 67

60 (Default)

42 –

NOTICE Set pressure tank’s pre-charge to 70 percent of the system operating pressure. When using an external set point as well as an internal set point, pre-charge tank to 70 percent of the lower setpoint of the two. Some applications may require a different percentage when determining the setpoint.

Transducer ConnectionsA 0-100 PSI 4-20 mA transducer is provided with Drive. Install the transducer downstream of tank, as shown in Figure 1. Install transducer in a tee in a straight section of pipe with at least 1 foot of straight pipe on each side of the tee (i.e., all fittings must be at least 1 foot away from transducer).Feed transducer cable through the open 1/2” conduit hole on bottom of the Drive enclosure.As shown in Figure 5, connect the red wire of the transducer cable to AI+, connect black wire to AI–, and connect the green cable shield to the metal cable shield screw.

To connect the transducer wires:1. Strip wire ½ inch2. Push spring terminal up with finger or slotted

screwdriver3. Insert wires from bottom4. Release spring terminal

Input Power ConnectionsThe input power terminals are located on the lower left side and are marked L1 and L2 (see Figure 9). There is a ground screw for the input ground wire to the right of the connector (torque to 10 lbs in). Feed wire through the 3/4” conduit hole on the bottom left side and into appropriate terminals. If wire is large enough to require a larger conduit hole, remove the 1-1/4” knockout and use appropriate conduit connections.To determine the correct wire sizes for installation, see Tables 2 through 6.NOTICE The PENTEK INTELLIDRIVE only accepts 230V single phase input power. If incoming power does not match this, have a qualified electrician alter supply voltage to 230V/1Ph before connecting it to the Drive.

11Initial Startup 11

Initial Startup and Programming ProceduresEnsure that the cover is installed before operating the PENTEK INTELLIDRIVE.Most installations will only require the initial startup settings. However, the installer may need to set additional parameters. Information about accessing all parameters, explanations of their functions, and procedures for changing parameter values, will be found later in this section.1. Program the Drive: Apply power to the

PENTEK INTELLIDRIVE. Setup Guide will appear in the display. Follow keypress sequence shown in Figure 10.NOTICE If Setup Guide does not appear, refer toDrive Reset Procedure, Figure 20.

2. Select 80 Hz Operation, if necessary (See 60 Hz to 80 Hz Operation for more information):A. Press MAIN MENU button.B. Followthekeypresssequenceshownin

Figure 11.

Service Factor AmpsTo maximize pump performance, be sure to enter the correct Service Factor Amps (SF Amps) in the PENTEK INTELLIDRIVE.• EnteringSFAmpshigher than the motor rating

lets the Drive supply more amps to the motor than the motor is designed for and may allow the motor to overheat (see Table 8).

• EnteringSFAmpslower than the motor rating limits the output amps to less than the motor is designed for and will reduce the performance of the pump.

• Forany1-Phase3-Wiremotor,thecorrectService Factor Amp rating for the Drive is Cap Start/Cap Run amps (see Table 8). This may not match the motor nameplate, which (for a Single Phase, 3-Wire motor) will generally be Cap Start/ Induction Run Amps.

• Forany3-Phaseor1Phase,2-Wiremotor,use the motor nameplate Service Factor Amp rating.

NOTICE PENTEK® submersible motors may differ from motors of the same horsepower from other manufacturers. For 1-Phase, 3-Wire motors from all other submersible motor manufacturers, enter the motor manufacturer’s CS/CR service factor amps for your motor. For 3-Phase or 2-Wire 1-Phase motors, use the motor nameplate amp value. Also see Retro Fit Applications.

Press Enter

Press Enter

Press Enter

Apply 230V to Drive

Set Time

Set Date

Setup Complete

1 Phase

Connection Type(2 Wire or 3 Wire)

3 Phase

Motor TypeSubm or Above Gnd

Enter ServiceFactor Amps

Enter Motor Phase(1 Phase or 3 Phase)

Press Enter

Figure 10 - Drive Setup Guide.

Use arrows to scroll to Motor

Press Enter

Use arrows to select 80 Hz

Press Enter to save

Press MAIN MENU button

Press Enter

Use arrows to select Max Frequency

Figure 11 - Select 80 Hz (3-phase operation only).

12

3. Pump out well (if necessary): Direct pump’s discharge to appropriate location

not connected to system and press Pump Out. The pump will run at 45 Hz.

Adjust frequency as appropriate:A. Press ENTERB. Changefrequencyvalue

NOTICE Above ground pumps should run at 60 Hz for this step (until pump is primed). Then adjust frequency as necessary.

C. Press ENTER again. Run the Drive in this mode until the well

discharge runs clear, then press STOP button to stop Drive.

Risk of explosion. In Pump Out mode, pump runs at a constant speed, which can cause very high pressure if flow is restricted.

4. Verify installation: Make sure that the system has properly-sized, pressure-relief valve and pressure tank.

Make sure pressure tank’s precharge is correct. See Table 7.

Make sure pump discharge is connected to system.

5. System Start:A. Open valves at the ends of lines so that air

will escape during pressurization.B. PressAuto Start; close valves at the ends of

lines after all air has escaped.C. The system goes into Constant Pressure

Operation as soon as the transducer registers the Dry Run Sensitivity parameter (default is 10 PSI). If system pressure does not reach that PSI value within 3 minutes, the Drive will stop. Press Auto Start again to restart line fill. If longer priming or line fill time is required, adjust Fill Time parameter. See Table 9.

Changing a Parameter ValueThis procedure works for ANY parameter.

A. Press MAIN MENU button.B. Followthekeypresssequenceshownin

Figure 12:A shorthand way to remember this is:• PressENTER to change a value• PressENTER again to save it• Ifnewvalueisnotsaved,anyscreenchangewill

result in the loss of the new value.

Table 9 lists all available commands and parameters for the PENTEK INTELLIDRIVE.

Initial Start-up 12

Use arrows tofind a parameter

Use arrows tochange the value

Press Enter to Save

Press Enter

Figure 12 - Changing parameter value.

Table 8 - PENTEK Motor Service Factor Amps

Motor Type

PENTEK Part Number

Rating @ 230V

Service FactorAmpsHP

2-Wire

P42B0005A2-01 1/2 4.7P42B0007A2-01 3/4 6.2

P42B0010A2-01 1 8.1

P42B0015A2-01 1-1/2 10.4P42B0005A2 1/2 4.7P42B0007A2 3/4 6.4P42B0010A2 1 9.1P42B0015A2 1-1/2 11.0

CS/CR 3-Wire

P43B0005A2-01 1/2 4.8P43B0007A2-01 3/4 6.0P43B0010A2-01 1 7.3P43B0015A2-01 1-1/2 10.9P43B0005A2 1/2 4.9P43B0007A2 3/4 6.3P43B0010A2 1 7.2P43B0015A2 1-1/2 11.1P43B0020A2 2 12.2

3-Phase

P43B0005A3 1/2 2.9P43B0007A3 3/4 3.9P43B0010A3 1 4.7P43B0015A3 1-1/2 6.1P43B0020A3 2 7.6P43B0030A3 3 10.1P43B0050A3 5 17.5

13Programming 13

60 Hz to 80 Hz OperationWhen installing the PENTEK INTELLIDRIVE with a motor and liquid end of the same HP rating, operate it at 60 Hz (the default value). The Drive can be operated at frequencies of up to 80 Hz when the installation uses a 3-phase motor 2 times the size of the pump. For example, a 1 HP pump with a 2 HP 3-phase motor. This combination will equal the performance of a conventional 2 HP pump.Press Main Menu and follow the keypress sequence shown in Figure 7.BesuretopressENTER to save the new Max Frequency selected. The Drive will now use the new value selected.NOTICE The Drive will not allow the output amps to go above the Service Factor Amps selected on thekeypad.Becauseofthis,some80Hzoperationsmay be limited. This protects the motor and may be a common occurrence in a 80Hz operation.

Keypad Lock - PasswordThe password locks or unlocks the blue buttons on keypad. All PENTEK INTELLIDRIVE units are shipped from factory with the default password 7777. It can be changed to any other 1 to 4 digit number. To reset password to a unique password for unit, unlock keypad (see below) and follow the keypress sequence shown in Figure 8 to make the change.If installer does not press the password button, then the keypad will automatically lock 60 minutes after the Drive is powered up. The time out period is adjustable (see Table 9).To unlock keypad press Password, use directional arrows to select numeric code and press ENTER.NOTICE For more detailed information on keypad functions, see Figure 2.

Pump Out OperationPress Pump Out. The Drive will start pump in a constant speed mode (default 45 Hz). The pump will run until STOP or Auto Start are pushed. If speed change is necessary, follow keypress sequence shown in Figure 8 to change parameter as desired.

Setting the PressureNOTICE Default pressure setting is 60 PSI. If this value is changed, adjust tank pressure accordingly (see Table 7).

There are three ways to change the pressure setpoint: 1. While running the pump• Follow keypress sequence shown in Figure

13 to make desired change. This parameter allows either Internal or External Setpoint to be changed, depending on which one is referenced at the time the change is made.

2. Via the PSI Preset

3. Via the Main Menu (Main Menu/Settings/Setpoint/Internal Setpoint)

Press PSI Preset

Use arrows tochange the value

Press Enter to Save

Press Enter

Figure 14 - Change PSI Setpoint using PSI Preset.

Press Auto Start

Use arrows tochange the value

Press Enter to Save

Press Enter

Verify“Running Fixed Press”displayed on screen

Figure 13 - Change PSI Setpoint while running pump.

14Programming 14

Table 9 - Main Menu and Parameters

Menu Settings Parameter Unit of

MeasureValue

DescriptionDefault Min. Max.

Time/Date

Hour Format Hours 12Hr 12Hr 24Hr Selects 12 or 24 hour time scale.

Time mm:ss 1:00 AM 1 24 Sets current time. Used for time stamp in fault log.

Date MM/DD/YYYY 1/1/12 – – Sets current date. Used for date stamp in fault log.

PID Control

Proportional Gain – 2500 0 10000

Sets the PID controller gain. Used in conjunction with all PID Control parameters to control how fast or slow the Drive reacts to pressure changes.

Integration Time Milliseconds 500 ms 20 ms 65000

ms

Sets the PID controller integration time. Used in conjunction with all PID Control parameters to control how fast or slow Drive reacts to pressure changes.

Derivation Time Milliseconds 60 ms 0 ms 10000

ms

Sets PID controller derivation time. Used in conjunction with all PID Control parameters to control how fast or slow Drive reacts to pressure changes.

Derivative Limit – 120 0 2000 Sets derivative filter time constant

for PID controller.

Sleep

BoostDifferential PSI 3 PSI 3 PSI 10 PSI

First part of Boost Process. Pressure boost that happens before it goes to Wake Delay.

BoostDelay MM:SS 1 Min 30 Sec 5 Min The time Drive takes to start Boost Process after system has stabilized.

Wake Up Differential PSI 5 PSI 5 PSI 15 PSI Pressure amount below setpoint that

wakes up Drive.

Wake Delay MM:SS 15 Sec 3 Sec 2 MinSecond part of the Boost Process. The time it takes to ramp down pressure during the Boost Process.

PasswordPassword Time

Out HrHr:mm 1 Hr 1 Min 6 Hr Amount of time it takes to lock keypad (after last button is pressed).

Password – 7777 0000 9999 Password used to unlock keypad.

Table 9 lists all available commands and parameters for the PENTEK INTELLIDRIVE.

15

Table 9 - Continued

Menu Settings Parameter Unit of

MeasureValue

DescriptionDefault Min Max

Setpoints

Internal Setpoint PSI 60 PSI 15 PSI

Max Sensor Value

minus 3 PSI.

Main pressure setpoint used. Sets main system operational pressure. This parameter is accessed here, through PSI Preset button, or by pressing Enter button while in Constant Pressure operation.

External Setpoint PSI 40 PSI 15 PSI

Max Sensor Value

minus 3 PSI.

Second pressure setpoint. When another pressure setting is desired other than Internal Setpoint. Additional programming needed in I/O section. Requires an external switch or timer to wired to I1 or I2 terminals. It is only active when there is voltage present I1 terminals (see Figure 11)

Sub Menu Parameter Unit of Measure Default Max Min Description

Motor

Motor Phase _ 1 1 3

Selects phase of motor to be operated. An additional sub menu will appear, based on phase selection, to select proper motor type.

Connection Type – 3 wire 3 wire 2 wire

Wire type for 1 phase motor operation only. Can only access by first setting Motor Phase parameter to 1 Phase.

Motor Type – Subm Subm Above Gnd

Motor type for 3 phase motor operation only. Can only access by first setting Motor Phase parameter to 3 Phase.

Service Factor Amps A 00.0 A 00.0 A

Per drive and

motor

Service factor amps (max. load) of motor the Drive is operating. Sets maximum allowed amps at output of Drive. See Table 7 for values.

Min Frequency Hz 30 Hz 30 Hz1 below

Max Hz

Minimum frequency (speed) motor will run.

Max Frequency Hz 60 Hz

1 above Min Hz

80 Hz

Maximum frequency (speed) motor will run. Up to 80Hz is only available on only when Motor Phase is set to 3.

Sensor Max Sensor Value PSI 100 PSI 10 PSI 300 PSI

Maximum pressure value of transducer sensor used with Drive. Only change if different transducer is used with Drive, other than 100 PSI max scale.

Programming 15

16

Table 9 - Continued

Menu or Sub Menu

Parameter Unit of MeasureValue

DescriptionDefault Min Max

Ex Runtime

Excessive Runtime

Detection_ Enabled Disabled Enabled

Enables or disables Excessive Runtime Detection.

Excessive Runtime Hours

Hours 24 1 100Number of hours Drive can run before it faults on Excessive Runtime.

Dry Run

Auto Restart Delay

Minutes 10 Min 3 Min 60 MinTime Drive waits to restart pump when Dry Run is detected.

Number of Resets

– 3 0 5Number of tries Drive attempts to restart pump when Dry Run condition is detected.

Detection Time M:SS 15 Sec 5 Sec 10 MinTime the Drive takes to recognize Dry Run condition.

Sensitivity PSI 10 0 300

Pressure value that Dry Run condition is detected at. Dry Run fault will occur if this pressure cannot be met within Detection Time window. Lower pressure = less sensitivity.

Fill Time M:SS 1 M 15 S 10 M

Time allowed to fill (prime) pipes during Auto Line Fill process. Relates to Dry Run Sensitivity value. (Time starts after 55 Hz is reached).

I/O

Digital Input 1

– Unused – –

Selects operation of Drive when terminal I1 is used. Select between Unused, Run Enabled, Ext Fault, and Setpoint. The Drive will respond to selected command when voltage is present at I1 terminal.

Digital Input 2

Relay Output – Unused – –

Selects the operation of Drive when terminal O1 is used. Select between Unused, Run, and Fault. The Drive closes the Relay when Run or Fault is selected.

Over Press Over Pressure PSI 80 PSI 15 PSI 97 PSISets Over Pressure Warning value. Change if higher than 80 PSI system pressure is needed.

No GroundNo Ground Detection

– Enabled Disabled Enabled

Selects whether Ground Detection parameter is Enabled or Disabled. If Disabled is selected, it will revert back to Enabled after 72 hours. Warning LED will flash entire time it is Disabled.

Reset Factory Reset – No No Yes

Resets all parameters to factory defaults. Displays Setup Guide after it is complete. Software version displayed here. Does not clear fault log.

SW Update Software Update – Disabled Disabled Enabled Used to update software, if necessary.

Programming 16

17I/O Connections 17

The I/O terminals are located in the center of the wiring compartment, as shown previously in Figure 9. The Digital Input connections (I1 and I2) are used to control the Drive based on the state of an external device, such as a flow switch, moisture sensor, alternator, or other device. Programming is needed to activate any of these functions (see Table 9).The Output Relay (O1) is used to control an external device based on two states of Drive; either Running the pump or Faulted. Programming is needed to activate any of these functions (see Table 9).

Cable InstallationThree 1/2” conduit knockouts are provided on the bottom of the Drive enclosure for the I/O wires.Breakouttheclosest1/2”knockoutandroutethewires through. Use a cord grip to prevent the wire from rubbing and causing a short.NOTICE Never run low voltage I/O wire through the same conduit hole as the 230V input wires or motor wires.To connect the external wires to the terminals:1. Strip wire ½ inch2. Push spring terminal up with finger or slotted

screwdriver3. Insert wires from bottom4. Release spring terminal

Connection ExamplesFigures 15-18 show various connection schemes for typical applications. Table 10 describes each I/O terminal, including purpose and rating.

Figure 15 - Example Input with internal 24 volt supply

Figure 17 - Example Output relay with internal 

24 volt supply

115 VACor

230 VAC

+

-

Figure 16 - Example external Input with external supply

115 VACor

230 VAC

+

-

Figure 18 - Example Output with external supply

18I/O Connections 18

Table 10 - I/O Function, Connections, Ratings

Label Function Connection Rating

AI+ Positive connection for transducer Red transducer wire 24 Volt (supplied)AI- Negative connection for transducer Blacktransducerwire

V+ Positive side of 24 volt power supply. Used to power external devices.

Positive side of 24V external device, i.e., flow switch, moisture sensor, alternator, etc. Need to complete the circuit with V-. See Figures 11 and 13. 40mA maximum

output

V- Negative side of 24 volt power supply. Used to power external devices.

Typically to I1-, I2-, or O1-. Used with a flow switch, moisture sensor, alternator, etc. Need to complete the circuit with V+. See Figures ll and 13.

I1+Positive (dry contacts) connection of Digital Input 1. Connect when using an external device to control Drive.

From an external device i.e., flow switch, moisture sensor, alternator, etc. Requires complete circuit connection with I1-. See Figures 11 and 12.

Accepts 24VDC and up to 230VAC

I1-Negative (dry contacts) connection of Digital Input 1. Connect when using an external device to control Drive.

Can be from V- or from the negative side of an external power supply. Requires complete circuit connection with I1+. See Figures 11 and 12.

I2+Positive (dry contacts) connection of Digital Input 2. Connect when using an external device to control Drive.

From an external device, i.e., flow switch, moisture sensor, alternator, etc. Requires complete circuit connection with I2-. See Figure 11 and 12.

I2-Negative (dry contacts) connection of Digital Input 2. Connect when using an external device to control Drive.

Can be from V- or from the negative side of an external power supply. Requires complete circuit connection with I2+. See Figure 11 and 12.

O1+Output relay (dry contacts) connection. Programmed to close when pump is Running or Faulted.

Positive wires of an external device. See Figures 13 and 14.

Accepts up to 5 Amps at 24VDC and 8 Amps at up to 230VACO1+

Output relay (dry contacts) connection. Programmed to close when pump is Running or Faulted.

Positive wires of an external device. See Figures 13 and 14.

P Positive connection of an RS-485 communication device (see Figure 15). Positive wire from RS-485 device.

Per RS-485 Standard

N Negative connection of an RS-485 communication device (see Figure 15). Negative wire from RS-485 device.

19

RS-485 CommunicationsRS-485 is a US-based telecommunications standard for binary serial communications between devices. It is the protocol, or set of specifications, that needs to be followed to allow devices that implement the standard to speak to each other. A fully compliant RS-485 port is included in the PENTEK INTELLIDRIVE system to permit serial connections among more than two devices on an RS-485 compliant network. Figure 15 shows two-wire connection to the Drive.

Lightning/Surge ProtectionLightning arrestors or other surge suppressing devices can be used with this product. MOV (Metal Oxide Varistor), SOV (Silicon Oxide Varistor).

AccessoriesPart Descrption Qty Part Number

Alternating Control Panel 1 VFD-ALT

Moisture Sensor 1 VFD-WS

Surge Protection Kits 1 VFD-SGA

300 PSI Transducer 1 U17-2000

Flow Switch 1 U17-1999

Retrofit ApplicationsWhen retrofitting an installation with the PENTEK INTELLIDRIVE, most of the preceding text can be applied. As a convenience, the recommended Service Factor Amps for non-PENTEK motors is provided in Table 11. Always verify Service Factor Amp values from current manufacturer literature.

Table 11 - Service Factor Amps @ 230V

Motor Type HPService Factor Rating,

in AmpsCentriPro¹ Franklin²

2-Wire

1/2 4.7

N/A3/4 6.41 9.1

1-1/2 11.0

CS/CR 3-Wire

1/2 4.9 4.33/4 6.3 5.71 7.2 7.1

1-1/2 11.1 11.52 12.2 13.2

3-Phase

1/2 2.9 2.93/4 3.9 3.81 4.7 4.7

1-1/2 6.1 5.92 7.6 8.13 10.1 10.95 17.5 17.8

¹CentriProSFAdatawastakenfromtheMarch2012BMAIDmanual on 4/2012.

² Franklin Electric SFA data was taken from the 7/2011 Franklin Electric AIM manual on 4/2012.

NOTICE The PENTEK INTELLIDRIVE will not operate Franklin Electric 2-wire motors.

Repair PartsPart Description Qty Part Number

InputTerminalBlockConnector 1 PID-CON2

OutputTerminalBlockConnector 1 PID-CON3

Cooling Fan 1 PID-FAN-R

Pressure Transducer 1 U17-1561-R

10’ Transducer Cable 1 U18-1593

25’ Transducer Cable* 1 U18-1594

50’ Transducer Cable* 1 U18-1595

100’ Transducer Cable* 1 U18-1596

150’ Transducer Cable* 1 U18-1597

200’ Transducer Cable* 1 U18-1598

Keypad 1 PID-HMI-R

* Purchase Separately

Additional Information 19

6544 04 2

AI- P N SD CA

Figure 19 - Example RS-485 Connection

20Troubleshooting* 20

Fault Possible Causes Solution

Over Current

Shorted output Check for any shorts in motor cables.

Locked rotor Check for debris in pump.

Damaged wire insulation Check motor wire insulation with a megger.

Over Voltage

Internal Drive short With power to Drive off, measure outputs with ohmmeter to detect short.

Power cycling on and off Check for a generator or switching on input line.

High line voltage Measure incoming line voltage to Drive; should be between 190V and 265V.

Under Voltage

Low line voltage

Temporary loss of power Check for local power outage.

Excessive load current Check motor is correctly sized for the application.

Loss of a motor phase Check correct voltage is present on all motor leads.

Power was removed from Drive

Check correct voltage is present on all input lines.

Cannot Start Motor

Exceeding Service Factor AmpsCheck Service Factor Amps entered are correct.

Check pump and motor are correct.

No Service Factor Amps value entered

Check Service Factor Amps entered and are correct.

There is an open (connection) in motor wires

Check resistance of all motor wires is correct.

Locked rotor Pull pump check for debris in pump.

Dry Run

Operation at open dischargeMay need to reduce Dry Run Sensitivity pressure or apply back pressure on transducer.

Drive cannot read transducer signal

Check linearity of transducer, as it may be damaged. See Troubleshooting Guide for more information.

Possible leak Check for pipe break or large leak.

Dry running pump Check water level in well.

Ground Fault

Ground wire shorted to motor phase

Check the ground wire for short to motor phase wire or check insulation integrity with a megger.

Long motor cable lengthIf motor cable length is more than 1000 ft a reactor or filter may be needed to limit capacitance between motor wires.

System Not Grounded Ungrounded Drive Ground Detect parameter can be disabled, but will reactivate after 72 hours.

*For additional Troubleshooting information, please visit www.sta-rite.com/resources/images/16455.pdf for a downloadable guide.

21Troubleshooting 21

Fault Possible Causes Solution

Open Transducer

Intermittent connection Check all transducer wires are securely connected or for damaged cable insulation.

Open ConnectionCheck for proper wiring of all transducer wires and verify cable connector securely attached to transducer.

Drive cannot read transducer signal

Check electrical system for ground loops or no ground connection.

Transducer wires crossed Check red is in AI+ and black is in AI-.

Possible failed transducer Check linearity of transducer; see Troubleshooting Guide for more information.

Shorted Transducer Short in transducer wires Check for shorted transducer wire or

damaged insulation.

Possible failed transducer Check linearity of transducer; see Troubleshooting Guide for more information.

Over Temperature Excessive heating in drive

Check ambient temperature is not above 50°C (122°F).

Check for inoperable or unobstructed fan.

Check vents are not obstructed.

Excessive Runtime

Leak detected Check for leaks in pipe system.

Application calls for long run times

Extend Excessive Runtime Hours limitation.

Disable Excessive Runtime Fault.

Internal Fault Internal voltages are out of range

Drive will auto reset and attempt to clear fault. Fault Reset can be pressed to clear fault as well. Then try to operate pump. If fault continues Drive may need replacement.

Hardware Fault Internal hardware failureFault Reset can be pressed to clear fault. Then try to operate pump. If fault continues Drive may need replacement.

External FaultThe external device detected fault condition and closed the I1 or I2 input

Check external device.

Low Amps

Under-sized pumpIncrease Minimum Speed to 35 Hz.

Low current draw from pump

Thermal protector open in motor (3 wire) Wait 20 minutes then restart pump.

Missing motor phase Check all motor connections at the Drive.

Troubleshooting, Continued

22Troubleshooting 22

Warning Possible Causes Solution

Warning LED flashing

Ungrounded Drive, with ground detection parameter disabled (will operate for 72 hours and then fault).

Verify ground wire is connected on both incoming voltage side and motor side of Drive.

With power disconnected, use ohmmeter to verify the pipe the transducer is connected to and that input ground wire are at same potential (approx 0 ohms).

Verify the input ground is connected all the way back to electrical panel.

Jam Warning Debris in pump stopping motor from turning (locked rotor).

Drive tries to free debris in pump by reversing or pulsing motor.

Over Pressure Warning Pressure rising above Over Pressure setting.

Drive stops and waits 1 minute, then checks that pressure is below the Setpoint pressure. Belowitrestarts,ifnotchecksagaininanother minute. Can increase over-pressure value.

Troubleshooting, Continued

Drive Reset Procedure

Press Passwordbutton

Press Enter to Edit

Change “No” to “Yes”

Confirm Reset

Press Main Menu button

Press up or down arrow until Reset appears

Enter Passwword(Default is 7777)

Press Enter

Press Enter

Follow the keypress sequence shown at right to test the Drive.

NOTICE In a domestic environment, this product may cause radio interference which may require supplementary mitigation measures.

Figure 20 - Drive Reset Procedure

23Warranty 23

Limited WarrantyPENTAIR warrants to the original consumer purchaser (“Purchaser” or “You”) of the products listed below, that they will be free from defects in material and workmanship for the Warranty Period shown below.

Product Warranty Period

Water Systems Products — jet pumps, small centrifugal pumps, submersible pumps and related accessories

whichever occurs first: 12 months from date of original installation, 18 months from date of manufacture

PENTEK INTELLIDRIVE™12 months from date of original installation, or 18 months from date of manufacture

Pro-Source™ Composite Tanks 5 years from date of original installationPro-Source™ Steel Pressure Tanks 5 years from date of original installationPro-Source™ Epoxy-Line Tanks 3 years from date of original installation

Sump/Sewage/Effluent Products12 months from date of original installation, or 18 months from date of manufacture

Our warranty will not apply to any product that, in our sole judgment, has been subject to negligence, misapplication, improper installation, or improper maintenance. Without limiting the foregoing, operating a three phase motor with single phase power through a phase converter will void the warranty. Note also that three phase motors must be protected by three-leg, ambient compensated, extra-quick trip overload relays of the recommended size or the warranty is void.Your only remedy, and PENTAIR’s only duty, is that PENTAIR repair or replace defective products (at PENTAIR’s choice). You must pay all labor and shipping charges associated with this warranty and must request warranty service through the installing dealer as soon as a problem is discovered. No request for service will be accepted if received after the Warranty Period has expired. This warranty is not transferable.PENTAIRISNOTLIABLEFORANYCONSEQUENTIAL,INCIDENTAL,ORCONTINGENTDAMAGESWHATSOEVER.THE FOREGOING LIMITED WARRANTIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER EXPRESS AND IMPLIED WARRANTIES, INCLUDINGBUTNOTLIMITEDTOIMPLIEDWARRANTIESOFMERCHANTABILITYANDFITNESSFORAPARTICULARPURPOSE.THEFOREGOINGLIMITEDWARRANTIESSHALLNOTEXTENDBEYONDTHEDURATIONPROVIDEDHEREIN.Some states do not allow the exclusion or limitation of incidental or consequential damages or limitations on how long an implied warranty lasts, so the above limitations or exclusions may not apply to You. This warranty gives You specific legal rights and You may also have other rights which vary from state to state.This Limited Warranty is effective June 1, 2011 and replaces all undated warranties and warranties dated before June 1, 2011.

PENTAIR 293 Wright Street • Delavan, WI 53115

Phone (262) 728-5551 • Fax (262) 728-7323