Omaha, NB

October 12, 2017

Wayne Hartmann VP, Smart Grid and Protection

Senior Member, IEEE

Implementing Volt/VAR Optimization

with DER Penetration

Page 2: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Wayne Hartmann is VP, Protection and Smart Grid Solutions for Beckwith Electric. He provides Customer and Industry linkage to Beckwith Electric’s solutions, as well as contributing expertise for application engineering, training and product development.

Wayne Hartmann VP, Protection and Smart Grid Solutions

Beckwith Electric Company [email protected]

904-238-3844

Before joining Beckwith Electric, Wayne performed in application, sales and marketing management capacities with PowerSecure, General Electric, Siemens Power T&D and Alstom T&D. During the course of Wayne's participation in the industry, his focus has been on the application of protection and control systems for electrical generation, transmission, distribution, and distributed energy resources.

Wayne is very active in IEEE as a Senior Member serving as a Main Committee Member of the IEEE Power System Relaying Committee for 25 years. His IEEE tenure includes having chaired the Rotating Machinery Protection Subcommittee (’07-’10), contributing to numerous standards, guides, transactions, reports and tutorials, and teaching at the T&D Conference and various local PES and IAS chapters. He has authored and presented numerous technical papers and contributed to McGraw-Hill's “Standard Handbook of Power Plant Engineering, 2nd Ed.”

2

MIPSYCON 2017

Page 3: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Definitions • CAPC = Capacitor Control

• REGC = Regulator Control

• LTCC = Load Tapchanging Transformer Control (2001D)

• OLTC = On Load Tapchanger (REG and PWR XFRM)

• FPF = Forward Power Flow

• RPF = Reverse Power Flow

• VVO= Volt/VAR Optimization

• CVR = Conservation Voltage Reduction

• CVRfactor = P / V (0.5 typ., >1,0 is excellent)

• DA = Distribution Automation

• EOL = End of Line, as in EOL Voltage

• Reconfig = System Reconfiguration

• ADVVOC = Advanced Distribution Volt/VAR Controller

3

3

MIPSYCON 2017

Page 4: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Exploration

1547a and the New 1547

Active VAR regulation by DER

VVO Issues:

Line drop compensation (LDC), R and XL, or Z

VAR-Bias vs. LDC for control of Active VAR DER

LDC issues with reverse power flow

Reverse power flow control modes for On-Load tapchanging Elements (OLTC = LTC Transformers and Substation Regulators)

Inverse time vs. fixed delay for OLTC Elements

4

4

MIPSYCON 2017

Page 5: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Exploration Substation Protection Issues:

Radial vs. Bidirectional Fault Current Flows • Out-of-section (sympathy) trip concerns and mitigation

• Remote interrupter failure protection

Reclosing treatment : • Increase of 1st Shot Time Delay (from instantaneous)

• Adaptive protection with voltage control of reclosing

Ferroresonance on load side of feeder CBs

Ungrounded fault backfeed into transmission protection • High side delta winding issue

• Summary and Q&A

5

MIPSYCON 2017

Page 6: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

DER Impact on VVO

DER is proliferating Powerflows and levels change, resulting in voltage changes

Placement of DER can change due to DA

IEEE 1547a, and soon-to-be approved IEEE 1547-2017 (?), allow reactive as well as active powerflow output, compounding the problem

6

MIPSYCON 2017

Page 7: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

1547A (2014): Active Voltage/VAR Control

• Coordination and approval of the area EPS and DR operators shall be required for the DR to actively participate to regulate the voltage by changes of real and reactive power.

• The DR shall not cause the Area EPS service voltage at other Local EPSs to go outside the requirements of ANSI C84.1-2006, Range A.

7

MIPSYCON 2017

Page 8: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

• If large amounts of DER are easily “shaken off” for transient out-of-section faults, voltage and power flow upset can occur in:

– Feeders

– Substations

– Transmission

• Fault ride-through capability makes the system more stable

– Distribution: Having large amounts of DER “shaken off” for transient events suddenly upsets loadflow and attendant voltage drops

• Impacts include unnecessary LTC, regulator and capacitor control switching

• If amount of DER shaken off is large enough, voltage limits may be violated

– Transmission: Having large amounts of DER “shaken off” for transient events may upset loadflow into transmission impacting voltage, VAR flow and stability

IEEE 1547 Addendum: IEEE 1547a

8 This will be part of IEEE 1547-2017 (?)

MIPSYCON 2017

Page 9: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

ANSI C84.1-2006

Standard for Electric Power Systems and Equipment – Voltage Ratings

• Range A is the optimal voltage range

• Range B is acceptable, but not optimal

9

MIPSYCON 2017

Page 10: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

VVO Concepts VVO Concepts

and DER Issuesand DER Issues

•• What is VVO?What is VVO? •• How do you obtain it?How do you obtain it? •• CVR and what do you get out of itCVR and what do you get out of it •• How DER can cause control issues How DER can cause control issues

with VVO and CVRwith VVO and CVR •• What to do about itWhat to do about it

10

MIPSYCON 2017

Page 11: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

VVO Adjusting system voltage and pf by properly controlling

OLTC and reactive assets. Ideally:

OLTC Assets used for Voltage Issues due to Real Power Changes • Load Tapchanging Transformer Controls (Substation)

• Voltage Regulator Controls (Substation and Line)

Reactive Assets used for VAR regulation (loss minimization)

Reactive Assets used for Voltage Issues due to Reactive Power Changes

• Capacitors (Line)

• Active VAR Regulating DER (new)

11

MIPSYCON 2017

Page 12: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

VVO Controllers LTC Controls (Load Tapchanger) Applied on LTC Transformers in Substations

Control voltage

Regulator Controls

Applied on Regulators o Substation and Line

Control voltage

Capacitor Controls

Applied on Pole Top Capacitor Banks

Provide VARs and influence voltage

We’ll explore some advanced applications

Advanced Volt/VAR Optimization Controllers = ADVVOC 12

MIPSYCON 2017

Page 13: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

126

120

114

1 2 3 4 5 6 7 8

Vo

lts

(s

ec

on

da

ry)

25% of Feeder Length

50% of Feeder Load

Substa

tion

Loads only

Voltage Profile

No VVO

13

MIPSYCON 2017

Page 14: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

126

120

114

1 2 3 4 5 6 7 8

Vo

lts

(s

ec

on

da

ry)

25% of Feeder Length

50% of Feeder Load

Substa

tion

Loads only

Voltage Profile

No VVO

CAPS ON

Capacitors decrease losses proving flatter voltage profile

14

MIPSYCON 2017

Page 15: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

126

120

114

1 2 3 4 5 6 7 8

Vo

lts

(s

ec

on

da

ry)

25% of Feeder Length

50% of Feeder Load

Substa

tion

Voltage Profile

Loads only No VVO

CAPs ON

Capacitors decrease losses proving flatter voltage profile

VVO

15

MIPSYCON 2017

Page 16: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

126

120

114

1 2 3 4 5 6 7 8

Vo

lts

(s

ec

on

da

ry)

25% of Feeder Length

50% of Feeder Load

Substa

tion

Voltage Profile

Loads only

No VVO

CAPs ON

Capacitors decrease losses proving flatter voltage profile

VVO

VVO + CVR

16

MIPSYCON 2017

Page 17: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

VVO Results

Reduce losses XC counters XL of lines

Decreased operation of OLTC elements Deferred capital expenditures and improved

capital asset utilization Reduced electricity generation and

environmental impacts Flatter voltage profile Allows better CVR without low voltage violation at

the end-of-line

17

MIPSYCON 2017

Page 18: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Vo

ltag

e A

dd

ed

to

Ban

dcen

ter

0 100 50 10 150

Load Current – Full Load at 200mA

5

10

15

20

25

200

2V

5V

10V

15V

Should use high voltage block for 1st house protection!!!

Forward Power and LDC

18

MIPSYCON 2017

Page 19: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Line Drop Compensation Principle

Peak

Loading

Light

Loading

Distance

Voltage

Load

Load

Center

Without LDC

Regulated Regulated

Bus

19

MIPSYCON 2017

Page 20: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Line Drop Compensation Principle

Distance

Voltage

Light

Loading

Peak

Loading

Load

Load

Center

With LDC

Regulated Regulated

Bus

20

MIPSYCON 2017

Page 21: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

• Regulates voltage at a point closer to the load as voltage drops due to loss in the line because of line impedance and current

Without LDC at full Load

With LDC at full Load and unity power factor(X=5)

52 79

Line Impedance (R+jX)

Load Center

52 79

Line Impedance (R+jX)

Load Center

120V 118V 115V

125V 123V 120V

LDC – R,X

21

MIPSYCON 2017

Page 22: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

LDC - Z

Application: Distribution bus regulation

Concept: Increase bus voltage as the load level increases

No individual line information

Uses current magnitude ONLY

BUS

Distribution

Feeders

200 ma

(CT)

V Set

0 0 I

V

22

MIPSYCON 2017

Page 23: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

CAPs use “feedforward” control such as time-of-day, day, temperature, seasonality

Feedforward is only as good as your assumptions and

correlation factors

CAPs use voltage or VAR w/voltage override

Difficult to coordinate with OLTC elements using LDC with

voltage or VAR w/voltage override

VAR controls not much good near end of line

Little load flow

VAR controls must be on main line

Voltage controls may be on line tap when “real estate” is sparse

23

Traditional Methods: Control Based Reactive Support Elements

MIPSYCON 2017

Page 24: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

CAP Voltage Control

24

Volts (Secondary)

Ca

pa

cito

r B

an

k St

ate

120 126114

ON

OFF

Deadband

Setting with Deadband

Deadband avoids hunting

MIPSYCON 2017

Page 25: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

• Why? As voltage rises, counter with absorbing VAr • Uses droop characteristic • Based on power and voltage sensing at PCC • If inverter based, a “Smart” Inverter

DER Actively Controlling VAR Volt-VAr

25

IEEE 1547-D6.0

MIPSYCON 2017

Page 26: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

CAPs and DER • As power flows and assumed reactive voltage drops can

change as DER proliferates, consider changing fixed CAPs to switched to avoid overvoltage (from excessive VAR support) under high DER output conditions

• Consider active voltage (VAR) control of DER as proliferation increases

26

Volts (Secondary)

Ca

pa

cito

r B

an

k St

ate

120 126114

ON

OFF

Deadband

Inve

rter

(V

ar)

Injection/Capacitive

Absorption/Inductive

Volts (Secondary)120 126114

Reference

Deadband

MIPSYCON 2017

Page 27: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Representation in Application Sequences • Voltage Low = Provide VARS

• Voltage High = Consume VARS

27

Inve

rter

(V

ar)

Injection/Capacitive

Absorption/Inductive

Volts (Secondary)120 126114

Reference

Deadband

MIPSYCON 2017

Page 28: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Traditional Methods: Control Based OLTC Elements

OLTCs use line drop compensation (LDC) to cope with line losses (R/XL, Z)

Only as good as line model

May not coordinate with downline reactive elements for VAR/pf regulation

How can LDC control voltage sensing CAPs?

How can LDC control DER VAR output?

28

MIPSYCON 2017

Page 29: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Use of VAR-Bias to Coordinate DERs/CAPs with REGs and LTCs

VAR-Bias as a new concept to unify VVO with OLTCs and CAPs

Use a “VAR-Bias” characteristic to change the response of the OLTC (REGC or LTCC)

The VAR-Bias characteristic can be tailored for normal operation (non-CVR) and CVR operation

– Normal (non-CVR) Operation: Negative VAR Bias

– CVR Operation: Positive VAR Bias

29

MIPSYCON 2017

Page 30: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Use of VAR-Bias to Coordinate DERs/CAPs with REGs and LTCs

• REGC and LTCC use information on VAR flow

– Is the VAR flow out to the line (load)?

– Is the VAR flow into the source?

• The above indicate if you are or are not at/near unity power factor

• VAR flow into the REG or LTC indicate the voltage downline is higher than the voltage at the REG or LTC

30

MIPSYCON 2017

Page 31: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Use of VAR Bias in OLTC Devices (instead of LDC)

• Use VAR-Bias control to modify behavior of the voltage adjustment with regard to real and reactive power flows to properly manipulate voltage bandcenter

Normal, Non-CVR ApplicationNegative Linear VAR Bias

Lagging VARs (+)

120V

118V

116V

122V

124V

Leading VARs (-)

31 31

MIPSYCON 2017

Page 32: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Negative VAR-Bias • Called “negative” as lagging VAR causes voltage band to be lowered

• Designed to maintain unity pf and coax proper voltage asset, OLTC or reactive asset, to act depending on the cause of the voltage change Voltage change from real power change, use OLTC asset

Voltage change by reactive power change, use VAR asset

Normal, Non-CVR ApplicationNegative Linear VAR Bias

Lagging VARs (+)

120V

118V

116V

122V

124V

Leading VARs (-)

32 32

MIPSYCON 2017

Page 33: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

VAR-Bias: Near or at Unity PF

Normal, Non-CVR ApplicationNegative Linear VAR Bias

Lagging VARs (+)

120V

118V

116V

122V

124V

Leading VARs (-)

OLTC Tap Down

OLTC Tap Up

33

MIPSYCON 2017

Page 34: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

VAR-Bias: Bandcenter Decreases with Lagging VAR

Normal, Non-CVR ApplicationNegative Linear VAR Bias

Lagging VARs (+)

120V

118V

116V

122V

124V

Leading VARs (-)

NO Tap Command

As voltage falls: CAPs switch ON DER exports VAr Voltage rises from

increase in VAr

34

MIPSYCON 2017

Page 35: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

VAR-Bias: Bandcenter Increases with Leading VAR

Normal, Non-CVR ApplicationNegative Linear VAR Bias

Lagging VARs (+)

120V

118V

116V

122V

124V

Leading VARs (-)

NO Tap Command

As voltage rises: CAPs switch OFF DER absorbs VAr Voltage lowers from

decrease in VAr

35 35

MIPSYCON 2017

Page 36: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Normal Operation: Negative VAR-Bias

• Voltage near center of band

• Near unity power factor

52

Closed

Opened

Closed

Opened

Closed

Opened

Closed

Opened

121V

118V

117V

116V

122V

123V

124V

119V

120V

NORMAL OPERATION (non-CVR)

DERVArOUT

VArIN

VLOW VHIGH

DERVArOUT

VArIN

VLOW VHIGH

36

Normal, Non-CVR ApplicationNegative Linear VAR Bias

Leading VARsLagging VARs120V

121V

118V

117V

116V

122V

123V

124V

119V (-)

(+)

MIPSYCON 2017

Page 37: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Normal Operation: Negative VAR-Bias

• Inductive load increases, pf lags, voltage decreases.

• REG bandcenter lowers.

• CAPs come on, DER outputs VAr

• Voltage and VAr normalize

52

Closed

Opened

Closed

Opened

Closed

Opened

Closed

Opened

121V

118V

117V

116V

122V

123V

124V

119V

120V

NORMAL OPERATION (non-CVR)

DERVArOUT

VArIN

VLOW VHIGH

DERVArOUT

VArIN

VLOW VHIGH

1

2

3

37

Normal, Non-CVR ApplicationNegative Linear VAR Bias

Leading VARsLagging VARs120V

121V

118V

117V

116V

122V

123V

124V

119V

2

1

3

(-)

(+)

MIPSYCON 2017

Page 38: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Normal Operation: Negative VAR-Bias

• Inductive load decreases, pf leads, voltage rises.

• REG bandcenter rises.

• CAPs switch off, DER consumes VAr

• Voltage and VAr normalize

52

Closed

Opened

Closed

Opened

Closed

Opened

Closed

Opened

121V

118V

117V

116V

122V

123V

124V

119V

120V

NORMAL OPERATION (non-CVR)

DERVArOUT

VArIN

VLOW VHIGH

DERVArOUT

VArIN

VLOW VHIGH

1

2

3

38

1

Normal, Non-CVR ApplicationNegative Linear VAR Bias

Leading VARsLagging VARs120V

121V

118V

117V

116V

122V

123V

124V

119V

2

31

(-)

(+)

MIPSYCON 2017

Page 39: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Normal Operation: Negative VAR-Bias

• Resistive load decreases, pf remains the same, voltage rises

• REG taps down, voltage normalizes

• CAPs and DER do not change VAr output

52

Closed

Opened

Closed

Opened

Closed

Opened

Closed

Opened

121V

118V

117V

116V

122V

123V

124V

119V

120V

NORMAL OPERATION (non-CVR)

1

2

3

DERVArOUT

VArIN

VLOW VHIGH

DERVArOUT

VArIN

VLOW VHIGH

39

1

Normal, Non-CVR ApplicationNegative Linear VAR Bias

Leading VARsLagging VARs120V

121V

118V

117V

116V

122V

123V

124V

119V

2

3

1

(+)

(-)

MIPSYCON 2017

Page 40: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Normal Operation: Negative VAR-Bias

• Resistive load increases, pf leads, voltage decreases

• REG taps up, voltage normalizes

• CAPs and DER do not change VAr output

52

Closed

Opened

Closed

Opened

Closed

Opened

Closed

Opened

121V

118V

117V

116V

122V

123V

124V

119V

120V

NORMAL OPERATION (non-CVR)

1

23

DERVArOUT

VArIN

VLOW VHIGH

DERVArOUT

VArIN

VLOW VHIGH

40

1

Normal, Non-CVR ApplicationNegative Linear VAR Bias

Leading VARsLagging VARs120V

121V

118V

117V

116V

122V

123V

124V

119V 3

2

1

(+)

(-)

MIPSYCON 2017

Page 41: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Voltage Bandcenter and Bandwidth: LTC/REG, CAP, DER

• CAPS and DER furthest away from source have shorter time delay than upline similar devices

• This examples uses CAPs before DER

– Assuming DER charges for reactive support

41

52

Closed

Opened

Closed

Opened

Closed

Opened

Closed

Opened

DERVArOUT

VArIN

VLOW VHIGH

DERVArOUT

VArIN

VLOW VHIGH

Normal, Non-CVR ApplicationNegative Linear VAR Bias

Leading VARsLagging VARs120V

121V

118V

117V

116V

122V

123V

124V

119V

REG

CAPDER

REG

CAP

DER

(+) (-)

MIPSYCON 2017

Page 42: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Voltage Settings and Timings: LTC/REG, CAP, DER

• CAPS and DER furthest away from source have shorter time delay than upline similar devices

• This examples uses CAPs switching before DER, assuming DER charges for reactive support

• REGs use VAR-Bias with larger bandwidth and longer time delays than CAPs or DER

42

52

DERVArOUT

VArIN

VLOW VHIGH

DERVArOUT

VArIN

VLOW VHIGH

70 sec. 60 sec. 45 sec. 30 sec.

3V80 sec.

3V95 sec.75 sec. 50 sec.

Normal, Non-CVR ApplicationNegative Linear VAR Bias

Leading VARsLagging VARs120V

121V

118V

117V

116V

122V

123V

124V

119V

REG

CAPDER

REG

CAP

DER

(-)(+)

MIPSYCON 2017

Page 43: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

VARVAR--Bias and Deep CVRBias and Deep CVR

How low can you go? Lower than you may think!

43

MIPSYCON 2017

Page 44: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

VVO and CVR - Why • Lowering distribution voltage levels during peak

periods to achieve peak demand reductions

• Reducing voltage levels for longer periods to achieve electricity conservation

• Reducing energy losses in the electric distribution system

Benefits include deferral of capital expenditures, energy savings, and greater operational flexibility

and efficiency

Voltage and Reactive Power Management – Initial Results: US DOE, 12/12

44

MIPSYCON 2017

Page 45: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Conservation Voltage Reduction

Goal of voltage reduction is to reduce load V= I * R for constant Z load The lower the V the lower the I The lower the I, the lower the I2R = W (constant Z load)

Ex., incandescent lights, strip heaters

Not true if load is not constant power type (constant PQ load): Ex., motors, power supplies

Can be deployed at: All times For load reduction periods (peak reduction) During system emergencies when the voltage is collapsing due

reactive load exceeding available supply

45

MIPSYCON 2017

Page 46: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Load Models and CVR Factor • Load models Constant Power (PQ)

Constant Impedance (Z)

Constant Current (I)

Load current changes inversely to the change in voltage

Load current changes linearly with the change in delivered voltage, and the demand varies as a squared function of the voltage change (ex., incandescent bulb)

Power delivered to the load varies linearly with the change in voltage delivered to the load

Evaluating Conservation Voltage Reduction with WindMil® - Milsoft

CVRf = P/V

0.5 to 0.7 is typical

Greater than 1 is really good

Constant Power (PQ or kVA)

Constant Impedance (Z) Constant Current (I)

Motors (at rated load) Incandescent/Dimmable LEDLighting

Welding Units

Power Supplies Resistive (Strip) Water Heaters Electroplating

Fluorescent/LED Lighting Electric Stoves

Washing Machines Clothes Dryers

46

MIPSYCON 2017

Page 47: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Load Models and CVR Factor

Evaluating Conservation Voltage Reduction with WindMil® - Milsoft

CVRf = P/V

0.5 is typical

Greater than 1 is really good

47

Constant Power (PQ or kVA)

Constant Impedance (Z) Constant Current (I)

Motors (at rated load) Incandescent/Dimmable LEDLighting

Welding Units

Power Supplies Resistive (Strip) Water Heaters Electroplating

Fluorescent/LED Lighting Electric Stoves

Washing Machines Clothes Dryers

MIPSYCON 2017

Page 48: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Negative VAR-Bias • Called “negative” as lagging VAR causes voltage band to be lowered

• Designed to maintain unity pf and coax proper voltage asset, OLTC or reactive asset, to act depending on the cause of the voltage change Voltage change from real power change, use OLTC asset

Voltage change by reactive power change, use VAR asset

Normal, Non-CVR ApplicationNegative Linear VAR Bias

Lagging VARs (+)

120V

118V

116V

122V

124V

Leading VARs (-)

48 48

MIPSYCON 2017

Page 49: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Positive VAR-Bias • Called “positive” as leading VAR causes voltage band to be lowered

• Designed to cause leading pf and raise voltage at end of the feeder Allows head of feeder to lower voltage near ANSI C84.1 low limits

Fosters greater power reduction during CVR operation

CVR ApplicationPositive Linear VAR Bias

Lagging VARs (+)

120V

118V

116V

122V

124V

Leading VARs (-)

49 49

MIPSYCON 2017

Page 50: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

CVR Operation: Positive VAR-Bias

52

Closed

Opened

Closed

Opened

Closed

Opened

Closed

Opened

121V

118V

117V

116V

122V

123V

124V

119V

120V

CVR OPERATION

1

2

DERVArOUT

VArIN

VLOW VHIGH

DERVArOUT

VArIN

VLOW VHIGH

• REG forces voltage lower

• CAPs begin to switch on and DER outputs VAr

50

Leading VARsLagging VARs120V

121V

118V

117V

116V

122V

123V

124V

119V

CVR ApplicationPositive Linear VAR Bias

1

2 (-)(+)

MIPSYCON 2017

Page 51: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

CVR Operation: Positive VAR-Bias

52

Closed

Opened

Closed

Opened

Closed

Opened

Closed

Opened

121V

118V

117V

116V

122V

123V

124V

119V

120V

CVR OPERATION

2

DERVArOUT

VArIN

VLOW VHIGH

DERVArOUT

VArIN

VLOW VHIGH

3

1

• VARs begin to lead.

• REG forces voltage even lower.

• More CAPs switch on and DER outputs VAr

51

Leading VARsLagging VARs120V

121V

118V

117V

116V

122V

123V

124V

119V

CVR ApplicationPositive Linear VAR Bias

1

3

2 (-)(+)

MIPSYCON 2017

Page 52: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

126

120

114

0 10 20 30 40 50 60 70 80

Positive VAR-Bias Method

Traditional VVO; CVR

Distance (%)

Vo

lts

(sec

on

da

ry)

Traditional VVO; non-CVR

No VVO

90 100

25% of Feeder

50% of Load

CVR: REGs/LTC with DERs/CAPs

• For CVR, forcing overVAr on feeder causes end of line voltage to rise

• You can have a deeper voltage reduction at the beginning of the line where most of the load is located (EPRI Green Circuits) 52

MIPSYCON 2017

Page 53: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

The cost is ADVVOCs, which you need anyway

No extensive comms system required

NO DMS required

Feedback loop from CAPs to OLTCs to modify voltage control is made from VAR flow/direction

VAR-Bias Take Away

53

MIPSYCON 2017

Page 54: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Terminology Cross Reference

Use of Powerflow Direction Change by REGC/LTCC

54

MIPSYCON 2017

Page 55: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

REGC/LTCC: Reverse Power Method Discussion

RPF Selection 55

MIPSYCON 2017

Page 56: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Return to Neutral • Return to Neutral – drives tap

position to neutral and then stops – Use where small unpredictable

change in voltage may be encountered on RPF side of REG

– “Feel safe” strategy when one cannot distinguish the source strength of the RFP

– Is it DER, and possible weak? – Is it DA, and strong?

– Can be risky as there is no control once at the neutral tap

56

MIPSYCON 2017

Page 57: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Block • Block – inhibits automatic

operation, leaving regulator on present tap – Use where source of RPF is not

expected to change voltage on RPF side of REG

– Also a “feel safe” strategy when one cannot distinguish the source strength of the RFP

– Is it DER, and possible weak? – Is it DA, and strong?

– Can be risky as there is no control and the voltage begins to deviate

57

MIPSYCON 2017

Page 58: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Ignore: Regulate Forward

• Regulate Forward (Ignore) – continues control action as though forward power flow continued to exist. – Uses same settings with

normal forward power flow – May use with small amounts

of RPF, or when you need to drive down voltage due to DER causing a voltage rise

– With strong reverse power flows, LDC will drive voltage down

58

MIPSYCON 2017

Page 59: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

• Regulating forward, +LDC raises bandcenter as FPF becomes larger

• Regulating forward, -LCD lowers bandcenter as RPF becomes larger

Ignore: Regulate Forward

with RFP

Load(FPF)

Source(FPF)

Source(RPF)

Load(RPF)

RPF

Regulates FPF Side

OLTCXFRM-1

OLTCREG-1

79/152/1

DER DER

Reverse Powerflow

Load Load Load Load

[Volts added to Bandcenter]

[Volts subtracted from Bandcenter]

FPFRPF

(+) LDC R/XL or Z

(-) LDC R/XL or Z

+V

-V

59

MIPSYCON 2017

Page 60: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Forward Power

Reverse Power

Vo

ltag

e

-10 0 -50 -100 50

Percent of Full Load Current

-5

0

5

10

15

100

2V

5V

10V

15V

Notice that if

the current is

reverse, LDC

drops the

voltage

instead of

raising it

Regulate Forward and LDC

60

MIPSYCON 2017

Page 61: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

DG Mode: Regulate Forward with New LDC Settings Regulate Forward (DG Mode)

– This mode of operation is the same as the Ignore mode, plus provides ability to change line drop compensation (LDC)

– Use where DER power output is large enough to warrant new LDC settings

61

A separate set of LDC settings can be specified which will be applied during reverse power

• This can include LDC factor magnitudes, signs and the use of R and XL , or Z

• VAR-Bias may also be selected

MIPSYCON 2017

Page 62: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

• Regulating forward, -LDC raises bandcenter as RPF becomes larger

• Regulating forward, +LCD lowers bandcenter as RPF becomes larger

“DG Mode” Regulate Forward

OLTCXFRM-1

OLTCREG-1

79/152/1

DER DER

Reverse Powerflowwith DER

Load Load Load Load

Load(FPF)

Source(FPF)

Source(RPF)

Load(RPF)

RPF

Regulates FPF Side

[Volts added to Bandcenter]

[Volts subtracted from Bandcenter]

(-) LDC R/XL or Z

FPF

+V

-V

(+) LDC R/XL or Z

62

MIPSYCON 2017

Page 63: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

REGC/LTCC: Reverse Power, “Regulate Reverse” • Regulate Reverse (Calculated): Voltage Sensing: With RPF, control uses tap

position knowledge and FPF side voltage Regulates according to reverse power settings

– Use where RPF source to OLTC is a stronger source – Regulate voltage on the RPF side of the OLTC

• Typically used for reconfiguration

• Regulate Reverse (Measured): Voltage Sensing: With RFP, control switches its

voltage sensing input to a RPF side VT – RFP side VT must be available

Regulates according to reverse power settings – Use where RPF source to REG is a stronger source – Regulate voltage on the RPF side of the REG

• Typically use for reconfiguration

63

Load(FPF)

Source(FPF)

Source(RPF)

Load(RPF)

RPF

RPF

Source(RPF)

Load(RPF)

Load(FPF)

Source(FPF)

MIPSYCON 2017

Page 64: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

REGC/LTCC: Reverse Power, “Regulate Reverse” • “Regulate Reverse” Calculated

• Regulates reverse with new voltage settings and LDC values

• Use with strong RPF source (reconfig)

• Uses tap position and calculates voltage on previous source side of regulator

• Additional VT not needed 64

MIPSYCON 2017

Page 65: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

REGC/LTCC: Reverse Power, “Regulate Reverse”

• “Regulate Reverse” Measured

• Regulates reverse with new voltage setpoints and LDC values

• Use with strong RPF source (reconfig)

• Uses additional VT on previous supply side of regulator

65

MIPSYCON 2017

Page 66: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Issues with DA and DER

Reverse Power Flow (RPF)

Both a reconfig and DER may cause RPF

With DER (weaker source than system), forward regulation should be employed

With reconfig (strong source switches), reverse regulation should be employed

How do we know weak and strong source

if you have mix of DA and DER?

66

MIPSYCON 2017

Page 67: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

How do you know after a reconfiguration which side of a regulator has the string source?

How do you control caps relocated due to reconfiguration

Normal power from Utility to load Utility strong source

DER may backfeed Typically a weaker source

What to do with power reversal from sectionalizing?

What to do with power reversal from DER?

What to do about LDC with DER influencing?

High Penetration of DER and/or DA on Distribution Systems

Requires Smart Technology to obtain VVO/CVR

67

67

MIPSYCON 2017

Page 68: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Sample DA ScenariosSample DA Scenarios

What does DA do to power flow and source strength on line sections?

68

68

MIPSYCON 2017

Page 69: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

69

Volt/VAR Control Considerations from DA

7952 79

7952 79

79

• Normal open loop

• Uses recloses to perform FLISR

• V/VAR feeder devices employed: REGC and CAPC

69

MIPSYCON 2017

Page 70: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

70

Volt/VAR Control Considerations from DA

7952 79

7952 79

79

X

• Fault occurs on feeder

70

MIPSYCON 2017

Page 71: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

71

Volt/VAR Control Considerations from DA

7952 79

7952 79

79

• Fault is cleared by 52 (O/C trip and LO) and 79 (27)

• Tie 79 closes (uses H/D logic)

• Power is restored to most of loop system

• Reverse power flow occurs on some section of the newly-

configured feeder 71

MIPSYCON 2017

Page 72: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

72

Voltage Control Considerations from DA: REGC

7952 79

7952 79

79

Reverse Power Flow

How to address RFP:

1. Do nothing (does not work; REG LDC causes operational errors)

2. Use communications to control by setpoint or setting group

3. Use change of powerflow direction to change to a new predetermined

control mode

4. Use change of powerflow direction and source strength (by REGC

measurement) to initiate autodetermination of best control mode

72

MIPSYCON 2017

Page 73: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

RPF: Why We Care????

• With high penetration levels of DA and/or DER on the

distribution system it is becoming more common to have

the voltage regulators deal with reverse power situations

• The solution to the OLTC problem gets complicated as the

control needs to know (or assume) the source of reverse

power.

• It is important to select the correct reverse power mode of

operation for voltage regulators otherwise dangerous high

or low voltage levels may result causing equipment

damage or misoperations

73 73

MIPSYCON 2017

Page 74: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Forward Power

Reverse Power

Vo

ltag

e

-10 0 -50 -100 50

Percent of Full Load Current

-5

0

5

10

15

100

2V

5V

10V

15V

LDC Graph

Notice that if

the current is

reverse, LDC

drops the

voltage

instead of

raising it

Forward Power and LDC

74

MIPSYCON 2017

Page 75: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

The Reverse Power Flow (RPF) Problem

• It’s all about source strength

– If the source is weak, small impact (most DER)

– If the source is strong, big impact (reconfiguration)

• Impacts of strong source RPF:

– Drives LDC the wrong way

– Regulation should be in the now reverse direction

• The tail cannot wag the dog

75

75

MIPSYCON 2017

Page 76: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

No RPF Source

76

OLTCXFRM-1

OLTCREG-1

79/152/1

Forward Powerflow

Load Load Load Load

76

MIPSYCON 2017

Page 77: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Weak RPF Source

77

OLTCXFRM-1

OLTCREG-1

79/152/1

DER DER

Forward Powerflow without DER

Reverse Powerflowwith DER

Load Load Load Load

77

MIPSYCON 2017

Page 78: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

No RPF Source: Open Loop

78

OLTCXFRM-1

Load Load Load Load

OLTCXFRM-1

OLTCREG-3

Load Load Load Load

Load

Load

Load

Load

OLTCREG-1

52/1 79/1

79/5

79/2

52/2 79/3 79/4

Forward Powerflow without Reconfig

OLTCREG-2

OLTCREG-4

Forward Powerflow without Reconfig

Forward Powerflow without Reconfig

Forward Powerflow without Reconfig

78

MIPSYCON 2017

Page 79: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Strong FPF Source: Reconfig

79

OLTCXFRM-1

Load Load Load Load

OLTCXFRM-1

OLTCREG-3

Load Load Load Load

Load

Load

Load

Load

OLTCREG-1

52/1

52/2 79/3 79/4

Forward Powerflow without Reconfig

OLTCREG-2

OLTCREG-4

Forward Powerflow without Reconfig

Forward Powerflow without Reconfig

OLTCREG-5

79/5

79/279/1

Dead Section

Forward Powerflowwith Reconfig

79

MIPSYCON 2017

Page 80: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Strong RPF Source: Reconfig

80

OLTCXFRM-1

Load Load Load Load

OLTCXFRM-1

OLTCREG-3

Load Load Load Load

Load

Load

Load

Load

OLTCREG-1

52/1

52/2 79/3 79/4

Forward Powerflow without Reconfig

OLTCREG-2

OLTCREG-4

Forward Powerflow without Reconfig

OLTCREG-5

79/5

79/279/1

Dead Section

Reverse Powerflowwith Reconfig

Forward Powerflow without Reconfig

Forward Powerflow without Reconfig

80

MIPSYCON 2017

Page 81: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

How Can One Know About Source Strength • Guess it, assume it

• Cheap and easy if one can make assumptions or guess

• LTC or REG makes RPF determination and goes into predetermined response mode, either:

• No DER on line, and the only way you can have RFP is a reconfiguration with a new source direction (assume new strong source)

• No reconfiguration possible, so only DER can cause RPF

81

MIPSYCON 2017

Page 82: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Knowing Relative Source Strength is KEY

• Use “Autodetermination” – Reverse Power Flow Source Strength

Determination • Control determines relative source strength

– Why it is important • Weak source (DER) results in continuing forward regulation

– May employ different LDC or VAR-Bias settings

• Strong source (Reconfig) results in use of reverse regulation

– May employ different Bandcenter, Bandwidth, and LDC or VAR-Bias settings

82

MIPSYCON 2017

Page 83: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Source 1

100 %

DPI1 = X1

LTC Transformer

Impedance =XT

VT1 VT2

DPI2 = X2

Source 2

100 %

Simulation of LTC Transformer/Regulator with Two sources: Simplified Model

83 83

MIPSYCON 2017

Page 84: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Case #

DPI1 DPI2

Reactive Current (IX)

Through the transformer

VT1 VT2 V

1 2% ∞ 0 100% 100.625% .625

2 ∞ 2% 0 99.375% 100% .625

3 2% 20% 1.953 % 99.96 % 100.4% .04

4 20% 2% 1.953 % 99.6 % 100.035% .04

5 2% 2% 7.14 % 99.85% 100.14% .29

Simulation Results

84 84

1 & 2: System reconfiguration; one source, radial

3 & 4: DER (weak) vs. System (strong)

5: Two weak sources

IOWA/NEBRASKA SYSTEM PROTECTION

AND SUBSTATION CONFERENCE MIPSYCON 2017

Page 85: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

When RPF is detected, operation is set initially to “DG Mode”

V is measured for two tap operations:

V = VMBT -VMAT

where VMBT = measured load side voltage just before a tap change VMAT = measured load side voltage one second after the tap change

Autodetermination of Source Strength with RPF

85

No

rma

lly e

xp

ec

t 0

.62

5V

per

tap

• If the measured V is > 0.47 (75%) of the normal expected value (0.625V) for two consecutive tap changes, Autodetermination will maintain “DG Mode” operation

• If the measured V is <= 0.31V (50%) of the normal expected value (0.625V) for two consecutive tap changes, Autodetermination changes to “Regulate Reverse Mode” operation

V ≥ 75%

0.6

25

V 50 < V < 75%

V ≤ 50%

MIPSYCON 2017

Page 86: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Reverse Power Source Strength Determination:

User Manually Designates

“DG Mode”

Reverse Power Flow Detected

User Manually Designates

Source Strength

“Regulate Reverse”

Weak Strong

86

MIPSYCON 2017

Page 87: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Reverse Power Source Strength Determination:

Autodetermination

“DG Mode”

Reverse Power Flow Detected

“Regulate Reverse”

Weak StrongAutodeterminationDynamically Designates

Source Strength

87

MIPSYCON 2017

Page 88: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

REGC/LTCC: Autodetermination of Operating Mode with Reverse Power

88 -1

Uses “Forward Power”Band Center, Band Width

and Time

Distributed Generation

121.0

4

+2

+5

Reverse Power

45

FPF

RPF

RPF Source StrongRPF Source Weak

Autodetermination:

Senses Reverse Powerflow (RPF), then:

If normal load side remains weak source,

switches to “DG Mode”

If normal load side changes to strong

source, switches to “Regulate Reverse”

(Reverse Power)

120.0

+1

+3

4

Forward Power

MIPSYCON 2017

Page 89: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Handling DER rapid output change

Irradiance and wind velocity can change very quickly

Large rise or drop in power (W, VAR) can cause large voltage swings

Normal fixed timing in OLTCs may not respond fast enough for good control

Employ inverse response curve for time delay

– Small changes yield longer time delays

– Large changes yield shorter time delays

89

MIPSYCON 2017

Page 90: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Definite Time OLTC Characteristic

Bandwidth(2 VAC)

120 VAC

121 VAC

119 VAC

< Time Delay

> Time Delay

Lower tap Command

90

MIPSYCON 2017

Page 91: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

V=BW/2

Voltage Deviation in Multiples of V

Tim

e D

elay

(%

of

Inve

rse

Tim

e D

elay

Set

tin

g)

91

Inverse Curve OLTC Time Characteristic

MIPSYCON 2017

Page 92: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Inverse TD Example

Example

Bandcenter = 120 V

Bandwidth = 2 V

Inverse Time Delay = 120 V

Sensed Voltage = 123 V

Time Delay Factor = (Vsense - Vbandcenter)/(BW/2)

Time Delay Factor =(123-120)/(2/2) = 3/1 = 3

From Graph, % Factor = 34%

Time = Setting * % Factor

Time = 120 sec. * 0.34 = 40.8 = 41 sec.

V=BW/2

Voltage Deviation in Multiples of V

Tim

e D

elay

(%

of

Inve

rse

Tim

e D

elay

Set

tin

g)

Bandwidth(2 VAC)

120 VAC

121 VAC

119 VAC

122 VAC

123 VAC

Voltage >Top of Deadband

by 2V

92

MIPSYCON 2017

Page 93: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Protection Concepts Protection Concepts

and DER Issuesand DER Issues Bidirectional Fault Current & DirectionalizationBidirectional Fault Current & Directionalization

Reclosing treatment :Reclosing treatment :

•• Increase of 1st Shot Time Increase of 1st Shot Time DelayDelay

•• Adaptive protection with voltage control of reclosingAdaptive protection with voltage control of reclosing

Ferroresonance on islanded feeder sFerroresonance on islanded feeder s

Ungrounded Ungrounded fault backfeed into transmission fault backfeed into transmission protection protection

93

MIPSYCON 2017

Page 94: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

• No effect – 22%

• Revised feeder coordination – 39%

• Added directional ground relays – 25%

• Added direction phase relays – 22%

• Added supervisory control - 22%

• Revised switching procedures – 19%

Impact on Utility Protection

IEEE Distribution Practices Survey – 1/02

94

MIPSYCON 2017

Page 95: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Bidirectional Fault Currents: Coordination

• Use directional elements in substation protection, mid-line reclosers and DER

Substation • Directionalize using 67 and 67N (instead of 50/51 and 50/51N)

• Trip toward DER (downstream) to avoid sympathy trips for out-of-section faults

• Trip toward Substation for remote breaker failure

Reclosers • Directionalize using 67 and 67N (instead of 50/51 and 50/51N)

• Trip toward Substation for remote breaker failure

DER • Directionalize using 67 and 67N (instead of 50/51 and 50/51N)

• Trip direction away from DER (upstream)

95

MIPSYCON 2017

Page 96: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

50

51

50

N

51

N

50

51

50

N

51

N

50

51

50

N

51

N 50

51

50

N

51

N

50

51

50

N

51

N

50 5150

N

51

N

Radial Distribution

• Non-directional phase and ground overcurrent elements

1 2

3

96

MIPSYCON 2017

Page 97: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

6767

N

67

67

N

67

67

N

67

67

N

67

67

N

67

67

N

6767

N

DER

DER

DER on System

• Directional phase and ground overcurrent elements

• Use voltage polarization

1 2

3

Directionalization toward DER helps prevent sympathy trips from out-of-section faults

97

1

No Trip No Trip

MIPSYCON 2017

Page 98: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

6767

N

67

67

N

67

67

N

67

67

N

67

67

N

67

67

N

6767

N

DER

DER

Directionalization toward Substation provides remote breaker failure protection

• Directional phase and ground overcurrent elements

• Use voltage polarization

• All reverse looking elements trip slower than all forward looking elements

1

2 3

4

DER on System

98

MIPSYCON 2017

Page 99: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

• Revise reclosing practices – 50%

• Added voltage relays to supervise reclosing – 36%

• Extend 1st shot reclose time – 26%

• Added transfer trip – 20%

• Eliminate reclosing – 14%

• Added sync check – 6%

• Reduce reclose attempts – 6%

DER Impact on Utility Reclosing

IEEE Distribution Practices Survey – 1/02

99

MIPSYCON 2017

Page 100: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

• If high-speed reclosing is employed, the DER

interconnection protection must be faster!

• Clearing time includes protection operation and breaker

opening

Utility Reclosing Issues: It is all about time……….

DER must trip from

utility in this interval

100

MIPSYCON 2017

Page 101: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Utility Reclosing Issues: It is all about time……….

DER must trip

from utility in

this interval

101

MIPSYCON 2017

Page 102: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Voltage Supervised Dead Time

102

52

Feeder Relay/Recloser Control

1

52

Feeder Relay/Recloser Control

52

Feeder Relay/Recloser Control

T/C

Status

T/C

Status

T/C

Status

52B

1 1

3Y or

Use minimal dead time and voltage supervision

for the reconnect t/reenergize permissive

MIPSYCON 2017

Page 103: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Voltage Supervised Dead Time

103

27

59

810

81U

NOT PUDO

Timer

Delay on Pick UpP

er IE

EE 1

54

7

27

All Phases< 5% Nominal

ANDReconnect PermissiveReenergize Permissive

PUDO

Timer

Delay on Pick Up AND

DERLong ClearingAlarm

Reconnect / Reenergize Timer DER Long Clearing Timer

Pickup

Pickup

Pickup

Pickup

Pickup

52

Feeder Relay/Recloser Control

1

52

Feeder Relay/Recloser Control

52

Feeder Relay/Recloser Control

T/C

Status

T/C

Status

T/C

Status

52B

1 1

3Y or

MIPSYCON 2017

Page 104: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

• Ferroresonance can take place between an induction generator and capacitors after utility disconnection from feeder

– Ferroresonance can also occur from Synchronous Generators and Inverter-based DER!

• Generator is excited by capacitors if the reactive components of the generator (XG) and aggregated capacitors (XC) are close in value

• This interplay produces non-sinusoidal waveforms with high voltage peaks. This causes transformers to saturate, causing non-linearities that exacerbate the problem.

Ferroresonance

104

MIPSYCON 2017

Page 105: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

New York Field Tests- 1989

Field Test Circuit (NYSEG)

105

Ferroresonance:

Test Circuit Setup

MIPSYCON 2017

Page 106: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Conditions:

Wye-Wye Transformers, 100kVAr capacitance, 60kW generator, 12kW load

New York Field Tests - 1989

Field Test Circuit (NYSEG)

Ferroresonance:

Observed Waveforms

106

MIPSYCON 2017

Page 107: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

• Need a peak detecting relay element “59I”

“RMSing” may smooth out high peaks

Ferroresonance

107

52

Feeder Relay/Recloser Control

52

Feeder Relay/Recloser Control

52

Feeder Relay/Recloser Control

T/C

Status

T/C

Status

T/C

Status

52B

3Y or 3Y or 3Y or

• May be applied at DER Interconnection (PoI)

• May be applied at feeder origin to detect ferroresonance after feeder is islanded (line side of CB)

MIPSYCON 2017

Page 108: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

a

bc

a

bc

ground

Van

=Vag

Vbn

=Vbg

Vbn

=Vbg

n=g

vag

=0

n

Van

= -Vng

Vcn

Vbn

Vbg

Vcg

Unfaulted

Ground Fault

Sensing Ungrounded System Ground Faults

108

DER Fault Backfeed

59

N

Feeder Substation

DER DER DER

DER DER

52

Remote

Upline CB

MIPSYCON 2017

Page 109: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

109

MIPSYCON 2017

Page 110: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

Recommended Reading • IEEE 1547 Series of Standards for Interconnecting

Distributed Resources with Electric Power Systems, http://grouper.ieee.org/groups/scc21/

• IEEE 1547-2017 (Draft 6.7)

• IEEE 1547a, 2014, Standard for Interconnecting Distributed Resources with Electric Power Systems, Addendum 1.

• Application of Automated Controls for Voltage and Reactive Power Management – Initial Results, US DOE, 12/2012

• Beckwith Electric Company, M-2001D Loadtapchanger Control Instruction Book, Chapter 6, 2016.

110

MIPSYCON 2017

Page 111: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

• “Smart Reverse Power Operating Mode for Distribution Voltage Regulators to Handle Distributed Generation along with Feeder Reconfiguration,” Dr. Murty V.V.S. Yalla. Presented at the PacWorld Conference, 2015.

• R. Bravo B. Yinger, P. Arons, "Fault Induced Delayed Voltage Recovery (FIDVR) Indicators," IEEE T&D, 2014

• Distribution Line Protection Practices Industry Survey Results, Dec. 2002, IEEE PSRC Working Group Report

• D. James, J. Kueck, " Commercial Building Motor Protection Response Report," US DOE, Pacific Northwest National Laboratory, 2015

Recommended Reading

111

MIPSYCON 2017

Page 112: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

• Evaluating Conservation Voltage Reduction with WindMil, Milsoft, G. Shirek, 2011

• C37.230, IEEE Guide for Protective Relay Applications to Distribution Lines, IEEE Power System Relaying Committee, Second Edition, 2007

• 1547a and Rule 21, Smart Inverter Workshop, June 21, 2013, SCE

• Bob McFetridge, Barry Stephens, “Can a Grid Be Smart without Communications? A Look at IVVC Implementation: Georgia Power’s Distribution Efficiency Program.” Presented at the Clemson Power Systems Conference, 2013.

Recommended Reading

112

MIPSYCON 2017

Page 113: Omaha, NB Implementing Volt/VAR Optimization October 12 ... · Implementing Volt/VAR Optimization with DER Penetration . Wayne Hartmann is VP, Protection and Smart Grid Solutions

• Implementing VVO with DER Penetration, IEEE

Innovative Smart Grid Technology (ISGT) Conference,

Washington DC, 2017

• Chuck Whitaker, Jeff Newmiller, Michael Ropp, Benn

Norris, “Renewable Systems Interconnection Study:

Distributed Photovoltaic Systems Design and Technology

Requirements,” Sandia National Labs, Dec. 2012.

• Turan Gonen, Electric Power Distribution Engineering,

2008, pp. 398-404.

• On-Site Power Generation, by EGSA,

ISBN# 0-9625949-4-6

• Effect of Distribution Automation on Protective Relaying,

2012, IEEE PSRC Working Group Report

113

Recommended Reading MIPSYCON 2017