Page 1: Nurse call system

Nurse Cal l Systemclino opt 9924.1

Page 2: Nurse call system

clino systems programme

clino opt

Nurse Call System with Audio-Visual Signalling

clino call Paging System

clino soft

Software Solutions for the Nursing Staff

clino com

Accounting System for TV and Telephone

clino serv

Maintenance and Service Package

clino phon

Nurse Call System with Two-Way Speech Facility

Page 3: Nurse call system

Albert Ackermann GmbH + Co. KGD-51641 Gummersbach

Tel. (02261) 83-0 • Fax 83-539www.ackermann.com

A member of Novar plc

Nurse Call Systemclino opt 99®

clino opt® is a registered trademark of Albert Ackermann GmbH + Co. KG

DIN EN ISO 9001Zertifikat: 09 100 4086 GEPRÜFTES

UMWELTMANAGEMENTREG. NR. D-142-00004

Page 4: Nurse call system

2

System overview clino opt 99

......................

...... 01 100 AAACKERMANN

..

Remind

Databus terminator and splitter

Call cancel push button

Electronic module without bed databus

Call push button (bed 1)

Pull cord(bathroom/WC)

Call push button (bath-room/WC)

Call push button (bed 2)

to further callpush buttons

Information displayBed databus to further call modules

Call module (bed 2)Call module (bed 1)Display module

Electronic module with bed databus

Call push button(bathroom / WC)

Display module

Electronic module for duty room

Pull cord(bathroom/WC)

Corridor databus

Power supply

Duty room unit

Service selection module

Zone controller(group 4-6)

Zone databus

Zone controller(group 1-3)

Power supply

to further zone con-trollers

Page 5: Nurse call system

Backboxes with accessories

3

Symbols Key / Table of Contents

Zone controller

Direction lamps

Electronic module

Call push button and call units

Pluggable call units

Cancel push button

Patient handset

Components for power supply

Call modules

Duty selection module

Cover plate

Master station

Display module

Information display

pageSystem overview clino opt 99 2Symbols key / table of contents 3System description clino opt 99 4

Zone controller 8Configuration module 8Interface unit 8Paging interface unit 9Printer interface 9PC interface 9Power supply 10Cover and mounting kit 10UPS module 24 V 11UPS module 230 V 12

Electronic module for patient room 14Electronic module for duty room 15Direction lamps 15Information Display 16Ceiling mounting set 16Zone indicator lamp 17Corridor lamp 18Databus terminator and splitter 18

Display module 20Speech module 20Call module 20Call module with push button and socket 21Patient handset 22Wall interface electronic 23Headphones 23Call push button 24Call push button for doctor call 24Call push button with socket 24Call push button with sockets 25Pull cord 25Pneumatic call push button 25Call unit with diagnostic sockets 26Pear push button, multiple push button 27Auto-release plug system 28Noise level sensor 28Pneumatic pear push button 28Call/cancel push button 29Cancel push button 29Cancel push button 30Touch-sensitive push button 30Backbox for touch-sensitive push button 30

Master station 32Databus connection unit 33Duty selection module 33Duty room unit 33Display module, speech module 34

Mounting frames for cover plates 36Standard plate 36Radio unit 37Programme selection switch 37Flush mounting backbox 38Cavity wall backbox 38Surface mounting socket 38Additional fastening for top-hat rail mounting 39Light bulb 39

Part numbers 41

27 TVR

PROG

LICHT

ACKERMANN clino opt 99

DUTY

CALLHNO 312 A

BATH/WCSTA. BATH

CALLHNO 355 B

AW 1DUTY

Page 6: Nurse call system

4

System description clino opt 99

Nurse call systemclino opt 99

GeneralAckermann´s nurse call system “clino opt 99” conforms to the currently valid standardsand conditions for call systems, DIN VDE 0834 part 1 and 2 : 2000-04 “clino opt 99” is ideally suited to hospitals, nursing homes, residences for handicappedpersons, rehabilitation clinics or sanatoria.

System overviewThe nurse call system “clino opt 99” combines intelligent network users with interactive datacommunication. The system is able to handle up to 16 zone controllers, each of whichcan be subdivided into 3 zones.

Up to 127 patient rooms (electronic modules) can be controlled via the corridor databusof the zone controller. It should be noted that other direct users, such as interface unitsor electronic modules with direction lamps, are treated like patient rooms. Up to 255active units, such as electronic modules, display modules or call modules can be used foreach zone. Each active unit represents a network user for the system and can be iden-tified by means of an 8-digit alpha-numeric text.

System characteristicsA distinguishing feature of the system “clino opt 99” is its quick and easy installation. Itis based on modular technology. The electronic modules can be replaced without enter-ing the patient’s room.

Calls and presences can be displayed in any room, e.g. in the duty and patient’s roomand can also be answered from there with the appropriate equipment. Additionally, anurse call guide system can be installed by using direction lamps. The system isequipped with two presence circuits. By activating a presence push button the call fromthe room concerned is cancelled, the call transfer is activated and the emergency call pre-pared. Calls from other rooms can then be audibly indicated in this room and displayedby using a display module. Calls from other zones can be displayed by means of zoneindicator lamps and display modules. Any zone linking occurs by means of an additionalduty selection module.

System structure“clino opt 99” system is an integrated system based on a controller unit, electronic mod-ules and room equipment.

The wiring consists of the corridor databus and the room databus (ZB-A, ZB-B), where-by the room databus is a twisted pair. A 6-core cable is required for supplying power, thespeech and data lines, where as 4-core cable is sufficient for systems without a two-wayspeech facility. A suitable cable must be used, taking into account the provision of powerin conjunction with the length of the cable as well as the number of modules connected.

The electronic modules which are mounted outside the rooms also serve as distributionpoints for the room wiring and as sockets for the printed circuit boards. The power issupplied by a 24V/DC power supply.

Page 7: Nurse call system

5

System description clino opt 99

Zone controllerThe zone controller is the central control unit which monitors and synchronizes thecomplete databus and at the same time represents a higher-level connection to furtherzone controllers. It controls the flashing phases of the room and zone signal lamps, aswell as the acoustic call signals. In this way doctor, emergency, normal, remind and tele-phone calls can be distinguished. Each zone controller supports 3 sub-groups and thushas appropriate outputs for zone indicator lamps, telephone lamps as well as a commonmalfunction message system. Further inputs allow staff, dinner and telephone calls to becoupled.

Electronic moduleThe electronics required for call identification as well as the logging of calls are to befound in the electronic module, which is used as the distribution point for the room wiring.

Electronic modules with integrated corridor lamp can be used for the whole system.Configuration data is stored in the electronic module’s memory module and is, thereby,still available if the electronic module is replaced. For duty rooms, special electronic mod-ules with additional memory for configured zone linking data are used.

Room equipmentVarious devices can be installed in the rooms, for example, call modules, call push but-tons, pear push buttons and pull cords for making calls, as well as cancel push buttonsfor cancelling calls. Patient handsets are also an option. In addition to their call function,these also enable patients to listen to radio.

The information in the nurse call system can be shown on display modules. Calls areindicated according to their urgency. If there are no calls in the system, then presencesare indicated. Use of additional speech modules enables queued calls to be addressed.Calls which have been addressed can be cancelled by remote control. Emergency callscannot be cancelled by remote control.

In the corridors, calls are visually indicated as text on the information displays and opti-cally indicated by the corridor lamps. The following call types are shown.

Type of call As per Visual signalsDIN VDE 0834-1 :2000-04

– Patient calls:normal call nurse call (abbr: call) permanent light – red – bathroom/WC call WC call permanent light – red –

(optional: and permanent light- white -)

Priority call (no information) flashing light - red -

– Staff calls:emergency call emergency call flashing light – red –

permanent light – green – and/or – yellow –

doctor call alarm call quickly flashing light – red –,permanent light – green – and/or – yellow –

bathroom/WC (no information) flashing light – red –emergency call (optional: and flashing light -

white -), permanent light - green – and/or – yellow –

– Further calls:diagnostic call diagnostic call flashing light – red –remind call (no information) flashing light – green –telephone call telephone call permanent light telephone

lamp – white –fault fault permanent light - red -

Page 8: Nurse call system

6

System description clino opt 99

Calls to the zone signal lamps or equipment with information displays (when connected)are recognisable throughout the zones.

In addition to the visual signals, acoustic signals are also sent to all rooms in which presences are set. The nurse call system divides the calls into three categories: catego-ry 1 comprises of normal and bathroom/WC calls; category 2 consists of emergency,diagnostic and priority calls, as well as bathroom/WC emergency calls; alarm calls, e.g.doctor calls, belong to category 3. Acoustically-transmitted calls are identified by meansof different call rhythms.

CouplingThe “clino opt 99” Nurse Call System can be connected to the “clino call” paging sys-tem via the paging interface unit. This transfers existing calls on the nurse call system tothe pocket pager of staff via the paging system, indicating type of call, room number andpossibly bed identification.

Additionally, internal signals, such as fire alarms or technical alarms, can be connectedvia interface units.

It is possible to connect the system to an Instabus EIB (European InstaBus).

SafetyIn the case of power failure, calls are stored for approximately 24 hours. As soon as thepower is switched on again, presences and calls which were set prior to power failureare indicated.

In the case of failure of the zone controller, the system operates in an emergency mode,which involves the functions normal and emergency calls, cancellation, presence indica-tion and call transfer to rooms where presence has been set, as well as the visual indi-cation of the corridor lamps.

The zone controller monitors all active units and displays any malfunctions as a collectivemessage or as individual messages on the information display.

The lamp outputs of the electronic modules are short-circuit protected. All electronicmodules are fitted with a “self-healing” fuse. This not only protects the electronic mod-ules but also the equipment in the room.

An auto-release plug mounted on the pear or multiple push button as well as on thepatient handset prevents damage to the cord. The electrical safety and EMV require-ments of all the system components are in accordance with the CE directives.

The IP protection classes indicated in the catalogue refer to the completely assembledappliance including cover plate and mounting frames.

Maintenance and serviceThe configuration module is connected via a service socket to the electronic module.This is used to address rooms and, where appropiate, individual beds. In addition, the configuration module can also be used for service purposes.

A zone controller can be exchanged without any problem. It gains access to the data stored in the active units and configures itself. Only particular special parameters have tobe entered again.

The electronic modules can be exchanged at any time without interrupting the operationof the system and, by standard installations, can be installed or exchanged within theentire system.

Page 9: Nurse call system
Page 10: Nurse call system

8

Central devices

Order No.

TOP OBEN

72640 Z1

1 2

TOP OBEN

72641 Z1

1 2

Zone controllerfor operating up to 127 rooms with a maximum of three sub-groups. The zone controller monitors and controls the data com-munication within the zone and provides for data transferbetween zone controllers. In the case of a power failure, calls andpresences are stored for 24 hours.

Dimensions: H = 182 mm, W = 110 mm, D = 34 mmInstallation: surface mounting or top-hat rail mounting Colour: white RAL 9016Protection: IP 40

Zone controller without audio 72640 A2appropriate connection board 72640 Z1Zone controller with audio 72640 B2appropriate connection board 72640 Z2

Additional equipment:fastening for top-hat rail mounting (page 39) 88899 A

Configuration modulefor easy and quick setting up of the room identification and systemparameters. The values are picked off from the documents orfrom printed room number lists by means of a barcode readingdevice. The configuration module leads the user through the dif-ferent menus via the 2x8 digit LC-Display.

Dimensions: H = 345 mm, W = 235 mm, D = 55 mm

Configuration module English 72649 AAother languages on request

Interface unitfor connection of the clino opt 99 system to an existing clino opt 90nurse call system or other alarm systems equipped with dry con-tacts.

Dimensions: H = 182 mm, W = 110 mm, D = 34 mmInstallation: surface mounting or top-hat rail mountingColour: white RAL 9016Protection: IP 40

Interface unit 72641 A2appropriate connection board 72641 Z1

Additional equipment:fastening for top-hat rail mounting (page 39) 88899 A

Page 11: Nurse call system

9

Central devices

Order No.

TOP OBEN

72643 Z1

1 2

TOP OBEN

72643 Z1

1 2

TOP OBEN

72643 Z1

1 2

Paging interface unit to connect the clino opt 99 system to a paging system. Datatransmission can be carried out via either an RS 422 or an RS232C (serial interface).

Dimensions: H = 182 mm, W = 110 mm, D = 34 mmInstallation: surface mounting or top-hat rail mounting Colour: white RAL 9016Protection: IP 40

Paging interface unit for connection to clino call HL 72643 C1appropriate connection board 72643 Z1

Connection to other paging systems on request

Additional equipment:fastening for top-hat rail mounting (page 39) 88899 A

Printer interface for connection of the clino opt 99 system to a printer. Data transmission can be carried out via either an RS 422 or an RS 232C (serial interface).

Dimensions: H = 182 mm, B = 110 mm, D = 34 mmInstallation: surface mounting or top-hat rail mounting Colour: white RAL 9016Protection: IP 40

Printer interface for connection to a printer 72643 I1appropriate connection board 72643 Z1

Additional equipment:fastening for top-hat rail mounting (page 39) 88899 A

PC interfacefor connection of the clino opt 99 system to a PC for call logging.Data transmission can be carried out via either an RS 422 or anRS 232C (serial interface).

Dimensions: H = 182 mm, W = 110 mm, D = 34 mmInstallation: surface mounting or top-hat rail mounting Colour: white RAL 9016Protection: IP 40

PC interface 72643 H1appropriate connection board 72643 Z1

Additional equipment:fastening for top-hat rail mounting (page 39) 88899 A

Page 12: Nurse call system

10

Central devices

Order No.

Protective cover and mounting kitfor wall mounting of power supplies outside a sub-distribution.Including top-hat rail.

Colour: grey RAL 7035

Protective cover and mounting kit

- for 5 A power supply 89954 MA

- for 10 A power supply 89954 MB

- for 20 A power supply 89954 MC

Power supplyfor a constant DC supply to nurse call systems. Compact designthanks to modern primary-clocked circuit technology according toEN 61000-3-2; suitable for top-hat rail assembly in the sub-distri-bution or also outside the sub-distribution by means of the mount-ing kit. The supply units are idling, overload and short-circuitproof.For uninterruptible power supply according to DIN 19240 at 24 Vsee UPS module.

Temperature range and protection classes:– Temperature range: 0 to +60 °C, with free convection

cooling– Protection class: IP 20– Protective low voltage SELV (according to EN 60950,

VDE 0100 part 410)PELV (according to VDE 0160)

– Protection Class 1 (IEC 536)

Single-phase power supply 5A 89954 M1Nominal output voltage: 24 V DC +5% -1%Output current: 5 AInput voltage: 85 - 132 VA / 176 - 264 VA

115/230 ± 15% VACreversible

Dimensions: W = 65 mm, H = 125 mm, D = 103 mm

Single-phase power supply 10A 89954 R2Nominal output voltage: adjustable 24 up to 28 V DCOutput current: 10 AInput voltage: 85 - 132 VA / 176 - 264 VA

115/230 ± 15% VACreversible

Dimensions: W = 122 mm, H = 125 mm, D = 103 mm

Single-phase power supply 20A 89954 R3Nominal output voltage: adjustable 24 up to 28 V DC Output current: 20 AInput voltage: 85 - 132 VA / 176 - 264 VA

230 ± 15% VACDimensions: W = 227 mm, H = 125 mm, D = 103 mm

Page 13: Nurse call system

UPS module 24 Vfor uninterruptible power supply according to DIN 19240, com-patible with power supplies on Page 10, consisting of controlelectronics for top-hat rail assembly and separate modular,extendable battery pack for wall mounting.

Nominal input voltage: 24 V DCInput voltage range: 22.5 ... 30 V DCOutput voltage when battery-driven: typ. 26.5 ... 19.5 V DCCharging time for discharged batteries to 90%: approx. 14 hrsBattery voltage thresholdSwitching threshold for pre-warming of battery switch-off: typ. 21.5 VSwitching threshold for total discharge protection: typ. 19.5 VProtection: IP20

Cooling: free air convectionAllowable ambient temperature: 0 ... + 50 °CStorage temperature: - 20 ... + 55 °CUPS module weight: 2.5 kgUPS module fastening: terminal for top-hat rail assemblyUPS module connection: screw terminalsBattery connection: screw terminals

UPS module 24 V5.0 A DC Nominal output current 89954 C6

Battery capacity: external battery 7 AhBattery life (by 80% load @ 20 °C): approx. 60 minutesCharging current: typ. 0.2 ... 0.5 A switchable in 5 incrementsBattery fuse internal: T 5 A (5 x 20 mm)Charging fuse internal: T 2 A (5 x 20 mm)UPS module dimensions W x H x D: 70 x 126 x 128.5 mmBattery weight: 5.6 kgBattery dimensions W x H x D: 180 x 159 x 110 mmBattery mounting (dimensions): wall mounting (235 x 131 mm)

UPS module 24 V10.0 A DC Nominal output current 89954 C7

Battery capacity: external battery 15 AhBattery life (by 70% load @ 20 °C): approx. 60 minutesCharging current: typ. 0.5 ... 1 A switchable in 5 incrementsBattery fuse internal: T 10 A (5 x 20 mm)Charging fuse internal: T 4 A (5 x 20 mm)UPS module dimensions W x H x D: 70 x 141 x 151 mmBattery weight: 12.7 kgBattery dimensions W x H x D: 250 x 159 x 175 mmBattery mounting (dimensions): wall mounting (235 x 131 mm)

UPS module 24 V20.0 A DC Nominal output current 89954 C8

Battery capacity: external battery 24 AhBattery life (by 60% load @ 20 °C): approx. 60 minutesCharging current: typ. 0.7 ... 2 A switchable in 5 incrementsBattery fuse internal: T 20 A (5 x 20 mm) FKHCharging fuse internal: T 4 A (5 x 20 mm)UPS module dimensions W x H x D: 86 x 220 x 160 mmBattery weight: 5.6 kgBattery dimensions W x H x D: 405 x 178 x 135 mmBattery mounting (dimensions): wall mounting (386 x 140 mm)

11

Central devices

Order No.

Page 14: Nurse call system

Central devices

Order No.

12

UPS module 230 Vfor uninterrupted power supply to the server and operating computer in clino systems.

Technical data:Output power: 700 VA / 490 Watts Output voltage: 230 V AC ± 2 %; 50/60 Hz ± 0.1 %Output current: 3.0 ASupply time: by 100 % load - 10 minutesInput voltage: 230 V AC, 50/60 HzInput current: 3.5 AAmbient conditions:- Temperature: 0 °C - 40 ° C- Relative humidity: 0 - 95 % non-condensingTypes:

UPS module 230 Vfreestanding model 7608903

Dimensions: W = 140 mm, H = 190 mm, D = 440 mmWeight: 12.5 kg

UPS module 230 V19“- mounting 76089 ACDimensions: 2 HU, D = 390 mmWeight: 16.4 kg

Page 15: Nurse call system
Page 16: Nurse call system

Electronic module for patient roomsThe electronic module is the central control unit for the patientroom; it is available with or without bed databus. In the case ofelectronic modules without bed databus, passive call push but-tons are used. Electronic modules with bed databus enable theadditional connection of active units. At the same time the elec-tronic module is used as a corridor lamp. As active units, a displaymodule, a speech module and up to eight call modules can beconnected via the bed databus. The active units can beaddressed with an eight-digit alpha-numeric text. Room identifica-tion and bed identification are defined during commissioning usingthe configuration module. All electronic modules are equipped withcall and cancel circuits for passive circuits.

Call circuits:– doctor call– diagnostic call– bathroom/WC call– patient call as normal call or as emergency call

when presence is set.

Cancel circuits:– presence – green –, for the cancellation of all calls and

presence 1;– presence – yellow –, for the cancellation of all calls and

presence 2;– separate bathroom/WC cancellation for bathroom/WC

calls in case of appropriate configuration

Dimensions: W = 158 mm, D = 87 mm, H = 110 mmInstallation: surface mountingColour: white lamp coverProtection: IP 20

Electronic module for patient roomswith corridor lamp (including lamps)without bed databus- without presence 2 72570 C2- with presence 2 72570 D2appropriate connection board, grey RAL 7040 72570 Z1appropriate connection board, white RAL 9016 72570 Z2

Electronic module for patient roomswith corridor lamp (including lamps)with bed databus and audio- without presence 2 72571 C2- with presence 2 72571 D2appropriate connection board, grey RAL 7040 72571 Z1appropriate connection board, white RAL 9016 72571 Z2

Electronic module for patient roomswith corridor lamp (including lamps)with bed databus and Radio, audio- without presence 2 72572 C2- with presence 2 72572 D2appropriate connection board, grey RAL 7040 72572 Z1appropriate connection board, white RAL 9016 72572 Z2

Electronic module for patient roomswithout corridor lamp, cover plate white Ral 9016:without bed databus, with presence 2 72570 A2appropriate connection board, white RAL 9016 72570 Z2

Electronic module for patient roomswithout corridor lamp, cover plate white Ral 9016:with bed databus, audio and presence 2 72571 A2 appropriate connection board, white RAL 9016 72571 Z2

Accessories:Protective hood for electronic module 89870 E1Name plate holder for electronic module 88886 A

Corridor

Order No.

14

Page 17: Nurse call system

Corridor

Order No.

15

2-way direction lampindicates visually the highest priority calls from the selected sec-tion of a zone. The calls on the direction lamp are displayed withdifferent call cycles: the normal call by a steady light and theemergency call by a flashing light.

Dimensions: W =158 mm, D = 87 mm, H = 110 mmInstallation: surface mountingColour: white lamp coverProtection: IP 20

2-way direction lamp (including lamps)direction lamp right/left 72574 C2appropriate connection board, grey RAL 7040 72574 Z1appropriate connection board, white RAL 9016 72574 Z2

Direction lamp with arrowindicates visually the highest priority calls on the direction lampfrom the selected section of a zone. The calls on the directionlamp are displayed with different call cycles: the normal call by asteady light and the emergency call by a flashing light.

Dimensions: W = 158 mm, D = 87 mm, H = 110 mmInstallation: surface mountingColour: white lamp coverProtection: IP 20

Direction lamp with arrow (including lamps):– direction lamp left 72574 A2– direction lamp right 72574 B2

appropriate connection board, grey RAL 7040 72574 Z1appropriate connection board, white RAL 9016 72574 Z2

Electronic module for duty roomswith additional functions to the electronic module for the patientroom. These include the acknowledgement of calls and the pos-sibility of connection to a duty selection module. It is also possibleto regulate the sound level of the buzzer, e.g. for night duty. It isused together with the duty room selection module to link zones.

Dimensions: W = 158 mm, D = 87 mm, H = 110 mmInstallation: surface mountingColour: white lamp coverProtection: IP 20Electronic module for duty roomswith corridor lamp (including lamps)with bed databus– electronic module without presence 2 72573 C2– electronic module with presence 2 72573 D2

appropriate connection board, grey RAL 7040 72571 Z1appropriate connection board, white RAL 9016 72571 Z2

Electronic module for duty roomswithout corridor lamp, cover plate white Ral 9016 72573 A2

appropriate connection board, white RAL 9016 72571 Z2

Page 18: Nurse call system

Corridor

Order No.

16

Information Display with red LEDs for luminescent, alpha-numerical display, with cleartext and integrated buzzer.

Functions when connected to system:– call indication according to configuration– indication of call type: doctor call, diagnostic call,

emergency call, bathroom/WC-emergency call,– enhanced call, bathroom/WC call, normal call (nurse call)– indication of the time in combination with clock module or PC– audible call transfer via buzzer if configured

Calls are displayed in the following order:– The calls are displayed according to their priority (in the order:

alarm call, emergency call, call). If more than one call of a par-ticular type exists, these are displayed in rotation, the displaychanging every 5 seconds.

Display: 8-digit LED-display

Material: surface mounted aluminium housing, white RAL 9010

Dimensions:– for wall mounting: L = 750 mm, H = 103 mm, D = 35 mm– for ceiling mounting: L = 750 mm, H = 103 mm, D = 100 mm

Information Display– single for wall mounting 74652 A2– double-sided for ceiling mounting 74653 A2

Ceiling mounting set for information display complete with cover and suspension kit for ceiling mounting of thedouble-sided information display unit.

Quantity: 2 piecesMaterial: steel (varnished)Colour: white RAL 9010Dimensions: ø = 13 mm

Ceiling mounting set L = 300 mm 89603 B1Ceiling mounting set L = 600 mm 89603 B2

Page 19: Nurse call system

Corridor

Order No.

17

Zone indicator lampsame design as corridor lamp, with one lamp section for eachlamp cover.

Dimensions: W = 158 mm, D = 87 mm, H = 110 mm each lamp cover

Installation: surface mountingColour: plastic base grey RAL 7040, with white lamp coverProtection: IP 20

Zone indicator lamp (including lamps)

- 1 lamp cover with the number 1 72515 A2- 2 lamp covers with the numbers 1 and 2 72515 B2- 3 lamp covers with the numbers 1 to 3 72515 C2- 4 lamp covers with the numbers 1 to 4 72515 D2

Zone indicator lampsame design as corridor lamp, with two lamp sections for eachlamp cover.

Dimensions: W = 158 mm, D = 87 mm, H = 110 mm each lamp cover

Installation: surface mountingColour: plastic base grey RAL 7040, with white lamp coverProtection: IP 20

Zone indicator lamp (including lamps)

1 lamp cover with the numbers 1 and 2 72515 A32 lamp covers with the numbers 1 to 4 72515 B33 lamp covers with the numbers 1 to 6 72515 C34 lamp covers with the numbers 1 to 8 72515 D3

Zone indicator lampsame design as corridor lamp, with one lamp section for eachlamp cover.

Dimensions: W = 158 mm, D = 87 mm, H = 110 mm each lamp cover

Installation: surface mountingColour: plastic base grey RAL 7040, with white lamp coverProtection: IP 20

Zone indicator lamp (including lamps):

- 1 neutral lamp cover 72515 A1- 2 neutral lamp covers 72515 B1- 3 neutral lamp covers 72515 C1- 4 neutral lamp covers 72515 D1

Page 20: Nurse call system

Corridor

Order No.

18

Corridor lampparallel display for the electronic module.

Dimensions: W = 158 mm, D = 87 mm, H = 110 mmInstallation: surface mountingColour: white lamp coverProtection: IP 20

Corridor lamp (including lamps):with 3 lamp sections (white, red, green) 72569 C

appropriate connection board, grey RAL 7040 72569 Z1appropriate connection board, white RAL 9016 72569 Z3

Corridor lamp (including lamps):with 4 lamp sections (white, red, green, yellow) 72569 Dappropriate connection board, grey RAL 7040 72569 Z2appropriate connection board, white RAL 9016 72569 Z4

Corridor lampin LED technology to connect to an electronic module without lamp.

Colour: white RAL 9016Dimensions 81 mm x 81 mm Installation: in flush box, DIN 49073Protection: IP 40

Type (including cover plate and frame):

Corridor lampwith LEDs red, green 72555 B1

Corridor lampwith LEDs red, white, green 72555 C1

Databus terminator and splitterterminates the corridor databus with the appropriate impedanceand enables branching and stub cable on the corridor databus.

Dimensions: 71 mm x 71 mm Installation: in flush box, DIN 49073Protection: IP 40

Databus terminator and splitter including connection terminals 72642 B

Additional equipment:suitable cover plate, white RAL 9016 88910 A3

suitable mounting frame (page 36)

Page 21: Nurse call system
Page 22: Nurse call system

Patient’s room

Order No.

20

Display module with call/cancel push buttonfor connection to the electronic modules with bed databus.forpatient and duty room Includes integrated call and cancel pushbutton. In case of set presence,existing calls are acoustically indi-cated and visually displayed.

Equipped with:– 2x8-digit alpha-numeric LCD with back light– call push button– cancel push button– buzzer– appropriate connection terminals

Installation: in flush box, DIN 49073Colour: white RAL 9016Protection: IP 40

Display module with call/cancel push button 74910 C2

Additional equipment: suitable mounting frame (page 36)

Speech moduleenables intercom within the clino opt 99 system. Connected tothe electronic module with bed databus, the existing calls or pres-ences which are displayed can be answered. A speech push but-ton makes it possible to start and release a conversation and adual speech push button controls the speech direction.

Equipped with:– microphone, loudspeaker, answering push button, push button

for speech direction

Dimensions: H = 140 mm, W = 69 mm, D = 25 mmInstallation: surface mounting in combination with

2 flush boxes fastening with claws or screwsColour: white RAL 9016Protection: IP 40

Speech module 74912 A4

Additional equipment: appropriate connection terminals 74912 Z1suitable mounting frame (page 36)

Call module for connection to the electronic module with bed databus. As anactive unit the call module can be addressed with an 8-digit alphanumerical text as bed identification. Released calls can then bedisplayed by means of this bed identification.

Equipped with:– 1 LED orientation/reassurance lamp – red –– appropriate connection terminals– push button

Dimensions: 71 mm x 71 mmInstallation: in flush box, DIN 49073Protection: IP 40

Call module with call push button 73071 F2

Additional equipment:cover plate white RAL 9016 with 1 call push button – red – 88881 K3suitable mounting frame (page 36)

Page 23: Nurse call system

Patient’s room

Order No.

21

Call module with push button and socketfor connection to the electronic module with bed databus. As anactive unit the call module can be identified with an 8-digit alphanumeric text as bed identification. Calls can then be displayed bymeans of this bed identification.

Equipped with:– 1 LED orientation/reassurance lamp – red –– 1 7-pole socket with call-circuit monitoring– appropriate connection terminals– push button

Dimensions: 71 mm x 71 mm Installation: in flush box, DIN 49073Protection: IP 40

Call module with push button and socket 73071 E2

Additional equipment:cover plate white RAL 9016 with 1 push button – red – 88881 L3suitable mounting frame (page 36)

Call module with push button and socketsfor connection to the electronic module with bed databus. As anactive unit the call module can be identified with an 8-digit alphanumeric text as bed identification. Released calls can then be dis-played by means of this bed identification.

Equipped with:– 1 LED orientation/reassurance lamp – red –– 1 7-pole socket with call-circuit monitoring– 1 6-pole socket for diagnostic equipment with call-circuit monitoring– appropiate connection terminals– push button

Dimensions: 71 mm x 71 mmInstallation: in flush box, DIN 49073Protection: IP 40

Call module with push button and sockets 73071 D2

Additional equipment:cover plate white RAL 9016 88881 J3suitable mounting frame (page 36)

Page 24: Nurse call system

Patient’s room

27 TVR

PROG

LICHT

Order No.

22

Patient handset Functions*:– nurse call

– call release

– radio and TV– “on“ switch and selection of 8 radio programmes– “on“ switch and selection of TV programmes – display of the selected programme on LED display– push buttons for volume control

– others– digital bi-directional data transmission via highly flexible

connecting cable to the wall interface electronics – plug-in system, auto-releasing depending on the mechanical

load**– automatic call release by pulling of the plug from the auto-

release plug system – “on“ switch for reading light– “on“ switch for room light

Equipped with:– 1 loudspeaker, possibly receiver capsule – 1 call push button with orientation light– 1 LED reassurance light – red –– 2 light push buttons– 1 function selector (see below)– 2 programme push buttons ( and )– 2 volume push buttons (+ and –)– 1 3.5 mm jack socket for connection of headphones– 2 m connection cable with auto-release plug

Colour: white RAL 9016Material: PC + ABS-FR

Patient handset- with function selector radio/TV 74130 A1- with function selector radio/external connection 74130 B1

Additional equipment:hook for patient handset 74131 A1

* The necessary connection to the nurse call system and the transmission of data, conversations and radio programmes occur via the wall interface electronics.

** In relation with wall interface electronic 73072 A2 or 73072 B2.

Page 25: Nurse call system

Patient’s room

Order No.

23

Wall interface electronic for patient handset.

Functions:– selection of radio and TV channels – transmission of data and radio programmes to and from

the patient handset/electronic module

Equipped with:– 1 call push button with LED orientation/reassurance lamp – red –– 1 7-pole socket for connection of a pear push button

or multiple push button– 1 6-pole socket for connection of diagnostic equipment– 1 auto-release plug system for auto-release plug

Colour: white RAL 9016Material: PC + ABS-FRDimensions of the surface housing:

H = 182 mm, W = 110 mm, D = 33 mm

Wall interface electronic– for surface mounting 73072 A2– for bedhead trunking unit 73072 B2

Additional equipment:

Housing base unitsuitable for surface mounting of wall electronic type 73072 A2 – for flush mounting 88950 A– for cavity wall mounting 88950 B

Frame for flush or cavity wall mounting 88956 BMaterial: insulating materialColour: white RAL 9016

Headphonesfor patient handset and radio unit with volume control.

Equipped with:1 adjustable clip2 ear protection sponges for headphones3 m connection cable1 jack plug (3.5 mm)

Impedance: 32 OhmMaximum capacity: 0.1 WInput: 0.05 WTransmission range: 40 Hz – 15 kHzWeight: 61 g

Headphones 89760 B

Page 26: Nurse call system

Patient’s room

Order No.

24

Call push buttonfor normally open and normally closed circuits.

Equipped with:– 1 LED orientation/reassurance lamp – red –– 1 push button

Dimensions: 71 mm x 71 mmInstallation: in flush box, DIN 49073Protection: IP 40

Call push button 73022 A2

Additional equipment:cover plate white RAL 9016 with 1 call push button – red – 88881 G3

suitable mounting frame (page 36)

Call push button for doctor callfor normally open and normally closed circuits.

Equipped with:– 1 LED orientation/reassurance lamp – red –– 1 push button

Dimensions: 71 mm x 71 mmInstallation: in flush box, DIN 49073Protection: IP 40

Call push button for doctor call 73022 A2

Additional equipment:cover plate white RAL 9016 with 1 doctor call push button – blue – 88881 D3

suitable mounting frame (page 36)

Call push button with socketfor normally closed circuits.

Equipped with:– 1 LED orientation/reassurance lamp – red –– 1 7-pole socket with call-circuit monitoring– 1 push button

Dimensions: 71 mm x 71 mmInstallation: in flush box, DIN 49073Protection: IP 40

Call push button with socket 73075 A

Additional equipment:cover plate white RAL 9016 with 1 call push button – red – 88881 L3

suitable mounting frame (page 36)

Page 27: Nurse call system

Patient’s room

Order No.

25

Call push button with socketsfor normally closed circuits.

Equipped with:– 1 LED orientation/reassurance lamp - red -– 1 7-pole socket with call-circuit monitoring – 1 6-pole diagnostic socket with call-circuit monitoring– 1 push button

Dimensions: 71 mm x 71 mmInstallation: in flush box, DIN 49073Protection: IP 40

Call push button with sockets 73075 B

Additional equipment:cover plate white RAL 9016 with 1 push button - red - 88881 J3

suitable mounting frame (page 36)

Pull cordfor normally closed circuitswith call-circuit monitoring.

Equipped with:– 2 m PVC cord with red handle– 1 LED reassurance lamp – red –

Dimensions: 71 mm x 71 mmInstallation: in flush box, DIN 49073Protection: IP 54

Pull cord 70045 A3

Additional equipment:cover plate white RAL 9016 88880 A3

suitable mounting frame (page 36)

Pneumatic call push buttonfor normally closed circuitswith call-circuit monitoring.

Equipped with:– 2 m insulating plastic tube and rubber ball– 1 reassurance lamp – red –

Dimensions: 71 mm x 71 mmInstallation: in flush box, DIN 49073Protection: IP 54

Pneumatic call push button 70006 B

Additional equipment:cover plate white RAL 9016 88880 C3

suitable mounting frame (page 36)

Page 28: Nurse call system

Patient’s room

Order No.

26

Call unit with diagnostic sockets

for normally closed circuits.

Equipped with:– 2 6-pole diagnostic sockets with call-circuit monitoring

Dimensions: 71 mm x 71 mmInstallation: in flush box, DIN 49073Protection: IP 40

Call unit with diagnostic sockets 73075 C

Additional equipment:cover plate white RAL 9016 88912 D3suitable mounting frame (page 36)

Page 29: Nurse call system

Patient’s room

Order No.

27

Pear push buttonfor call-circuit monitoring,with 7-pole plug or auto-release plug, 2 m connection cable2

and drop wire for variable looping and strain relief.

Equipped with:– 1 call push button – red – with nursing staff symbol– 1 LED reassurance lamp – red –

Dimensions: W = 40 mm, L = 110 mm, D = 18 mmColour: white RAL 9016

Pear push buttonfor call-circuit monitoring with:– 7-pole plug 74141 A1– auto-release plug1, 3 74141 A3- auto-release plug A-coded4 74141 A4

1 In connection with wall electronic system or auto-release plug system, page 28.2 Other lengths on request

Multiple push buttonfor call-circuit monitoring,with 7-pole plug or auto-release plug, 2 m connection cable2

and drop wire for variable looping and strain relief.

Equipped with:– 1 call push button – red – with nursing staff symbol– 1 LED reassurance lamp – red –– 1 light push button – yellow –

Dimensions: W = 40 mm, L = 110 mm, D = 18 mmColour: white RAL 9016

Multiple push buttonfor call-circuit monitoring with:

– 1 light push button - yellow - 7-pole plug 74151 A1– 1 light push button - yellow -auto-release plug, A-coded1, 4 74151 A4

– 2 light push buttons - yellow - 7-pole plug 74153 A1– 2 light push buttons - yellow - auto-release plug, A-coded1, 4 74153 A4

3 4

1 In connection with wall electronic system or auto-release plug system, page 28.2 Other lengths on request

Page 30: Nurse call system

Patient’s room

RUFZEIT PEGELRUF

TEST

ACKERMANNTEST

Order No.

28

Auto-release plug system - A-codedfor connection of pear push button or multiple push button withauto-release plug, suitable for flush mounting combination boxesand backboxes with 60 mm screw fixing centre.

Dimensions: 71 mm x 71 mmInstallation: in flush box, DIN 49073Protection: IP 40

Auto-release plug system -A-coded 74189 A

Additional equipment:cover plate white RAL 9016 88910 N3suitable mounting frame (page 36)

Noise level sensorfor normally open and normally closed circuitswith adjustable noise detection and time delay facility.

Equipped with:– 1 microphone– 1 call push button – red – – 1 push button for call interlock in order to test the noise wave– 2 LED control lights– 2 m connection cable with 7-pole diode plug

Dimensions: 155 mm x 95 mm, D = 38 mmColour: black RAL 9011

Noise level sensor 73300 B7(English version)

Pneumatic pear push buttonfor call-circuit monitoring,with 7-pole connection plug.

Colour: white

Equipped with:– 2 m insulating plastic tube with rubber ball and retaining clip

Pneumatic pear push button 70007 A

Page 31: Nurse call system

Patient’s room

Order No.

29

Cancel push button, presence 2

for normally open and normally closed circuits.

Equipped with:– 1 LED remind lamp – yellow –– 1 buzzer for call transfer

Dimensions: 71 mm x 71 mmInstallation: in flush box, DIN 49073Protection: IP 40

Cancel push button, presence 2 73642 D

Additional equipment:cover plate white RAL 9016 with 1 cancel push button – yellow – 88881 M3suitable mounting frame (page 36)

Call/cancel push button

for normally open and normally closed circuits.

Equipped with:– 1 LED remind lamp – green –– 1 buzzer for call transfer– 1 LED orientation/reassurance lamp – red –

Dimensions: 71 mm x 71 mmInstallation: in flush box, DIN 49073Protection: IP 40

Call/cancel push button 73642 B2

Additional equipment:cover plate white RAL 9016 with1 call push button – red –, 1 cancel push button – green – 88882 A3suitable mounting frame (page 36)

Cancel push button, presence 1

for normally open and normally closed circuits.

Equipped with:– 1 LED remind lamp – green –– 1 buzzer for call transfer

Dimensions: 71 mm x 71 mmInstallation: in flush box, DIN 49073Protection: IP 40

Cancel push button, presence 1 73642 C

Additional equipment:cover plate white RAL 9016 with 1 cancel push button – green – 88881 H3suitable mounting frame (page 36)

Page 32: Nurse call system

Patient’s room

Order No.

30

Touch-sensitive push buttonfor normally open and normally closed circuits,

with 4 mm VA cover plate, Ø 70 mm.

Touch-sensitive push button with call sensor and LED orientation/reassurance lamp - red - 71185 E2

Touch-sensitive push button with cancel sensor and LED remind lamp - green - 71185 D2

Backbox for touch-sensitive push buttonfor flush mounting of touch-sensitive call push button, with backand side entry.

Equipped with:– 1 metal spacer for plaster tolerance– 1 dust cover– 1 gasket– 1 anchor plate

Material: steel, galvanized and chromatized

Backbox for touch-sensitive push button 89450 B

Cancel push buttonfor normally open and normally closed circuits.

Equipped with:– 2 LED remind lamps – green and yellow –– 1 buzzer for call transfer

Dimensions: 71 mm x 71 mmInstallation: in flush box, DIN 49073Protection: IP 40

Cancel push button 73642 E

Additional equipment:cover plate white RAL 9016 with2 cancel push buttons – green and yellow – 88882 B3suitable mounting frame (page 36)

Page 33: Nurse call system
Page 34: Nurse call system

Duty room

ACKERMANN clino opt 99

DUTY

CALLHNO 312 A

BATH/WCSTA. BATH

CALLHNO 355 B

AW 1DUTY

Order No.

32

Master station centralized display unit with optional speech facility.

Dimensions: L = 200 mm, W = 228 mm, H = 65 mm Colour: white RAL 9016Material: ABS, base anodized aluminiumProtection: IP 20

Structure: desktop unit with 2 m connection cable and 8-pole plug

Functions:– call and status identification with following indications:

zone, patient room, bed, normal call (nurse call), bathroom/WC calls, emergency call, bathroom/WC emergency call, diagnosticcall, doctor call, answered call in remind mode, presence 1, presence 2, malfunction, other calls, conversation, plug release call

– call activation– doctor call activation (types "74420 B1" and "74421 B1")– call reminder function and call cancellation

(types "74421 A1" and "74421 B1")– selection of zone linking– call answering– nurse-to-nurse communication– nurse/patient two-way speech– simultaneous display of several calls and presences– general address call to all rooms and zones– general address call to presence 1 and/or presence 2– function activation (e.g., call answering, zone linking)

by just touching the display screen – menu index and free allocation of function push buttons

( e.g., day/night switching)

Equipped with:– 1 loudspeaker – 1 microphone – 1 call push button – red – with LED reassurance lamp – 1 doctor call push button – blue – with LED reassurance lamp

(types "74420 B1" and "74421 B1")– 2 presence push buttons – green and yellow –

with LED remind lamps– 1 push button “answer/off“ – white – with speech indication lamp– 1 push button for speech direction – brown –– 1 buzzer for call transfer – 1 lit graphic LC display with touch-sensitive surface

(touch screen)

Master station – Desktop unit without speech facility:

without doctor call push button 74420 A1with doctor call push button 74420 B1

– Desktop unit with speech facility:without doctor call push button 74421 A1with doctor call push button 74421 B1

Page 35: Nurse call system

Duty room

Order No.

33

Duty selection modulefor connection to electronic module for duty room. With inte-grated push button for selection and activation of zone linking.

Installation: in flush box, DIN 49073Colour: white RAL 9016Protection: IP 40

Equipped with:– 2 white push buttons– suitable connection terminal

Duty selection module 74911 B3

Additional equipment: suitable mounting frame (page 36)

Duty room unitfor connection to electronic module for duty room with acknow-ledgement option for queued calls.

Dimensions: 71 mm x 71 mmInstallation: in flush box, DIN 49073Colour: white RAL 9016Protection: IP 40

Equipped with:– 2 LED remind lamp – green – and – red –– 1 buzzer for call transfer

Duty room unit 73642 B

Additional equipment:cover plate white RAL 9016 with 1 presence push button 88882 CA– green – and 1 acknowledge push button – white –

(English version)suitable mounting frame (page 36)

Databus connection unitfor connecting master station to electronic module duty room.

Dimensions: 71 mm x 71 mmInstallation: in flush box, DIN 49073 Protection: IP 40

Equipped with:– 1 8-pole data plug

databus connection unit 73070 A

Additional equipment:cover plate white RAL 9016 88911 J3suitable mounting frame (page 36)

Page 36: Nurse call system

Duty room

Order No.

34

Speech moduleenables intercom within the clino opt 99 system. Connected tothe electronic module with bed databus, the existing calls or pres-ences which are displayed can be answered. A speech push but-ton makes it possible to start and release a conversation and adual speech push button controls the speech direction.

Dimensions: 140 mm x 69 mm, D = 25 mmInstallation: surface mounting in combination with 2 flush boxes

claw or screw fastening.Colour: white RAL 9016Protection: IP 40

Equipped with:– microphone, loudspeaker, answering push button,

push button for speech direction

Speech modul 74912 A4

Additional equipment: appropriate connection terminals 74912 Z1suitable mounting frame (page 36)

Display module with call/cancel push buttonfor connection to the electronic modules with bed databus for patient and duty room. Includes integrated call and cancel push button. In the case of set presence, existing calls are acoustically indicatedand are shown on the display.

Installation: in flush box, DIN 49073Colour: white RAL 9016Protection: IP 40

Equipped with:– 2x8-digit alpha-numeric LCD with back light– call push button– cancel push button– buzzer– appropriate connection terminals – 1 LED remind lamp - green -– 1 LED orientation/reassurance lamp - red -

Display module with call/cancel push button 74910 C2

Additional equipment: suitable mounting frame (page 36)

Page 37: Nurse call system
Page 38: Nurse call system

Additional equipment

Order No.

36

Standard plateas per DIN 49075, suitable for all frame types (see above).

Colour: white RAL 9016

Standard plate 88910 B3

Mounting frames for cover platesclino opt 99 design.

Colour: white RAL 9016

Mounting frames for cover plates

- Single (Dimensions: 81 mm x 81 mm) 88914 A3

- Double (Dimensions: 81 mm x 152 mm) 88914 B3

- Triple (Dimensions: 81 mm x 223 mm) 88914 C3

Page 39: Nurse call system

Additional equipment

Order No.

37

Radio unitwith volume control and connection to dynamic headphones(page 23).

Dimensions: 71 mm x 71 mmInstallation: in flush box, DIN 49073Protection: IP 20

Equipped with:– 1 volume control– 1 jack plug socket for the connection of dynamic headphones

Radio unit 73120 H

Additional equipment:cover plate white RAL 9016 88912 K3suitable mounting frame (page 36)

Programme selection switchwith mounting plate and expanding retaining clamps suitable for flush mounting in backboxes.

Dimensions: 71 mm x 71 mmInstallation: in flush box, DIN 49073Protection: IP 40

Equipped with:– 1 programme selection switch for 5 radio programmes

Programme selection switch 73120 A

Additional equipment:cover plate white RAL 9016 88912 H3suitable mounting frame (page 36)

Page 40: Nurse call system

Additional equipment

Order No.

38

Cavity wall backboxfor wood, plaster and other cavity walls.

Dimensions: Ø = 71 mm, D = 65 mmMaterial: thermoplastic, flame-retardantFixing centre: 60 mm

Cavity wall backbox 18971 B

Flush mounting backbox

as per DIN 49073, for expanding retaining clamps and screw fastening.

Dimensions: Ø = 58 mm, D = 40 mm

Flush mounting backbox 18971 A

Surface mounting socketDimensions: 81 mm x 81 mm, D = 20.2 mmColour: white RAL 9016

Surface mounting socketfor flush mounting units, stackable. 88915 A3

Dimensions: 85 mm x 156 mm, D = 20.1 mmColour: white RAL 9016

Surface mounting socketfor the speech module 74912 A4. 88915 C3

Page 41: Nurse call system

Additional equipment

Order No.

39

Light bulbfor electronic modules, zone indicator lamps and direction lamps.

24 V / 3.5 W

Light bulb- clear 88894 A- red 88894 B- green 88894 C- yellow 88894 D

Additional fastening for top-hat rail mounting

for:– Zone controller– Paging interface unit for connection to the paging system– Interface unit

Additional fastening for top-hat rail mounting 88899 A

Page 42: Nurse call system

40

Page 43: Nurse call system

Part Numbers

41

18971 A 3818971 B 38

70006 B 2570007 A 28

70045 A3 25

71185 D2 3071185 E2 30

72515 A1 1772515 A2 1772515 A3 1772515 B1 1772515 B2 1772515 B3 1772515 C1 1772515 C2 1772515 C3 1772515 D1 1772515 D2 1772515 D3 17

72555 B1 1872555 C1 18

72569 C 1872569 D 1872569 Z1 1872569 Z2 1872569 Z3 1872569 Z4 18

72570 A2 1472570 C2 1472570 D2 1472570 Z1 1472570 Z2 14

72571 A2 1472571 C2 1472571 D2 1472571 Z1 14, 1572571 Z2 14, 15

72572 C2 1472572 D2 1472572 Z1 1472572 Z2 14

72573 A2 1572573 C2 1572573 D2 15

72574 A2 1572574 B2 1572574 C2 1572574 Z1 1572574 Z2 15

72640 A2 8

72640 B2 872640 Z1 872640 Z2 8

72641 A2 872641 Z1 8

72642 B 18

72643 C1 972643 H1 972643 I1 972643 Z1 9

72649 AA 8

73022 A2 24

73070 A 33

73071 D2 2173071 E2 2173071 F2 20

73072 A2 2373072 B2 23

73075 A 2473075 B 2573075 C 26

73120 A 3773120 H 37

73300 B7 28

73642 B 3373642 B2 2973642 C 2973642 D 2973642 E 30

74130 A1 2274130 B1 22

74131 A1 22

74141 A1 2774141 A3 2774141 A4 27

74151 A1 2774151 A4 27

74153 A1 2774153 A4 27

74189 A 28

74420 A1 3274420 B1 3274421 A1 32

74421 B1 32

74652 A2 16

74653 A2 16

74910 C2 20, 34

74911 B3 33

74912 A4 20, 3474912 Z1 20, 34

76089 AC 12

7608903 12

88880 A3 2588880 C3 25

88881 D3 2488881 G3 2488881 H3 2988881 J3 21, 2588881 K3 2088881 L3 21, 2488881 M3 29

88882 A3 2988882 B3 3088882 CA 33

88886 A 14

88894 A 3988894 B 3988894 C 3988894 D 39

88899 A 8, 9, 39

88910 A3 1888910 B3 3688910 N3 28

88911 J3 33

88912 D3 2688912 H3 3788912 K3 37

88914 A3 3688914 B3 3688914 C3 36

88915 A3 3888915 C3 38

88950 A 2388950 B 23

88956 B 23

89450 B 30

89603 B1 1689603 B2 16

89760 B 23

89870 E1 14

89954 C6 1189954 C7 1189954 C8 1189954 M1 1089954 MA 1089954 MB 1089954 MC 1089954 R2 1089954 R3 10

Order No. Order No. Order No. Order No.Page Page Page Page

Page 44: Nurse call system

Albert Ackermann GmbH + Co. KGD-51641 Gummersbach

Telefon (0 22 61) 83–0 . Fax (0 22 61) 8 35 39www.ackermann.com

A member of Novar plc

24.1

GB

/ 0

503

/ 2000 /

aD

©

Ackerm

ann, G

um

mers

bach 2

003

Printe

d o

n e

nvironm

enta

lly friendly

paper

usin

g c

hlo

rine fre

e p

ulp

s.