NUCLEAR POWER CORPORATION OF INDIA LTD (A Government of India Enterprise) SPECIFICATION NO : PC-E-240/Rev. No. 1 TECHNICAL SPECIFICATION ON EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES REF: USI NO. : 60110 REVISION NO. : 0 1 DATE OF ISSUE : SEPT JUN (MONTH/YEAR) 2008 2010 TOTAL NO. OF PAGES : 26 24 (Including Cover Sheet) ORIGINAL PREPARED BY : DEEPAK KUMAR, EE Sd/- 19/09/08 CHECKED BY : S.PATRA, ACE Sd/- 19/09/08 REVIEWED BY : ASIS DAS, ACE Sd/- 25/09/08 APPROVED BY : V.K.MINHAS, ACE Sd/- 30/09/08 (Name & Designation) (Signature) (Date) (For Revisions See Revision Control Sheet) FILE NAME: PC-E-240-R1.DOC

Upload: others

Post on 17-Aug-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD

(A Government of India Enterprise)

SPECIFICATION NO : PC-E-240/Rev. No. 1

TECHNICAL SPECIFICATION

ON

EPR INSULATED LHLS SHEATHED

ARMOURED CONTROL CABLES

REF: USI NO. : 60110

REVISION NO. : 0 1

DATE OF ISSUE : SEPT JUN

(MONTH/YEAR) 2008 2010

TOTAL NO. OF PAGES : 26 24

(Including Cover Sheet)

ORIGINAL

PREPARED BY : DEEPAK KUMAR, EE Sd/- 19/09/08

CHECKED BY : S.PATRA, ACE Sd/- 19/09/08

REVIEWED BY : ASIS DAS, ACE Sd/- 25/09/08

APPROVED BY : V.K.MINHAS, ACE Sd/- 30/09/08

(Name & Designation) (Signature) (Date)

(For Revisions See Revision Control Sheet) FILE NAME: PC-E-240-R1.DOC

Page 2: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

REVISION CONTROL SHEET

DOCUMENT TYPE: TECHNICAL SPECIFICATION

NO: PC-E-240/Rev. No. 1

TITLE: TECHNICAL SPECIFICATION ON

EPR INSULATED LHLS SHEATHED

ARMOURED CONTROL CABLES

REV NO DESCRIPTION REVISED BY CHECKED REVIEWED APPROVED & DATE OF REVISION NAME & BY NAME & BY NAME & BY NAME &

SIGNATURE SIGNATURE SIGNATURE SIGNATURE

1 & Made applicable

17/06/10 for all 700MWe

PHWR projects

and misc. Deepak Kumar S.Patra Asis Das V.K.Minhas

changes.

Page 3: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON PAGE: 3 of 24 EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES REV NO. : 1

1.0 SCOPE

Manufacture, testing, delivery and guarantee of various sizes of annealed tinned copper conductor, Ethylene-Propylene Rubber (EPR) insulated and Low Halogen Low Smoke (LHLS) sheathed galvanised steel round wire armoured control cables generally conforming to IS-9968 (Part-1) and IS-6380 for two reactor units of 700 MWe PHWR project.

2.0 CONTENTS

Requirements of this specification are presented under the following section headings:

Description Section

Applicable standards 3

Materials & workmanship 4

General Function and Description 5

Design requirements 6

Inspection, Test and Reports 7

Shop Tests 8

Packing and Shipment 9

Information required with the bid 10

Colour codes required for the cores, inner & outer sheaths Annexure-A

Technical details require Annexure-B

Quality Assurance Plan (Sample) Annexure-C

3.0 APPLICABLE STANDARDS

3.1 IS-9968 (Part I): Specification for elastomer insulated cables for working voltage

upto and including 1100 volts.

3.2 IS: 6380: Specification for elastomeric insulation and sheath of electric cables.

3.3 ASTM-D-2843: Standard test method for density of smoke from the burning or

decomposition of plastics.

60110/PC-E-240 JUN 2010

Page 4: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON PAGE: 4 of 24 EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES REV NO. : 1

OR

3.4 IS-10810-63: Measurement of smoke density of electric cables under fire

conditions (supplier to indicate the acceptance criteria which is equivalent to ASTM-D-2843 vide section no.6.7 of specification.)

3.5 ASTM-D-2863: Standard method for measuring the minimum oxygen concentration to support candle like combustion of plastic (oxygen index and temperature index.)

OR

3.6 IS-10810-58: Oxygen Index tests.

3.7 IEC-754-1: Determination of the amount of halogen acid gas evolved during the

combustion of polymeric materials taken from cables.

OR

3.8 IS-10810-59: Determination of the amount of halogen acid gas evolved during

the combustion of polymeric materials taken from cables.

3.9 Swedish Svensk Standard-424-14-75 (Class F-3): Swedish Chimney Flame

Test

OR

3.10 IS-10810-61: Flame Retardant Test.

3.11 BS-6360 (or IS-8130): Specification for conductors for insulated electric cables

and flexible cords.

3.12 IS-3975: Specification for mild steel wires, strips, and tapes for armouring of

cables.

3.13 IS-10810: Methods of tests for cables.

3.14 NES 713: Determination of the toxicity index of the products of combustion from

small specimens of materials.

4.0 MATERIALS AND WORKMANSHIP

4.1 The materials and processes for the components of cables and their assembly shall

be chosen as specified here-in. Material should be thermoset. Use of any substitute materials shall be suitably qualified in terms of its electrical,

60110/PC-E-240 JUN 2010

Page 5: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON PAGE: 5 of 24 EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES REV NO. : 1

mechanical and physical properties and the details shall be submitted by supplier for purchaser’s approval. All the materials and processes which are not specified herein shall be chosen so as to enable the purchased product to meet the performance requirements of this specification. The construction of cable shall in general conform to IS-9968 (Part-1) and IS-6380. Vendor shall have proper machinery for steam vulcanization/ e-beam cross linking.

4.2 Workmanship

Workmanship shall be of high industrial quality to ensure the product to be uniform in quality and free from all defects and deformities so as to perform its required function in the specified environment as mentioned in this specification over an expected plant life of 40 years.

5.0 GENERAL FUNCTIONS AND DESCRIPTION

5.1 The cables shall be suitable for continuos and reliable operation at maximum conductor temperature of 90 C and voltage upto and including 300V for core to earth and 500 V for core to core.

5.2 Environment conditions

Normal operating conditions

Ambient temperature from 8ºC to 45ºC and relative humidity up to 90 %

Occasional/Storage conditions

Ambient temperature from 5ºC to 55ºC and relative humidity up to 95 %

6.0 DESIGN REQUIREMENTS

All materials used should be first class and of standard conforming to the requirements of this specification.

6.1 Conductor

Conductors shall be 1.5mm2 annealed tinned high conductivity coppers as per

BS-6360 or IS- 8130. Joints of any kind in the conductor are not allowed.

6.2 Insulation

Insulation shall be 900C, Ethylene-Propylene Rubber (EPR) (Type IE-2 of IS-

6380) and shall be meeting physical requirement of this standard. Grade of insulation shall be 500 V. No joints of any kind in the insulation are permitted.

60110/PC-E-240 JUN 2010

Page 6: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON PAGE: 6 of 24 EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES REV NO. : 1

Insulation shall be applied by extrusion process and curing by steam vulcanization / e-beam method. Insulation thickness shall be 0.65mm (nominal) 10%.

6.3 Colour Code

Cores of all cables shall be colour coded as per Annexure-A of this specification.

6.4 Inner Sheath

The individual cores shall be laid up as per IS-9968(Part-I) and then be surrounded by common covering of LHLS compound applied by extrusion process and curing by steam vulcanization / e-beam method. The sheath shall meet the applicable requirements specified in IS-6380 and it should also meet the

special requirements mentioned in section 6.7 of this specification. It should be possible to strip the sheath easily from the cores without damaging the insulation of the cores. Inner sheath shall be of black colour. Inner sheath thickness shall be

0.5mm (nominal) 20%.

6.5 Armouring

The armouring shall be arranged over the inner sheath. The armour shall consist of galvanized round steel wires. Armouring shall meet the dimensional requirements specified in IS: 9968 (Part-I) and physical requirements specified in IS: 3975. Diameter of armour wire shall be 0.90mm for 3 core armoured cables and 1.4mm for 4 core and 7 core armoured cables. Please note that 0.91mm dia armour wire is preferable for 3 core armoured cables.

6.6 Outer sheath

The outer sheath shall consist of LHLS compound with termite proof for use as a sheath on armour. The sheath shall meet the applicable requirements specified in IS:9968 (Part-I) and it shall also meet special requirements mentioned in section 6.7 of this specification. It should be possible to strip the sheath easily without damaging the insulation. Sheath shall be of black colour. Outer sheath shall be applied by extrusion process and curing by steam vulcanization / e-beam method. Thickness of outer sheath shall be 1.5mm (nominal) 20%.

6.7 Special Requirements for Inner & Outer Sheath Materials

6.7.1 Limiting oxygen index of inner and outer sheath shall not be less than 29% and

the temperature index shall be 2500C as per ASTM-D-2863 or IS-10810-58.

6.7.2 Smoke density rating of sheaths shall be maximum 20% as per ASTM-D-2843 or

smoke density test may be conducted as per IS-10810-63. Supplier to indicate the acceptance criteria which are equivalent to 20% smoke density as per ASTM-D-

60110/PC-E-240 JUN 2010

Page 7: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON PAGE: 7 of 24 EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES REV NO. : 1

2843 if the test is done as per IS-10810-63. Test shall be conducted for 12 minutes instead of 4 minutes as specified by the standard (4 minutes testing as mentioned in ASTM standard is for PVC plastics. Since elastomeric compound specified here, do not conform exactly to the standard, test shall be conducted for 12 minutes).

6.7.3 Halogen (HCL) emission of the sheaths shall be maximum 2% as per IEC: 754-1

or IS-10810-59.

6.7.4 Complete cable shall be flame retardant, and it shall pass Swedish Chimney flame

test as per Swedish Svensk standard 4224-14-75(class F-3) or IS-10810-61.

6.7.5 Toxicity Index shall not exceed 5 when tested as per NES 713.

6.7.6 Outer sheath shall be termite proof.

6.8 Construction detail of cables

6.8.1 1.5 Sq.mm 7 core cable

Each conductor shall be 1.5 Sq.mm solid annealed tinned copper insulated with EPR compound by extrusion process and curing by steam vulcanization / e-beam method. Each core shall be colour coded as per Annexure-A of this specification.

Individual cores shall be laid up and then LHLS compound applied by extrusion process and curing by steam vulcanization/ e-beam method as inner sheath of 0.5mm thickness. Then galvanized steel wire of 1.4mm dia armouring shall be provided and finally outer sheath of LHLS compound shall be applied by extrusion process and curing by steam vulcanization / e-beam method of thickness 1.5mm. Overall diameter shall not exceed 20mm.

6.8.2 1.5 Sq.mm 4 core cable

Same as 6.8.1 but 4 core and overall diameter not to exceed 18mm.

6.8.3 1.5 Sq.mm 3 core cable

Same as 6.8.1 but 3 core armouring with wire diameter of 0.90mm and overall diameter not to exceed 16mm.

6.9 Cable Identification

The following particulars shall be embossed on the cable outer sheath throughout the length of all the cables at a span of 1 meter.

a) Name of the manufacturer

60110/PC-E-240 JUN 2010

Page 8: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON PAGE: 8 of 24 EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES REV NO. : 1

b) Year of the manufacture.

c) LHLS ARMOURED

d) Voltage grade : 500 volts

e) Size of cable

It may be noted than embossing on the cable outer sheath is preferred to printing.

6.10 COIL LENGTHS

The cables shall be supplied in coil lengths of 500m 10% at least 90% of the total ordered quantity. Coil lengths of 100m to 449m are considered nonstandard lengths. Nonstandard lengths of only 10% of ordered quantity are acceptable. Lengths of less than 100m are not acceptable.

7.0 INSPECTION, TESTS & REPORTS

The Supplier shall be responsible for and shall perform all the tests and inspection as mentioned in this specification and any other tests which may be necessary to assess the required performance of the cable. The characteristic and performance of the cable shall conform to this specification on completion of tests.

The purchaser or his representative shall have right to access to manufacture’s premises at all reasonable times for following up the manufacturing activities and validation of testing procedures to ensure that quality of performance meets this specification.

The purchaser shall have right to conduct at his own expenses any additional inspection and testing deemed necessary by him.

Quality surveillance relating to all aspects of manufacture shall be carried out by the purchaser. The supplier shall provide all the testing and inspection services and facilities satisfactorily as required. Inspection shall be carried out in satisfactory manner and shall be subjected to approval by the purchaser. A sample Quality Assurance Plan (QAP) has been enclosed with the specification. The supplier shall prepare an inspection plan based on enclosed sample QAP and submit to purchaser for approval.

Three copies of test reports and certificates of compliance stating the material is in accordance with the requirement specified in the specification shall be furnished by the supplier.

60110/PC-E-240 JUN 2010

Page 9: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON PAGE: 9 of 24 EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES REV NO. : 1

8.0 SHOP TESTS

The following tests shall be carried out.

8.1 Type Tests Applicable Standard

8.1.1 Annealing test for copper IS-8130

8.1.2 Conductor Resistance Test IS-8130

8.1.3 Measurement of diameter of conductor IS-8130

8.1.4 Persulphate Test for copper (Conductor) IS-8130

8.1.5 Test for armour wires

8.1.5.1 Tensile test IS-3975

8.1.5.2 Torsion test IS-3975

8.1.5.3 Zinc coating test IS-3975

8.1.5.4 Elongation Test Torsion test IS-10810-37

8.1.6 Tests for thickness of Insulation and sheaths IS-10810-6

8.1.7 Tensile test on Insulation and Sheath IS-6380

8.1.8 Elongation test on insulation and sheath IS-6380 & BS-6899

8.1.9 Hot set test on insulation and sheath IS-6380

8.1.10 Accelerated ageing test on insulation and sheath IS-6380

8.1.11 Measurement of overall diameter IS-5608

8.1.12 Insulation Resistance Test IS-6380

8.1.13 High Voltage Test At 1.5 KV as per

IS-9968(Part-I)

8.1.14 Oxygen Index & Temperature Index tests on sheaths ASTM-D-2843/

IS-10810-58

8.1.15 Smoke density rating test on Sheaths ASTM-D-2843/

IS-10810-63 with

test duration as per

section no. 6.7 of spec.

60110/PC-E-240 JUN 2010

Page 10: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON PAGE : 10 of 24 EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES REV NO. : 1

(Supplier to indicate the acceptance criteria

which is equivalent to ASTM-D-2843 vide

section no.6.7 of spec. if test is done as per

IS-10810-63)

8.1.16 HCL Emission Test on sheaths IEC-754-1/IS-10810-59

8.1.17 Swedish Chimney Flame Test SS-424-14-75(F-3)/

IS-10810-61

8.1.18 Toxicity index Test on sheaths NES713(Applicable

for same lot. If lot

changes than test is to

be repeated)

8.1.19 Termite proof test on outer sheath Supplier’s specification

8.2 Acceptance tests

The following acceptance tests shall be carried out on samples taken from the lot of each type of cable. The total number of drums of each type of cable offered at a time shall be treated as lot size. The sample size for the acceptance test shall be as per Appendix-A of IS-1554-Part-I

8.2.1 Annealing test for copper IS-8130

8.2.2 Conductor Resistance Test IS-8130

8.2.3 Measurement of diameter of Conductor IS-8130

8.2.4 Test for thickness of Insulation and sheaths IS-10810-6

8.2.5 Insulation resistance test IS-6380

8.2.6 High Voltage test At 1.5 KV as per

IS-9968 (Part-I)

8.2.7 Oxygen Index &Temperature Index test on sheaths ASTM-D-2863/

IS-10810-58

8.2.8 Smoke density rating test on sheaths ASTM-D-2843/

IS-10810-63 with test duration as per

section no. 6.5 of this spec.

60110/PC-E-240 JUN 2010

Page 11: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON PAGE: 11 of 24 EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES REV NO. : 1

(Supplier to indicate the acceptance criteria

which is equivalent to ASTM-D-2843 vide

section no.6.7 of spec. if test is done as

perIS-10810-63)

8.2.9 HCL Emission Test on sheaths IEC-754-1/IS-10810-59

8.2.10 Swedish Chimney Flame Test SS-424-14-75(F-3)/

IS-10810-61

8.2.11 Termite proof test on outer sheath Supplier’s specification

8.3 Routine Tests

8.3.1 Conductor resistance test IS-8130

8.3.2 Insulation resistance test IS-6380

8.3.3 High voltage test at 1.5 KV as per

IS-9968 (Part-I)

9.0 PACKING AND SHIPMENT

The cables shall be so packed as not to suffer deterioration, damage or breakage during shipment. The ends of the cables shall be sealed to prevent ingress of moisture. Packing should be such that the ingress of moisture, dirt and other foreign material can be avoided. Packing method shall be adequate to withstand a period in transit for more that two months and storage at site under a tropical climate for minimum period of one year without suffering any damage or deterioration. Each package shall be properly labeled to indicate the type and

quantity of material it contains, purchase order number, dimensions, weight, and any other necessary data to identify the equipment and relate it to the contract.

Contractor shall not ship the material without the prior approval of the purchaser or his authorised representative and subsequent instruction to do so.

Complete instructions relation to shipping and documentation will be furnished with the P.O.

10.0 INFORMATION REQUIRED WITH THE BID

The supplier should give the technical details of the cables as per the format given in Annexure-B.

60110/PC-E-240 JUN 2010

Page 12: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON PAGE: 12 of 24 EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES REV NO. : 1

ANNEXURE-A

COLOUR CODES REQUIRED FOR THE CORES,

INNER SHEATH & OUTER SHEATH OF THE ARMOURED CABLES

1.0 COLOUR CODE OF THE CABLES

1.1 3 Core Black Blue Orange

1.2 4 Core Black

Blue

Orange

Green

1.3 7 Core Black-1

Black-2

Black-3

Black-4

Black-5

Black-6

Black-7

1.4 Colour Code for inner and outer sheath

For all the cables inner and outer sheath colour shall be “black”.

60110/PC-E-240 JUN 2010

Page 13: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON PAGE: 13 of 24 EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES REV NO. : 1

ANNEXURE-B

TECHNICAL DETAILS REQUIRE

1.0 COMPLETE CABLE

1.1 Make

1.2 Type reference

1.3 Minimum bending / Radius

1.4 Weight of Cable (Kg/Km)

1.5 Voltage Grade

1.6 Continuous working temperature

1.7 Max. overall diameter of cable (mm)

1.8 Coil lengths offered

1.9 Construction details of the cable

1.10 Confirm whether Cable can pass Swedish test Chimney as

per Swedish standard 424-14-75 (class F-3)

2.0 CONDUCTOR MATERIAL

2.1 Nominal Conductor resistance per km at 200C

2.2 Conductor diameter

2.3 Conductor material

2.4 Conductor material tinned copper as per IS-8130?

3.0 INSULATION

3.1 Insulation resistance at 200C

3.2 Insulation Material

3.3 Insulation wall thickness mm

60110/PC-E-240 JUN 2010

Page 14: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON PAGE: 14 of 24 EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES REV NO. : 1

4.0 ARMOURING

4.1 Material used for Armouring

4.2 Diameter of the galvanized armouring wire

5.0 SHEATH (INNER & OUTER)

5.1 Sheath material (Inner & Outer)

5.2 Nominal Sheath wall thickness (Inner)

5.3 Nominal sheath wall thickness (outer)

5.4 Colour of the Inner & Outer Sheaths

5.5 Oxygen Index as per ASTM-D-2863

5.6 Smoke density rating as per ASTM-D-2843

with test duration as per section no. 6.5 of this spec.

5.7 Halogen (HCL) emission as per IEC-754-1

5.8 Toxicity Index as per NES 713

5.9 Termite proof test of outer sheath as per supplier’s spec.

6.0 DEVIATIONS

6.1 Deviations from the Specification

6.2 Any deviation in test procedure from the specification.

6.3 Any deviation in cable offered.

7.0 COLOUR CODE

Whether colour code is followed as per Annexure A of our specification.

8.0 PROOF OF CAPABILITY

a) The bidder shall submit a list of similar supplies made by him to standards

and tolerances specified in this tender document.

60110/PC-E-240 JUN 2010

Page 15: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON PAGE: 15 of 24 EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES REV NO. : 1

b) The bidder shall submit alongwith the offer, a list of inhouse test facilities

available with them for carrying out all tests specified in specification PP-E-1147.

c) Bidder shall submit along with the offer descriptive and illustrative literature

covering construction and materials used for the cables offered.

d) The vendor information form enclosed shall be filled and submitted along

with the bid.

9.0 INFORMATION REQUIRED AFTER AWARD OF CONTRACT

Five (5) copies of History Docket in hard form and soft form shall be furnished. History Docket shall be made as per PRD-PROC-19. A sample History Docket shall be submitted to the purchaser for clearance. Once purchaser clears the same, 5 copies of History Docket shall be submitted in hard form and soft form.

60110/PC-E-240 JUN 2010

Page 16: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES PAGE : 16 of 24

REV. NO. : 1

ANNEXURE-C QUALITY ASSURANCE PLAN FOR EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES (SAMPLE)

Sl. Component Characteristic Class TYPE OF QUANTUM OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS No and Operations CHECK CHECK DOCUMENT NORMS OF (10)

RECORDS P W V (1) (2) (3) (4) (5) (6) (7) (8) (9) (11)

1.0 RAW

MATERIALS

1.1 CONDUCTOR The conductor shall

1.1.1 Copper Surface finish B Visual Random sample be smooth & free The conductor shall be T.C. 2 2 1 conductor from scratches & smooth & free from

burns scratches & burns

Diameter B Physical One sample NPCIL Spec. & IS- NPCIL Spec. & IS- -do- 2 2 1

from lot of 10 8130 8130

Conductor C Electrical bobbins/Baskets “ -do- 2 2 1

Resistance at /Drums or part --do--

20 deg.C there of

Annealing test C Physical “ “ “ -do- 2 2 1 (Cu)

Tinning test of C Chemical “ “ “ -do- 2 2 1

Cu wire

1.2 INSULATION

EPR Type of C Visual Each lot Should be free from Should be free from T.C. 2 2 1

Compound Compound foreign particles & foreign particles &

(TYPE IE-2) IS-6380 IS-6380

Tensile C Physical One sample per IS-10810 Part 7 & IS-6380 -do- 2 2 1 strength & Batch of 10 MT IS-6380

Elongation or part there of

PREPARED BY CHECKED BY REVIEWED BY APPROVED BY

(DEEPAK KUMAR) (S.PATRA) (ASIS D AS) (V.K.MINHAS)

60110/PC-E-240 JUN 2010

Page 17: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES PAGE: 17 of 24

REV. NO. : 1

ANNEXURE-C QUALITY ASSURANCE PLAN FOR EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES (SAMPLE)

Sl. Component Characteristic Class TYPE OF QUANTUM OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS No and Operations CHECK CHECK DOCUMENT NORMS OF (10)

(5) RECORDS P W V (1) (2) (3) (4) (6) (7) (8) (9) (11)

1.3 Armouring Diameter of B Physical Each lot NPCIL Spec. NPCIL Spec. T.C. 2 2 1

wires wire

Tensile strength B Physical “ IS-3975 IS-3975 -do- 2 2 1 Torsion test B Physical “ IS-3975 IS-3975 -do- 2 2 1 Zinc coating B Chemical “ IS-3975 IS-3975 -do- 2 2 1 Elongation test B Physical “ IS-10810-37 IS-10810-37 -do- 2 2 1

1.4 INNER & Visual Check of A Visual

OUTER material Each lot one Should be free from Should be free -do- 2 2 1 SHEATH Type of C Visual sample per batch foreign particles from foreign

compound of 10MT or part IS-6380 particles IS-6380

LHLS thereof

( Type- SE3) Tensile strength C Physical “ IS-6380 & BS-6899 IS-6380&BS-6899 -do- 2 2 1 & Elongation

Oxygen index C Physical “ ASTM-D-2863/IS- NPCIL Spec. -do- 2 2 1 10810-58 Smoke density C Physical “ ASTM-D-2843/IS- “ -do- 2 2 1 10810/63

HCL emission C Chemical “ IEC-754-1/IS- “ -do- 2 2 1 10810/59

Toxicity Index C Chemical “ NES 713 “ -do- 2 2 1 Termite proof C Chemical “ Supplier Supplier -do- 2 2 1 specification. specification.

PREPARED BY CHECKED BY REVIEWED BY APPROVED BY

(DEEPAK KUMAR) (S.PATRA) (ASIS DAS) (V.K.MIN HAS)

60110/PC-E-240 JUN 2010

Page 18: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES PAGE: 18 of 24

REV. NO. : 1

ANNEXURE-C

QUALITY ASSURANCE PLAN FOR EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES (SAMPLE)

Sl. Component Characteristic Class TYPE OF QUANTUM REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS No and Operations CHECK OF CHECK DOCUMENT NORMS OF (10)

RECORDS P W V (11) (1) (2) (3) (4) (5) (6) (7) (8) (9)

2.0 PROCESS

INSPECTION

2.1 Insulation Type of insulation B Physical Each setting & Approved Data Sheet Approved Data T.C. 2 2 1

Compound once in a shift & NPCIL spec. Sheet and NPCIL Spec.

Dimensions/Dia. B Physical -do- “ -do- 2 2 1

over conductor

Dimensions/Dia. B Physical “ “ -do- 2 2 1 over core

Thickness of C Physical “ “ -do- 2 2 1 insulation (Avg. &

Min)

Spark Testing Electrical 100% IS-9968 IS-9968 -do- 2 2 1

Surface Finish Visual Each Setting Smooth and free Smooth and free -do- 2 2 1 “ from porosity from porosity

Colour Visual NPCIL Specification NPCIL -do- 2 2 1

Specification

PREPARED BY CHECKED BY REVIEWED BY APPROVED BY

(DEEPAK KUMAR) (S.PATRA) (ASIS DAS) (V.K.MINHAS)

60110/PC-E-240 JUN 2010

Page 19: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD

TECHNICAL SPECIFICATION ON EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES PAGE : 19 of 24

REV. NO. : 1

ANNEXURE-C QUALITY ASSURANCE PLAN FOR EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES (SAMPLE)

Sl. Component Characteristic Class TYPE OF QUANTUM REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS No and Operations CHECK OF CHECK DOCUMENT NORMS OF (10)

RECORDS (11)

(1) (2) (3) (4) (5) (6) (7) (8) (9) P W V

2.2 Core Sequence of Cores C Visual Each setting & Approved data sheet Approved data sheet T.C. 2 2 1

twice in a shift & NPCIL Spec

Colour code C Physical -do- -do- -do- -do- 2 2 1

2.2.1 Laying up Direction of lay C Visual -do- -do- Approved data sheet -do- 2 2 1

Diameter over B Physical -do Approved data Sheet Approved data sheet -do- 2 2 1

laidup

2.3 Armouring Direction of lay A Visual -do- IS-9968-1 IS-9968-1 -do- 2 2 1

Diameter A Visual -do- Approved data sheet Approved data sheet -do- 2 2 1

armouring & NPCIL spec.

PREPARED BY CHECKED BY REVIEWED BY APPROVED BY

(DEEPAK KUMAR) (S.PATRA) (ASIS DAS) (V.K.MINHAS)

60110/PC-E-240 JUN 2010

Page 20: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES PAGE: 20 of 24

REV. NO. : 1

ANNEXURE-C

QUALITY ASSURANCE PLAN FOR EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES (SAMPLE)

Sl. Component Characteristic Class TYPE OF QUANTUM REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS No and Operations CHECK OF CHECK DOCUMENT NORMS OF (10)

RECORDS P W V (11) (1) (2) (3) (4) (5) (6) (7) (8) (9)

2.4 LHLS Type of C Physical Each setting & IS-6380 IS-6380 -do- 2 2 1

Sheath Compound at random

(Type SE-3) Thickness C Physical Each setting & NPCIL Spec. NPCIL Spec. -do- 2 2 1 Average/ twice in a shift

minimum

Dia over inner/ B Physical -do- -do- -do- -do- 2 2 1 outer sheath

Colour B Visual During setting NPCIL Spec. Approved Data -do- 2 2 1

& running Sheet and NPCIL

Surface finish B Visual In each shift Surface shall be spec. -do- 2 2 1 smooth & free from Surface shall be

porosity smooth & free from

Embossing/ B -do- Each setting & Approved Data Sheet porosity -do- 2 2 1

Printing/ twice in a shift and NPCIL Spec. Approved Data Sequential Sheet and NPCIL

Marking on outer Spec.

sheath

PREPARED BY CHECKED BY REVIEWED BY APPROVED BY (DEEPAK KUMAR) (S.PATRA) (ASIS DAS) (V.K.MINHAS)

60110/PC-E-240 JUN 2010

Page 21: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES PAGE: 21 of 24

REV. NO. : 1

ANNEXURE-C

QUALITY ASSURANCE PLAN FOR EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES (SAMPLE)

Sl. Component Characteristic Class TYPE OF QUANTUM OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS No and Operations CHECK CHECK DOCUMENT NORMS OF (10)

(5) RECORDS P W V (1) (2) (3) (4) (6) (7) (8) (9) (11)

3.0 TYPE TESTS

ON FINISHED

CABLE 3.1 Annealing test for cu C Physical Random sample IS-8130 IS-8130 TR 2 1,2 1

3.2 Conductor resistance test C Electrical -do- IS-8130 IS-8130 -do- 2 1,2 1

3.3 Dia of conductor C Physical -do- NPCIL Spec. NPCIL Spec. -do- 2 1,2 1

3.4 Test for armouring C Physical -do- IS-9968-1 & IS- IS-9968-1 & IS-

3975 3975 3.5 Thickness of insulation C Physical -do- NPCIL Spec. NPCIL Spec. -do- 2 1,2 1

and sheath

3.6 Tensile & elongation on C Physical -do- IS-6380 IS-6380 -do- 2 1,2 1

insulation & sheath 3.7 Hot set test on sheaths C Physical -do- IS-6380 IS-6380 -do- 2 1,2 1

(Inner & Outer)

3.8 Dia. of finished cable C Physical -do- NPCIL Spec. NPCIL Spec. -do- 2 1,2 1

PREPARED BY CHECKED BY REVIEWED BY APPROVED BY (DEEPAK KUMAR) (S.PATRA) (ASIS DAS) (V.K.MINHAS)

60110/PC-E-240 JUN 2010

Page 22: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES PAGE: 22 of 24

REV. NO. : 1

ANNEXURE-C

QUALITY ASSURANCE PLAN FOR EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES (SAMPLE)

Sl. Component Characteristic Class TYPE OF QUANTUM OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS No and Operations CHECK CHECK DOCUMENT NORMS OF (10)

RECORDS P W V (1) (2) (3) (4) (5) (6) (7) (8) (9) (11)

TYPE TESTS

ON FINISHED

CABLE

3.9 IR test at 270C and at C Electrical Random sample IS-6380 IS-6380 -do- 2 1,2 1

max. rated temperature

3.10 H. V. Test C Electrical -do- IS-9968 Part I NPCIL Spec. -do- 2 1,2 1

3.11 Oxygen index on sheath C Physical -do- ASTM-D- NPCIL Spec. -do- 2 1,2 1

(Inner & Outer) 2863/IS- 10810/58

3.12 Temperature index on C Physical -do- ASTM-D- NPCIL Spec. -do- 2 1,2 1

sheath (Inner & Outer) 2863/IS-

10810/58 3.13 Smoke density on sheath C Physical -do- ASTM-D- NPCIL Spec. -do- 2 1,2 1

(Inner & Outer) 2843/IS-

10810-63

3.14 HCL emission on sheath C Physical -do- IEC-754-1/IS- NPCIL Spec. -do- 2 1,2 1 10810-59

3.15 Flame retardant test C Physical -do- SS 424-14-175 SS 424-14-175 -do- 2 1,2 1

Class F-3 / Class F-3/

IS10810-61 IS10810-61 3.16 Toxicity Index on sheath C Chemical -do- NES 713 NES 713 -do- 2 1,2 1

(Inner & Outer) 3.17 Termite Proof test on C Chemical -do- Supplier spec. Supplier spec. -do- 2 1,2 1

outer sheath

PREPARED BY CHECKED BY REVIEWED BY APPROVED BY (DEEPAK KUMAR) (S.PATRA) (ASIS DAS) (V.K.MINHAS)

60110/PC-E-240 JUN 2010

Page 23: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES PAGE: 23 of 24

REV. NO. : 1

ANNEXURE-C

QUALITY ASSURANCE PLAN FOR EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES (SAMPLE)

Sl. Component and Characteristic Class TYPE OF QUANTUM OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS No Operations CHECK CHECK DOCUMENT NORMS OF (10)

RECORDS P W V (1) (2) (3) (4) (5) (6) (7) (8) (9) (11)

4.0 ROUTINE

TESTS ON

FINISHED CABLE

4.1 Conductor resistance test C Electrical 100% IS-8130 IS-8130 TR 2 1,2 1

4.2 H. V. test C Electrical 100% IS-9968-1 NPCIL Spec. -do- 2 1,2 1

4.3 IR test C Electrical 100% IS-6380 IS-6380 -do- 2 1,2 1

5.0 ACCEPTANCE

TESTS ON

FINISHED

CABLE

5.1 Annealing test on cu C Physical Samples as per IS-8130 IS-8130 -do- 2 1,2 1

IS-9968 Part-I

5.2 O.D. of cable C Physical -do- NPCIL Spec. NPCIL Spec. -do- 2 1,2 1

5.3 Conductor resistance test C Electrical -do- IS-8130 IS-8130 -do- 2 1,2 1

5.4 H. V. test C Electrical -do- IS-9968-1 NPCIL Spec. -do- 2 1,2 1

5.5 Thickness of insulation C Physical -do- NPCIL Spec. NPCIL Spec. -do- 2 1,2 1 sheath

PREPARED BY CHECKED BY REVIEWED BY APPROVED BY

(DEEPAK KUMAR) (S.PATRA) (ASIS DAS) (V.K.MINHAS)

60110/PC-E-240 JUN 2010

Page 24: NUCLEAR POWER CORPORATION OF INDIA LTD (A ......3.4 IS-10810-63: Measurement of smoke density of electric cables under fire conditions (supplier to indicate the acceptance criteria

NUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES PAGE: 24 of 24

REV. NO. : 1

ANNEXURE-C

QUALITY ASSURANCE PLAN FOR EPR INSULATED LHLS SHEATHED ARMOURED CONTROL CABLES (SAMPLE)

Sl. Component and Characteristic Class TYPE OF QUANTUM REFERENCE ACCEPTANC FORMAT AGENCY REMARKS No Operations CHECK OF CHECK DOCUMENT E NORMS OF (10)

RECORDS P W V (1) (2) (3) (4) (5) (6) (7) (8) (9) (11)

ACCEPTANCE

TESTS ON

FINISHED

CABLE

5.6 IR at 270C C Electrical Samples as per IS-6380 IS-6380 TR 2 1,2 1

IS-9968 Part-I

5.7 Oxygen index in C Physical -do- ASTM-D-2863/ NPCIL Spec. TR 2 1,2 1

sheaths IS-10810-58

5.8 Temperature index C Physical -do- ASTM-D-2863/ NPCIL Spec. TR 2 1,2 1

on sheaths IS-10810-58 5.9 Smoke density on C Physical -do- ASTM-D-2843/ NPCIL Spec. TR 2 1,2 1

sheaths IS-10810-63

5.10 HCL emission on C Physical -do- IEC-754-1/IS-10810-59 NPCIL Spec. TR 2 1,2 1

sheaths 5.11 Flame retardant C Physical -do- SS-424-14-75 Class F3 SS-424-14-75 TR 2 1,2 1

test IS-10810-61 Class F3/

IS-10810-61

5.12 Termite proof test C Chemical -do- Supplier Spec. Supplier Spec. 2 1,2 1 on outer sheath

5.13 Embossing on the B Visual -do- NPCIL Spec. NPCIL Spec. TR 2 1,2 1

cable

LEGEND:

P : Performed by A : Minor 1 : Purchaser (NPCIL)

W : Witnessed by B : Major 2 : Prime Supplier

V : Verified by C : Critical 3 : External Laboratory

TC : Test Certificate

TR : Test Report

PREPARED BY CHECKED BY REVIEWED BY APPROVED BY (DEEPAK KUMAR) (S.PATRA) (ASIS DAS) (V.K.MINHAS)

60110/PC-E-240 JUN 2010