    Use of REHVA Guidebook

    Power Point Presentations

    This Power Point Presentation can be freely

    used for training purposes by REHVA members.It is prepared by the main author to the REHVAGuidebook.

    Please refer the original author always when

    making the presentation.Inform REHVA secretariat each time thepresentation is used: [email protected]

  • 8/10/2019 Nr 12 Solar Shading

    3/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    SolarShading

    by

    Wouter Beck (ed.),Dick Dolmans,

    Gonzague DutooAnders Hall

    Olli Seppnen

  • 8/10/2019 Nr 12 Solar Shading

    4/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    Task force Solar Shading

    started 2008

  • 8/10/2019 Nr 12 Solar Shading

    5/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    Table of Contents

    Terminology Solar radiation

    Effect of windows on indoor environment

    Window systems

    Energy effects of solar shading

    How to choose a shading solution

    Automating and integrating solar shading

    Existing buildings Double-skin facades

    Maintenance of solar shading systems

    Cases

  • 8/10/2019 Nr 12 Solar Shading

    6/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    Reviewers

    Prof. Jan Hensen, Eindhoven University of

    Technology, The Netherlands

    Prof. Mat Santamouris, University of

    Athens, Greece

    Herv Lamy, SNFPSA, Paris, France

    Prof. Michael G Hutchins, Sonnergy Ltd,

    Abingdon, UK

    Dr. Thanos Tzempelikos, Purdue

    University, West Lafayette, IN, USA

  • 8/10/2019 Nr 12 Solar Shading

    7/52Federation of European Heating, Ventilation and Air-conditioning Associations

    Solar radiation

  • 8/10/2019 Nr 12 Solar Shading

    8/52

  • 8/10/2019 Nr 12 Solar Shading

    9/52Federation of European Heating, Ventilation and Air-conditioning Associations

    Solar paths

  • 8/10/2019 Nr 12 Solar Shading

    10/52Federation of European Heating, Ventilation and Air-conditioning Associations

    Solar irradiance on a faade(lat. 50 N, clear sky)

  • 8/10/2019 Nr 12 Solar Shading

    11/52Federation of European Heating, Ventilation and Air-conditioning Associations

    Solar irradiance on a faade(lat. 50 N, clear sky)

  • 8/10/2019 Nr 12 Solar Shading

    12/52Federation of European Heating, Ventilation and Air-conditioning Associations

    Solar irradiance on a faade(lat. 50 N, clear sky)

  • 8/10/2019 Nr 12 Solar Shading

    13/52Federation of European Heating, Ventilation and Air-conditioning Associations

    Solar irradiance on a faade(lat. 50 N, clear sky)

  • 8/10/2019 Nr 12 Solar Shading

    14/52Federation of European Heating, Ventilation and Air-conditioning Associations

    Effect of windows on indoor environment

  • 8/10/2019 Nr 12 Solar Shading

    15/52Federation of European Heating, Ventilation and Air-conditioning Associations

    Effect of windows on indoor

    environment

    Thermal comfort

    Visual comfort

    Acoustic comfort

    Indoor air quality

    Daylighting Impact of productivity

  • 8/10/2019 Nr 12 Solar Shading

    16/52Federation of European Heating, Ventilation and Air-conditioning Associations

    Thermal comfort

    Air temperature

    Radiant temperature

    Operative temperature

    Relation to office

    worker productivity

  • 8/10/2019 Nr 12 Solar Shading

    17/52Federation of European Heating, Ventilation and Air-conditioning Associations

    Visual comfort

    Contact with the outdoors

    Absolute brightness

    Luminance ratios

    Color rendition

  • 8/10/2019 Nr 12 Solar Shading

    18/52Federation of European Heating, Ventilation and Air-conditioning Associations

    Effect of good visual comfort

    3.75% median productivity increase [CMU]

    20 to 25% less health complaints

    [Hartkopf]

    15% reduced absenteeism [Thayer]

    10 to 25% better performance on test of

    mental function

    20 to 26% faster progress of students

    [Heshong]

  • 8/10/2019 Nr 12 Solar Shading

    19/52Federation of European Heating, Ventilation and Air-conditioning Associations

    Predicting visual comfort

    Photo: Hunter Douglas

  • 8/10/2019 Nr 12 Solar Shading

    20/52Federation of European Heating, Ventilation and Air-conditioning Associations

    Predicting visual comfort

    Photo: Hunter Douglas

  • 8/10/2019 Nr 12 Solar Shading

    21/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    The economic impact of

    productivity

  • 8/10/2019 Nr 12 Solar Shading

    22/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    Window systems

  • 8/10/2019 Nr 12 Solar Shading

    23/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    Glazing properties

    Thermal transmittance U [W/m2K]

    Light transmittance Tv [-]

    g-value [-]

  • 8/10/2019 Nr 12 Solar Shading

    24/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    Energy flows

  • 8/10/2019 Nr 12 Solar Shading

    25/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    Convection loads

  • 8/10/2019 Nr 12 Solar Shading

    26/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    Cooling loads no shading

  • 8/10/2019 Nr 12 Solar Shading

    27/52

    Surface temperature interior

  • 8/10/2019 Nr 12 Solar Shading

    28/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    Surface temperature interior

    window pane under peak load

    conditions

    no shading

    Surface temperature interior

  • 8/10/2019 Nr 12 Solar Shading

    29/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    Surface temperature interior

    window pane under peak load

    conditions

    exterior shading

  • 8/10/2019 Nr 12 Solar Shading

    30/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    Influence of shading on

    lighting needs

    Daylight illuminance in a south oriented officeautomatic Venetian blind @ 200 W/m2

  • 8/10/2019 Nr 12 Solar Shading

    31/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    Energy effects

  • 8/10/2019 Nr 12 Solar Shading

    32/52

  • 8/10/2019 Nr 12 Solar Shading

    33/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    Standard office

    dimension 3.6 x 5 x 3 m

    ventilation 1.5 dm3/m2s

    infiltration 0.1 ACH

    daylight dependent lighting 500 lx

    max. internal load art. lighting 12 W/m2

    internal loads people 10 W/m2

    internal loads equipment 15 W/m2

    thermostat cooling 25/30 C (8-18/otherwise)

    thermostat heating 21/15 C (8-18/otherwise)

    shading set point 200 W/m2

  • 8/10/2019 Nr 12 Solar Shading

    34/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    Conversion to primary energy

  • 8/10/2019 Nr 12 Solar Shading

    35/52

  • 8/10/2019 Nr 12 Solar Shading

    36/52

  • 8/10/2019 Nr 12 Solar Shading

    37/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    Stockholm cooling load, low-

    e glazing, orientation: south

    no shading

    exterior shading

  • 8/10/2019 Nr 12 Solar Shading

    38/52

    Reduction in primary energy

  • 8/10/2019 Nr 12 Solar Shading

    39/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    std. double

    low-e

    solar ctrl

    Reduction in primary energy

    use for heating, cooling and

    lighting through shading

    C t b fit l i f l

  • 8/10/2019 Nr 12 Solar Shading

    40/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    Cost benefit analysis of solar

    shading

  • 8/10/2019 Nr 12 Solar Shading

    41/52

  • 8/10/2019 Nr 12 Solar Shading

    42/52

  • 8/10/2019 Nr 12 Solar Shading

    43/52

  • 8/10/2019 Nr 12 Solar Shading

    44/52

  • 8/10/2019 Nr 12 Solar Shading

    45/52

  • 8/10/2019 Nr 12 Solar Shading

    46/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    Central Plaza Brussels

    Photo: Hunter Douglas

  • 8/10/2019 Nr 12 Solar Shading

    47/52

  • 8/10/2019 Nr 12 Solar Shading

    48/52

  • 8/10/2019 Nr 12 Solar Shading

    49/52

  • 8/10/2019 Nr 12 Solar Shading

    50/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    Appendices

    EU standards concerning shuttersand blinds

    Specification example

    Matrix of responsibilities

  • 8/10/2019 Nr 12 Solar Shading

    51/52

    Federation of European Heating, Ventilation and Air-conditioning Associations

    Acknowledgements

    Ellen Kohl (Warema), Maaike Berckmoes (Scheldebouw-Permasteelisa),

    Risto Kosonen (Halton),

    Bernard Gilmont (European Aluminium Association), Maija Virta (Halton),

    Prof. Dirk Saelens (Catholic University of Leuven,

    Belgium

    Prof. Zoltan Magyar (University of Pcs, Hungary)