np v np submittal data v2 - phoenix energy supply...sd 1334-1335-1336-1334n-1335n-1336n rev....

4
. Submial Data Variable Speed Dual Circuit Non-pressurized Flow Center Project Name: Contractor: Engineer: Order Number: Addional Informaon: Technical Data Electrical Data Approved Anfreeze Mounng Pump Power Curves** Circulator: Cabinet: Tank: Insulaon: Valves: Grundfos Magna GEO* (variable spd.) and/or UPS26-99 (3 spd.) Powder coated galvanized steel Polyvinyl chloride (PVC) CFC-free polyurethane foam Quanty six 1”, 3-way, 4-posion flushing and isolaon/service valves. Four boom valves have composite body and spool; Top valves have brass body and spool. All valves ulize NBR seals and stainless steel retaining ring. Max. fluid temp.: 140°F [60°C] Min. fluid temp.: 20°F [-7°C] Max. operang press.: 13 psig [89.6 kPa] Max. ambient air temp.: 104°F [40°C] Propylene Glycol Methanol Ethanol Flow center is designed for indoor installaon only. Flow center must be installed in an upright posion as shown to the right. The pump terminal box must be located in one of the following orientaons: Motor: 208-230V, 60 Hz, single phase, 2-pole, UL and CSA approved, internal thermal overload protecon, insulaon class F GEO-FLO PRODUCTS CORPORATION 905 Williams Park Drive Bedford, IN 47421 U.S.A. PH: 812-275-8513; FAX: 812-275-8523 www.geo-flo.com SD 1334-1335-1336-1334N-1335N-1336N rev. 22SEP2015 NP Series Pump Motor Speed Nominal HP Volts Amps* Watts* Capacitor Pump Housing (Volute) Magna GEO Variable 1/6 208230 0.09 to 1.7 5 to 230 N/A Cast Iron High 0.9 196 Medium 0.8 179 Low 0.7 150 *All data is per pump at 230V 1/6 UPS2699 230 5μF/400V Cast Iron Power in Watts Flow Rate in GPM [l/s] [0.13 0.25 0.38 0.50 0.63 0.76 0.88 1.00 1.14 1.26 1.39 1.51 1.64 1.77 1.89 2.02 2.15 2.27] **Power is per pump. Page 1 of 4 Variable Speed Constant Speed *Available with standard or inverse profile PWM signal. Add “N” to part number for inverted profile (e.g. 1335N). Cable and/or controller required. Models NPDV 2A (1334 & 1334N), NPDV 2B (1335 & 1335N), NPDV 3 (1336 & 1336N)

Upload: others

Post on 07-Feb-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

  • .

    Submittal DataVariable Speed Dual Circuit Non-pressurized Flow Center

    Project Name:Contractor:Engineer:Order Number:Additional Information:

    Technical Data

    Electrical Data Approved Antifreeze

    Mounting

    Pump Power Curves**

    Circulator:Cabinet:Tank:Insulation:Valves:

    Grundfos Magna GEO* (variable spd.) and/or UPS26-99 (3 spd.)Powder coated galvanized steel Polyvinyl chloride (PVC)CFC-free polyurethane foamQuantity six 1”, 3-way, 4-position flushing and isolation/service valves. Four bottom valves have composite body and spool; Top valves have brass body and spool. All valves utilize NBR seals and stainless steel retaining ring.

    Max. fluid temp.: 140°F [60°C]Min. fluid temp.: 20°F [-7°C] Max. operating press.: 13 psig [89.6 kPa]Max. ambient air temp.: 104°F [40°C]

    Propylene GlycolMethanolEthanol

    Flow center is designed for indoor installation only.

    Flow center must be installed in an upright position as shown to the right.

    The pump terminal box must be located in one of the following orientations:

    Motor: 208-230V, 60 Hz, single phase, 2-pole, UL and CSA approved, internal thermal overload protection, insulation class F

    GEO-FLO PRODUCTS CORPORATION905 Williams Park DriveBedford, IN 47421 U.S.A.PH: 812-275-8513; FAX: 812-275-8523www.geo-flo.com

    SD 1334-1335-1336-1334N-1335N-1336N rev. 22SEP2015

    NP 1 NP 2 NP V NP V2 NP Series

    Pump  Motor Speed

    Nominal  HP Volts Amps* Watts* Capacitor

    Pump  Housing  (Volute)

    Magna  GEO Variable 1/6 208-‐230 0.09  to  1.7 5  to  230 N/A Cast  IronHigh 0.9 196

    Medium 0.8 179Low 0.7 150

    *All  data  is  per  pump  at  230V

    1/6UPS26-‐99 230 5μF/400V Cast  Iron

    Pow

    er in

    Wat

    ts

    Flow Rate in GPM [l/s]

    [0.13 0.25 0.38 0.50 0.63 0.76 0.88 1.00 1.14 1.26 1.39 1.51 1.64 1.77 1.89 2.02 2.15 2.27]

    **Power is per pump.Page 1 of 4

    Variable Speed

    Constant Speed

    *Available with standard or inverse profile PWM signal. Add “N” to part number for inverted profile (e.g. 1335N). Cable and/or controller required.

    Models NPDV2A (1334 & 1334N), NPDV2B (1335 & 1335N), NPDV3 (1336 & 1336N)

  • Pump Performance Curves

    Grundfos Pump Performance Curves: Magna GEO and UPS26-99(NPDV2: Magna GEO on LH side; UPS26-99 on RH side -- two pumps in parallel)

    Head

    (Fee

    t) [k

    Pa]

    Flow (U.S. GPM) [l/s]

    [30]

    [60]

    [90]

    [119]

    [15]

    [45]

    [75]

    [105]

    [149]

    [135]

    Curve when both pumps are operating

    Maximum Curve for Magna GEO

    [0.13 0.25 0.38 0.50 0.63 0.76 0.88 1.00 1.14 1.26 1.39 1.51 1.64 1.77 1.89 2.02 2.15 2.27]

    UPS26-99 HI NPDV-2 (L) GEO (R) 99

    2 6 10 14 18 22 26 30 34

    Grundfos Pump Performance Curves: Magna GEO Variable Speed(NPDV2: one pump on LH side; one pump on RH side -- two pumps in parallel)

    Head

    (Fee

    t) [k

    Pa]

    Flow (U.S. GPM) [l/s]

    [0.13 0.25 0.38 0.50 0.63 0.76 0.88 1.00 1.14 1.26 1.39 1.51 1.64 1.77 1.89 2.02 2.15 2.27]

    [30]

    [60]

    [90]

    [119]

    [15]

    [45]

    [75]

    [105]

    [149]

    [135]

    Magna GEO (Max)

    DESIGN NOTES:1. The dual circuit flow center includes a pump(s) for each heat pump. The pump(s) for unit A is in parallel with the pump(s) for

    unit B. If one side has two pumps (e.g. NDP3 or NDP4), the two pumps on each side are in series. Page 4 shows a transparent view of the flow center with internal piping.

    2. When sizing pumps for a dual circuit flow center, a pressure drop calculation should be done for the entire system when both heat pumps are running. Pump selection must be based upon both units running. For example, if the left side is a 3 ton heat pump with one pump, and the right side is a 2 ton heat pump with one pump; the pumps in parallel must be able to provide adequate flow and head when both units are running. Verify with online Calculators at www.geo-flo.com, or to manually select pumps, use the curves below, which include parallel operation.

    3. The internal check valves and 3-way valves must be added to the system pressure drop before selecting pumps. Page 3 includes a chart based upon the flow rate for each heat pump.

    4. All pump curves are manufacturer’s reported averages using water at 68°F [20°C].

    Page 2 of 4

    NPDV2AMagna GEO (L)UPS26-99 (R)

    NPDV2B - Magna GEO

    The NPDV2A (P/Ns 1334 & 1334N) flow center uses one pump on each side. The chart to the left provides curves for a Magna GEO (variable speed)* and a UPS26-99 (constant speed) pump operating in parallel. Use these curves to determine pump selection when both heat pumps are operating. Two non-identical pumps in parallel creates a curve that is the sum of the two curves (gray line). Internal check valves are factory-installed to prevent short circuiting.

    The NPDV2B (P/Ns 1335 & 1335N) flow center uses two Magna GEO (variable speed) pumps, one on each side. The chart to the left provides maximum* curves for these two pumps operating in paral-lel. Use these curves to determine pump selection when both heat pumps are operating. Two pumps in parallel provide twice the flow rate, but the head of only one pump. Internal check valves are factory-installed to prevent short circuiting.

    *Above curves for Magna GEO are maximum operating curves. The Magna GEO can operate between its minimum and maximum curves, depending upon flow rate and pressure drop requirements.

    SD 1334-1335-1336-1334N-1335N-1336N rev. 22SEP2015

  • [0.13 0.25 0.38 0.50 0.63 0.76 0.88 1.00 1.14 1.26 1.39 1.51 1.64 1.77 1.89 2.02 2.15 2.27]

    Magna GEO+UPS26-99Hi

    Head

    (Fee

    t) [k

    Pa]

    Flow (U.S. GPM) [l/s]

    Maximum Curve,Magna GEO+26-99H

    Maximum Curve for Magna GEO

    [30]

    [60]

    [90]

    [119]

    [149]

    [179]

    [209]

    [239]

    Grundfos Pump Performance Curves, Magna GEO (NPDV3: Magna GEO+UPS26-99 (Hi Spd) on LH side; Magna GEO on RH side -- two sets in parallel)

    Curve when all three pumps are operating

    Pump Performance Curves

    Page 3 of 4

    NPDV3

    The NPDV3 (P/Ns 1336 & 1336N)flow center uses a Magna GEO (variable speed) in series with a UPS26-99 (constant speed) on one side and a Magna GEO on the other side. The chart to the left provides curves for these two sets of pumps operating in parallel.* Use these curves to determine pump selection when both heat pumps are operat-ing. Two pumps in parallel with one pump creates a curve that is the sum of the two curves (gray line). Internal check valves are factory-installed to prevent short circuiting.

    Use the chart on the left to account for the pressure drop of the internal components of the dual circuit flow center.

    *Above curves for Magna GEO are maximum operating curves. The Magna GEO can operate between its minimum and maximum curves, depending upon flow rate and pressure drop requirements.

    SD 1334-1335-1336-1334N-1335N-1336N rev. 22SEP2015

  • Dimensional Data

    Flow (U.S. GPM) [l/s]

    Grundfos Pump Performance Curves (single UPS26-99)

    Head

    (Fee

    t) [k

    Pa]

    UPS26-99 high spd UPS26-99 med spd UPS26-99 low spd

    [0.13 0.25 0.38 0.50 0.63 0.76 0.88 1.00 1.14 1.26 1.39 1.51 1.64 1.77 1.89 2.02 2.15 2.27]

    [14.9]

    [29.8]

    [44.8]

    [59.7]

    [74.6]

    [89.5]

    [104.5]

    [119.4]

    A B C D E F G H I K Weight Lbs KgNPDV2A* NPDV2B* NPDV3 All  Models NPDV2A* 85 38.6

    Inches 48-‐1/8 10 11-‐1/8 15-‐7/8 49-‐3/4 5 9-‐3/8 11 9-‐1/8 10-‐7/8 11 10-‐7/8 NPDV2B* 89 40.4CM 122.2 25.4 28.3 40.3 126.3 12.7 23.7 27.9 23.2 27.6 27.9 27.6 NPDV3 95 43.1

    3/8"  DRIVE  SOCKET

    UnitsAll  Models

    J

    NOTE: All connections require Flo-Link™ (double O-ring) transition fittings. Internal check valves are factory-installed.

    LH Side RH Side FrontNPV2A

    Pump Performance Curves

    Page 4 of 4

    The pump curves below represent the pumps on each side of the dual circuit flow center. For operation when only one heat pump is running, the curves below show a single pump or two pumps in series. For proper flow center selection, operation when both heat pumps are running must also be considered (previous pages).

    All pump curves are based upon manufacturer’s reported averages using water at 68°F [20°C].

    Flow (U.S. GPM) [l/s]

    Grundfos Magna GEO 32-140 and UPS26-99 (pumps in series)

    Pumps operate in seriesbetween these curves*to maintain flow rateor temperature diff.

    Magna GEO + UPS26-99 (high speed)

    Magna GEO (maximum curve -- highest flow/head)

    Magna GEO (minimum curve -- lowest flow/head)

    [0.32 0.63 0.95 1.26 1.58 1.89 2.21 2.52 2.84 3.15] 0 5 10 15 20 25 30 35 40 45 50

    0

    101520253035404550556065707580

    [134]

    [15]

    [30]

    [45]

    [60]

    [75]

    [90]

    [105]

    [119]

    [149]

    [164]

    [179]

    [194]

    [209]

    [224]

    [239]

    Head

    (Fee

    t) [k

    Pa]

    5

    *UPS26-99 is a constant speed pump; Magna GEO is a variable speed pump. When both pumps are running, the Magna GEO operates between min.-max. curves shown below to maintain set flow rate or temperature difference.

    Dimensional data provided for informational purposes, and is rounded to the nearest 1/8”. Metric data is a simple conversion, and should not be considered more accurate.

    SD 1334-1335-1336-1334N-1335N-1336N rev. 22SEP2015

    *Pumps:2A = Magna GEO (Left), UPS26-99 (Right)2B = Magna GEO (both sides)

    Models NPDV2A (1334 & 1334N), NPDV2B (1335 & 1335N), NPDV3 (1336 & 1336N)

    FrontNPV3

    FrontNPV2B

    TopGEO-FLO PRODUCTS CORPORATION905 Williams Park DriveBedford, IN 47421 U.S.A.PH: 812-275-8513; FAX: 812-275-8523www.geo-flo.com

    To tank

    From tankFrom tank

    Ground Loop or Flushing Connec� ons

    From/ToHeat Pump #2

    PipingArrangment ...

    From/ToHeat Pump #1

    Ground Loop or Flushing

    Connec� ons

    FromHPs