noise reduction in the data center & office processing facilities
DESCRIPTION
Noise Reduction in the Data Center & Office Processing Facilities. Data Center Noise. “Consolidation and denser equipment make for noisier data centers.” Computer World (2007) - PowerPoint PPT PresentationTRANSCRIPT
![Page 1: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/1.jpg)
Noise Reduction in the Data Center & Office Processing Facilities
![Page 2: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/2.jpg)
“Consolidation and denser equipment make for noisier data centers.”
Computer World (2007)
In 2001, the World Health Organization published revised guidelines for Community Noise in which it recommends a 70 dB (A) noise level limit for commercial areas. It is worth noting that the combined noise level of just eight low form factor servers operating with average CPU loads would be approximately 74 dB
(A).
Data Center Noise
![Page 3: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/3.jpg)
Demand for quiet racks is growing in these sectors;
Audio Visual/Graphic Design Studios
Education, Schools and Universities, Libraries
SOHO sector
Large Enterprise / Government Facilities with satellite/branch Cloud Deployments
Niche requirements: Healthcare Clinics, Ships, Marketing Exhibits
Decision makers respond well to the following triggers;
Efficiency / Green / Reduced EnergyDirect comparison between the huge cost (both upfront and ongoing) and inflexibility of a dedicated Computer Room. Desire to be leading edgeImproving the Working EnvironmentJustifiable ROI
![Page 4: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/4.jpg)
Is a sound that is noticeably unpleasant
Any sound that is undesired or interferes with one’s hearing of something
What is Noise?
Merriam-Webster.com (2011)
![Page 5: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/5.jpg)
Decibel (dB) is a measurement of Sound Pressure Level (SPL)Sound Pressure Level is the physical intensity of soundThe (A) after the dB refers to an ‘A weighting’. This weighting gives more significance to audible sound frequencies and therefore attempts to reflect sound levels as they are experience by a human ear.
What Does dB(A) Mean?
![Page 6: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/6.jpg)
60 dB(A) - A normal office conversation70 dB(A) – A Vacuum Cleaner77 dB(A) – A Passenger Car @ 65 mph80 dB(A) – Garbage Disposal90 dB(A) – Power Lawn Mower140 dB(A) - Jet Engine at takeoff
How Loud is Loud?
![Page 7: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/7.jpg)
70dB(A) - Sun Fire X2270 M2 Server72dB(A) – IBM 8852 BladeCenter H (Performance Mode, Enhanced Blowers)
66dB(A) – IBM 8852 BladeCenter H (Performance Mode, Original Blowers)
71dB(A) – Dell PowerEdge 6800
Data Center Equipment Noise
Ratings based on single unit. SPL increases approximately 3dB(A) for each additional unit added to the environment.
![Page 8: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/8.jpg)
Several Studies have shown that noise levels within Data Centers vary from 68dB(A) to 80dB(A).
Size of facility, amount of equipment, type of cooling systems all have an impact on the noise levels.
Data Center Equipment Noise
![Page 9: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/9.jpg)
Workplace Regulations
The Human Effects
Cost to Business
Considerations
![Page 10: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/10.jpg)
When an employee is exposed to noise levels of at least 85dB(A) for a period of 8 hours or more, employers must implement programs to monitor the environment and provide employees with hearing protection.
Workplace Regulations
Occupational Safety & Health Administration
![Page 11: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/11.jpg)
Hearing ImpairmentInterferences with Spoken CommunicationCardiovascular DisturbancesMental Health DisturbancesImpaired Task PerformanceAnnoyance Reactions
The Human Effects
World Health Organization
![Page 12: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/12.jpg)
Exposure to constant sound levels above 85dB(A) is potentially hazardous and can be a main contributor to hearing loss.
Hearing Impairment
![Page 13: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/13.jpg)
Noise at increased levels interferes with the ability to comprehend normal speech.
Decreased working capacity and stress reactions can also occur.
Interference With Spoken Communication
![Page 14: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/14.jpg)
Daily exposure to noises above 65dB(A) can trigger nervous system responses that affect the cardiovascular system leading to hypertension, increased blood pressure and increased heart rates.
Cardiovascular Disturbances
![Page 15: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/15.jpg)
Noise may cause or contribute to effects like anxiety, stress, headaches and changes in mood.
Mental Health Disturbances
![Page 16: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/16.jpg)
Noise can impair task performance at work, increasing errors and decreasing motivation.
Reading attention, problem solving, and memory are strongly affected by noise.
Impaired Task Performances
![Page 17: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/17.jpg)
Sound levels above 45dB(A) can produce annoyance reactions in a significant number of people.
Annoyance Reactions
![Page 18: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/18.jpg)
Employee ProductivityHealth InsuranceWorkman’s Compensation ClaimsGovernment Regulations
Cost to Business
![Page 19: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/19.jpg)
Hearing ProtectionLights-Out OperationsSpecialized Server Enclosures
Possible Solutions
World Health Organization
![Page 20: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/20.jpg)
Low cost, quick to implementDoes not reduce noise in workplaceTemporary Solution
Hearing Protection
![Page 21: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/21.jpg)
Provides reduced exposure for employeesDifficult and costly to implement Does not reduce noise in workplace
Lights-Out Operations
![Page 22: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/22.jpg)
Reduces noise of data center equipment (from 14 to 30dB(A) reduction)Immediate installation, no construction costsAddresses equipment thermals, potentially decreasing cooling costs
Specialized Acoustic Server Enclosures
![Page 23: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/23.jpg)
Offers alternative to dedicated server room100% PortableScalableUse of ambient air for cooling
Specialized Acoustic Server Enclosures
![Page 24: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/24.jpg)
Use of high density foam designed to attenuate the specific frequencies of server noise
Designed to minimize sound leakage at cable access points
Use of fan systems to facilitate proper thermal dissipation using ambient air
Specialized Acoustic Server Enclosures
![Page 25: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/25.jpg)
Attractive appearances to fit most workplace environmentsProvides secure environment for sensitive equipmentDesigned with operational cost-savings in mind
Specialized Acoustic Server Enclosures
![Page 26: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/26.jpg)
28.5 dB(A) Noise Reduction
Thermal Dissipation of 7.2kW
Energy Efficient
Available in 12u, 24u and 42u sizes
Specialized Acoustic Server Enclosures:
UCOUSTIC
![Page 27: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/27.jpg)
28.5 dB(A) Noise Reduction
Thermal Dissipation of 7.2kW
Energy Efficient
Available in: Oak, Maple, Beech, Cherry, Ash, Walnut, Mahogany for 12u, 24u and 42u sizes
Specialized Acoustic Server Enclosures:
UCOUSTIC Premium Wood Option
![Page 28: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/28.jpg)
Up to 30 dB(A) Noise Reduction using Active Noise Cancellation Technology
Thermal Dissipation of 8kW
Glass Front Door
Available in 15u and 33u sizes
Active Silencer Fan Tray™(ASFT™)
AcoustiRACK ACTIVE is an alliance partner in HP BladeSystem Solution Builder Program and for Intel Modular Servers supporting Active Noise Control Enclosure Solutions.
http://www.youtube.com/watch?v=4ExBkpLJmpM&feature=related
Specialized Acoustic Server Enclosures: AcoustiRACK
Active
![Page 29: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/29.jpg)
20.7 dB(A) Noise Reduction
Thermal Dissipation up to 3kW
Built for the Budget conscious Cost-Effective
Available in a variety of sizes & Depths 24U, 35U & 44U – (36” & 42” deep)
Specialized Acoustic Server Enclosures:
AcoustiQuiet
![Page 30: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/30.jpg)
14 dB(A) Noise Reduction
Thermal Dissipation
9u (1.2KW) & 12u (1.5KW)
Cost-Effective, SOHO applications
Available in 9u & 12u
Specialized Acoustic Server Enclosures: AcoustiQuiet Mini
Cabinet
![Page 31: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/31.jpg)
Isolation of loud servers in existing data center rooms / NOC (network operation centers)Laboratories /Libraries / Broadcast & Sound StudiosClassrooms / Lecture Halls /Training RoomsMedical Offices & Clinics / HospitalsBoardrooms / Public Safety Facilities
Acoustic Server Enclosure Applications
![Page 32: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/32.jpg)
Open Office EnvironmentsAlternative to data room build-out in smaller satellite offices / Branch OfficesEnvironments with limited space / rented spaceFuture Relocation / Temporary IT MovesWorkspaces where cooling options are limited
Acoustic Server Enclosure Applications
![Page 33: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/33.jpg)
BudgetsAvailable Floor SpaceElectrical Requirements and ConsumptionHVAC RequirementsDeployment TimelineScalabilityPortability
Deployment Considerations
![Page 34: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/34.jpg)
ROI ScenariosMkt. Research Firm, Mid Atlantic USNot building a server room saved:Total Savings Over 3 Years: $119,817
Savings Breakdown:Rental Cost Per Year: $18,720AC Running Cost Per Year: $4,719Room Conversion Cost: $49,500
Equipment Deployed:• 3 x Cisco Catalyst Gb PoE Switches• 6 x Switches• 3 fibre panels• 1 x UPSApprox Max Thermal Load: 8kWQuiet Rack Solution*: 3 x 42U racksQuiet Rack Purchase Price: $16,000
A-V Studio, Los Angeles CANot building a server room saved:Total Savings Over 3 Years: $91,443
Savings Breakdown:Rental Cost Per Year: $13,520AC Running Cost Per Year: $5,961Room Conversion Cost: $33,000
Equipment Deployed:• 2 x XServe (Dual Processor)• 1 x Telephone System• 2 x File Servers• 10 x Render NodesApprox Max Thermal Load: 10kWQuiet Rack Solution: 2 x 12U Quiet Rack Purchase Price: $9,000
![Page 35: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/35.jpg)
Medium Size Enterprise, Chicago MetroNot building a server room saved:Total Savings Over 3 Years: $55,020 Savings Breakdown:Rental Cost Per Year: $8,700AC. Running Cost Per Year: $1,390Room Conversion Cost: $24,750
Equipment Deployed:• 2 x PoE Switches• 2 x Tower Server (Single Processor)• 3 x Servers (5 Processors in Total)• 2 x NAS boxes• 1 x UPSApprox Max Thermal Load: 2kWQuiet Rack Solution*: 1 x 24U rackQuiet Rack Purchase Price: $4,900
Private Middle School, North East USNot building a server room saved:Total Savings Over 3 Years: $45,906
Savings Breakdown:Rental Cost Per Year: $4,355AC. Running Cost Per Year: $2,697Room Conversion Cost: $24,750
Equipment Deployed:• 5 x mini desktops• 5 x Dual Processor Servers• 1 x fully populated RAID• 2 x Switches• 1 x Firewall & 1 x UPSApprox Max Thermal Load: 4kWQuiet Rack Solution*: 1 x 42U rackQuiet Rack Purchase Price: $8,300
ROI Scenarios
![Page 36: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/36.jpg)
http://usrackdistributors.com/dealers/dealers.aspUS Rack Distributors Password protected Dealer Web PageUSER NAME: dealers ; Pass Word: USRD2010!
http://usrackdistributors.com/noise-reduction.aspDemonstrating dB(A) Noise Reduction Effect
http://www.quiet-rack.com/
Industry Forum Web Page
Helpful URL’s
![Page 37: Noise Reduction in the Data Center & Office Processing Facilities](https://reader033.vdocuments.site/reader033/viewer/2022051219/56816030550346895dcf4b98/html5/thumbnails/37.jpg)
As OSHA tightens down on undue noise in the work place, in the Data Centers, or at processing facilities, driving workers compensation insurance claims against the enterprise, we offer practical solutions. Our Soundproof Rack Server Cabinets help mitigate the incessant Noise caused by the proliferation of Servers, Network Elements and AV Electronics, even while optimizing power consumption efficiencies. Quiet Server Rack Cabinet Deployments can resolve noise pollution, increase energy efficiency, and reduce costs.
QUESTIONS?
Noise Reduction in the Data Center